Exp1 - Labajo, JM
Exp1 - Labajo, JM
College of Engineering
Mechanical Engineering Laboratory
EXPERIMENT # 1
Flash and Fire Point of Lubricating Oil
I. OBJECTIVE
To study and determine the flash and fire point of lubricating oil.
II. DISCUSSION
There are two kinds that are used for flash and fire point determination
of oil, namely, (1) the open type and (2) the close type. The close type is
generally considered as standard but the open type tester gives sufficient
accurate results for more particular work. In the open type of tester, which is
used to a great deal in commercial testing of lubricating oil, heat is applied to
the cup by the use of Bunsen burner which should be protected from air drop
by suitable shield. It is necessary to be careful in making this test to be sure
that the temperature of the oil is continuously rising as any reaction at about
the flash point or the fire point would invalidate the result of the work.
Temperature of oil must be kept steadily increasing at the specified rate.
III. APPARATUS
2 Thermometers
Evaporating Dish
Bunsen Burner
Tripod
Wire Gauze
Iron Stand with Clamp
Oil Sample
IV. SKETCH
Draw the actual set-up of the experiment neatly and label each
apparatus.
V. PROCEDURE
1. Set up oil tester and fill the cup up to a standardized mark at the inside
of the cup which is about 3/8 inch (9.5 mm) below its upper edge.
2. Place the cup on the tripod then immerses the thermometer bulb
completely in the oil but not touching the bottom of the cup.
3. Apply the test flame. This flame should be about 3 inches in length and
should not be drawn across. The test flame should be applied at 50 deg F
interval throughout the test.
4. Record the temperature reading as the flash point at which fire flash or
vapour combustion takes place near the surface of the oil.
5. Repeat the procedure using another type of soil.
VII. GRAPH
.
VIII. OBSERVATION
As we observe the data above, the oil sample took atleast16 minutes and
11 seconds to reach the flash point with a temperature of 270 degrees Celsius.
Approximately a minute later, the fire point was achieved at a time of 17
minutes and 12 seconds with a temperature of 284 degrees Celsius. Room
temperature or the initial temperature was 36 degrees Celsius. At the 200-
degree mark, the oil sample started showing steam indicating that it is on its
way to boil. With a constant interval, a matchstick was ignited to test if the oil
sample has already achieved the flash point. At the 250-degree mark, the oil
sample started to get dark in color. Symptoms of occurring flash point
indicated the sudden ignition at the oil level in a short time. During the last
degrees, when a matchstick is ignited, fire started to contain itself within the
surface of the oil, thus, signifying that the fire point has achieved. Meanwhile,
in the graph shown above, it almost resembles a linear equation, however,
temperature’s rising up exponentially over time. At 230-degree mark, the
temperature was gradually increasing slowly as it reaches the flash point and
fire point. Lastly, flash point occurs first than the fire point with an
approximate difference of 10%.
IX. CONCLUSION