1) The X5 is a panel mounting, Class II Modbus Master/Slave controller with 3 digital inputs, 9 status LEDs, and 4 alarm status LEDs. 2) It has been designed with compliance to European Directives and all information on use can be found in the user manual downloaded from the manufacturer's website. 3) The Declaration of Conformity and user manual for the controller can be downloaded free of charge from the manufacturer's website by searching for "X5" and clicking on the result.

Uploaded by

Sadikul Fuad
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views

Manual Ascon - 1

1) The X5 is a panel mounting, Class II Modbus Master/Slave controller with 3 digital inputs, 9 status LEDs, and 4 alarm status LEDs. 2) It has been designed with compliance to European Directives and all information on use can be found in the user manual downloaded from the manufacturer's website. 3) The Declaration of Conformity and user manual for the controller can be downloaded free of charge from the manufacturer's website by searching for "X5" and clicking on the result.

Uploaded by

Sadikul Fuad
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Process controller with Declaration of Conformity and Manual retrieval Description and dimensions Electrical connections

X5 is panel mounting, Class II instrument. It has been designed Depth: 110 mm


Modbus Master/Slave with compliance to the European Directives.

(Slave)
RS485
1/8 DIN - 48 x 96 All information about the controller use can be found in the User 3 Digital Inputs PV control input
Manual: MIU_X5_EN.pdf. C
X5 line The Declaration of Conformity and the manual of the controller
LEDs (yellow) in eng. units
100%
% Control output TTL NPN NO
Q u i c k G u i d e • Ι STR-FX5ENG02
can be downloaded (free of charge) from the web-site: or program status
POT
9 Status LEDs SP operating Setpoint
www.ascontecnologic.com 0%
(green) (Local/Remote or Stored)
Once connected to the web-site, search: REM
4 Alarm status Control Output LEDS (red) SP
X5 LEDs (red) OP1/4 ON - OP2/4 OFF V V
then click on X5 from the result list. OP6
Run/Stop Timer (opt.)
In the lower part of the product page (in any language) is present mA mA
or a program
the download area with links to the documents available for the Auto/Man mV mA Thermo- N/C
Menu access Enter key for selection/ couple
controller (in the available languages). setting confirmation
IN2
(opt.)
Setpoint setting

Panel cut out and mounting


Pt100 2 wire transmitter

 Warning! PV mA
4…20mA
Rj
24Vdc
- Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, things or animals, please
remember that the plant must be equipped with additional
Terminals
devices which will guarantee safety.
- We warrant that the products will be free from defects in Ø
material and workmanship for 18 months from the date of L
viale Indipendenza 56, 27029 - Vigevano (PV)
delivery. Products and components that are subject to wear Pin connector Fork-shape Stripped wire
Tel.: +39 0381 698 71, Fax: +39 0381 698 730
internet site: www.ascontecnologic.com due to conditions of use, service life and misuse are not covered q 1.4 mm -
0.055 in. max.
AMP165004
Ø 5.5 mm - 0.21 in.
L 5.5 mm -
0.21 in.
E-mail: [email protected] by this warranty.

Model Code Configuration menu Configuration Operator mode


The product code indicates the specific hardware configuration of the
instrument, that can be modified by specialized engineers only.
Enter the configuration password Press until
Line Basic Accessories Must be equal to the
from -999...9999
Model: X 5 A 1 C D - E 9 0 0 value of the parameter
(33 factory default)
C.pas C.pas
Line X 5

Power supply
100...240Vac (-15...+10%)
A
3
Inp. s.p. Out l.inp AlM EHit
24Vac (-25...+12%) or 24Vdc (-15....+25%) 5 IL1 digital
Setpoint Control 1st retransmitted AL1 alarm
Serial Communications C
Inp. Input type s.p.ty type
Cn.ty type
rt. 1 output selection
Il1 input function Al. 1 type Back to:
None
Mathematical package (MP)
0
1 Unit
Engineering
units
s.p.tr
Stored
Setpoint M.C.Op
Main output
(Heat) O.rt.1
1st retransmission
output Il2
IL2 digital
input function A1.Ou
AL1 output
address
inp
Tracking
RS485 Modbus/Jbus + MP 5 Setpoint slope Secondary 1st retransmission IL3 digital
RS485 Modbus/Jbus SLAVE + MASTER + MP 6
If linear scales are s.p.tM time units
s.C.Op output (Cool)
rt.l1 low range
Il3 input function ltch AL1 latching
choosen, set also the
following parameters Remote Cool output 1st retransmission AL1 start-up
Options D
rs.in Setpoint C.Op.s on OP5
rt.H1 high range
bloc blocking
None 0 Number input
Frequency input + OP6 6 sc.dd of decimals Remote Main output 2nd retransmitted
rs.sa Slope s.Out safety value rt. 2 output selection donb Disables AL1
Setpoint Programmer [1] E Setpoint on sensor break
sc.lo Low range
enable Main output 2nd retransmission
Not fitted 0 f.Out forcing value
O.rt.2 output
4 Output adressing (A .ou),
4 programs with 16 segments
sc.Hi High range
2nd retransmission Latching (ltch),
sp.lt Split range % rt.l2 low range Blocking (bloc),
[1] Not available with split range control mode. Square
sqr Disabling (donb),
root Split Range 2nd retransmission
sp.lA Control action rt.H2 high range
for AL2, AL3 and AL4
Linear inputs
Char characterisation

Parameterisation menu Operator mode


Press until

s.p. Al pId tune Inp Out CoMM accs Conf


Stored AL1 alarm Initial tune Filter time SLAVE
Proportional When PID algorithm is
s.sel Setpoint 1=== threshold
p.b. band tune start t.fil constant
Add.s address Consult the Consult the
selection selected, set the comm.s Installation and Configuration
1st stored Continuous Measure following parameters User manual for menu previously
Integral SLAVE
s.p. 1 Setpoint 2nd, 3rd and 4th t.i. time adpt tune start in.sh bias bdr.s baud rate details described
alarm thresholds
Derivative When Adaptive tune is Sampling t.c. Cycle time SLAVE
2nd and 3rd AL1 hysteresis t.d. time t.saM time
pro.s comm.s
selected, the instrument protocol
stored Setpoint hy.1u asymmetric
displays: p.b., t.i. and t.d. Op. l Control Output
upper Error dead low limit
AL1 hysteresis
d.Err band (PID) values calculated for the pAr.y Parity
s.p. l Setpoint
hy.1d asymmetric process. [2] Control Output
d.bnd Dead band
low limit
lower Overshoot Op. H high limit MASTER
O.C. control Cool cycle time Mast enable
Setpoint [2] These values are not
s.p. H tf1- AL1 delay Control output t.c. C (time propor-
high limit Manual t.i. C Cool integral automatically stored in Op. r rate limit tional only) MASTER
M.res reset time p.b., t.i. and t.d
Cool control
bdr.M baud rate
sl. u Slope up 2nd, 3rd
and 4th
Proportional
parameters.
st.Op Control Output Op.C.H output high MASTER
alarm hysreresis Cool derivative Copy these (PID) values soft start value
and delay
p.b. C band Cool t.d. C time for back-up.
limit (PID only) pro.M comm.s
Soft start Cool output
sl. d Slope down channel
st.tM function
protocol
activation
Op.rC rate limit
(user enabled/
time disabled)

Parameter list
The parameters pointed out with grey background are those necessary to configure the options and are NOT shown in the menus. All the parameters are fully described and explained in the user manual of the controller.
Configuration Value Value Value
Code Parameter Name Code Parameter Name Code Parameter Name
Value Default User Default User Default User
Code Parameter Name
Default User O.rt.- nth retransmission output 4-20 Program parameters Op.hy Output Hysteresis 1
(consult the Installation and user manual for details)
Inp. Input type selection 0 - 10 rt.l- nth retransmission low range 0 t.c. Cycle time 10.0
1--- AL1 alarm threshold 0
Unit Engineering units NONE rt.H- nth retransmission high range 9999 Op. l Control ouput low limit 0.0
2--- AL2 alarm threshold 0
sc.dd Number of decimals (0... 3) 0 Il- ILn digital input function OFF Op. H Control output high limit 100.0
3--- AL3 alarm threshold 0
sc.lo Low range 0 Al. - ALn alarm type OFF Op.r Control output maximum speed OFF
4--- AL4 alarm threshold 0
sc.Hi High range 9999 A-.Ou ALn addressing OP1 st.Op Soft start output high value OFF
hy.-u ALn alarm hysteresis Up 1.0
sqr Square root (0 = OFF, 1 = ON) NO ltch ALn latching no st.tM Soft start time 10
hy.-d ALn alarm hysteresis Down 1.0
CHar Linear input characterization NO bloc ALn start-up disabling no Mu.tM Servomotor travel time 60
tf-- ALn delay 1
sp.ty Setpoint type LOC donb Disables ALn on sensor break no Mu.hy Output minimum step Servomotor 0.5
p.b. Proportional band 5.0
sp.tr Stored Setpoint tracking NO
d.bnd Heat/Cool Dead band 0.5
t.i. Integral time 60
sp.tM Time units and Setpoint slope P.SEC
Parameterisation t.d. Derivative time
tc .C Cool cycle time 10.0
12.0
rs.In Remote Setpoint input Value d.Err Error Dead Band Op.C.H Cool output maximum value 100.0
4 - 20 OFF
Code Parameter Name Op..rC Cool output maximum speed
Default User O.C. Overshoot Control OFF
rs.sa Remote Setpoint Slope enable NO 1.00
s.sel Setpoint selection NONE M.res Manual Reset 50.0
Add.s Communication SLAVE address 1
Cn.ty Control type PID
th
s.p. - n stored Setpoint 0 p.b. C Cool proportional band 5.0 bd.rs SLAVE Baud rate 9600
M.C.Op Main output (Heat) OFF
s.p. l Setpoint low limit PV.LO t.i. C Cool integral time 60 pro.s SLAVE Communication protocol JBUS
s.C.Op Secondary output (Cool) OFF
s.p. H Setpoint high limit PV.HI t.d. C Cool derivative time 12.0 par.y Parity NONE
C.Op.5 Cool output on OP5 (Heat/Cool only) NO
s.l. u Setpoint ramp up OFF tune Start/Stop One shot tuning NO Mast Enable MASTER NO
s.Out Main output safety value OFF
s.l. d Setpoint ramp down OFF adpt Start/Stop Adaptive tuning NO bdr.M MASTER Baud rate 9600
f.Out Main output forcing value OFF
rs.sl Remote setpoint slope enable OFF t.fil Input filter OFF pro.M MASTER Communication protocol JBUS
sp.lt Split range % (split range only) 50
rtio Ratio remote Setpoint 1.00 In.sh Input shift OFF
sp.lA Split Range Control action dir
bias Remote Setpoint Bias 0 t.saM Sampling time 0.1
rt. - nth retransmitted output selection none