Notes U8-HVAC
Notes U8-HVAC
http://www.rfcafe.com/references/general/psychometric_chart.htm
http://ohioline.osu.edu/aex-fact/0120.html
Engr 540: Intro. To Ship Systems Unit 8: HVAC
Humidity is the measure of the amount of water vapor in the air. The following Notes:
terms are all associated with the concept of humidity:
Dew Point-- the temperature at which a sample of air becomes completely
saturated with water vapor (100% relative humidity). If the air temperature
is reduced below the dew point, some of the water vapor condenses.
Maximum Water Vapor Content-- At a given temperature, the maximum
amount of vapor (lbs H2O) which can be contained in a ft3 of air without
condensing. This amount is higher at high temperatures anf lower at low
temperatures.
Absolute Humidity-- the actual amount of water vapor (lbs H2O) in a
pound of air. (or grains of H20 in a lb of air, or Kg or H2O in a Kg or air –
also called Humidity Ratio, W)
Relative humidity-- ratio of the Absolute Humidity to the Maximum Water
Vapor Content at the present temperature. i.e., 100% humidity means that
the air is saturated.
Filter
Compressor
Evaporator
Coils Condenser
Coils
Fan
Primary Refrigerant Cooling:
mixtureof inside and outside air passes over condenser coils and is
returned outside (condensing temperature must be above outside
temperature
2 -- 6
Engr 540: Intro. To Ship Systems Unit 8: HVAC
Notes:
Secondary Refrigerant Cooling:
liquid
(secondary refrigerant--glycol or “brine”) is cooled by
primary refrigerant in a “chiller”
Chill
water is circulated to air handlers where ventilation air is
passed over cooling coils
load
on system determined by temperature of returning chill
water and compressor capacity adjusted accordingly
Compressor
PRIMARY
LOOP
Evaporator Condenser
Expansion
(Chiller,Cooler)
Device
SECONDARY
Chill Water LOOP
Pump S.W. Circ.
Pump
Air Handler
http://www.chillers.com/RefrigCycle.htm
3 -- 6
Engr 540: Intro. To Ship Systems Unit 8: HVAC
Notes:
HVAC Components
Air Handler: fans, motor, duct work, for moving air in an HVAC system
Air Change: intake/exhaust of air to reduce odors, CO2 and indoor pollution levels
Pre-heater: steam or HW coil which heats intake air used in air change. Typically in
winter operation to maintain plenum air temp at 50 oF
Cooling Coil: primary or sec-ondary refrigerant heat exchanger reducing supply air
temp for cooling or dehumid.
exhaust intake
(simplified) Pre-heater
AIR HANDLER
Damper:
75% recirc.
position
Exhaust Fan
from spaces
Filter
to spaces
Plenum
Heating Coil: steam or HW heat exchanger used to bring air temp to desired level.
In winter, with cooling coils secured, pre-heater delivers 50o air to the heating coil
(there is no re-heating).
Humidifier: device using direct injection of steam, water spray, or pan & wick
evaporation to increase moisture content of air. Note that air saturated at 50 oF will
be at approximately 50% RH at 72oF.
Louvers: fixed or moving shutters to direct air flow into a space. Dampers are
louver arrangements used to control air flow.
4 -- 6
Engr 540: Intro. To Ship Systems Unit 8: HVAC
HVAC Distribution
http://greenbuildings.santa-monica.org/hvac/hvacintro.html
5 -- 6
Engr 540: Intro. To Ship Systems Unit 8: HVAC
Notes:
6 -- 6