Transient Voltage ST-SPT Series

Surge Suppressors By:


Series Wired AC Unit with Frequency Attenuation and Discrete All-Mode Protection

5500 E. Loop 820 #205


Ft. Worth, TX 76119
Phone: 817.483.8497
Fax: 817.572.2242
“Power Quality is our Only Business” www.sinetamer.com

The SineTamer© ST-SPT devices provide the best ring wave transient protection available for a device of its type.
These devices are intended for single 120, 240, 380 or 480 VAC circuit applications at locations feeding
sensitive/critical equipment. It is extremely effective in limiting transients generated inside the facility and is an
absolute must on circuits feeding critical microprocessor based equipment. It boasts a robust 120kA per phase peak
surge current rating on all models.
This economical device is unique in that it is designed as a stand-alone surge suppression device and requires no
special enclosure when used outside an existing enclosure or cabinet. Its compact size makes installation a breeze
and the warranty is the best in the industry. Add to all that, dedicated “all mode” Frequency Attenuation Network
and completely encapsulated Optimal Response Network, and you get a device that defines effective and reliable
surge suppression.
We believe that we offer the most versatile SPD devices on the market with performance specs that are superior to
our competitors and a warranty that is second to none.

GENERAL
Description: Series wired parallel-connected transient voltage surge suppressor with encapsulated
Optimal Response Network and Frequency Attenuation Network circuitry
Application: Designed for use at ANSI/IEEE Category A with susceptibility up to medium exposure levels
to protect sensitive/critical loads fed by a single circuit.
Warranty: 25 Years Unlimited Free Replacement
Unit Listings: Recognized Component for 120 and 240V versions under ANSI/UL VZCA-1449-2006 (4th
Edition) by CSA (CSA MC#241804); UL1283 and CE Compliant

MECHANICAL
Enclosure: Plastic, UL 94V
Mounting: External mounting feet.
Connection Method: 3-Lug screw terminal strip at both the input and output sides of the device.
Shipping Weight: ≈ 2 lbs

ELECTRICAL
Circuit Design: Series wired, parallel connected hybrid design incorporating discrete all mode protection with
our Optimal Response Network and Frequency Attenuation Network circuitry design. All
suppression circuits are completely encapsulated in our exclusive dielectric compound to
assure long component life and complete protection from the environment and/or vibration.
Protection Modes: Dedicated protection components and circuitry for each mode. Discrete L-N (Normal Mode),
and Discrete L-G, N-G (Common Mode)
UL 4th SVR 120V = 500V - L-N/L-G/N-G // 240V = 900V - L-N/L-G/N-G
Input Power Frequency: 50-60Hz
Max Operating Current: Up to 30 Amps AC (60 Amp models available)
Nominal Discharge Current 5 Ka
Altitude: 6000 meters
EMI/RFI Attenuation: 40dB Max. from 1kHz to 10MHz
Circuit Diagnostics: Super Bright LED, normally on.
Circuit Interrupt: External (see installation instructions for details).
kAIC Rating: 10 kAIC when installed per installation instructions
Options: -T = Touch safe cover, -P = wires on one end for parallel install, -N = remove N-G tracking,
-DIN = din rail mounting feet. –C = DRC (125Vrms, 0.5 amps; 30VDC, 1.0 amps – N/O, N/C)
Operating Temperature: Up to 80°C

Because we are constantly seeking to improve our products, specifications are subject to change at any time.
© 2020 ECS International Inc. Specification Last Changed 08/20
MEASURED LIMITING VOLTAGE PERFORMANCE AND ELECTRICAL SPECIFICATIONS
Voltage Table ANSI/IEEE C62.41 & C62.45
1P1, 2N1 120 volts H-N-G / H-H-G Let-Through Voltage Test Results
1P2, 2N2 240 volts H-N-G / H-H-G A1 A3 B3/C1
1P3/1P4 380/480 H-N-G 2kV, 67A 6kV, 200A 6kV, 3kA
Mode 100KHz Ring 100KHz Ring Impulse Wave
2N3/2N4 380/480 H-H-G
Wave Wave 90º Phase Angle
Model MCOV 180º Phase 90º Phase
Angle Angle

150 L-L L-L 45 (D) 95V (D) 345 (D)


ST-SP2N1
150 L-G L-G 345 (D)
150 L-N L-N 20V (D) 94V (D) 285V (D)
ST-SPT1P1 150 L-G L-G 45V (D) 190V (D) 395V (D)
150 N-G N-G 30V (S) 94V (S) 435V (S)
150 L-N L-N 28V (D) 99V (D) 400V (D)
ST-SP1P1-P
150 L-G L-G 50V (D) 210V (D) 510V (D)
(Up to 60 amps)
150 N-G N-G 35V (S) 102V (S) 545V (S)
320 L-N L-N 20V (S) 105V (D) 525V (S)
ST-SPT1P2 320 L-G L-G 50V (S) 105V (S) 525V (S)
320 N-G N-G 33V (S) 150V (S) 830V (S)
320 L-N L-N 23V (S) 130V (S) 578V (S)
ST-SP1P2-P
320 L-G L-G 55V (S) 185V (S) 588V (S)
(Up to 60 amps)
320 N-G N-G 36V (S) 160V (S) 940V (S)
320 L-L L-L 36V (S) 135V (S) 578V (S)
ST-SPT2N2
320 L-G L-G 588V (S)
ST-SP2N2-P 320 L-L L-L 40V (S) 140V (S) 578V (S)
(Up to 60 amps) 320 L-G L-G 588V (S)
550 L-N L-N 35 (S) 725 (S) 855 (S)
ST-SPT1P3
550 L-G L-G 87 (S) 950 (S) 1,014 (S)
ST-SP1P4-P
550 N-G N-G 65 (S) 725 (S) 855 (S)
*Measured Limiting Voltage (Let-Through) Test Environment: Dynamic (D) or Static (S), positive polarity. All voltages are peak (10%). Time Base is 1ms. 180
phase angle voltages are measured form the zero crossing, 90 phase angle voltages are measured from the positive peak of the sine wave to the positive peak of
the surge indicating actual excess voltage let through. All tests were performed with the device connected in series simulating actual installation.
**Suppressed Voltage Test Environment using test parameters as defined by Underwriters Laboratory: Dynamic (D) or Static (S), Positive Polarity. Time
base=10s. All voltages are peak (±10%), 90° phase angle voltages are measured from the zero crossing to the peak of the surge. All SineTamer products are
manufactured exclusively for Energy Control Systems by Surge Suppression Incorporated.

Because we are constantly seeking to improve our products, specifications are subject to change at any time.
© 2020 ECS International Inc. Specification Last Changed 08/20
Because we are constantly seeking to improve our products, specifications are subject to change at any time.
© 2020 ECS International Inc. Specification Last Changed 08/20

You might also like