Contactor Catalogue

The document provides specifications for various CJX2 AC contactors including their rated insulation voltage, rated operation current, electrical and mechanical life, matching fuse and thermal relay types, wiring capacity and more. It also lists the available models with their corresponding rated currents and specifications.

Uploaded by

Roqueo RD
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
156 views

Contactor Catalogue

The document provides specifications for various CJX2 AC contactors including their rated insulation voltage, rated operation current, electrical and mechanical life, matching fuse and thermal relay types, wiring capacity and more. It also lists the available models with their corresponding rated currents and specifications.

Uploaded by

Roqueo RD
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

B

Contactor, Relay, Starter & Frequency Inverter

CJX2 SSR-1
AC Contactor 129-134 Solid State Relay 164

CJX2N
SSR-1
AC Contactor 135-137
Solid State Voltage Regulator 165
CJX2-F
AC Contactor 138-141 SSR
Solid State Relay 166
CJX2-E
AC Contactor 142-143
SSR
CJX2-K Solid State Voltage Regulator 167
AC Contactor 144
SSR
YCCH6 & YCCH7 Solid State Relay 168
DC Contactors 145-146

CJX2-Z SSR-3
DC Contactors 147-148 Solid State Relay 169

CJX2-N
GENERAL-PURPOSE RELAY 170-180
Mechanical Interlocking Contactor 149

CJ19C POWER RELAY 181-191


Changeover Capacitor AC Contactor 150-151
HOUR METER 192
JR28
Thermal Relay 152-153
TIMERS 193-197

JR28N
Thermal Relay 154 COUNTERS RELAY 198

LE1 TIME RELAY 199-212


Magnetic Starter 155-156

FLOATLESS CONTROLLER 213


LC3
Star-delta Decompression Starter 157-158
DEVICE PROTECTED RELAY 214
YCB1000
Inverter Mini Type 159-163 RELAY SOCKET 215
CJX2 CJX2
AC Contactor AC Contactor

CJX2 AC Contactor Specifications


General Type CJX2-09 CJX2-12 CJX2-18 CJX2-25 CJX2-32 CJX2-40 CJX2-50 CJX2-65 CJX2-80 CJX2-95
CJX2 series AC Contactor is suitable for using in the circuits of rated voltage up to
Rated insulation voltage (Ui) V 690
660V AC 50Hz or 60Hz, rated current up to 95A, for making, breaking, frequently
Rated thermal current (Ith) A 20 20 32 40 50 60 80 80 95 95
starting & controlling the AC motor. Combined with the auxiliary contact block,
timer delay & machine-interlocking device etc, it becomes the delay contactor,
mechanical interlocking contactor, star-delta starter. With the thermal relay, it is
AC-3, 380V A 9 12 18 25 32 40 50 65 80 95
B
AC-3, 660V A 6.6 8.9 12 18 21 34 39 42 49 55
combined into the electromagnetic starter. The Contactor is produced according to Rated operation current (Ie)
IEC 60947-4. AC-4, 380V A 3.5 5 7.7 8.5 12 18.5 24 28 37 41

AC-4, 660V A 1.5 2 3.8 4.4 7.5 9 12 14 17.3 21.3

AC-3, 220V kW 2.2 3 4 5.5 7.5 11 15 18.5 22 25


Max. power of 3 phase
AC-3, 380V kW 4 5.5 7.5 11 15 18.5 22 30 37 45
Coil voltage of contactor and code motor controlled
AC-3, 660V kW 5.5 7.5 10 15 18.5 30 33 37 45 55
Coil voltage
24 36 42 48 110 220 230 240 380 400 415 440 600 AC-3 10000 t 100 80 80 60
Us(V)
Electrical life
50Hz B5 C5 D5 E5 F5 M5 P5 U5 Q5 V5 N5 R5 X5 AC-4 10000 t 20 20 15 10

60Hz B6 C6 D6 E6 F6 M6 P6 U6 Q6 V6 N6 R6 X6 Mechanical life 10000 t 1000 800 800 600

50/60Hz B7 C7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 X7 AC-3 t/h 1200 600 600 600


Operation frequency
AC-4 t/h 300 300 300 300

Matching fuse type RT16-20 RT16-20 RT16-32 RT16-40 RT16-50 RT16-63 RT16-80 RT16-80 RT16-100 RT16-125

Type designation Matching thermal relay type JR28-25 JR28-25 JR28-25 JR28-25 JR28-36 JR28-93 JR28-93 JR28-93 JR28-93 JR28-93

Wiring capacity mm² 1.5 1.5 2.5 4 6 10 16 16 25 35


Name Rated current Auxiliary contact Pole number Coil voltage Frequency
Coil
CJX2 ·
Control power voltage (Us) AC V 36, 110, 127, 220, 380

Close V 85%~110%Us
Auxiliary contact
Allowed control circuit voltage
Rated current (A) Type
Open V 20%~75%Us(AC)
Normal open (NO) Normal close (NC)
Close VA 70 110 200
1 - CJX2-0910*.
9 Keeping VA 8 11 20
- 1 CJX2-0901*.
Loss power W 1.8~2.7 3~4 6~10
1 - CJX2-1210*.
12
CJX2-1201*. Auxiliary contact
- 1
1 - CJX2-1810*. Rated thermal current (Ith) A 10
18
- 1 CJX2-1801*. AC-15 V 380
Rated operation voltage (Ue)
1 - CJX2-2510*. DC-13 V 220
25
- 1 CJX2-2501*. AC-15 VA 360
Rated control capacity
1 - CJX2-3210*. DC-13 W 33
32
- 1 CJX2-3201*.
Note:3 pole is normal type,not remarked in the type name.
40 1 1 CJX2-4011*.
50 1 1 CJX2-5011*.
65 1 1 CJX2-6511*.
80 1 1 CJX2-8011*.
95 1 1 CJX2-9511*.

129 130
CJX2 CJX2
AC Contactor AC Contactor

Overall and mounting dimensions(mm) Pic. 3 CJX2-40~95

Pic.1 CJX2-09,12,18

C2

B C2
C1

Cmax
Amax
Φ6.5 B
C1

Cmax Amax 2-Φ4.5

100

110
86max
Note:

35
2-Φ4.5 C: CJX2
Note:
76max
35mm

C1: CJX2+F4

50
60
C:CJX2 C2: CJX2+SK2-2/3
C1:CJX2+F4
C2:CJX2+SK2-2/3 40

35

Unit: mm

Unit: mm Type Amax Cmax C1 C2

Type Amax Cmax C1 C2 CJX2-40,50,65 79 116 149 168

CJX2-09,12 47 82 115 134 CJX2-80,95 87 127 160 179

CJX2-18 47 87 120 139

Pic. 2 CJX2-25,32

Specifications

Ambient temperature -5℃~+40℃


C2
Altitude ≤2000m
C1
Amax
Cmax 2-Φ4.5
The maximum temperature of 40 degrees, the air relative humidity not exceed 50%, at
Relative humidity a lower temperature can allow for a higher relative humidity, if humidity changes as a
result of occasional gel generated,should eliminate it.
35mm

86max

Note:
50
60

C: CJX2 Pollution level 3


C1: CJX2+F4
C2: CJX2+SK2-2/3 Installation category III

45
The installation degree of the tilt and vertical plane should not exceed ±22.5°, should
Installation position
be installed in place with no significant impact shaking and vibration

Unit: mm The installation of fastening screws can be used,the CJX1-9~38 contactor can also be
Installation
installed on 35mm standard DIN rail.
Type Amax Cmax C1 C2

CJX2-25 59 97 130 149

CJX2-32 59 102 135 154

131 132
CJX2 CJX2
AC Contactor AC Contactor

LA1-D, LA2-D, LA3-D Contact Block Derived Products When The Contactor is Assembled With Following Accessory Module

Configuration of contacts Derived products Contactor Accessorial modular Picture


Type Product
Number of N/O contact Number of N/C contact

B LA1-DN20
LA1-DN11
2
1
0
1 B
LA1-DN02 0 2 Time-delay
contactor

LA1-DN40 4 0
LA1-DN31 3 1
LA1-DN22 2 2
LA1-DN13 1 3
LA1-DN04 0 4

Type Time-delay range Number of time-delay contacts

Reversing
LA2-DT0 0.1s~3s NO+NC contactor
LA2-DT2 0.1s~30s NO+NC
LA2-DT4 10s~180s NO+NC

LA3-DR0 0.1s~3s NO+NC


LA3-DR2 0.1s~30s NO+NC
LA3-DR4 10s~180s NO+NC

Magnetic
starter

LX1-D Coil

Coil voltage
Type Us(V)
Product 24 36 42 48 110 127 220 230 240 380 400 415 440 600
Frequency
(Hz)

Changeover
capacitor
LX1-D2 50Hz B5 C5 D5 E5 F5 G5 M5 P5 U5 Q5 V5 N5 R5 X5 AC contactor

LX1-D4 60Hz B6 C6 D6 E6 F6 G6 M6 P6 U6 Q6 V6 N6 R6 X6

Star-delta
contactor

LX1-D6 50/60Hz B7 C7 D7 E7 F7 G7 M7 P7 U7 Q7 V7 N7 R7 X7

133 134
CJX2N CJX2N
AC Contactor AC Contactor

Application CJX2N CJX2N CJX2N CJX2N CJX2N


Type
-40 -50 -65 -80 -95
CJX2N series AC contactor is suitable for frequency 50/60Hz, rated insulation voltage
up to 1000V, rated operation current 9~150A under AC~3 duty. It is mainly used for Rated working current le (A) 40 50 65 80 95
AC-3 Ue≤440V
making/breaking electric circuits at a long distance & for frequent starting/stopping
& controlling AC Motors. It is used in combination with thermal relay to compose a Rated heat current Ith (A) 60 80 80 125 125
magnetic motor starter. The products comply with IEC60947-4-1 standard.
B Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000
B
Specification Rated operating voltage Ue (V) Max 1000 1000 1000 1000 1000

220/230V 11 15 18.5 22 25
Type CJX2N CJX2N CJX2N CJX2N CJX2N CJX2N
-09 -12 -18 -25 -32 -38
380/400V 18.5 22 30 37 45
Rated working current le (A) 9 12 18 25 32 38 Rated operational
AC-3 Ue≤440V 415/440V 22 25/30 37 45 45
power in AC-3 Pe(kW)
Rated heat current Ith (A) 25 25 32 40 50 50
500V 22 30 37 55 55
Rated insulation voltage Ui (V) 690 690 690 690 690 690
660/690V 30 33 37 45 45
Rated operating voltage Ue (V) Max 690 690 690 690 690 690
220/230V 4 5.5 7.5 7.5 9
220/230V 2.2 3 4 5.5 7.5 9
380/400V 9 11 11 15 15
380/400V 4 5.5 7.5 11 15 18.5 Rated operational
415/440V 9/11 11 11/15 15 15
Rated operational power in AC-4 Pe(kW)
415/440V 4 5.5 9 11 15 18.5
power in AC-3 Pe(kW) 500V 11 15 18.5 22 22
500V 5.5 7.5 10 15 18.5 18.5
660/690V 15 18.5 22 25 25
660/690V 5.5 7.5 10 15 18.5 18.5
Frequency of operation (I/h) 1000 1000 1000 750 750
220/230V 1.5 1.5 2.2 3 4 4
AC-3 80 60 60 60 60
380/400V 2.2 3.7 4 5.5 7.5 7.5 Electrical endurance (x104)
AC-4 15 15 15 10 10
Rated operational
415/440V 2.2 3 3.7 5.5 7.5 7.5
power in AC-4 Pe(kW) Mechanical endurance (x106) 6 6 6 4 4
500V 3 4 5.5 7.5 9 9
Operating voltage range of coil Close voltage: (0.85~1.1)Us Open voltage: (20%~75%)Us
660/690V 4 5.5 7.5 10 11 11
Atracting 20 20 20 20 20
Frequency of operation (I/h) Power consumption of coil (VA)
1200 1200 1200 1200 1000 1000
Starting 200 200 200 200 200
AC-3 100 100 100 100 80 80 Rated insulation voltage of
Electrical endurance (x104) auxiliary contacts (V) 690 690 690 690 690 690
AC-4 20 20 20 20 20 20 Conventional thermal current
of auxiliary contacts (A) 10 10 10 10 10 10
Mechanical endurance (x106) 15 15 15 15 15 15
Auxiliary contacts specification AC-15:360VA DC-13:33W
Operating voltage range of coil Close voltage: (0.85~1.1)Us Open voltage: (20%~75%)Us

Atracting 7 7 7 7 7 7 Standard Control Circuit Voltage


Power consumption of coil (VA)
Starting 70 70 70 70 70 70
Volts 24 42 48 110 220 230 240 380 400 415 440 500 660
Rated insulation voltage of
auxiliary contacts (V) 690 690 690 690 690 690 690
50Hz B5 D5 E5 F5 M5 P5 U5 Q5 V5 N5 R5 S5 Y5
Conventional thermal current
of auxiliary contacts (A) 10 10 10 10 10 10 10
60Hz B6 D6 E6 F6 M6 - U6 Q6 - - R6
Auxiliary contacts specification AC-15:360VA DC-13:33W 50/60Hz B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7

135 136
CJX2N CJX2-F
AC Contactor AC Contactor

Characteristic CJX2-F AC Contactor

Contactor and other auxiliary blocks General


CJX2-F series AC Contactor is applied to the circuit rated voltage up to 1000V AC.
Contactor Auxiliary Blocks Relative Products 50/60Hz,rated current up to 780A, for long distance breaking circuit and frequently
starting or controlling the motor. It also can be used for the control of distributing

B circuits of rated current from 200A to 1600A(AC-1)/115A to 780A(AC-3).The products


comply with IEC60947-4.
B
+

Type designation
Delay timer Time-delay contactor
Name Rated current Auxiliary contact Pole number Coil voltage Frequency

CJX2-F ·

+ Auxiliary contact
Type
Rated current (A)
Normal open (NO) Normal close (NC)

115 - - CJX2-F11500*.

Thermal relay Magnetic starter 150 - - CJX2-F15000*.


185 - - CJX2-F18500*.
225 - - CJX2-F22500*.
265 - - CJX2-F26500*.

+ 330
400
-
-
-
-
CJX2-F33000*.
CJX2-F40000*.
500 - - CJX2-F50000*.
630 - - CJX2-F63000*.

Auxiliary blocks Note:3 pole is normal type,not remarked in the type name.
AC Contactor

Outline and Mounting Dimension


b

Standard Control Circuit Voltage

09 12 18 25 32 38 40 50 65 80 95 115 150

b 76.6 76.6 76.6 76.6 76.6 76.6 127 127 127 127 127 158 158

c 87 87 87 94 94 94 116 116 116 123.8 123.8 132 132

137 138
CJX2-F CJX2-F
AC Contactor AC Contactor

Specifications Overall and mounting dimensions(mm)

CJX2-F CJX2-F CJX2-F CJX2-F CJX2-F CJX2-F CJX2-F CJX2-F CJX2-F


CJX2-F115-F330 figure and installation dimension
Type
115 150 185 225 265 330 400 500 630

Poles 3P, 4P
Q 4-Φ6.5
S Φ

B B
Rated insulation voltage (Ui) V 1000

Rated thermal current (Ith) A 200 200 275 275 315 380 450 630 800

AC-3, 380V A 115 150 185 225 265 330 400 500 630

bmax
b1max

106

120
AC-3, 660V A 86 108 118 137 170 235 303 353 462

F
Rated operation current (Ie)
AC-3, 1000V A 46 50 71 90 112 155 200 232 311

AC-4, 660V A 86 108 118 137 170 235 303 353 462

AC-3, 380V kW 55 75 90 110 132 160 200 250 335 L


Max. power of 3 phase P Q1
motor controlled Cmax A max G
AC-3, 660V kW 80 100 110 129 160 220 280 335 450 f
Electrical life AC-3 10000 t 120 100 80

Mechanical life 10000 t 1000 600

Operation frequency AC-3 t/h 1200 600 Type Amax bmax b1max Cmax G L Q Q1 S Φ F P
Matching fuse type RT16-160 RT16-200 RT16-250 RT16-315 RT16-400 RT16-400 RT16-500 RT16-630 RT16-800
CJX2-F115 165 164 137 167 80±0.8 108 29.5 60 15 M6×15 133 37
Matching thermal relay type LR9-F53 LR9-F73
CJX2-F150 165 172 137 167 80±0.8 108 29.5 57.5 20 M6×20 133 40
Wiring capacity mm² 50 50 95 95 150 185 30×5(2) 40×5(2) 50×5(2)
CJX2-F185 171 176 137 181 80±0.8 114 30 60 20 M6×20 133 40
Coil
CJX2-F225 171 199 137 181 80±0.8 114 22 52 25 M6×30 133 48
Control power voltage (Us) AC V 24, 36, 48, 110, 127, 240, 380, 440
CJX2-F265 204 205 145 210 96±1.1 143 39 66.5 25 M10×30 147 48
Close V 85%~110%Us
Allowed control circuit voltage CJX2-F330 209 209 145 216 96±1.1 148 36 74 25 M10×30 147 48
Open V 20%~75%Us(AC)

Close VA 550 800 1200 1200 1250 1650


CJX2-F400,F500 figure and installation dimension
Coil power Keeping VA 45 55 13 20 24 22

Loss power W 12~16 18~24 12 14 18 20


Q S Φ 8-Φ8.5
Auxiliary contact

Rated thermal current (Ith) A 10

AC V 380
Rated operation voltage (Ue)

B max
209
DC V 220

115

175
AC-15 VA 360
Rated control capacity
DC-13 W 33

L G
P P Q1
C max A max 23.5 G1
f 5

Type Amax Bmax Cmax f k S L P Q Q1 Gmax G Gmax G1 G1min

CJX2-F400 213 206 213 119 70 25 145 48 43 74 102 80 192 170 156

CJX2-F500 233 238 226 141 70 30 146 55 46 77 120 80 210 170 156

139 140
CJX2-F CJX2-E
AC Contactor AC Contactor

CJX2-F630 figure and installation dimension Scope of application

CJX2-E series AC Contactor (contactor for short), is mainly used in circuit of AC 50Hz
4×Φ10.5
or 60Hz, rated voltage to 660v and below, DC voltage to 220v and below, or in circuit
140 40 of AC-3 type, 380V operating voltage, rated current to 9A.
M12×45

B Type and meaning


CJX2 - E
B
280 max

304 max

180
Operation Code

4 means four pairs of normally open main contacts;


8 means two pairs of normally open main contacts
and two pairs of normally close main contacts.
Number of normally close (NC) auxiliary contacts

155 Number of normally open (NO) auxiliary contacts


80 80 89
The rated operating current in circuit of AC-3 type,
255 max 309 max 60.5 180 68.5 380V rated operating voltage (A)
81
Industry Code

Specifications Normal working and installation conditions

Ambient temperature -5℃~+40℃ 1、Ambient temperature:-5℃~+40℃,the average temperature is no more than


+35℃ within 24 hours;
Altitude ≤2000m 2、Altitude: ≤2000m;
3、Atmosphere conditions: when the temperature is +40℃,the relative atmosphere
humidity is no more than 50%,it can be high in low temperature, the average
The maximum temperature of 40 degrees, the air relative humidity not exceed 50%, at minimum temperature in the wettest month is no more than +25℃ and the
average maximum temperature is no more than 90%.The rime that are variable
Relative humidity a lower temperature can allow for a higher relative humidity, if humidity changes as a
with the temperature change on the products should be taken into consideration;
result of occasional gel generated,should eliminate it. 4、Pollution degree: Grade 3.
5、Installation type: Ⅲ type.
6、Installation condition: the gradient between installation surface and vertical
Pollution level 3 surface is more than ±5°;
7、Impact vibration: The products must be installed and in the place with no obvious
Installation category III shake, impact and vibrate.

The installation degree of the tilt and vertical plane should not exceed ±22.5°, should
Installation position Structure feature
be installed in place with no significant impact shaking and vibration

1、The products are assembled in plastic clips, which can make full use of the
The installation of fastening screws can be used,the CJX1-9~38 contactor can also be elasticity of the plastic. This is no need for screw and special tools for
Installation dismounting, serving the purpose of labor-saving, time-saving and material-
installed on 35mm standard DIN rail.
saving.
2、The products are direct-acting moving structure. The counter-force elasticity is
pagoda-shaped. Its acting characteristic is reliable. Mechanism is flexible. The
LX1-F Coil product is compact-designed. All of the features make it inaccessible to the clutter
and dust. The moving part of the terminal has shroud, making it impossible for
Type Product Contactor type Control power voltage(V) Coil type(3P) Coil type(4P) people to touch the field with electricity and safe to use. The product is
complying with the electric standards. The product is mini in dimension. It is
CJX2-F115,F150 LX1-F1153 LX1-F1154 stalled in the standard 35mm DIN with screw-fixed or clip-fastened, making it
easy to dismount in a short time.
CJX2-F185,F225 LX1-F1853 LX1-F1854 3、The contacts are all double-breaking bridging ones. They are made of silver-base
alloy which are superior in function, wear-resisting and long-lived. The arching
CJX2-F265,F330 LX1-F2653 LX1-F2654 chamber is sealed and made of anti-flaming material, preventing the arcing
48, 110, 220 splashing outside and protecting human and adjacent electric equipment’s
LX1-F
380, 440, 660 safety.
CJX2-F400 LX1-F4003 LX1-F4004
4、Magnetic system for this product is the reliable E-shaped iron core with low loss,
low noise and high mechanical strength. Coil terminal A1, A2, voltage
CJX2-F500 LX1-F5003 LX1-F5004 specifications are expressed clearly, which makes wiring easier.
5、Auxiliary contacts with modulus, building-block structure could be assembled
CJX2-F630 LX1-F6303 LX1-F6304 flexibly to use.

141 142
CJX2-E CJX2-K
AC Contactor AC Contactor

Contactor, Auxiliary contact group, signs and wiring diagrams CJX2-K AC Contactor
General
CJX2-0610E CJX2-0601E CJX2-06008E CJX2-K series AC Contactor is suitable for using in the circuits the rated voltage up to
CJX2-0910E CJX2-0901E CJX2-09008E
660V AC 50Hz or 60Hz, rated current up to 12A in AC-3 using category , for making
1 3 5 13
A1
1 3 5 21
A1 A1 & breaking, frequently starting & controlling the AC motor. Combine with the

B B
L1 L1 L3 NO L1 L1 L3 NO 1 R1 R3 3
auxiliary contact block, timer delay & machine- interlocking device etc, it becomes
the delay contactor,mechanical interlocking contactor, star-delta starter. With the
T1 T1 T3 T1 T1 T3 2 R2 R4 4 thermal relay, it is combined into the electromagnetic starter. The contactor is
14 A2 22 A2 A2
2 4 6 2 4 6 produced according to IEC 60947-4.

Type designation
Technical Specifications
CJ X 2 - □□ □□
1、The main technical performance index of CJX2-E (see Chart 1 and Chart 2)
Quantity of contacts, showing by number:
2、Coil voltage: AC 24V, 36V, 48V, 110V, 220V, 380V,
10 stands for three normal open main contacts, a normal
3、Allowed control circuit voltage: Close: 85~110%Us, Open: 20~75%Us
open auxiliary contacts
01 stands for three normal open main contacts, a normal
Type close auxiliary contact
CJX2-06E CJX2-09E 04 stands for 4 normal open main contacts
Specification
08 stands for 2 normal open and 2 normal close main contacts
Rated operation voltage (Ue) 660(690)
Rated operating current (AC-3, 380V)
Rated AC-3 6 9 Design sequence number
operation 380V
current (A) AC-4 2.6 3.5 Mini type
Conventional thermal current (A) 16 16 AC Contactor
Maximum 380V 60 90
operation Specifications
current (A) 660V 72 108
Maximum 380V 48 72 Type CJX2-K06 CJX2-K09 CJX2-K12
disconnect
current (A) 660V 60 90 Rated operation voltage (Ue) V 660 660 660
Controlled 220V 1.5 2.2
three-phase Rated thermal current (Ith) A 20 20 20
squirrel 380V 2.2 4
cage motor AC-3, 380V A 6 9 12
power AC3(KW) 660V 3 5.5 Rated operation current (Ie)
AC-3, 660V A 2.6 3.5 5
Operation Electrical AC-3 1200
frequency /h life(t) 300 AC-3, 220V kW 1.5 2.2 3
AC-4
100 Max. power of 3 phase
AC-3 AC-3, 380V kW 2.2 4 5.5
Electrical life(t) motor controlled
AC-4 20
AC-3, 660V kW 3 5.5 7.5
Machinery life 10 thousand times 1000
AC-3 10000 t 100
AC coil power consumption (W) 2 Electrical life
AC-4 10000 t 20
Conductor cross-section (mm²) 1.5
Matching fuse type NTOO-16 Mechanical life 10000 t 1000

Standard IEC60947-4、GB-14048.4 AC-3 t/h 1200


Operation frequency
AC-4 t/h 300
Size and installation dimensions
Matching fuse type NT00-16
4×φ4.5
Wiring capacity mm² 1.5
12

F4-E
Coil
35mm

Control power voltage (Us) AC V 24, 36, 48, 110, 220, 380
48
40

Close V 85%~110%Us
Allowed control
35 Open V 20%~75%Us(AC)
56
44
Coil power Loss power W 2

143 144
YCCH6 & YCCH7 YCCH6 & YCCH7
DC Contactors DC Contactors

General Operation (Manual Operation Contactor)


1. YCCH6/YCCH7 series AC contactor (hereinafter referred to as the household
appliances control a contactor) is used for remote switch on and off without a
sense of feeling or low load, resistance furnace, household appliances and similar Position: O Position: auto Position: I Position: I+P
low load, motor and other household.

B 2. The main contactor is used in AC 50Hz/60Hz, rated voltage to 400V, rated current
of power system to 100A, AC-1, AC-7a (in no sense or sense of low load,
I
auto
O
P I
auto
O
P I
auto
O
P I
auto
O
P
B
resistance furnace, household appliances and similar low load) categories, long
distance switch and control circuit.
YCCH6-25/40 3. Contactor is not used for breaking short circuit current, so it is necessary to
A1
(Automatic style) choose suitable short circuit protection electrical equipment.
A2

Specifications
A1 1
Automatic A2 2

Rating AC-7a 16A 20A 25A 40A 63A 100A


Auto back to "auto" position
current In AC-7b 6A 7A 8.5A 15A 20A —
Width 18mm 36mm
Control voltage 24V, 110V, 230V 24V, 110V, 230V 24V, 110V, 230V
Contact 2NO, 2NC, 1NO, 1NC, 1NO+1NC 2NO
Dimensions (mm)
YCCH6-63/40
(Automatic style)
Automatic

AC-7a 16A 20A 25A 40A 63A 100A 68 68


Rating
49 49
current In AC-7b 6A 7A 8.5A 15A 20A — 54 5.5 23.5
18 36 5.5 23.5 36

Width 36mm 54mm 108mm


Control voltage 24V, 110V, 230V 24V, 110V, 230V 24V, 110V, 230V
Contact 4NO, 4NC, 3NO, 3NC, 3NO+1NC, 2NO+2NC 4NO

45
85
81

45

2.5
2.5
Manual

Rating AC-7a 16A 20A 25A 40A 63A YCCH6/YCCH7 16-25A 2P 4P YCCH6/YCCH7 40-63A 2P 4P
YCCH7-63/20
(Manual style) current In AC-7b 6A 7A 8.5A 15A 20A
Width 18mm 36mm 68 68
49
Control voltage 24V, 110V, 230V 24V, 110V, 230V 49
54 108 5.5 23.5 9 5.5 23.5
Contact 2NO, 2NC, 1NO, 1NC, 1NO+1NC

Manual

45
85

45
81
Rating AC-7a 16A 20A 25A 40A 63A
current In AC-7b 6A 7A 8.5A 15A 20A
Width 36mm 54mm

2.5
Control voltage 24V, 110V, 230V 24V, 110V, 230V
Contact 2NO, 2NC, 1NO, 1NC, 1NO+1NC YCCH6 automatic style 100A 2P 4P Auxiliary style O+F
YCCH7-63/40
(Manual style)

145 146
CJX2-Z CJX2-Z
DC Contactors DC Contactors

Application Outline and Mounting Dimension


CJX2-Z series DC operated contactor is suitable for use in the circuits up to rated CJX2-09~32Z
voltage 660V DC 50Hz or 60Hz, and in rated current 9-95A in DC-3/380V load
circuits. For remote controlling circuit making, breaking and frequent starting DC
D(F4)/E(F5) A
motors. It can also combine with the auxiliary contact group, air delayer, thermal
relay devices etc.
B B
S
C
P P Φ
Specifications
Type CJX2-09Z CJX2-12Z CJX2-18Z CJX2-25Z CJX2-32Z
AC3 9 12 18 25 32
Rated 380V
AC4 3.5 5 7.7 8.5 12

B
working

b
current(A) AC3 6.6 8.9 12 18 21
CJX2-09~32Z 660V
AC4 1.5 2 3.8 4.4 7.5
Rated heat current(A) 25 25 32 40 50
220/240V 2.2 3 4 5.5 7.5

Controllable 380/400V 4 5.5 7.5 11 15 L


a
power 415V 4 5.5 9 11 15
(kW)
500V 5.5 7.5 10 15 18.5
600/690V 5.58 7.5 10 15 18.5
Pole 3,4 3,4 3 3,4 3
Rated working voltage(V) 380,660 380,660 380,660 380,660 380,660 CJX2-40~95Z
Rated insulation voltage(V) 660 660 660 660 660
Mechanical life×104 1000 1000 1000 1000 1000
Electrical AC×104 100 100 100 100 100 P P Φ
D(F4)/E(F5)
life AC4×104 20 20 20 20 20
4
Electrical AC×10 1200 1200 1200 1200 1200
Operating C
life AC4×104 300 300 300 300 300
frequency
4
Mechanical life×10 3600 3600 3600 3600 3600
Rated controlled voltage(V) 24-660 24-660 24-660 24-660 24-660

b
Working Close DC% 0.85~1.1Us 0.85~1.1Us 0.85~1.1Us 0.85~1.1Us 0.85~1.1Us
voltage Open DC% 0.10~0.75Us 0.10~0.75Us 0.10~0.75Us 0.10~0.75Us 0.10~0.75Us

B
Type CJX2-40Z CJX2-50Z CJX2-65Z CJX2-80Z CJX2-95Z
AC3 40 50 65 80 95
CJX2-40~95Z Rated 380V
AC4 18.5 24 28 37 44
working a
current(A) AC3 34 39 42 49 55
660V L
AC4 9 12 14 17.3 21.3 A
Rated heat current(A) 60 80 80 125 125
220/240V 11 15 18.5 22 25

Controllable 380/400V 18.5 22 30 37 45


power 415V 22 30 37 45 45
(kW)
500V 22 30 37 55 55 Type Amax Bmax Cmax Dmax Emax a b Φ L P S
600/690V 30 33 37 45 55
Pole 3,4 3,4 3,4 3,4 3,4 CJX2-09Z~12Z 47 76 82(116) 120.5(154.5) 140.5(174.5) 34/35 50/60 4.5 60(95) 105 8.6
Rated working voltage(V) 380,660 380,660 380,660 380,660 380,660 CJX2-18Z 47 76 87(122) 125.5(160.5) 145.5(180.5) 34/35 50/60 4.5 61(96) 11.3 10.4
Rated insulation voltage(V) 660 660 660 660 660 CJX2-25Z 57 86 95(131) 133.5(169.5) 153.5(189.5) 40 48 4.5 70(107) 13.2 11.7
Mechanical life×104 800 800 800 800 800
CJX2-32Z 57 86 100(138) 138.5(176.5) 158.5(196.5) 40 48 4.5 71.6(120) 14.5 13
Electrical AC×104 80 80 80 80 80
life AC4×104 15 15 15 15 15 CJX2-4011Z~6511Z 77 129 116(173) 154.5(211.5) 174.5(231.5) 40 100/10 6.5 78(135) 20 8.6
4
Electrical AC×10 600 600 600 600 600 CJX2-4004/4008Z
Operating 84 129 116(173) 154.5(211.5) 174.5(231.5) 40 100/10 6.5 78(135) 20 8.6
life AC4×104 300 300 300 300 300 ~6504/6508Z
frequency
4
Mechanical life×10 3600 3600 3600 3600 3600
CJX2-8011Z~9511Z 87 129 127(188) 165.5(226.5) 165.5(226.5) 40 100/10 6.5 83(140) 23.5 12
Rated controlled voltage(V) 24-660 24-660 24-660 24-660 24-660
Working Close DC% 0.85~1.1Us 0.85~1.1Us 0.85~1.1Us 0.85~1.1Us 0.85~1.1Us CJX2-8004/8008Z
~9504/9508Z 96 129 127(183) 160.5(221.5) 180.5(241.5) 40 100/10 6.5 83(140) 23.5 12
voltage Open DC% 0.10~0.75Us 0.10~0.75Us 0.10~0.75Us 0.10~0.75Us 0.10~0.75Us

147 148
CJX2-N CJ19C
Mechanical Interlocking Contactor Changeover Capacitor AC Contactor

CJX2-N Mechanical Interlocking Contactor CJ19C Changeover Capacitor AC Contactor


Specifications General

Rated operational power CJ19C series AC Contactor is suitable for using in the circuits the rated voltage up to
Rated Rated thermal
Type operation current in category AC-3 (kW) 3800V AC 50Hz or 60Hz.CJ19C is used to combine with low voltage reactive power
current(Ie)(A) (Ith)(A) compensators or cut off low voltage shunt capacitor. CJ19C series AC Contactor has
380V 660V
B CJX2-09N 9 20 4 5.5
restraining device to effectively decrease impact caused by inrush transient current
when switch on or over voltage when switch off.
B
CJX2-12N 12 20 5.5 7.5
Type designation
CJX2-18N 18 32 7.5 10
CJ 19C - □ / □ □
CJX2-25N 25 40 11 15 Stands for the quantity of auxiliary contact (normal open)
Stands for the quantity of auxiliary contact (normal close)
CJX2-32N 32 50 15 18.5
Basic specification code means with AC-6b,the rated working
CJX2-40N 40 60 18.5 30 current based on utilization category's rated voltage which
is 380V.
CJX2-50N 50 80 22 33 Design sequence number
AC Contactor
CJX2-63N 63 80 30 37
Note:
CJX2-80N 80 95 37 45 A. Acquiesce in 3 pairs of N/O main auxiliary contacts and 3 pairs of N/O precharge
auxiliary contacts
CJX2-95N 95 95 45 55 B. CJX2 with F4's derivate code;
C. CJX2 with F4 and electromagnet's derivate code

Type designation

Type
Rated operational power CJ19C-25 CJ19C-32 CJ19C-43 CJ19C-63
Rated Rated Item
Rated
Type operation thermal in category AC-3 (kW) insulation
current(Ie)(A) current(Ith)(A) 380V 660V voltage(Ui)(V) 230V 6 9 10 15
Controllable capacitor
capacity (kvar)
CJX2-F115N 115 200 55 80 1000 400V 12 18 20 30

CJX2-F150N 150 200 75 100 1000 Rated insulation voltage (V) 500

CJX2-F185N 185 275 90 110 1000 Rated operation voltage (V) 380

Conventional thermal
CJX2-F225N 225 275 110 129 1000 25 32 43 63
current (A)

CJX2-F265N 265 315 132 160 1000 AC-6b rated working 17 23 29 43


current (A)
Restrained surge capacity/
CJX2-F330N 330 380 160 220 1000 20Ie
Capacitor rated current

Controlled power
CJX2-F400N 400 450 200 280 1000 48, 110, 127, 220, 380
voltage (V)

Conventional thermal current


CJX2-F500N 500 630 250 335 1000 6 10
of auxiliary contacts (A)

Operating frequency
CJX2-F630N 630 800 335 450 1000 120
(cycles/h)

Electrical life (×105 time) 1

Mechanical life (×105 time) 10

149 150
CJ19C JR28
Changeover Capacitor AC Contactor Thermal Relay

Outline and installation dimensions Application


VR28 series thermal overload relay are suitable for overload and phase-failure protection of AC motors with frequency of 50/60Hz,
voltage up to 690V, current up to 0.1-150A under 8-hours duty or uninterrupted duty.
Functions provided by these relays, are phase-failure protection, ON/OFF indication, temperature compensation, and
136(130)
manual/automatic reset.
Applicable Standard: GB 14048.
B International Standard: IEC 60947-4-1
The relays can be mounted onto contactors or installed as single units.
B

87(84)

140
35
Protection Characteristics
Times the
Item NO. setting current Release time Test condition

1 1.05 >2h Start from Cold status


Overload 2 1.2 <2h Start from Hot status
protection 3 1.5 <2m right after item no.1
58(56)
40 4 7.2 2s<Tp≤10s Start from Cold status
Φ4.5
Any two Another
phases phase
Phase

50/60
failure 5 1.0 0.9 >2h Start from Cold status
protection
Start from Hot status
6 1.15 0 <2h right after item no.5

Selection and Parameters

150 Number Rated current A For contactor

1301 0.1-0.16
1302 0.16-0.25
1303 0.25-0.4
1304 0.4-0.63
1305 0.63-1
129

180
75

JR28-25 (LR2-D13) 1306 1-1.6


1307 1.6-2.5
1308 2.5-4 CJX2-09
CJX2-12
1310 4-6
CJX2-18
1312 5.5-8 CJX2-25
1314 7-10
79 1316 9-13
Φ6.5 1321 12-18
40
JR28-36 (LR2-D23) 1322 17-25
1353 23-32
2353 23-32
CJX2-32
2355 28-36
100/110

3353 23-32
3355 30-40
CJX2-40
3357 37-50 CJX2-50
3359 48-65 CJX2-65
3361 55-70 CJX2-80
CJX2-95
3363 63-80
JR28-93 (LR2-D33)
3365 80-93

151 152
JR28 JR28N
Thermal Relay Thermal Relay

Selection and Parameters Application

JR28N series thermal relay is suitable for using in the circuits rated voltage up to
Number Rated current A Contactor
660V, rated current 93A AC 50/60Hz, for over-current protection of AC motor. The
relay has the differential mechanism and temperature compensation and can plug in
4365 80-104
CJX2-95 CJX2N series AC contactor. The product conforms to IEC 60947-4-1 standard.

B 4367

4369
95-120

110-140
CJX2-115
CJX2-150
Motion Characteristic: Three-phase Balance Motion Time
B
5357 30~50
JR28-140 (LR2-D43) Times of the Ambient
5363 48~80 No Motion time Start conidition
setting current (A) temperature

5367 60~100 CJX2-F115~F185 1 1.05 >2h Cold state

5369 90~150 2 1.2 <2h Heat state


3 1.5 <4min (Following the No.1 test) 20±5℃
5371 132~220
10A 2s<Tp≤10s ≤63A
7375 200~330 4 Cold state
CJX2-F225~F265 10A 4s<Tp≤10s >63A
7379 300~500 CJX2-F225~F500
CJX2-F400~F630
JR28-200 (LR9-F53) 7381 380~630
Phase-losing Motion Characteristic

Overall and Mounting Dimensions Times of the setting current (A) Ambient
Motion
No Start conidition
Any two phases Another phase time temperature

1 1.0 0.9 >2h Cold state

46max 94max 117max Heat state 20±5℃


2 1.15 0 <2h
(Following the No.1 test)
78max
66max

83max
47

55
56max
Phase-losing Motion Characteristic
94max 72max

JR28-D13 JR28-D23 JR28-D33 Type Number Setting range (A) For contactor

D01 0.10~0.16
D02 0.16~0.25
D03 0.25~0.40
5
40 A direction
A direction D04 0.40~0.63
50
D05 0.63~1
90max

35

R
100max

R
D06 1~1.7
35

CJX2N-09
55

A
81

D07 1.6~2.5 CJX2N-12


6
5

A
JR28N-25 D08 2.5~4 CJX2N-18
55max 100max
5 5 CJX2N-25
4 75max 121max D10 4~6 CJX2N-38
D12 5.5~8
JR28-D23 JR28-D33 D14 7~10
D16 9~13
D21 12~18
30 D22 16~24
14

Φ11
22

127.6
123.5 4×Φ5.5
3 56.8
48 48 120 42.2 D23 30~38
Φ11 25 50 50
3322 17~25
5.5

136.8
108.8

3353 23~32
82
70

3355 30~40 CJX2N-40


44.8
44.8

101
76

71
60

CJX2N-50
3357 37~50
25
JR28N-93 CJX2N-65
51.5 51.5
3359 48~65 CJX2N-80
125 4×Φ5.5 CJX2N-95
3 46.8 6
66 66 3361 55~70
150
3363 63~80
LR9-F53 LR9-F73 3365 80~93

153 154
LE1 LE1
Magnetic Starter Magnetic Starter

LE1 Magnetic Starter Overall and mounting dimensions(mm)


General
LE1 Magnetic starter is suitable for using in the circuits the rated voltage up to 690V 2×Φ5.5 2×PE13
AC 50Hz or 60Hz.With AC-3 type,LE1 is used for starting or halting of three-phase (2×PE13)A20
squirrel case electromotor which rated working voltage is 380V and rated working

B current is from 9A to 95A. Combining with matchable thermal relay can protect the
motor from overload and phase failure.
B

166
150
Operation and installation condition
1. Ambient air temperature:-5℃~+40℃, average temperature of 24 hours must
below +35℃ 120
2×PE13
2. Altitude:≤2000m 88 (2×PE13)A20
140
3. Relative humidity: The maximum temperature of 40 degrees,the air relative
humidity not exceed 50%,at a lower temperature can allow for a higher relative
humidity.The humidest month’s average lowest temperature must be below LE1-D09, D12, D18
25℃, the max relative humidity of that month should not exceed 90%.If
humidity changes as a result of occasional gel generated,should eliminate it.
4. Pollution level: 3 2×Φ5.5
5. Installation category: III PE16 PE13
6. Installation position: The installation degree of the tilt and vertical plane should
not exceed ±5°.
7. Shock vibration:Products should be installed and used without severe shake,
shock and vibration of the place.

185
165
Specifications
135
Maximum power AC3 duty (kW) Rated Matched 2×PE16
142 101
Type current thermal relay
220V 380V 660V
(A) (A)
230V 400V 690V
LE1-D25, D32
LE1-09 2.2 4 5.5 9 LR2 D13

LE1-12 3 5.5 7.5 12 LR2 D13


PE13 PE36
105
LE1-16 4 7.5 10 18 LR2 D13

LR2 D13
LE1-25 5.5 11 15 25
LR2-D23

LE1-32 7.5 15 18.5 32 LR2 D23 4×Φ7.7

307
165
LE1-40 11 18.5 30 40 LR2 D33

LE1-50 15 22 33 50 LR2 D33

LE1-65 18.5 30 37 65 LR2 D33 165


PE13 257 2×PE36
176
LE1-80 22 37 45 80 LR2 D33

LE1-D40, D50, D65, D80, D95


LE1-95 25 45 45 95 LR2 D33

155 156
LC3 LC3
Star-delta Decompression Starter Star-delta Decompression Starter

LC3 Star-delta Decompression Starter Main Technical Parameters


General Model LC3D-123 LC3D-183 LC3D-253 LC3D-323 LC3D-403 LC3D-503 LC3D-653 LC3D-803 LC3D-953
Parameters
For AC 50hz or 60hz, rated insulation voltage of 660V (690V), use the AC-3 category
rated working voltage of 380V, power of 80KW and the following three-phase Rated working current
20 31 43 55 69 86 109 138 164
Ie(AC-3, <380V)A
squirrel cage induction motor for controlling the stator winding by star for access to

B the triangular shape to start and stop. After assembling the corresponding
specifications of thermal relay can be related to the motor and circuit overload
Rated insulation voltage Ui V
Rated working voltage Ue V
660(690)
380
B
protection. The starters and QJX4 have the same functionality can be equated with Standards compliant GB14048.4
the same specification used interchangeably. AC-3, 380V Electrical life 5.5×10 4 4
2.5×10 2×104 1.5×104
Mechanical life 30×10
Rated working voltage in
AC380 DC220
auxiliary circuit load
Type Designation
Conventional thermal in
LC3 - □ □ auxiliary circuit load
10

Star-delta Starter Seires Pull-in voltage 0.85~1.1


Coil
Rated working current Release voltage 0.2~0.75
Number 3 means the main circuit is 3

Dimensions, Mounting Dimensions and Wiring


LC3-D12,D18,D25,D32 outline and mounting dimensions
Normal Operating and Installation Conditions
Model amax bmax
1. Ambient air temperature -5℃~+40℃;
2. Altitude less than 2000m; 4-M6 LC3-D12 144 140
3. Vibration conditions: starter should be installed in the absence of a significant LC3-D18 149 140
shake, shock and vibration LC3-D25 160 170

124max
LC3-D32 165 170

107
90

10
a max b max
Size and Composition
Selection Y initiator element

Control motor power


Main circuit contactor Standard thermal relay
(kW) With LC3-D40,D50,D65 outline and mounting dimensions LC3-D80,D95 outline and mounting dimensions
Model
Isolation Isolation Isolation Current setting Thermal fuses
220V 380V 415V 440V
KM2 KM1 KM3 range (A) relay models
315max
LC3-D123 CJX2-1210 CJX2-0901 CJX2-1201 10~13 JR28-12316 5.5 10 10 10 20 285max
293
LC3-D183 CJX2-1810 CJX2-1201 CJX2-1801 13~18 JR28-16321 17.5 15 15 15 32 263
LC3-D253 CJX2-2510 CJX2-1201 CJX2-2501 18~25 JR28-25322 11 18.5 22 22 50

100/110
143max
LC3-D323 CJX2-3210 CJX2-2501 CJX2-3201 23~32 JR28-32353 15 25 25 30 63

100/110

60
143max

60
LC3-D403 CJX2-4011 CJX2-2501 CJX2-4011 30~40 JR28-40355 18.5 33 37 37 80
LC3-D503 CJX2-5011 CJX2-4011 CJX2-5011 48~57 JR28-63359 25 45 45 45 100
4-7×12 4-Φ7
LC3-D653 CJX2-6511 CJX2-4011 CJX2-6511 57~66 JR28-63361 30 55 59 59 125

130

50
LC3-D803 CJX2-8011 CJX2-5011 CJX2-8011 63~80 JR28-80363 40 75 75 75 160
40
180max 4-7×12 4-Φ7 2-Φ4.5
185max 60
LC3-D953 CJX2-9511 CJX2-6511 CJX2-9511 75~105 JR28-14605 40 80 80 80 200

157 158
YCB1000 YCB1000
Inverter Mini Type(Volt:220V Power:0.4kW-2.2kW) Inverter Mini Type(Volt:380V Power:0.4kW-500kW)

YCB1000 Inverter Mini Type(Volt:220V Power:0.4kW-2.2kW) YCB1000 Inverter Mini Type(Volt:380V Power:0.4kW-500kW)
Product Features Product Features
1. High performance without a sense vector control with good low frequency torque 1. Sensorless vector control with the best low frequency compensation ability
2. Standard RS485 communication interface, support MODBUS communication 2. Designed with special radiator tree and switch power, all of such kinds of new
protocol technologies improvethe performance

B 3. High performance V/F control algorithm with several kinds of V/F curve
4. Small size, light weight, strong function, stable performance and seay to use
3. Several protective technologies and new component have been applied to the
circuit, notably improve the anti-interference ability
B
5. Flexible and easy use design, simple installation and commissioning steps 4. Realize the preset frequency, or central frequency adjustable swing frequency
function
5. Several phases speed operation controlled by build-in PLC or controlling terminal
6. Modulation Mode: space vector pulse width modulation SVPWN
Application Fields 7. Automatic energy saving operation: automatically optimize V/F curve to save the
1. Suitable for OEM application energy
2. Widely deployed in machinery industry, textile industry, package industry, 8. Switch input channel: forward and reversal roration control, 8 channel program
printing industry and pharmacy industy, etc. switch input, 35 kinds of function
9. Strong overload performance: 150% rated corrent for 1 minute, 180% rated
current for 3 seconds
10. Communication function: RS485 standard communication interface, support
Product Features ASCII and RTU format MODBUS communication protocol

QF
Power
R U
Motor Application Fields
S V M 1. Applied with boiler drunm, induced draft fan, coal mine ventilator, etc
T W 2. Applied in central air-condition energy saving optimization, air compressor

E
energy saving renovation, music fountain, etc
X1 YCB1000 PE
3. Applied with water circulating pump, water supply pump, clear water pump,
X2 sewage pump, purification pump, constant pressure water supply, oilfield water
P+
X3 Braking resistant
PB
injection pump, oil pump, etc
X4 4. Applied with mine conveyer, coal feeder, mixer, pulverizer, converter, blast furnace,
Ta
X5 etc
Tb
X6 Failure electric relay output
5. Applied with extruder, bottle blowing machine, film blowing machine, film
Tc
FWD DC current meter conveying belt, centrifugal separator, compressor, sprayer, etc
4-20mA Current signal
REV AO
COM
GND

+10V High speed pulse output


0~10V DO Type Designation
V1 Open collector output
0~10V/4~20mA OC YCB1000 - 4 T 0015 G
C1
485+ Standard RS485 communication interface Frequency inverter type number
GND
485-
G: Constant Torque; P: Fan & Pump type

Adaptive motor
0007: 0.75kW; 0015: 1.5kW; 0075: 7.5kW

Input voltage
S: Single phase; T: Triple phase

Voltage level
2: 220V; 4: 380V

Frequency inverter

159 160
YCB1000 YCB1000
Inverter Mini Type Inverter Mini Type

Technical Index

Item Item Description Item Item Description

Rated voltage, frequency Sing Braking by power consumption Outer connected to braking resistance, maxi braking torque 100%
Braking
Output
B Permissible working voltage
Effective value of voltage: 220V class 180~230V, 380V class 320~460V
Voltage unbalanced rate: <3%; Frequency error: ≤+5%
Function Brake by direct current
When starting or stopping, it is optional respectively, action frequency: 0-20Hz,
action voltage level: 0-20%, action time 0-30s, continuously adjustable. B
Rated voltage Three phases 0~input voltage IJumpinf frequency, point function, counter, rotation speed track, restart after
Input instan-staneous power off, upper and lower frequency limit, acceleration and
Frequency 0~400Hz
Other Function slow-down modes adjustable, cymometer and voltmeter output, multi-step /
program running, two lines / three lines control, double polar control, selection of
G type: 110% long term, 150% 1min, 180% 1s, 200% instantaneous trip
Overloading capacity multifunctional input terminal, auto reset after fault, 485 serial communication.
P type: 120% 1min, 150% 1s, 180% instantaneous trip

Working mode Electromagnetic vector PWM modulation Input protection against phase failure, over-current protection, overloading
Protection Function protection, under-voltage protection, overheating protection, output short circuit
Adjustment range 1:100 protection and etc.

Starting torque 100% rated torque at 3Hz


It can display inverter real-time working status, monitoring parameters, function data,
LED Display
Digital setting: highest frequency×±0.01% fault codes and etc.
Frequency accuracy
Analog setting: highest frequency×±0.2%
Optional Accessories Braking parts, remote and operation panel and connection wire, communication panel
Freq dissolutions Digital setting: 0.01Hz; Analog setting: highest frequency×0.1%
Working site Indoor, without direct sunshine, no dust, corrosive gas, flammable and explosive gas,
Automatically rise torque up, according to output current it auto rise the torque up. oil fog, steam, water drop, salty
Torque
Manually rise torque up, scope:1~30%
Altitude Altitude less than 1000m

Control 1. Linear curve Ambient Ambient temperature -10-+45℃ (The only machine: -10~+50℃)
V/F curve
Function 2. Square curve Conditions Humidity 20~90%RH, Without water condensation
Acceleration, slow-down time 0.1~6000s continuous adjustment. Vibration <0.5G

Setting scope: 0~20%, it can auto adjust the output frequency of inverter according Storage temperature -20~+60℃
Compensation for rotation error
to the motor loading, to reduce the speed change due the motor load fluctuates.
Protection grade IP20

Easily form the loop control system, that it is suitable for pressure control, Cooling mode Fan cooling
Built-in PID Structure
flux control and etc.
Mounting mode Wall hung type, standing type.

When network voltage change, it can auto adjust the output of PWM
Auto voltage regulation
and keep output voltage constant

Auto energy-saving run As load change, it auto optimize the V/F curve, to realize the energy-saved running.

The setting of Potentiometer in the panel: operation panel / key setting, terminal of
outer control Rise / Drop setting, ananlog voltage signal or outer potentiometer
Freq setting
setting, analog current signal setting, ananlog combination setting, setting of 485
serial communication.

Running Running command Control of operation panel, control of outer terminals, control of serial communication
Function
0~10V DC voltage signal output, can realize the output of frequency,
Analog output terminal
current and etc, physical parameters

Input signal Positive/megative rotation signal, multi-step signal, fault signal, resetting signal

Output signal Programmable integrated circuit opening output, fault signal output

161 162
YCB1000 SSR-1
Inverter Mini Type Solid State Relay

Structure and Size SSR-1 D48□


Item Data
YCB1000/380V
Appearance Size (mm) Aperture Size of Panel (mm) Load Voltage 480VAC
L×W×D L×H
No. Model Power Voltage Load Current 10,15,20,25,30,40,50,60,75,80,90,100,120A
1 0.75kW
B 2 1.5kW 169×125×172 Panel: 75×55
Control Voltage
Control Current
3-32VDC
DC10mA B
3 2.2kW Panel Cover: 95×61 On Voltage ≤1.5V

4 4kW 221×151×186 Off Leakage Current ≤2mA


On-off Time ≤10mS
5 5.5kW
280×190×182 Dielectric Strength 2500VAC
6 7.5kW SSR-1 D4840
Insulation Resistance 1000MΩ/500VDC
7 11kW
339×230×212 Ambient Temperature -30~+75℃
8 15kW
Mounting Methods Bolted
9 18.5kW The work instructions LED
450×280×260
10 22kW

11 30kW 520×290×290 43
4 1
LOAD
12 37kW

CIRCUIT

PHASE CONTROL
TNPUT

CIRCUIT
2-φ45
3-32VDC 480VAC

44.8

28
25

21
28
12
13 45kW 580×290×320

LED
3 2

14 55kW 48 57.4L×44.8W×28H
YCB1000 380V 57.4

15 75kW
630×380×350
16 90kW
Panel: 130×70
Panel Cover: 156×80 SSR-1 A48□
17 110kW

18 132kW 880×510×400 Item Data

19 160kW Load Voltage 480VAC


Load Current 10,15,20,25,30,40,50,60,75,80,90,100,120A
20 185kW
980×510×400 Control Voltage 70-280VAC
21 200kW
Control Current AC≤12mA
22 220kW
On Voltage ≤1.5V
23 250kW
1050×710×420 Off Leakage Current ≤2mA
24 280kW
On-off Time ≤10mS
25 315kW Dielectric Strength 2500VAC
SSR-1 A4825
26 350kW Insulation Resistance 1000MΩ/500VDC
27 400kW 1900×800×420 Ambient Temperature -30~+75℃

28 500kW Mounting Methods Bolted


The work instructions LED
* Remark:
YCB1000/220V 1. When the load current is 10A, you must 43
Appearance Size (mm)
install the radiator. When it's 40A or above,
L×W×D 4 1
LOAD
No. Model Power Voltage

CIRCUIT
you must use fan forced cooling or water

PHASE CONTROL
TNPUT
2-φ45

44.8

CIRCUIT
28
25

21
28
90-250VAC

12
480VAC
1 0.75kW cooling.

LED
142×85×122 2. When using inductive load, please connect
3 2
2 YCB1000 1.5kW 220V 48
a varistor on the output terminal, its value 57.4 57.4L×44.8W×28H
3 2.2kW 185×96×150 should be 1.6-1.9 times of the load voltage.

163 164
SSR-1 SSR
Solid State Voltage Regulator Solid State Relay

SSR-1 DD48D□ SSR-□DA (Fundamental type)


Item Data Item Data

Load Voltage 5-480VDC Load Voltage 24-380VAC


Load Current 10,15,20,25,30,40,50,60,80,100A Load Current 10,15,25,40,50,60,75,90A

B Control Voltage
Control Current
3-32VDC
DC40mA
Control Voltage
Control Current
3-32VDC
DC10mA B
On Voltage ≤1V On Voltage ≤1.5V
Off Leakage Current ≤2mA Off Leakage Current ≤2mA
On-off Time ≤5mS On-off Time ≤10mS
SSR-1 DD480D100 Dielectric Strength 2000VAC SSR-40DA Dielectric Strength 2500VAC
Insulation Resistance 500MΩ/500VDC Insulation Resistance 1000MΩ/500VDC
Ambient Temperature -30~+75℃ Ambient Temperature -30~+75℃
Mounting Methods Bolted Mounting Methods Bolted
The work instructions LED The work instructions LED

43
LED 4 1
4 1 LOAD

CONTROL
3~32VDC
LOAD

ZERO CROSS
CIRCUIT
CONTROL
3-32VDC

CIRCUIT

CIRCUIT
23.5
Φ4.5

OUTPUT
CIRCUIT

45
10
24~380V
2-φ45

44.8

28
24-480VDC
25

21
28
12

3
LED

3 2 3 2
48 48 6
62L×45W×23.5H 62L×45W×23.5H
57.4 62

SSR-1 DD220D□ SSR-□AA (Fundamental type)


Item Data Item Data

Load Voltage 5-60VDC,5-100VDC,5-220VDC Load Voltage 24-380VAC


Load Current 10,15,20,25,30,40,50,60,80,100A Load Current 10,15,25,40,50,60,75,90A
Control Voltage 3-32VDC Control Voltage 80-250VAC
Control Current DC10-40mA Control Current AC≤12mA
On Voltage ≤1V On Voltage ≤1.5V
Off Leakage Current ≤2mA Off Leakage Current ≤4mA
On-off Time ≤5mS On-off Time ≤10mS
Dielectric Strength 2000VAC SSR-40AA Dielectric Strength 2500VAC
Insulation Resistance 500MΩ/500VDC Insulation Resistance 1000MΩ/500VDC
SSR-1 DD220D10
Ambient Temperature -30~+75℃ Ambient Temperature -30~+75℃
Mounting Methods Bolted Mounting Methods Bolted
The work instructions LED The work instructions LED
* Remark:
* Remark: 1. When the load current is 10A, you must
43
install the radiator. When it's 40A or above, LED 4 1
1. When the load current is 10A, you must 4 1 LOAD

80~250VAC

CONTROL
LOAD

ZERO CROSS
CIRCUIT
CONTROL
3-32VDC

you must use fan forced cooling or water


CIRCUIT

CIRCUIT
23.5
install the radiator. When it's 40A or above, Φ4.5
OUTPUT
CIRCUIT

45
10
24~380V
2-φ45

44.8

28

24-220VDC
25

21
28
12

3
you must use fan forced cooling or water cooling.
LED

3 2 3 2
cooling. 2. When using inductive load, please connect 6
48 48
57.4L×44.8W×28H a varistor on the output terminal, its value 62L×45W×23.5H
2. When using inductive load, users must add 57.4 62

suppressive circuit. should be 1.6-1.9 times of the load voltage.

165 166
SSR SSR
Solid State Voltage Regulator Solid State Relay

SSR-□VA (Fundamental type) SSR-H3100ZF


Item Data Item Data

Load Voltage 24-380VAC 440VAC (Fundamental type), 660VAC (High


Load Voltage
voltage type) and 1200 (Enhanced type)
Load Current 10,25,40,50,60,80A
Load Current 80,100,120A
B
VR:250KΩ/110VAC
Control Voltage
470-560KΩ/220VAC Control Voltage 90-250VAC or 3-32VDC B
Control Current AC≤12mA DC10mA
Control Current /
On Voltage ≤1.5V
On Voltage ≤1.5V
Off Leakage Current ≤4mA
Off Leakage Current ≤2mA
On-off Time ≤10mS
SSR-40VA On-off Time /
Dielectric Strength 2500VAC
Dielectric Strength 2500VAC Input and output terminals cooling plate SSR-H3100ZF
Insulation Resistance 1000MΩ/500VDC
Insulation Resistance 1000MΩ/500VDC Ambient Temperature -30~+75℃
Ambient Temperature -30~+75℃ Mounting Methods Bolted
Mounting Methods Bolted The work instructions LED
The work instructions /
Load Power

Load
LED 4 1 94
LOAD
80 80

CONTROL
CIRCUIT
2-Φ6 2-Φ6

23.5
Φ4.5
45
10

38.5
24~380V

25
3
LED LED

3 2 94L×25W×38H
48 6
62L×45W×23.5H Control Power
62

SSR-H3200ZF
SSR-□DD (Fundamental type)
Item Data
Item Data
440VAC (Fundamental type), 660VAC (High
Load Current 10A、25A、40A、50A Load Voltage
voltage type) and 1200 (Enhanced type)
Load Voltage 5-60VDC 150,200,250,290A
Load Current
Control Voltage 3-32VDC Control Voltage 90-250VAC or 3-32VDC
Control Current DC10-50mA Control Current AC≤12mA DC10mA
On Voltage ≤1V On Voltage ≤1.5V
Off Leakage Current ≤2mA Off Leakage Current ≤4mA

On-off Time ≤10mS On-off Time ≤10mS

Dielectric Strength 2000VAC Dielectric Strength 2500VAC


SSR-H3200ZF
Insulation Resistance 1000MΩ/500VDC
Insulation Resistance 500MΩ/500VDC
Ambient Temperature -30~+75℃
Ambient Temperature -30~+75℃
SSR-10DD Mounting Methods Bolted
Mounting Methods Bolted
The work instructions LED
The work instructions LED * Remark:
* Remark:
1. When the load current is 10A, you must Load Power
1. When the load current is 10A, you must
install the radiator. When it's 40A or above, install the radiator. When it's 40A or above,

Load
you must use fan forced cooling or water you must use fan forced cooling or water 94
80 80
cooling. cooling. 2-Φ6 2-Φ6

42
34
2. When using inductive load, please connect LED
2. When using inductive load, please connect LED

a varistor on the output terminal, its value a varistor on the output terminal, its value 94L×34W×42H

should be 1.6-1.9 times of the load voltage. should be 1.6-1.9 times of the load voltage. Control Power

167 168
SSR-3
Solid State Relay

SSR-3 032 38□Z (Fundamental type)


Item Data

Load Voltage 380VAC,660VAC


Load Current 10,15,20,25,30,40,50,60,75,80,100,120,150,200A

B Control Voltage
Control Current
3-32VDC
20mA B
On Voltage ≤1.5V
Off Leakage Current ≤10mA
On-off Time ≤10mS
Dielectric Strength 2500VAC
SSR-3 032 3840Z Insulation Resistance 1000MΩ/500VDC
Ambient Temperature -30~+75℃
Mounting Methods Bolted
The work instructions LED

105
Input 3-32VDC
90±0.1
Rapid fuse Control Power
Rv Y Load
C
48±0.1

C1 v C2
LED

33
74

Rv
6-M5 B v
B1 B2
Rv
A
12

A1 v A2
4.8

105.0L×74.0W×33.0H

SSR-3 A38□Z (High voltage type)


Item Data

Load Voltage 380VAC,660VAC


Load Current 10,15,20,25,30,40,50,60,75,80,100,120,150,200A
Control Voltage 70-280VAC
Control Current AC≤12mA
On Voltage ≤1.5V
Off Leakage Current ≤10mA
On-off Time ≤10mS
Dielectric Strength 2500VAC
SSR-3 A3840Z Insulation Resistance 1000MΩ/500VDC
Ambient Temperature -30~+75℃
Mounting Methods Bolted
The work instructions LED
* Remark:
1. When the load current is 10A, you must 105
Input 90-280VDC
install the radiator. When it's 40A or above, 90±0.1

you must use fan forced cooling or water Rapid fuse Control Power
Rv Y Load
C
48±0.1

v
cooling. LED C1 C2
33
74

Rv
6-M5 B v
B1 B2
2. When using inductive load, please connect A
Rv
12

A1 v A2
a varistor on the output terminal, its value
4.8

105.0L×74.0W×33.0H
should be 1.6-1.9 times of the load voltage.

169