(BWT) (Ex Manual) HMD 2531serise (2015.11.09) Rev.A
(BWT) (Ex Manual) HMD 2531serise (2015.11.09) Rev.A
at +82-51-601-4500
(LR) 2532/2534/2536/2538/2540
Table of Contents
1. WARNING................................................................................................................... 8
2. ABBREVIATION.......................................................................................................... 13
3. ECS OVERVIEW.......................................................................................................... 17
3.1 Introduction of ECS............................................................................................ 17
3.1.1 General Information........................................................................................ 17
3.1.2 Principles of disinfection.................................................................................. 17
3.1.3 Safety.............................................................................................................. 17
3.1.4 Environment friendly....................................................................................... 18
3.2 Outline of ECS.................................................................................................... 18
3.2.1 Specifications of ECS........................................................................................ 18
3.2.2 Specifications of ECS........................................................................................ 19
3.3 OPERATION PROCESS......................................................................................... 20
3.3.1 Ballasting Procedure........................................................................................ 20
3.3.2 Deballasting Procedure .................................................................................. 20
3.4 ECS COMPONENTS............................................................................................. 21
4. OPERATION............................................................................................................... 26
4.1 General Information........................................................................................... 26
4.2 Preparation for operation .................................................................................. 28
4.2.1 Preparation for Power up................................................................................. 28
4.2.2 Ballasting Operation Flows ............................................................................. 34
4.2.3 Deballasting Operation Flows ......................................................................... 38
4.3 Automatic Operation ......................................................................................... 41
4.3.1 Selection of Control position of ECS ................................................................ 41
4.3.2 HMI Overview ................................................................................................ 42
4.3.3 Ballasting Operation ...................................................................................... 43
4.3.4 Deballasting Operation .................................................................................. 45
4.4 Stop Procedure ................................................................................................. 47
4.4.1 Stop Procedure of CPC..................................................................................... 47
4.4.2 Stop Procedure of ECS..................................................................................... 48
Table of Contents
5. MAINTENANCE......................................................................................................... 50
5.1 General Information........................................................................................... 50
5.2 Routine maintenance of Equipment................................................................... 50
5.2.1 Ex-Electro-chamber Unit (EX-ECU)................................................................... 50
5.2.2 Ex-Power Rectifier Unit (EX-PRU)...................................................................... 52
5.2.3 Power Distributor Equipment (PDE)................................................................. 53
5.2.4 Control PC (CPC).............................................................................................. 55
5.2.5 TRO Sensor Unit (TSU Panel + EX-CLX)............................................................. 56
5.2.6 Auto Neutralization Unit (ANU)........................................................................ 58
5.2.7 Ex-Flow meter unit (Ex-FMU)............................................................................ 60
5.2.8 Ex-Conductivity Sensor Unit (Ex-CSU).............................................................. 61
5.2.0 Ex-Freshwater Temperature Sensor (Ex-FTS).................................................... 62
5.2.10 Gas Detection Sensor(GDS)............................................................................ 62
5.2.11 T-Strainer....................................................................................................... 62
5.3 Regular maintenance Procedure........................................................................ 63
5.3.1 TSU Panel + EX-CLX ........................................................................................ 63
5.3.2 ANU ................................................................................................................ 66
5.3.3 EX-PRU ........................................................................................................... 67
5.3.4 T-STRAINER ..................................................................................................... 68
5.4 Long-term Lay-up .............................................................................................. 69
5.4.1 MAIN CPC ....................................................................................................... 69
5.4.2 PDE and MSBD................................................................................................ 70
5.4.3 ANU tank ........................................................................................................ 71
5.4.4 Close TSU valve and remove reagent............................................................... 73
5.4.5 Close all the EX-ECU valves.............................................................................. 75
5.4.6 HEU&EX-FTU ................................................................................................... 76
5.5 Spare parts ........................................................................................................ 77
5.5.1 General Information........................................................................................ 77
5.5.2 Standard spare part......................................................................................... 77
5.5.3 Additional consumables ................................................................................. 79
4
ECS Quick Manual
5.6 Replacement of consumables............................................................................ 80
5.6.1 Replacement of TRO Sensor(EX-CLX) Reagent.................................................. 80
5.6.2 Replacement of Sodium Thiosulfate................................................................ 84
6. TROUBLESHOOTING................................................................................................. 87
6.1 Checking Alarms & Log messages...................................................................... 87
6.2 Trouble Shooting for ECS Major Alarm Message................................................. 88
6.3 Main Problems and Measures ............................................................................ 97
5
ECS Quick Manual
Table of Contents
7.3.5 When HEU / Ex-FTU are located in BWTS room on deck without heater.......... 160
7.3.6 Procedure for maintenance of EX-Solenoid Valve.......................................... 162
7.4 Detailed Troubleshooting Procedure................................................................ 164
7.4.1 PDE............................................................................................................... 164
7.4.2 TSU............................................................................................................... 166
7.4.3 ANU.............................................................................................................. 167
7.4.4 ECU (Ex-PRU)................................................................................................. 168
7.4.5 SENSOR......................................................................................................... 168
7.4.6 Ex-FTU........................................................................................................... 169
7.4.7 HEU................................................................................................................170
※Additional documents
- Type Approval Cert’ (KR, ABS, RINA, BV and RS)
- AMS acceptance letter
- Ex-ECU450B cert’
- MSDS(TSU_CLX, ANU_Sodium Thiosulfate, EWU_Citric-Acid)
6
ECS Quick Manual
WARNING
Head Office/Factory
84 Younginsan-ro, Inju-myeon, Asan-si, Chungcheongnam-do, Korea. (336-833)
Tel : +82-41-420-9032(Rep.) Fax : +82-41-420-9090 http://www.techcross.com
7
ECS Quick Manual
ECS Manual
1. WARNING
Only qualified personnel should operate and maintain ECS after becoming thoroughly familiar with
proper operation, all warnings, safety notices, maintenance requirements and troubleshooting.
• DO NOT operate if Inlet /Outlet valves of ECU are CLOSED. It can cause severe damage
to the equipment and crews.
Make sure that Inlet & Outlet valves of the ballast pump are OPEN before operation of ECS.
• DO NOT open the cover of the equipment or maintain the equipment when power is ON in
an explosive and flammable environment.
Failure to heed warning and danger labels may result in equipment damage and possible personal injury.
HAZARDOUS VOLTAGE
Contact with any live part may cause burn or death.
(Attached on PDE/PRU/PCU/PRE)
Attached :
EM'CY use only 1. Near emergency stop Button
2. Near RCM selection switch
AUTHORIZED
Attached above CPC (HMI) @ CCR (or remote CPC position)
PERSONNEL
ONLY & PDE
NO LIGHTS WITH
Attached near vent pipe on deck (Safety area)
EXPOSED BULBS
WARNING
Do not close this valve during Attached manual in/outlet valves for ECS
ECS operation
9
ECS Quick Manual
ECS Manual
10
ECS Quick Manual
Attached above Ex-CLX
ECS Manual
ABBREVIATION
Head Office/Factory
84 Younginsan-ro, Inju-myeon, Asan-si, Chungcheongnam-do, Korea. (336-833)
Tel : +82-41-420-9032(Rep.) Fax : +82-41-420-9090 http://www.techcross.com
* Ex- : Ex-proof
Abbr Full Name
CPC Control PC
C
Ex-CSU Ex-proof Conductivity Sensor Unit
E EM Electrode Module
13
ECS Quick Manual
ECS Manual
PI Pressure Indicator
P PS Pressure Switch
T-STRAINER TEE-STRAINER
T
TSU TRO Sensor Unit
14
ECS Quick Manual
Revision Status
- 14/04/01 Established
15
ECS Quick Manual
ECS OVERVIEW
Head Office/Factory
84 Younginsan-ro, Inju-myeon, Asan-si, Chungcheongnam-do, Korea. (336-833)
Tel : +82-41-420-9032(Rep.) Fax : +82-41-420-9090 http://www.techcross.com
3.1.3 Safety
ECS is developed and designed to ensure that the operation is conducted in a safe and efficient
manner, and to familiarize the users with the basic procedures that affect their own safety and
the safety of their fellow users. However, the users should read the manual thoroughly and be
educated to be able to maintain overall control of software and hardware safety before starting to
operate ECS.
17
ECS Quick Manual
ECS Manual
Division Specifications
Biological
Compliance with D-2 performance standard regulated by IMO
Efficacy
Operation
Less than TRO 10mg/L (At the inside of EM, average 6~10 mg/L)
Performance
Neutralization
Less than TRO 0.2mg/L after neutralization before discharging
Performance
Neutralization
Automatic input of Neutralization solution
Method
Neutralizing
Sodium Thiosulfate
Agent
Operation
• Automatic (Remote / Local) operation by CPC
Method
18
ECS Quick Manual
3.2.2 Specifications of ECS
Current 1100A
PRU
Temperature Less than +45°C
Allowable operating
Fresh water in
Temperature of fresh +36°C
PRU
water in PRU
19
ECS Quick Manual
ECS Manual
20
ECS Quick Manual
3.4 ECS COMPONENTS
21
ECS Quick Manual
ECS Manual
3. Control PC (CPC)
22
ECS Quick Manual
6. Ex-Flow Meter Unit (Ex-FMU)
23
ECS Quick Manual
ECS Manual
10. T-Strainer
24
ECS Quick Manual
OPERATION
Head Office/Factory
84 Younginsan-ro, Inju-myeon, Asan-si, Chungcheongnam-do, Korea. (336-833)
Tel : +82-41-420-9032(Rep.) Fax : +82-41-420-9090 http://www.techcross.com
4. OPERATION
• Purpose
The chapter provides the operating manual and procedures to operate ECS safely and efficiently during
ballasting / deballasting operation. Please make sure to read carefully and understand the manual
before use. To secure an operator’s safety, it is recommended to establish and execute plans.
• Precautions on operation
Please, read carefully before operating ECS in order to prevent any accident and damage.
Caution
• Operation is allowed only to the skilled operator.
Make sure that an operator should be well aware of ECS and ECS
operation system.
• Protect any potential static electricity in body part during repairs of ECS
system. Warning
26
ECS Quick Manual
• Low flow rate cause ECS Shut down
In case of under 10% of nominal flow rate, ECS system will alarm and shutdown
• Contaminated sea water, e.g. oil pollution, will decrease the performance of the ECU
- In case of contaminated seawater cannot be treated with lower than target TRO generation,
system will alarm and shutdown
- Stripping mode. ECU to be isolated during stripping mode.
• It is to be stop the ballast pump to prevent Over pumping of ballast water tanks
- In order to prevent spillage of ballast water with high TRO content over the air pipe heads the
ballast pump is to be stopped before overfilling.
• It is to be checked all related valves on pipelines for safety operation.
- ECS system incorporate a lot of hand operated valves , especially to sensors and units such
as CSU, TSU, ANU and cooling water to ECU.
Monitoring of related valve is needed.
• In order to prevent the freezing during operating in cold condition, we recommend drain the residual
water in piping and ANU.
27
ECS Quick Manual
ECS Manual
4.2.1.1 MSBD
1. Turn on BWMS MAIN MCCB in MSBD.
4.2.1.2 PDE/PCU
1. Open the door of PDE and Turn on the MAIN MCCB.
2. On the front door of PDE, flip the switch to “Remote Mode”.
28
ECS Quick Manual
3. Turn on OPERATION switch of the PDE to set HMI of CPC to Remote.
Remote (Default): HMI controlled by CCR / Local: HMI controlled by PDE
4.2.1.3 CPC
1. Press the Power button.
2. The computer will boot up and HMI will operate automatically.
29
ECS Quick Manual
ECS Manual
2. Close air inlet Manual valve of Ex-CLX and Verify the "0" pressure of Regulator.
30
ECS Quick Manual
3. Open the door of Ex-CLX(TRO Sensor) #1 and #2 by using key.
Check replacement cycle and remaining quantity of Ex-CLX Reagent before using it.
Peplace it with new one if it is expired or remaining quantity of regents is lower than
20%
4. Close the door of Ex-CLX and Open the Air inlet by opening manual valve.
Check the pressure level of regulator and set the pressure "5~7.5"mber by using
regulator
31
ECS Quick Manual
ECS Manual
* CAUTION!!
Power shall not be restored after after enclosure has been opend untill Enclosure has been purged
for 5 minutes at a flow rete of 11,8 SLPM.
6. Check whether the state lamp of Ex-CLX is flicking green (Remote mode ready)
(Green : Remote mode ready, Red : Remote mode standby / Emergency mode)
32
ECS Quick Manual
4.2.1.5 ANU
1. Refer to Ch. 5.6.2 Replacement of Sodium Thiosulfate
4.2.1.6 HEU/Ex-FTU
1. Fill cooling water more than medium level of Ex-FTU
4. Refill cooling water more than medium level of Ex-FTU after "2" and "3"
33
ECS Quick Manual
34
ECS Quick Manual
ECS Manual
EVACUATION
SYSTEM
UPPER DECK
NO.4 W.B.TK(P)
ABT 500MM(P&S)
FULL L.W.L
NO.5 W.B.TK(P) LS SE
PX A
CH
(P
ES
T
OR
T)
NO.2 BALLAST
PUMP(800M3/H)
NO.1 BALLAST
PUMP(800M3/H)
SE
A
(S CH
T' ES
BD
) T
PX LS
NO.5 W.B.TK(S)
FULL L.W.L
NO.4 W.B.TK(P)
UPPER DECK
EVACUATION
SYSTEM
TO T/C PUMP
DWG NO:1A000T001- 3
Preparation for Ballasting Operation
* CAUTION!! Make sure that all the valves on pipelines for ballasting are open.
10 If it is not in “Ballast Mode”, Check Ship’s Signal by following the procedure below.
35
ECS Quick Manual
ECS Manual
36
ECS Quick Manual
Step 4: Ship’s Valve and Pump Signal will be displayed in Ship’s Signal.
Match Ship’s Signal (ship’s conditions) with Required Signal.
If these two requirements match, Ballast in Current Status will be selected automatically.
(“Ballast Operation”)
If “Ballast Operation” is not selected, match the ship’s conditions with operating
requirements.
37
ECS Quick Manual
38
ECS Quick Manual
ECS Manual
EVACUATION
SYSTEM
UPPER DECK
NO.4 W.B.TK(P)
ABT 500MM(P&S)
FULL L.W.L
NO.5 W.B.TK(P) LS SE
PX A
CH
(P
ES
T
OR
T)
NO.2 BALLAST
PUMP(800M3/H)
NO.1 BALLAST
PUMP(800M3/H)
SE
A
(S CH
T'
BD ES
) T
PX LS
NO.5 W.B.TK(S)
FULL L.W.L
NO.4 W.B.TK(P)
UPPER DECK
EVACUATION
SYSTEM
TO T/C PUMP
DWG NO:1A000T001- 3
Preparation for Deballasting Operation
* CAUTION!! Make sure that all the valves on pipelines for deballasting are open.
8. If it is not in “Deballast Mode”, Check Ship’s Signal by following the procedure below.
Step 1: Click “MENU” and “Operation View” on HMI MAIN screen.
39
ECS Quick Manual
ECS Manual
Step 4: Ship’s Valve and Pump signal of ship will be displayed in Ship’s Signal.
Match Ship’s Signal (ship’s conditions) with Required Signal.
If these two requirements match, Deballast in Current Status will be selected automatically.
(“Deballast Operation”)
If “Deballast operation” is not selected, match the ship’s conditions with operating
requirements.
40
ECS Quick Manual
4.3 Automatic Operation
41
ECS Quick Manual
ECS Manual
3. PDE
13. TSU
5. ECU Selection
11. ANU
6. HMI Select Status
4 Sensor Measured value of ECS Sensors (CSU, FMU, FTS, GDS, etc.)
Selection of ECU
5 ECU Selection
(when there are more than 2 sets of ECU installed)
6 HMI Select Status State of CPC HMI (REMOTE / LOCAL)
7 Logo & Version ECS Logo (able to check HMI version by clicking)
8 Start Button Start-up ECS
42
ECS Quick Manual
No. Name Specifications
43
ECS Quick Manual
ECS Manual
Step 3: Ensure that ECU value and TRO value are displayed in 5 minutes after starting ECS.
(Alarm or Shutdown should not occur during normal operation.)
44
ECS Quick Manual
Step 4: Click “STOP” on HMI Screen to stop ballasting operation.
Stop ballast pump after stopping ECS operation.
45
ECS Quick Manual
ECS Manual
Step 3: Ensure that ANU value and TRO value are displayed immediately after operating ECS.
(Alarm or Shutdown should not occur during normal operation.)
46
ECS Quick Manual
Step 4: Stop ballast pump before stopping deballasting operation.
Click “STOP” button on HMI screen to stop ECS operation.
Step 1: Click “POWER” button on HMI screen of Main CPC to turn off HMI.
Step 2: Click “YES” to turn off HMI.
Step 3: Click “OK” to turn off HMI.
Step 4: Click “Turn off” button on Window XP “START” menu to shut down Main CPC.
Step 5: After shutting down Main CPC, shut down sub CPC, following instruction step 4.
47
ECS Quick Manual
ECS Manual
48
ECS Quick Manual
MAINTENANCE
Head Office/Factory
84 Younginsan-ro, Inju-myeon, Asan-si, Chungcheongnam-do, Korea. (336-833)
Tel : +82-41-420-9032(Rep.) Fax : +82-41-420-9090 http://www.techcross.com
5. MAINTENANCE
Purpose
Potential accidents during ECS operation can be prevented through a systematic maintenance
plan.
• The inspection / maintenance of ECS components should be performed based on the inspection /
maintenance schedule recommended by ECS manufacturer.
• It is important to ensure the condition of functions of ECS operation through regular or
intermit¬tent inspection / maintenance.
• A person in charge should check maintenance schedule sheet and equipment history card
to make sure that it is being executed as planned
• Inspection of spare parts should be performed on a regular basis in order to maintain them
in good condition.
Appearance
Weekly Cleaning it with soft cloth
status of ECM
Appearance If broken, replace it with spare part.
Weekly status of drain Refer to Appendix 7.3 Replacement
Electro-Chamber
ECU-M-001 bolt of Spare parts.
Module
If drain gasket is defective, replace
Appearance
it with spare part.
Weekly status of drain
Refer to Appendix 7.3 Replacement
gasket
of Spare parts.
50
ECS Quick Manual
Interval Main Check
Code Description Countermeasures
(M) Points
Appearance status
Weekly Cleaning it with soft cloth
of name plate
Check if painting of
3 Painting
Electro-Chamber ECM is damaged
ECU-M-002
Module Cleaning EM with EM Washing Unit
Total Ballast
(EWU)
200Hour Operation Time on
Refer to Appendix 7.3.2 Procedure
HMI
for ECU Cleaning.
Connection status
of Tightening bolts and nuts with
Weekly
ECM protector washer
cover with ECM
Appearance status
Weekly Cleaning it with soft cloth
ECM of electric label
ECU-M-003
Protector Cover Appearance status
of
Weekly Cleaning it with soft cloth
general avoidance
label
Appearance status
Weekly Cleaning it with soft cloth
of name plate
Cleaning cooling Cleaning it with air brushing by air
Weekly
water inlet pipe compressor
Operation status of
PS & PI 1 If defective, contacct Techcross
ECU-M-004 PS
Connection status
Reconnecting quick coupler socket
12 of joint and check if
with quick coupler plug
joint is leaking
51
ECS Quick Manual
ECS Manual
Appearance status of
PRU-M-001 Name Plate Weekly Cleaning it with soft cloth
name plate
Operation status of
Handle Weekly If defective, contact Techcross.
PRU-M-002 handle
Connection status
Reconnecting quick coupler
of joint and check if
socket with quick coupler plug
joint is leaking
52
ECS Quick Manual
Interval Main Check
Code Description Countermeasures
(M) Points
53
ECS Quick Manual
ECS Manual
54
ECS Quick Manual
Interval Main Check
Code Description Countermeasures
(M) Points
Attachment
Electric Sub status of
PDE-M-010 Weekly Tightening bolts and nuts
Assembly electric sub
assembly
Appearance
PDE-M-011 PCB Connection Weekly status of Tightening bolts and nuts
PCB connection
Insulation
Power Cable and status of power
PDE-M-012 Communication Weekly cable and If defective, contact Techcross
Cable communication
cable
Power Distributor Cleaning it with air brushing and
PDE-M-013 24 Cleaning PDE
Equipment soft cloth
Operation status
LCD Display Cleaning it with air brushing
CPC-M-001 Weekly of LCD display
(Touch Screen) and soft cloth
(Touch Screen)
Connection If LAN Port is defective,
CPC-M-002 LAN Port Weekly
status of LAN port contact Techcross.
Connection If USB Port is defective,
CPC-M-003 USB Port Weekly
status of USB port contact Techcross.
Operation status
Power On/Off
CPC-M-004 Weekly of power on/off If defective, contact Techcross.
Switch
switch
Appearance
CPC-M-005 Name Plate Weekly status of name Cleaning it with soft cloth
plate
55
ECS Quick Manual
ECS Manual
Appearance
CPC-M-006 Cable Entry Weekly status of cable If defective, contact Techcross.
entry
Attachment
Wall Mount status of
CPC-M-007 Weekly Tightening bolts and nuts
Bracket wall mount
bracket
Appearance
A/Vibration status of
CPC-M-008 Weekly If defective, contact Techcross.
Rubber anti-vibration
rubber
Appearance
CPC-M-009 Cable Gland Weekly status of cable If defective, contact Techcross.
gland
Overhaul CPC by ship’s service
CPC-M-010 Control PC Weekly Overhaul engineer. Refer to Appendix 4.1
CPC manual.
56
ECS Quick Manual
Interval Main Check
Code Description Countermeasures
(M) Points
Appearance
Control Panel status of If broken, contact Techcross.
TSU-M-006 Weekly
Cover control panel Cleaning it with soft cloth
cover
Connection
status of
Reconnecting coupling of flexible
Weekly WASTE
hose with WASTE male connector
male connector
and flexible hose
Connection
status of
Reconnecting coupling of flexible
Weekly BYPASS
hose with BYPASS male connector
male connector
and flexible hose
Connection
status of Reconnecting coupling of flexible
TSU-M-007 Male Connector
Weekly DIS¬CHARGE hose with DISCHARGE male
male connector connector
and flexible hose
Connection
status of Reconnecting coupling of flexible
Weekly STAR¬BOARD hose with STARBOARD male
male connector connector
and flexible hose
Connection
status of PORT Reconnecting coupling of flexible
Weekly
male connector hose with PORT male connector
and flexible hose
Check the stauts
Weekly If defective, contact Techcross.
of Air pump
Operation status
1 If defective, contact Techcross.
of pump
TSU-M-008 Air Pump
Overhaul pump by ship’s service
engineer
24 Overhaul
Refer to AppendixⅡ Air Pump
manual.
57
ECS Quick Manual
ECS Manual
58
ECS Quick Manual
Interval Main Check
Code Description Countermeasures
(M) Points
Appearance
Tightening bolts and nuts
ANU-M-005 Tank Top Cover Weekly status of
Cleaning it with soft cloth
tank top cover
Tightening bolts and nuts
Appearance
Cleaning it with soft cloth
ANU-M-006 Tower Lamp Weekly status of tower
If tower lamp is defective, contact
lamp
Techcross.
Appearance
XGT Housing status of Cleaning it with air brushing and
ANU-M-007 Weekly
Assembly XGT housing soft cloth
assembly
Appearance Tightening bolts and nuts.
ANU-M-008 Sensor Cover Weekly status of sensor Cleaning it with soft cloth
cover If broken, contact Techcross.
Appearance and
Tightening bolts and nuts.
ANU-M-009 Torque Hinge Weekly operation status
If broken, Contact to Techcross.
of torque hinge
Appearance and
Tightening bolts and nuts
ANU-M-010 Draw Latch Weekly operation status
If broken, contact Techcross
of draw latch
Appearance
Cleaning it with soft cloth
ANU-M-011 Tank Window Weekly status of tank
If broken, contact Techcross
window
Appearance
Tightening bolts and nuts
ANU-M-012 Window Plate Weekly status of window
Cleaning it with soft cloth
plate
Operation status
ANU-M-013 Level Sensor 1 If defective, contact Techcross
of level sen¬sor
Operation status
ANU-M-014 Agitator 1 If defective, contact Techcross
of agitator
Operation status
1 If broken, contact Techcross
of quantity pump
60
ECS Quick Manual
Interval Main Check
Code Description Countermeasures
(M) Points
Appearance
status of
ground¬ing ring.
FMU-M-007 Grounding Ring Weekly If defective, contact Techcross.
Check if the status
of grounding is
normal
Replace gasket every dock.
FMU-M-008 Gasket 60 Gasket of flange Refer to Appendix 7.3 Replacement
of Spare parts.
Operation status
1 Conducting self function test
of TMS pro-gram
FMU-M-009 KTM Detector Adjust flow rate and flow velocity
Adjust flow rate
60 by maker’s service engineer.
and flow velocity
Refer to Appendix Ⅱ FMU Manual
Operation status of
Weekly If defective, contact Techcross.
CSU
Appearance
Weekly Cleaning it with soft cloth
status of CSU
Conductivity
CSU-M-001 Connection and
Sensor Unit If teflon is defective, contact
Weekly leakage status of
Techcross.
CSU with ECM
Cleaning it with air brushing with
6 Cleaning CSU
an air compressor
61
ECS Quick Manual
ECS Manual
Appearance status
F.W. Temperature
FTS-M-001 Weekly of F.W. temperature If defective, contact Techcross.
Input Cable
input cable
F.W. Temperature Appearance Cleaning it with air brushing and soft
FTS-M-002 Weekly
Sensor status of FTS cloth
5.2.11 T-Strainer
62
ECS Quick Manual
5.3 Regular maintenance Procedure
63
ECS Quick Manual
ECS Manual
Step 2 : Drain the water from the filter and clean it with an air compressor (4~7kg/cm2)
Step 3 : Reassemble the filter, following instructions in reverse order (from stop 2 to step 1).
Step 4 : Check that all pipe connections and valves inside or ourside of Ex-CLX are not leaking.
64
ECS Quick Manual
5.3.1.4 Adjust pressure level of Regulator and Check the ready state
Close the door of Ex-CLX and Open the air inlet manual valve.
Check the pressure level of regulator and Set the pressure "5~7.5" mber by adjusting dial of
regulator
* CAUTION!!
Power shall not be restored after after enclosure has been opend untill Enclosure has been purged
for 5 minutes at a flow rete of 11,8 SLPM.
65
ECS Quick Manual
ECS Manual
Check whether the state lamp of Ex-CLX is flicking green (Remote mode ready)
(Green : Remote mode ready, Red : Remote mode standby / Emergency mode)
5.3.2 ANU
2)-1 Cleaning strainer of ANU tank
Step 1: Open the valve of drain line and drain the remaining neutralizing solution from both
left and right tank.
Step 2: Clean both left and right tank with freshwater.
66
ECS Quick Manual
Step 4: Open the front cover and the side cover of ANU.
Check that all pipe connections and valves are not leaking.
5.3.3 Ex-PRU
3)-1 Check leakage of cooling water connector
Step 1: Check leakage from both Inlet and Outlet cooling water connector.
Step 2: Tighten the connector using tools in case of leakage.
Step 3: Reassemble the connector if the leakage continues.
67
ECS Quick Manual
ECS Manual
5.3.4 STRAINER
1. Clean the strainer if the difference between the pressure of Inlet and Outlet is over 0.5 bar.
2. Close both front and back valves of the strainer.
3. Open drain plug (4) slowly to drain all the fluid.
4. Unscrew nut (5) to remove cover (7).
5. Remove filter (8) and clean it.
(Clean residuals with high-pressure water and air.)
6. Check condition of filter. If it is damaged, replace it with its cover Gasket (9).
7. Clean residuals in the strainer.
8. Reassemble the filter, following instructions in reverse order.
(Please consider the flow direction and shape of filter.)
68
ECS Quick Manual
5.4 Long-term Lay-up
When the system is not in use for long-term period due to the international purposes such as
“Don’t want to use before IMO D2 ratification” , long-term anchorage , etc
Component What to do
69
ECS Quick Manual
ECS Manual
Step 2: Click “Turn off” on Window XP “START” menu to turn off Main CPC and Sub CPC.
70
ECS Quick Manual
Step 3: Turn off BWMS power of MSBD.
71
ECS Quick Manual
ECS Manual
Step 3: Turn the draining rubber hose at the bottom of ANU facing outward.
Open drain valve (right and left side of the tank at the bottom) to drain neutralizing solution
from the tank.
Use air to clean up ANU strainer.
72
ECS Quick Manual
5.4.4 Close TSU valve and remove reagent (TSU Panel + Ex-CLX)
Step 1: Close Sampling valves (Port 1~3).
Step 2: Close air inlet manual valve of Ex-CLX and Verify the "0" oressure Regulator.
73
ECS Quick Manual
ECS Manual
② Drain the water from the filter and clean it with an air compressor (4~7kg/cm2)
74
ECS Quick Manual
5.4.5 Close all the Ex-ECU valves
Step 1: Close Inlet, Outlet, and Drain valves of Ex-ECU.
Step 2: Close Ex-PRU cooling water Inlet and Outlet valves of Ex-ECU.
3
2
2
75
ECS Quick Manual
ECS Manual
Step 3: To re-operate ECS, follow the instruction for “Preparation for Operation”.
76
ECS Quick Manual
5.5 Spare parts
External
No. Component Name Model
Appearance
3 DC RELAY YM2-LD
4 AC RELAY YM2-L
5 LAMP 1 YS3324(White)
6 LAMP 2 YS3324(Red)
77
ECS Quick Manual
ECS Manual
External
No. Component Name Model
Appearance
FR14AM50V50
11 PRU FUSE
(50A/500V)
MC-65A
16 Magnet Switch
MC-85A
78
ECS Quick Manual
External
No. Component Name Model
Appearance
21 Diaphragm 108839
Component External
No. Description Model
Name Appearance
JAW
Checking TRO den¬sity
(Just Add Water)
1 CLX Reagent during ballasting or
Reagents
deballasting
(12EA = 1Set)
Neutralizing TRO Pentahydate 98.5%,
Neutralizing Agent
2 density CAS No. : 10102- 17.7
for ANU
during debal¬lasting (25Kg = 1PKT)
Diluting CLX Reagent
3 Purified Water to adjust proper General Product
concentration
To order spare parts, please send e-mail to TECHCROSS or ECS dealer. For the information about ECS
dealers, please visit TECHCROSS website http://www.techcross.
79
ECS Quick Manual
ECS Manual
Caution
• CLX Reagent, a corrosive substance can cause burns on your skin and stain your clothes.
• Do not handle this reagent without protective equipment such as protective clothes, gloves and
glasses.
• Do not work when the Ex-CLX is high pressured by air because you did not close the air inlet
valve.
80
ECS Quick Manual
Step 3: Remove the old Ex-CLX Reagent (Chlorine Indicator, Buffer Solution)
Step 5: Clean the both tube by injecting fresh water to the tube with flushing kit.
(Flushing kit is placed inside of EX-CLX.)
Step 6: Install the Buffer Solution (on the right side of EX-CLX sensor)
Remove the cap of buffer solution. Insert the hose into the solution.
81
ECS Quick Manual
ECS Manual
Step 7 : Install the Chlorine Indicator (on the left side of EX-CLX sensor)
Remove the cap of chlorine Indicator. Insert the hose into a new solution
Switch to XGT “F1” EMERGENCY Mode. Press “F3” and Make sure that B/P1 is Selected.
82
ECS Quick Manual
Press PRIME button. Press ENTER. Set as approximately “70 times pumping”. Check
injection of Reagent.
Press " ◀" to stop → Make sure that Ex-CLX power is OFF
83
ECS Quick Manual
ECS Manual
84
ECS Quick Manual
Step 3: Press “F1” button for the left tank and “F3” for the right tank to operate each agitator.
The operation of agitator will be stopped after approximately 15 to 20 minutes.
Check [RDY] on XGT after the agitators are stopped.
Re-operate the agitator (stirrer) until the neutralization solution is completely dis-solved if
Caution it is not dissolved due to certain circumstances or water temperature.
Sodium Thiosulfate
Caution
85
ECS Quick Manual
ECS Manual
TROUBLESHOOTING
Head Office/Factory
84 Younginsan-ro, Inju-myeon, Asan-si, Chungcheongnam-do, Korea. (336-833)
Tel : +82-41-420-9032(Rep.) Fax : +82-41-420-9090 http://www.techcross.com
86
ECS Quick Manual
6. TROUBLESHOOTING
87
ECS Quick Manual
ECS Manual
1. Click one of four items on Query Condition I (All / Normal / Warning / Fault) to sort out the list of
alarms.
A. “ALL” button: All of log level will be sorted & displayed.
B. “Normal” button: Only the NORMAL part of log level will be sorted & displayed
C. “Warning” button: Only the WARNING part of log level will be sorted & displayed.
D. “Fault” button: Only the FAULT part of log level will be sorted & displayed.
2. Click one of two items on Query Condition II (TODAY / ALL) to sort out the list of alarms.
A. “TODAY” button: Only the alarms which occurred on today will be sorted & displayed.
B. “ALL” button: All alarms during operation will be sorted & displayed.
Error
[CODE7] TRO concentration High. TRO[Value] Pump[Number]
message
Alarm TRO concentration in Ballast >10mg/L
(warning) (The alarm will operate after 5 minutes since ECS starts)
TRO concentration in Ballast >11mg/L
Fault
(If status continue during 10 minutes)
TSU (1) Measure the TRO concentration with pocket colorimeter in the spare
parts box on your own.
(2) Compare TRO concentration measured by pocket colorimeter with
Trouble TRO level as shown on the HMI.
shooting (3) If TRO level on HMI is higher than the level by the colorimeter, restart
TSU after replacing CLX reagent.
(4) If the problem persists, stop operating ECS and contact Techcross A/S
team.
88
ECS Quick Manual
Device List Description
Error
[CODE8] TRO concentration Low. TRO[Value] Pump[Number]
message
Alarm TRO concentration in Ballast > 5mg/L
(warning) (The alarm will operate after 5 minutes since ECS starts)
TRO concentration in Ballast > 4mg/L
Fault
(If status continue during 10 minutes)
(1) Check if other valves except the valve for sampling are closed.
(2) Check that sampling water flows smoothly into TRO sensor.
(3) While sampling water is flowing in, if message (Too fast / slow) pops
up, adjust regulator adequately.
Trouble
(4) Check the expiration date (1 month) of CLX reagent. If it is expired,
shooting
replace the CLX reagent.
(5) Measure TRO level with pocket colorimeter.
(6) If TRO level measured by colorimeter is lower than standard, contact
Techcross A/S team.
Error
[CODE7] TRO concentration High. TRO[Value] Pump[Number]
message
TSU Alarm TRO concentration in De-ballast > 0.1mg/L
(warning) (The alarm will operate after 5 minutes since ECS starts)
TRO concentration in De-ballast > 0.2mg/L
Fault
(If status continue during 10 minutes)
(1) Check that sodium thiosulfate has been added to ANU tank.
(2) Check if other valves except the valve for sampling are closed.
Trouble (3) Check that the valve for sampling is not clogged up and pump in the
shooting ANU is properly working.
(4) If TRO level is over standard when neutralizing agent is injected
properly, contact Techcross A/S team.
Error
[CODE72] Unit EM'CY Mode.
message
Alarm
If operation mode is Emergency
(warning)
Fault
Trouble (1) Check if selector switch of TSU control panel is in Emergency Mode.
shooting (2) If yes, switch to Remote Mode according to the manual.
89
ECS Quick Manual
ECS Manual
90
ECS Quick Manual
Device List Description
Fault
ANU (1) Check if operation mode on ANU control panel is set to Remote
Trouble
Mode.
shooting
(2) If not, reset it to Remote Mode according to the manual.
Error [CODE39] The input Voltage Low.
message PMU[number]Value[Value]
Alarm
Master input voltage is < 440V-15% (374V)
(warning)
Fault Master input voltage is < 440V-20% (352V)
(1) Check if voltage from MSBD is normal after turning off MCCB of PDE.
Trouble
(2) If voltage from MSBD is normal, measure insulation resistance of ECS.
shooting
PMU (3) If insulation fails, contact Techcross A/S team
Error [CODE40] The input Voltage High.
message PMU[number]Value[Value]
Alarm
Master input voltage is > 440V+15% (506V)
(warning)
Fault Master input voltage is > 440V+20% (528V)
Trouble
Check whether the voltage from MSBD is normal or not
shooting
Error
[CODE77] The F.W Pump / S.W Pump confirmed
message
Trouble
The freshwater pump / seawater pump signal should be confirmed.
Freshwater shooting
Pump Fault Shutdown if alarm lasts more than one minute
&
Seawater (1) Check leakage, damage and insulation of seawater / freshwater
Pump pump.
(2) If the pump is okay, check EOCR in the PDE. If EOCR shows fault,
Trouble
reactivate it after resetting
shooting
(3) If EOCR fails again, try again after raising load of EOCR by a notch on
clockwise.
(4) If the problem persists, contact Techcross A/S team.
91
ECS Quick Manual
ECS Manual
Error
[CODE49] FMU Flow rate is high. FMU[Number] Value[Value]
message
Alarm
Flow velocity >110% m3/h
(warning)
Flow velocity >115% m3/h
Fault
(If status continue during one minutes)
(1) Regulate the flow rate so that the flow does not exceed 110% of ECS
capacity.
(2) If flow rate on HMI shows -20 value, check if power supply and cable
Trouble
connection of FMU are normal.
shooting
(3) If they are normal, refer to the troubleshooting for sensor failure as
described in communication.
(4) If FMU display shows errors, contact Techcross A/S team.
FMU
Error
[CODE48] FMU Flow rate is Low. FMU[Number] Value[Value]
message
Alarm
Flow velocity >15% m3/h
(warning)
Flow velocity >10% m3/h
Fault
(If status continue during one minutes)
(1) Regulate the flow rate so that the flow can exceed at least 15% of ECS
capacity.
(2) If flow rate on HMI shows -20 value, check if power supply and cable
Trouble
connection of FMU are normal.
shooting
(3) If they are normal, refer to troubleshooting for sensor failure as
described in communication.
(4) If FMU display shows errors, contact Techcross A/S team.
92
ECS Quick Manual
Device List Description
Error
[CODE50] Detected H2 Gas. GDS[Number] Value[Value]
message
Alarm
H2 gas concentration > 25% LEL
(warning)
Fault H2 gas concentration > 50% LEL
GDS (1) Turn off MCCB of PDE or MSBD and check if alarm for H2 gas rings
through AMS of the vessel.
(2) Check if there is any leakage of H2 gas with H2 gas detector equipped
Trouble
in the vessel.
shooting
(3) If alarm rings or GDS shows - 20 value when there is no leakage of H2
gas, check if power and cable connection is normal.
(4) If no problem is found, refer to the troubleshooting for sensor failure.
Error
[CODE59] PDE EM'CY Stop. PDE[Number].
message
Alarm
(warning)
The PDE operation has been stopped by an operator as an emergency
Fault
PDE measure PDE[Number]
(1) If Emergency Stop Button on PDE is on, release the button by turning
it clockwise.
Trouble (2) If fault continues, check malfunction of button and cable connection
shooting to RTU for Emergency signal.
(3) If fault persists without connection problems, contact Techcross A/S
team.
Error
[CODE46] The Current Higt. ESJ[Number] Value[Value]
message
Alarm
Current > (Number of PRU per ECU x 1125A)
ESJ (warning)
Fault Current > (Number of PRU per ECU x 1150A)
Trouble (1) Check if selector switch is in Emergency Mode.
shooting (2) If yes, switch to Remote & Local Operation Mode.
93
ECS Quick Manual
ECS Manual
Error
[CODE72] Unit EM'CY Mode
message
Alarm
If RCM Select switch is chaged (Emergency mode)
(warning)
Fault
Trouble (1) Check if selector switch is in Emergency Mode.
shooting (2) If yes, switch to Remote & Local Operation Mode.
Error
[CODE33] ECU EM'CY State (High Press ).
message
Alarm
(warning)
94
ECS Quick Manual
Device List Description
Error
[CODE42] F.W TEMP. High. FTS[Number] Value[Value]
message
Alarm
freshwater temperature(Outlet) is >43℃
(warning)
Fault freshwater temperature(Outlet) is >45℃
Error
[CODE71] 440V MC Fail.
message
Alarm
(warning)
Fault 440V Magnet malfunction
(1) Refer to the following instructions to check if magnetic contactor is
defective.
Magnetic - Turn off the MCCB of PDE or MSBD to cut off power to ECS.
Contactor - If the contactor has no short circuit, fasten loose cables tightly after
checking cable connection.
Trouble - Check insulation resistance of 440V line in PDE.
shooting - Contact Techcross A/S team if no problem is found with insulation.
- If the contactor is found to be defective, replace the contactor
without repair.
- If the problem persists, contact Techcross A/S team.
(2) If power of ECS shuts off automatically of itself within 1 min after the
magnetic contactor fails, contact Techcross A/S team immediately
without checking the magnetic contactor on your own.
95
ECS Quick Manual
ECS Manual
Error
[CODE2] Communication [device name]
message
Alarm
Failure of communication between ECS equipment.
(warning)
Fault Shutdown if communication failure lasts more than one minute.
(1) In case of communication failure in CPC / RTU / ESJ / PRE / ANU / TSU
/ ADAM relating to LAN
- Check power supply & LAN cable connection between HUB and
each module above.
Communication (2) In case of communication failure in ESJ / PRE / PMU / ANU / TSU
relating to RS-485
- Check power supply & communication cable connection between
Trouble of KG-30 and each module above.
shooting (3) In case of communication failure in sensors
- Check power supply & communication cable connection between
ADAM-6017 and each module above.
(4) Check if MCCB in the PDE is on. If it is turned off, turn it on
(5) If MCCB is not working properly after it is turned on, contact
Techcross A/S team.
(6) If communication failure persists without power & connection
problems, contact Techcross A/S team.
96
ECS Quick Manual
6.3 Main Problems and Measures
Problem:
- ECS shuts down one minute after alarm message “The flow rate is higher the regulated standards”
appears.
Reason:
- Flow rate is above the normal range. (Normal Range: 10% ~ 110% of pump capacity)
Solution:
- Valve throttling is required to ensure that the measured flow rate of FMU is within the normal
range of rated flow of ECS.
- Lower the flow rate by turning the valve to the close direction. (Make sure that the flow rate of
ECS is within normal range.)
Problem:
- ECS shuts down 10 minutes after alarm message, “The amount of TRO concentration is lower
than the regulated standard” appears.
Solution:
- Close Air inlet manual valve of Ex-CLX and Verfity the "0" pressure of Regulator
97
ECS Quick Manual
ECS Manual
Switch to XGT "F1" EMERGENCY MODE Pressure "F3" and Make sure that B/P1 Selected
Press " ◀" to stop → Make sure that Ex-CLX power is OFF
98
ECS Quick Manual
1. When Sampling water does not flow into the Ex-CLX sensor:
1). Check whether Air Pump Unit (APU) is normally working or not.
2). Check whether pipe or SV(Solenoid Valve) is clogged up or not.
3). When the pipe or SV is clogged up, disassemble the Solenoid valve and remove the foreign
materials after disassembling
(Please refer to 7.3.3 Procedure for maintenance of Ex-Soleniod valve)
2. When the same problem persists even if sampling water flows into the sensor:
1). Check replacement date of Ex-CLX Sensor.
(Please refer to “Check points before operation-Selecting Remote mode
and Checking Supplies -step3”.)
2). Make sure to prevent air coming into the tube between CLX reagent and the Ex-CLX
when replacing the solution.
(Please refer to “Replacement of Supplies–Replacement of Ex-CLX Reagent”.)
3). If the same problem persists, please contact the manufacturer.
3. If ECS operates outside the range of the salinity from 0.2 to 4.2%, it is not possible to produce normal
TRO concentrations.
If Ex-CSU displays the value lower than 1.7ms, ECS may not operate properly.
(There are exceptions in case control valve for conductivity concentration is supplied as an option.)
99
ECS Quick Manual
ECS Manual
Problem:
- ECS shuts down 1 minute after alarm message “The communication failure has occurred
between PRE and RCM” appears.
Solution:
- Please refer to “Troubleshooting for communication section of the equipment”.
Problem:
- It is not sure which valve to control to operate ECS.
Solution:
- Please refer to “Troubleshooting for automatic operation of ECS”.
Problem:
- ECS shuts down 10 minutes after alarm message “The amount of TRO concentration is lower
than the regulated standard” appears.
Reason:
- Discharged neutralizing solution is not injected to the pipe properly during deballasting operation.
- Outlet pipe of ANU is clogged up.
Solution:
- Disassemble the ANU Solenoid valve and clean the inside of the valve in case ANU is not in
operation for a long period.
100
ECS Quick Manual
APPENDIX
Head Office/Factory
84 Younginsan-ro, Inju-myeon, Asan-si, Chungcheongnam-do, Korea. (336-833)
Tel : +82-41-420-9032(Rep.) Fax : +82-41-420-9090 http://www.techcross.com
7. APPENDIX
Additional functions are the functions that are not controlled by nor viewed on HMI screen. Using
them, an operator may check RTU operation state, log file, communication state between PDE and ECS
components, operation state of ECU component and values.
102
ECS Quick Manual
7.1.1 Log
< Combined Logs >
1. Click “MENU” button on the bottom right of HMI screen.
2. Log window appears when clicking “Log” on MENU screen.
103
ECS Quick Manual
ECS Manual
2. Click one of four items on Query Condition I (All / Normal / Warning / Fault) to sort out the list of alarms.
A. “ALL” button: All of log level will be sorted & displayed.
B. “Normal” button: Only the NORMAL part of log level will be sorted & displayed
C. “Warning” button: Only the WARNING part of log level will be sorted & displayed.
D. “Fault” button: Only the FAULT part of log level will be sorted & displayed.
3. Click one of two items on Query Condition II (ALL / Period) to sort out the list of alarms.
A. “ALL” button: All alarm during operation will be sorted & displayed.
B. “Period” button: Only the alarms which occurred on today will be sorted & displayed.
5. Click “Close” to go back to HMI’s main menu.
104
ECS Quick Manual
< Operation Time >
ECS records running time to check its replacement time and operating hours. This information can be
checked on HMI screen.
1. Operation Time window appears when clicking “Operation Time” on the bottom right of Log screen.
2. Click one of two items on Query Condition II (ALL / Period) to sort out the list of alarms.
A. “ALL” button: All alarm during operation will be sorted & displayed.
B. “Period” button: Only the alarms which occurred on today will be sorted & displayed.
105
ECS Quick Manual
ECS Manual
2. Click one of two items on Query Condition II (ALL / Period) to sort out the list of alarms.
A. “ALL” button: All alarm during operation will be sorted & displayed.
B. “Period” button: Only the alarms which occurred on today will be sorted & displayed.
106
ECS Quick Manual
7.1.2 Comm. Status (Communication Status)
It monitors the communication state between and among ECS components, which are connected to PDE,
in real time.
107
ECS Quick Manual
ECS Manual
3. It checks numbers / values and states of ECS components. To see the state of ESJ, ANU and PDE, click
“Next” button.
As a component attached on PDE [refer to Chapter 3, Section 2, 3.2.3 Main Components, 1) RTU], RTU
consists of two DI (digital input) cards and one DO (digital output) card, with which an operator can see
the control state of each component on HMI screen. In addition, the control state of each PDE can be also
checked by pressing .
108
ECS Quick Manual
<RTU (Romote Terminal Unit)>
As a component attached on PDE [refer to Chapter 3, Section 2, 3.2.3 Main Components, 1) RTU], RTU
consists of two DI (digital input) cards and one DO (digital output) card, with which an operator can see
the control state of each component on HMI screen. In addition, the control state of each PDE can be also
checked by pressing .
109
ECS Quick Manual
ECS Manual
110
ECS Quick Manual
7.1.5 Operation View
111
ECS Quick Manual
ECS Manual
2. Current Status
3. Select Condition
4. Required Signal
5. Ship's signal
Operation
1 Current state of valve, pump, etc.
Condition Monitor
Current state of operation
2 Current Status Green light indicates that conditions of ship correspond to requirements
for ECS operations.
Selection of Ballast / Deballast / Stripping operation
3 Select Condition Requirements of ECS operations for selected mode are displayed in
Required Signal.
Required Signal
4 Requirements of ECS operation for selected mode
for Operation
5 Ship’s Signal Real-time information on Operation condition of VALVE, PUMP, etc.
112
ECS Quick Manual
7.1.5.3 Selecting and Operating ballast Mode
113
ECS Quick Manual
ECS Manual
Step 2: Ship’s Valve and Pump signal of ship will be displayed in Ship’s Signal.
Match Ship’s Signal (ship’s conditions) with Required Signal.
If these two requirements match, Deballast in Current Status will be selected automatically.
(“ Deballast Operation”)
If “Deballast operation” is not selected, match the ship’s conditions with operating requirements.
114
ECS Quick Manual
7.1.5.5 Selecting and Operating Stripping Mode
115
ECS Quick Manual
ECS Manual
116
ECS Quick Manual
7.1.6.2 Simulation Mode Display
• Added Simulation button as the lower end of left. Remark Simulation Mode by Biink.
• Marked Sensor in Orange that could be configurable.
• Simulation value renews REAL value before Simulation value sets up, and the value is fixed
after it. (Marked " * " for setting Simulation value and Simulation setting for changed control
color of sensor)
117
ECS Quick Manual
ECS Manual
• If we click the sensor of HMI UI, okay to set up the Simulation value on the window of
Simulation setting.
118
ECS Quick Manual
• Click AI Sensor Button to change value of AL Sensor
• Click ECU Button, it is possible for ECU Current and Pressure Switch Signal to set up Click top of
"Emergency Status" Button for setting of Pressure Switch Signal.
119
ECS Quick Manual
ECS Manual
• Click TRO Button to change TRO value and Alarm & Fault
120
ECS Quick Manual
• Click Alarm / Fault time Button, TRO Alarm / Fault Delay Time by the Pop-up sign is changed
30sec(Alarm), 60sec(Fault) relatively.
• Initialize Value
- Click "Simulation" button at the lower left of Main UI, the message is shown to check
initialization. Click "Yes", the Simulation Value can initialize.
(Initialized simulation value renews Real Value)
121
ECS Quick Manual
ECS Manual
122
ECS Quick Manual
< Description of Unit Enable / Disable >
123
ECS Quick Manual
ECS Manual
124
ECS Quick Manual
4. Copy File [AlarmDB.mdb].
125
ECS Quick Manual
ECS Manual
126
ECS Quick Manual
7.1.9 Reading operation signs of HMI
ECS can check the specific operation state of ECS components thru HMI.
During Normal Operation of ECS, each indication lamp on HMI shows light green color.
Conversely, when ECS is abnormal status or not in operation, each lamp shows dark green color.
Digital Power Meter is the equipment to measure the input voltage and current consumption of
main power, which is supplied to PDE. The measurement appears on LCD of Digital Power Meter.
The operating range of current consumption is between 0 and 60A while the operating range of
input voltage is between 380 and 480V.
• Alarms on PDE
If current is higher than the limit or main power is disconnected, alarm rings and HMI stops ECS
operation automatically.
127
ECS Quick Manual
ECS Manual
If power is supplied to ECU during ballasting, ECU indication lamp is ON. Then, ESU installed on
each EM measures the current consumption.
Two CLX sensors are installed on TSU while HMI calculates TRO concentration measured by
these two CLX sensors. If either sensor is malfunctioning, it shows the TRO concentration from the
CLX that works properly.
128
ECS Quick Manual
Operation Sign Status Description
129
ECS Quick Manual
ECS Manual
There are two fresh water tanks to inject neutralization solution. In case of normal communication
state during deballasting, ANU is displayed on HMI screen as above.
If one fresh water tank uses up neutralization solution, the other fresh water tank will be filled with
neutralization solution automatically. Then, fresh water is automatically supplied to a fresh water
tank using up the solution. Indication lamp will be ON if fresh water is filled up to a specific level.
When indication lamp blinks, ECS operator has to inject neutralization solution and then operate
the agitator.
130
ECS Quick Manual
7.1.9.5 Sensors
Sensors installed on ECS contain CSU. GSU is installed in PDE. FMU is installed in FMU. Other
sensors are displayed on HMI screen as follows.
131
ECS Quick Manual
ECS Manual
F/W Supplied
Insufficient D/W
On Supplying D/W
Ready to operate
CLX Stop
CLX Run
TSU
Insufficient Reagent
Error Occurrence
132
ECS Quick Manual
7.2 Additional Functions of Equipment
133
ECS Quick Manual
ECS Manual
7.2.2 RCM(M1)
RCM consists of 4 Digit 7-Segment LEDs, and MODE / SET buttons; setting and checking menus
as well as controlling and monitoring PRU will be done with the buttons.
134
ECS Quick Manual
7.2.3 RCM(M4)
RCM consists of 4 Digit 7-Segment LEDs, and MODE / SET buttons; setting and checking menus
as well as controlling and monitoring PRU will be done with the buttons.
135
ECS Quick Manual
ECS Manual
7.2.4 TSU
136
ECS Quick Manual
7.2.4.2 Configuration of TSU XGT control panel
1 2
3 4
8 5 6 7 9
The text shadow is changed and dark color indicates the current selection
137
ECS Quick Manual
ECS Manual
1. PASSWORD UNLOCK
2. PASSWORD LOCK
3. PASSWORD CHANGE
4. DATE/TIME SET
5. BUZZER VOLUME SET
6. BACK LIGHT SET
7. DOWNLOAD SPEED
8. SYSTEM INFORMATION
138
ECS Quick Manual
7.2.5 ANU
139
ECS Quick Manual
ECS Manual
1 3
2 4
8 9 5 6 7 10
140
ECS Quick Manual
7.2.5.3 Icons used in ANU XGT control panel
Left fresh water tank not Right fresh water tank not
ready ready
Left fresh water tank ready Right fresh water tank ready
Abort the valve on the left Abort the valve on the right
fresh water tank fresh water tank
Choose the valve on the left Choose the valve on the right
fresh water tank fresh water tank
Supply the left fresh water Supply the right fresh water
tank with fresh water tank with fresh water
141
ECS Quick Manual
ECS Manual
7.3.1.1 Relay
Voltage: DC 24V Voltage: AC 220V
142
ECS Quick Manual
Step 1: Remove Relay supporting hook.
Step 2: Remove defective Relay by shaking up and down.
Step 3: Install a new relay in the relay socket after checking voltages.
(LED Lamp Color: red - AC220V / blue - DC24V)
Step 4: Check the operation.
(LED Lamp light and operation state)
(White) (Red)
143
ECS Quick Manual
ECS Manual
Step 1: Disassemble lamp part and Acryl cover with a screw driver.
Step 2: Remove lamp from the lamp part with a screw driver.
Step 3: Check socket and voltages of a new lamp and reassemble the lamp, following instructions
in reverse order (from step 2 to step 1).
Step 4: After the power is ON, check the operation state using lamp test switch.
144
ECS Quick Manual
Step 1: Take apart the power part of button lamp and remove the defective lamp by turning to the
left.
Step 2: Remove defective lamp by turning 90 degrees to the left while pressing inward.
Step 3: Check color and voltages of a new lamp and replace it, following instructions in reverse
order (from step 2 to step 1).
Step 4: After the power is ON, Check operation of lamp. (Lamp light)
145
ECS Quick Manual
ECS Manual
Step 1: Remove body / pipe / wiring of defective SOL V/V with a screw driver and a wrench.
Step 2: Check installation direction of a new SOL V/V and replace it, following instructions in
reverse order (from step 2 to step 1).
Step 3: After the power is ON, Check operation state.
7.3.1.5 PT-Fuse
146
ECS Quick Manual
Step 1: Check the connection of Fuse (1A) of P, T, R and S by using a tester
Step 2: Remove disconnected fuse with a screw driver
Step 3: Assemble new fuse in the fuse holder
Step 4: Check voltage value of Power Meter
147
ECS Quick Manual
ECS Manual
Air Regulator
1. Intake / Delivery connections : 1/2" - Supply Air pressure of : 10bar
2. Air connection : 3/8"
2 Air Pump 3. Max flow rate : 50L/min
4. Max Head : 70m
5. Max Air supply pressure : 7bar
148
ECS Quick Manual
No. Item Description Remark
1. Material : Steel
6 Hose Storage Box
2. Size : 700 X 700 X 380
149
ECS Quick Manual
ECS Manual
ECS 150 60 80 8 10
ECS 300 80 100 10 10
ECS 450 110 130 13 10
ECS 600 140 160 16 10
ECS 1000 250 270 27 10
150
ECS Quick Manual
7.3.2.3 Circulating cleaning agent
151
ECS Quick Manual
ECS Manual
1. Drain sea water from chamber through Drain (D1, D2) of ECU.
D2
D1
T2
152
ECS Quick Manual
7.3.2.4 Collecting Cleaning agent
<Horizontal type>
<Vertical type>
153
ECS Quick Manual
ECS Manual
Connector
C3
C4
Connector
5. Drain waste water containing cleaning agent and open valves (V3, V4) to clean inside of ECU.
V3
6. Close Valve (V3) after flushing out fresh water for approximately 15 minutes.
7. Disassemble the Pipe Ass'y-1 ~ Pipe Ass'y-3.
8. Dispose of the collected cleaning agent according to the rules and regulations.
154
ECS Quick Manual
7.3.3 Procedure for maintenance of solenoid Valve
Step 1: Turn off the power of ANU.
155
ECS Quick Manual
ECS Manual
156
ECS Quick Manual
Step 7: Disassemble the inner pipe of Solenoid Valve.
Step 8: Immerse the valve in hot water (over 60℃) for 3 minutes and clean inside of the valve with
an air compressor (4~7kg/cm2).
Step 9: Reassemble the valve, following instructions in reverse order (from step 6 to step 1).
157
ECS Quick Manual
ECS Manual
Step. 3 Make sure that flushing with all pipes (Port#1, Port#2, and External) are operating.
Step. 4 After Flushing, Press “ESC” button to enter Menu of XGT Panel and select “1.Remote
Mode” using up / down button and Press “ENT”.
158
ECS Quick Manual
7.3.5 When HEU / FTU are located in BWTS room on deck without heater
5. Refill the tank with cooling water up to more than medium level of FTU after 2 and 3.
159
ECS Quick Manual
ECS Manual
Caution
• Anti-freeze liquid is hazardous to health. Avoid contact with the eyes and skin.
• Never use only water as coolant because it will cause corrosion and cavitation.
160
ECS Quick Manual
7.3.6 Procedure for maintenance of EX- Solenoid Valve
Step 1: Open the door and Turn off the power of TSU.
-----
161
ECS Quick Manual
ECS Manual
162
ECS Quick Manual
7.4 Detailed Troubleshooting Procedure
7.4.1 PDE
Problem:
• ECS shuts down 1 minute after alarm message “Communication Failure ” appears.
Solution:
• Check the state of CAN communication of RCM in the PDE.
163
ECS Quick Manual
ECS Manual
Problem:
• The sub CPC of PDE is not turned on.
Solution:
• Check the power of sub CPC of PDE, as shown in the picture.
• Check if power and communication cables are connected properly.
• Check if the power switch is “ON”.
• If it is not turned on with its switch “ON”, check the fuse of CPC.
• If the fuse is broken, replace it with new fuse for CPC.
• (Refer to “maintenance of spare part” for replacement. (P.xxx))
• If the same problem persists, please contact the Techcross.
164
ECS Quick Manual
7.4.2 TSU
Problem:
• TSU is not turned on.
Solution:
• Check breaker in the TSU and make sure it is “ON”.
* In case circuit breaker shuts off automatically, do not turn it on and contact the Techcross.
Problem:
• Communication Failure between HMI and TSU
Solution:
• Check connection of the cables linked to PDE communication parts. If the cables are loose,
connect them tightly again until a “click” sound is made.
• If the same problem persists when there is no problem with cables and LED LAMP, please
contact the Techcross.
165
ECS Quick Manual
ECS Manual
7.4.3 ANU
Problem:
• ANU is not turned on.
Solution:
• Make sure that circuit breaker of ANU is “ON”.
* In case circuit breaker shuts off automatically, do not turn it on and contact the Techcross.
Problem:
• Failure of communication between HMI and ANU
Solution:
• Check connection of the cables linked to PDE communication parts. If the cables are loose,
connect them tightly again until a “click” sound is made.
• If the same problem persists when there is no problem with cables and LED LAMP, please
contact the Techcross.
166
ECS Quick Manual
7.4.4 ECU (EX-PRU)
Problem:
• ECS shuts down immediately after alarm message “PRU module Fault ” appears.
Reason:
• There are problems in EX-PRU of EX-ECU.
• Insufficient cooling water causes overheating of EX-PRU.
Solution:
• Make sure that manual valves (front and back of EX-PRU cooling pipe) are open.
(Refer to check points before operation.)
7.4.5 SENSOR
Problem:
• ECS shuts down 1 minute after alarm message "The sensor communication failed
Value=-20 ” appears.
Reason:
• Sensors (FMU/GDS) fail to transmit the values due to communication failures.
Solution:
• Check if the power of each sensor is “ON”.
• Check connection of communication cables attached to each sensor.
• If all the sensors are found to be defective, check power state and connection of cables &
connectors in the PDE.
• If the same problem persists, please contact the Techcross.
167
ECS Quick Manual
ECS Manual
7.4.6 EX-FTU
Problem:
• ECS shuts down immediately after alarm message “The freshwater is insufficient ” appears.
Reason:
• Cooling water level in EX-FTU TANK is lower than water level sensor.
Solution:
• Need to provide sufficient cooling water to cool down EX-PRU of EX-ECU
• Open the valve installed in the Inlet and Outlet of EX-FTU.
(Refer to check points before operation.)
Check leakage from EX-FTU TANK and EX-ECU (EX-PRU) Cooling pipes.
• Supply cooling water (fresh water) if the cooling water is insufficient. (in case of long-term storage)
• If the same problelm persists, please contact the Techcross.
168
ECS Quick Manual
7.4.7 HEU
Problem:
• ECS shuts down immediately after alarm message “The fresh water tem¬perature is higher
than the regulated tempera¬ture ” appears.
Reason:
• The temperature of cooling water is over 40℃
Solution:
• Check if sea water is supplied properly.
• Check if there is any problem with circulation of sea water and cooling water which can
be caused by foreign materials in the HEU through a pressure gauge and a thermometer
installed in HEU.
169
ECS Quick Manual
Certificate Number: 11-BK774755/2-PDA
01/JAN/2014
01/01/2014 5:02:41 PM Copyright 2001 American Bureau of Shipping. All rights reserved. Page 1 of 2
Certificate Number: 11-BK774755/2-PDA
ABS Programs
ABS has used due diligence in the preparation of this certificate and it represents the information on the product in the ABS Records as of the
date and time the certificate was printed. Type Approval requires Drawing Assessment, Prototype Testing and assessment of the
manufacturer's quality assurance and quality control arrangements. Limited circumstances may allow only Prototype Testing to satisfy Type
Approval. The approvals of Drawings and Products remain valid as long as the ABS Rule, to which they were assessed, remains valid. ABS
cautions manufacturers to review and maintain compliance with all other specifications to which the product may have been assessed. Further,
unless it is specifically indicated in the description of the product; Type Approval does not necessarily waive witnessed inspection or survey
procedures (where otherwise required) for products to be used in a vessel, MODU or facility intended to be ABS classed or that is presently in
class with ABS. Questions regarding the validity of ABS Rules or the need for supplemental testing or inspection of such products should, in all
cases, be addressed to ABS.
01/01/2014 5:02:41 PM Copyright 2001 American Bureau of Shipping. All rights reserved. Page 2 of 2
Commandant 2703 Martin Luther King Jr. Ave. SE
United States Coast Guard Washington, DC 20593-7509
Staff Symbol: CG-OES
Phone: 202-372-1431
Fax: 202-372-1926
Email: [email protected]
5760
October 4, 2013
Techcross Inc
Attn: Dr. Dong H. Shon
25-1 Kwanam-ri, Inju-myun, Asan
Chung Nam 336-833
Republic of Korea
The Coast Guard has completed its review of the Alternate Management System (AMS)
application submitted by Techcross Inc. for the Electro-Cleen ballast water treatment system
(BWTS). This letter grants AMS acceptance in accordance with the requirements of 33 CFR
151.2026 for the following Electro-Cleen BWMS models:
The Electro-Cleen BWTSs are assigned the following AMS identification number:
Coast Guard acceptance of the Electro-Cleen BWTS as an AMS does not accord or imply
conformance to or compliance with any other Federal, state, or local water discharge effluent
limitations that may apply to the vessel on which the AMS operates or the regulatory regimes
and locations within which it operates. The owner and operator of the vessel must comply with
all applicable laws, regulations, and treaties, including the Clean Water Act and associated
provisions of the Vessel General Permit (VGP); the Federal Insecticide, Fungicide, and
Rodenticide Act of 1972, as amended (FIFRA); other Coast Guard safety regulations and
requirements; and other applicable laws and regulations.
Subj: AMS ACCEPTANCE LETTER – Techcross-Electro-Cleen 5760
October 04, 2013
In accordance with 33 CFR 151.2026 (a)(5), the AMS application required the submittal of a
type approval application for the BWTS. The type approval information submitted with the
AMS application does not have any bearing on the type approval status of the BWTS, nor does
Coast Guard acceptance of the Electro-Cleen BWTS as an AMS indicate that the BWTS meets
requirements for Coast Guard type approval.
The following conditions apply for the operation of the Electro-Cleen BWTS in U.S. waters:
1. The AMS manufacturer must comply with all general conditions of certification
stipulated in the type approval certificate issued by the Republic of Korea, as referenced
above. Revocation of type approval by the approving authority will result in revocation
of this AMS acceptance. Copies of all reports required under the stated conditions of use
must be submitted to the Office of Environmental Standards (OES-3) at the following
address or email:
COMMANDANT (CG-OES-3)
United States Coast Guard Stop 7509
2703 Martin Luther King Jr. Ave SE
Washington DC 20593-7509
Tel: 202-372-1402
e-mail: [email protected]
2. Because the AMS has not been adequately tested in freshwater, its use as an AMS is
limited to the treatment of marine and brackish water with a practical salinity unit (PSU)
concentration greater than 1.
3. Installation and repairs of the AMS must be performed in accordance with the
manufacturer’s instructions and approved by the flag administration or its representative.
4. Operation and maintenance must be conducted in accordance with all specifications and
limiting conditions stipulated on the certificate of type approval and with the
manufacturer’s instructions, including any limitations posed by environment (for
example, water quality, temperature, salinity, or other parameters) or vessel operations
(for example, voyage duration, pumping rates, or other constraints). The following
specific conditions apply:
a. Flow rates: The flow rate of ballast water through the system should not exceed the
treatment rated capacity (TRC) for the installed system.
2
Subj: AMS ACCEPTANCE LETTER – Techcross-Electro-Cleen 5760
October 04, 2013
A historical record documenting that the system has been operated within these criteria,
including a record of any alarm conditions, shall be made available for review onboard
the vessel.
5. In accordance with the type approval by the Republic of Korea, Electro-Cleen systems
may be combined in parallel to achieve higher TRCs. Flow partitioning to each
individual system must be approved by the flag administration or its representative before
installation.
6. If installed on a U.S. flag vessel, it must be shown that the system and installation comply
with or provide an equivalent level of safety to the requirements of 46 CFR Subchapter F
(Marine Engineering) and Subchapter J (Electrical Engineering). All electrical
equipment located within hazardous areas must be explosion proof or intrinsically safe as
certified by an independent laboratory recognized by USCG per 46 CFR 111.105-7.
7. Use of the AMS is specified in the ship’s ballast water management plan (BW plan),
required by 33CFR 151.2050(g). The BW plan must identify: (1) the ballast water
management practices to be used in the event the AMS cannot be used and (2) the
personnel responsible for the operation, maintenance, and repair of the BWTS. An up-to-
date record of the operation, maintenance, and repair of the BWTS must be maintained
onboard the ship.
3
Subj: AMS ACCEPTANCE LETTER – Techcross-Electro-Cleen 5760
October 04, 2013
The notification must include: (1) a description of the change, the reason it is required,
and its intended advantages; (2) an explanation of any effect of the change on installation,
operation, maintenance, or repair requirements; and (3) an indication of whether or not
the original configuration of the BWTS will be discontinued.
9. If the installed AMS does not operate properly when treating ballast water intended for
discharge in U.S. waters, the person directing the movement of the vessel must ensure
that the problem is reported to the nearest Coast Guard Captain of the Port (COTP) or
District Commander as soon as practicable. The Coast Guard shall be notified of any
treatment system or component failures, irreparable damage to components of the AMS,
frequent process upsets or out-of-bounds operating conditions, or other situations or
process-related conditions that may reduce treatment effectiveness. The vessel may
continue to the next U.S. port of call, subject to the directions of the COTP or District
Commander, as provided by 33 CFR 160.
10. All transport and handling of chemicals required for proper operation of the AMS must
be conducted in accordance with 46 CFR 147 (Hazardous Ships' Stores), 49 CFR 171-
180 (Hazardous Materials Regulations), and 46 CFR 98.30 (portable tanks), as
appropriate.
11. Use of the AMS must be reported in the ship’s ballast water management reports
submitted to the National Ballast Information Clearinghouse, as required by 33CFR
151.2060, as follows:
a. In Section 4, report the number of tanks treated by the AMS in the space labeled
“Underwent Alternative Management,”
b. In Section 4, write the AMS identification number (AMS-2013-Techcross Electro-
Cleen -001) in the space labeled “Please specify alternative method(s) used, if any,”
and;
c. In Section 5, in the middle section titled “BW MANAGEMENT PRACTICES”
identify the management method as “ALT” under the heading “Method
(ER/FT/ALT)” for each tank for which the AMS was used.
The Coast Guard may suspend, withdraw or terminate the acceptance of this BWTS as an AMS
in accordance with 46 CFR 2.75-40, 2.75-50(a) and 2.75-50(b), respectively.
A copy of this letter shall be provided to each vessel with this installed AMS and shall be
available for review when the vessel is operating in U.S. waters.
I thank you for your dedicated efforts to seek out AMS acceptance, and we look forward to
working with you throughout the type approval process. If you have any questions concerning
4
He a lt h 2
0 0
F ir e
2 0
Re a c t iv it y 0
Pe rson a l E
P r o t e c t io n
Toxicological Data on Ingredients: Sodium thiosulfate pentahydrate LD50: Not available. LC50: Not available.
Eye Contact:
Check for and remove any contact lenses. In case of contact, immediately flush eyes with plenty of water for at least 15
minutes. Cold water may be used. Get medical attention if irritation occurs.
p. 1
Skin Contact:
Wash with soap and water. Cover the irritated skin with an emollient. Get medical attention if irritation develops. Cold water
may be used.
Serious Skin Contact: Not available.
Inhalation:
If inhaled, remove to fresh air. If not breathing, give artificial respiration. If breathing is difficult, give oxygen. Get medical
attention.
Serious Inhalation: Not available.
Ingestion:
Do NOT induce vomiting unless directed to do so by medical personnel. Never give anything by mouth to an unconscious
person. If large quantities of this material are swallowed, call a physician immediately. Loosen tight clothing such as a collar,
tie, belt or waistband.
Serious Ingestion: Not available.
Small Spill:
Use appropriate tools to put the spilled solid in a convenient waste disposal container. Finish cleaning by spreading water on
the contaminated surface and dispose of according to local and regional authority requirements.
Large Spill:
Use a shovel to put the material into a convenient waste disposal container. Finish cleaning by spreading water on the
contaminated surface and allow to evacuate through the sanitary system.
Precautions:
Do not breathe dust. Wear suitable protective clothing. In case of insufficient ventilation, wear suitable respiratory equipment.
If you feel unwell, seek medical attention and show the label when possible. Keep away from incompatibles such as oxidizing
agents, acids, alkalis.
p. 2
Storage: Hygroscopic. Keep container tightly closed. Keep container in a cool, well-ventilated area.
Engineering Controls:
Use process enclosures, local exhaust ventilation, or other engineering controls to keep airborne levels below recommended
exposure limits. If user operations generate dust, fume or mist, use ventilation to keep exposure to airborne contaminants
below the exposure limit.
Personal Protection: Safety glasses. Lab coat. Dust respirator. Be sure to use an approved/certified respirator or equivalent.
Gloves.
Personal Protection in Case of a Large Spill:
Splash goggles. Full suit. Dust respirator. Boots. Gloves. A self contained breathing apparatus should be used to avoid
inhalation of the product. Suggested protective clothing might not be sufficient; consult a specialist BEFORE handling this
product.
Exposure Limits: Not available.
p. 3
Conditions of Instability: Incompatible materials, moisture
Incompatibility with various substances: Reactive with oxidizing agents, acids, alkalis.
Corrosivity: Non-corrosive in presence of glass.
Special Remarks on Reactivity:
It is a strong reducing and can react with oxidizers. Reacts with acids to release sulfur dioxide. Sodium Thiosulfate
pentahydrate dissolves in its own water of hydation; it effloresces in warm dry air. Sodium Thiosulfate pentahydrate loses
water at 100 deg. C. It is incompatible with iodine, acids, lead, mercury, and silver salts (e.g. silver nitrate), halogens.
Hygroscopic; keep container tightly closed. Protect from moisture
Special Remarks on Corrosivity: Not available.
Polymerization: Will not occur.
Waste Disposal:
Waste must be disposed of in accordance with federal, state and local environmental control regulations.
p. 4
DOT Classification: Not a DOT controlled material (United States).
Identification: Not applicable.
Special Provisions for Transport: Not applicable.
The information above is believed to be accurate and represents the best information currently available to us. However, we
make no warranty of merchantability or any other warranty, express or implied, with respect to such information, and we assume
no liability resulting from its use. Users should make their own investigations to determine the suitability of the information for
their particular purposes. In no event shall ScienceLab.com be liable for any claims, losses, or damages of any third party or for
lost profits or any special, indirect, incidental, consequential or exemplary damages, howsoever arising, even if ScienceLab.com
has been advised of the possibility of such damages.
p. 5
Citric Acid Anhydrous
Material Safety Data Sheet
2. HAZARDS IDENTIFICATION
Emergency Overview
Irritating to eyes, Irritating to skin, Corrosive to metals (as aqueous solution).
3. COMPOSITION/INFORMATION ON INGREDIENTS
The following component(s) in this product are considered hazardous under applicable OSHA (USA), WHMIS (Canada), and/or
NOM-002-SCT-2003 (Mexico) regulations
Chemical Name CAS-No Weight % North American Hazard
Indicator
Citric acid 77-92-9 99-100 yes
General Advice If symptoms persist, call a physician. Show this safety data sheet to the doctor in attendance.
Eye Contact Immediately flush with plenty of water. After initial flushing, remove any contact lenses and
continue flushing for at least 15 minutes. Keep eyes wide open while rinsing. If symptoms
persist, call a physician.
Skin Contact Wash off immediately with soap and plenty of water removing all contaminated clothes and
shoes.
Ingestion Clean mouth with water and afterwards drink plenty of water.
5. FIRE-FIGHTING MEASURES
Suitable Extinguishing Media Dry chemical. Carbon dioxide (CO2 ). Water spray. Foam. Use
extinguishing measures that are appropriate to local
circumstances and the surrounding environment.
Hazardous Combustion Products Carbon monoxide (CO), Carbon dioxide (CO2 ) , Thermal
decomposition can lead to release of irritating gases and
vapours.
Explosion Data
Sensitivity to mechanical impact No
Sensitivity to static discharge No
NFPA
Environmental Precautions Prevent further leakage or spillage if safe to do so. Prevent product from entering drains.
Methods for Clean-up Pick up and transfer to properly labelled containers. Avoid dust formation. Keep in suitable,
closed containers for disposal.
Handling Wear personal protective equipment. Avoid contact with skin, eyes and clothing. Handle in
accordance with good industrial hygiene and safety practice. Do not breathe vapours/dust.
Use only in area provided with appropriate exhaust ventilation. Avoid dust formation in
confined areas. Fine dust dispersed in air may ignite.
Storage Keep containers tightly closed in a cool, well-ventilated place. Keep in properly labelled
containers.
Exposure Limits
This product is not known to contain any hazardous materials with occupational exposure limits established by the region specific
regulatory bodies.
General Hygiene Considerations When using, do not eat, drink or smoke. Regular cleaning of equipment, work area and
clothing.
Incompatible Materials Amines. Heavy metals. Strong oxidizing agents. Strong bases.
Acute Toxicity
Product Information
LD50 Oral: 3000(rat) mg/kg
LD50 Dermal: No information available
LC50 Inhalation: No information available
Chronic Effects
Carcinogenicity
There are no known carcinogenic chemicals in this product.
Ecotoxicity
Environmental properties.
Chemical Name Acute Fish Toxicity Daphnia (Water flea) Fresh Water Algae
Citric acid 96 Hr LC50 Lepomis macrochirus: 72 Hr EC50 Daphnia magna: 120
1516 mg/L [static] mg/L
Waste Disposal Methods Hazardous waste. Dispose of in compliance with the laws and regulations pertaining to this
product in your jurisdiction.
Contaminated Packaging Empty containers should be taken for local recycling, recovery or waste disposal.
International Inventories
The components of this product are reported in the following inventories:
Chemical TSCA DSL NDSL EINECS ELINCS AICS ENCS CHINA PICCS KECL NZLoC
Name
Citric acid Yes Yes No Yes No Yes Yes Yes Yes Yes Yes
201-069-1 2-1318 KE-20831
Legend
TSCA - Toxic Substances Control Act, Section 8(b) Inventory (USA). DSL - Domestic Substance List (Canada). NDSL - Non
Domestic Substances List (Canada). EINECS - European Inventory of Existing Commercial Chemical Substances (EU). ELINCS -
European List of Notified Chemical Substances (EU). AICS - Australian Inventory of Chemical Substances (Australia). ENCS -
Existing and New Chemical Substances (Japan). CHINA - Chinese Inventory of Existing Chemical Substances (China). PICCS -
Inventory of Chemicals and Chemical Substances (Philippines). KECL - Korean Existing and Evaluated Chemical Substances (Korea).
NZLoC - New Zealand Inventory of Chemicals (New Zealand)
USA
Federal Regulations
Ozone Depleting Substances:
No Class I or Class II material is known to be used in the manufacture of, or contained, in this product.
SARA 313
Section 313 of Title III of the Superfund Amendments and Reauthorization Act of 1986 (SARA). This product is not known to contain any
chemicals which are subject to the reporting requirements of the Act or regulations contained in 40 CFR 372.
Clean Air Act, Section 112 Hazardous Air Pollutants (HAPs) (see 40 CFR 61)
This product is not known to contain any HAPs.
State Regulations
California Proposition 65
Proposition 65 chemicals are not expected to be found in this product above those naturally present in their agricultural source.
Proposition 65 exempts naturally occurring listed chemicals from an obligation to label.
State Right-to-Know
No known components subject to "Right-To-Know" legislation in the following States:
Chemical Name Weight % Illinois Massachusetts New Jersey Pennsylvania Rhode Island
Citric acid 99-100 No No No No No
Canada
WHMIS Product Classification
Class E: Corrosive Material.
This product has been classified in accordance with the hazard criteria of the Controlled Products Regulations (CPR) and the SDS
contains all the information required by the CPR.
Mexico
Mexico - Grade Slight risk, Grade 1
Disclaimer
The information provided on this (M)SDS is correct to the best of our knowledge, information and belief at the date of its
publication. The information given is designed only as a guide for safe handling, use, processing, storage, transportation,
disposal and release and is not to be considered as a warranty or quality specification. The information relates only to the
specific material designated and may not be valid for such material used in combination with any other material or in any
process, unless specified in the text.
End of (M)SDS