Drip Legs Definition Purpose Configuration Selection Installation and Sizing PDF
Drip Legs Definition Purpose Configuration Selection Installation and Sizing PDF
Drip Legs are used for removing entrained moisture from the steam transmission
and distribution lines to ensure high-quality steam for use in various plant
applications, while also preventing damaging and dangerous water hammer.
As steam travels at high velocity through piping, moisture forms as the result of
piping heat losses and/or improper boiler control resulting in condensate carryover.
Drip legs are therefore located at points where condensate may accumulate to
allow for drainage by gravity down to a steam trap for proper discharge from the
system. Since condensate drains by gravity, drip legs must be located on the bottom
of piping and designed with diameters large enough to promote the collection.
Drip legs should be located at Vertical Lifts, Drops, or at the end of the steam line.
In the straight run of piping every 30 to 50 meters.
1/4
Installed directly ahead of the regulating or control valve, Manual Valves Closed for
a Long Time.
Ahead of expansion joints or elbows.
Provide proper supports (no sagging)
Provide slope towards Drip legs.
2/4
Fig. 2: Typical Drip Leg Loops from Steam
Mains
Fig. 3 below provides the recommended Drip leg Sizes (Drip Leg Diameter and Leg
Length) with respect to main steam piping size.
A carefully designed drip leg enables steam traps to effectively drain the condensate from
steam mains. For that, the drip legs should be large enough to allow the condensate to
drop out of the steam at the pipe bottom. Recommended drip leg sizing table (Fig. 3)
provides a good reference for such a scenario. In case the drip leg is not sized properly,
the condensate will blow along with the steam without separating out as shown in Fig. 4.
Click here to know about Steam Traps: Steam Traps: Definition, Types, Selection,
Features, Codes & Standards
3/4
Fig. 3: Recommended Drip Leg Sizing
4/4