Siemens Masterdrives - Detailed Fault History Readout

The document provides instructions for reading the detailed fault history from a Siemens Masterdrives drive, including operating hours at the time of the last fault, fault codes and values, and last 8 warning codes. Fault and warning code memory can store up to 8 events at a time with details on the codes, times, and values for troubleshooting drive issues.

Uploaded by

mati
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views

Siemens Masterdrives - Detailed Fault History Readout

The document provides instructions for reading the detailed fault history from a Siemens Masterdrives drive, including operating hours at the time of the last fault, fault codes and values, and last 8 warning codes. Fault and warning code memory can store up to 8 events at a time with details on the codes, times, and values for troubleshooting drive issues.

Uploaded by

mati
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Siemens Masterdrives – detailed fault history readout.

Actual Operating hours for CUVC


Index:001 index:002 index:003
Days Hours Seconds
r825

Status at time of the last fault:


r783 r784 r785 r786 r787
n/f(Act) dn/dt Isq(Act) Out Volts CtrlStatus

Read out fault history parameter with operating hours as reference.


Fault 1 2 3 4 5 6 7 8
number (last
fault)
1 9 17 25 33 41 49 57
r947 2 10 18 26 34 42 50 58
Fault 3 11 19 27 35 43 51 59
memory 4 12 20 28 36 44 52 60
5 13 21 29 37 45 53 61
6 14 22 30 38 46 54 62
7 15 23 31 39 47 55 63
8 16 24 32 40 48 56 64

1 9 17 25 33 41 49 57
r949 2 10 18 26 34 42 50 58
Fault 3 11 19 27 35 43 51 59
value 4 12 20 28 36 44 52 60
5 13 21 29 37 45 53 61
6 14 22 30 38 46 54 62
7 15 23 31 39 47 55 63
8 16 24 32 40 48 56 64

R782 :001 :004 :007 :010 :013 :016 :019 :022


Days:

R782 :002 :005 :008 :011 :014 :017 :020 :023


Hours:

R782 :003 :006 :009 :012 :015 :018 :021 :024


Seconds:

Memory for up to 8 trips can be stored at the same time.


For each trip up to 8 fault messages occurring at the same time can be stored.
Write down values different from 0 / F000 .

Read out of the last 8 warning codes.


P1090 P1091 P1092 P1093 P1094 P1095 P0196 P1097