Data Sheet Transjawa
Data Sheet Transjawa
Document Title : DATA SHEET FOR TRANSMITTER (INCLUDDIING RTD AND THERMOWELL)
System : General
Name :
Date :
Signature :
PT PDC – PT ELNUSA
DATA SHEET FOR TRANSMITTER (INCLUDDIING RTD AND THERMOWELL)
Document No. Rev.
Page 2 of 7
PGDD-KPE-1472-00-EIC-DS-V41-002 0
TABLE OF CONTENTS
DATA SHEET FOR TRANSMITTER (INCLUDDIING RTD AND THERMOWELL)
Document No. Rev.
Page 5 of 7
PGDD-KPE-1472-00-EIC-DS-V41-002 0
GENERAL 1 Tag Number PIT-001A, PIT-001B
2 Service Export Gas Pressure To Pertamina
3 P&ID No. DUDM-02-PRO-PID-006 SHEET 1 OF 1
4 Design Pressure 690 Psig
5 Design Temp. 150°F
PROCESS 6 Fluid Name Hydrocarbon
CONDITIONS 7 Fluid State Gas/Vapor
8 Pressure Min. Nor. Max. 363 Psig 363 Psig 363 Psig
9 Temperature Min. Nor. Max. 86°F 100°F 100°F
10 Base Pressure 14.73 Psia
11 Base Temperature 60 °F
UNIT 12 Capsule Type Single crystal silicon resonant
13 Transmitter Type Pressure Transmitter
14 Instrument Range Min Max. −14.5 Psig 1450 Psig
15 Zero & Span Adjustment MIn Max. 72.5 Psig 1450 Psig
16 Meter Range MIn Max. 0 Psig 800 Psig
17 Maximum Pressure Limit (psig) 1450
18 Housing Material Cast aluminum alloy with Epoxy and polyurethane resin solvent coating
19 Capsule Material Hastelloy C-276 (Diaphgram); 316L SST (Others)
20 Connection In Size Rating 1/2" NPT M
21 Type Bottom Connection
22 Elec. Haz. Protection STD Method Gr. Temp. II 2G 2D Ex d Ex d IIC T4...T6
23 Weather Protection IP66
24 Sourge Arrester Yes
25 Output Signal 4-20 mA with Hart
26 Power Supply 10.5 to 32 V DC
27 Electrical Connection 1/2" NPT
28 Accuracy ±0.055% of Full Span
29 Stability ±0.1% of URL per 10 years
DIAPHRAGM SEAL 30 Seal Type NA
31 Diaphragm Material NA
32 Flange Material NA
33 Connection Size Rating NA NA
34 Type Facing NA NA
35 Capillary Type Material NA NA
36 Capillary Length NA
OPTIONS 37 Integral Meter Integrated LCD Display
38 Integral Meter Range Min. Max. NA NA
39 Remote Output Gauge Tag No. NA NA
40 Remote Output Gauge Range Min. Max. NA NA
41 Manifold Type Material 2 Way Manifold 316 SS
42 Mounting Brackets Universal Mounting Bracket for 2"-Pipe
43 Upper / Down Burnout Failure Up-scale: 110%, 21.6 mA DC and Down-scale: –5%, 3.2 mA DC
44 Lightning Protector Yes
45 Material 316 Stainless Steel
46 Manifold Type: 2-Way
47 Inlet Connection: 1/2" NPT F
48 Outlet Connection: 1/2" NPT F
Manifold 49 Vent Size (inch): 1/4" NPT F
50 Packing Material: PTFE
51 Maximum Working Pressure (psi): 6000
52 Manufacturer Parker
53 Model HLS2VNC
LINE/VESSEL 54 Number 16"-PG-DM-A02A-026
55 Size Class Sch. 16 inch 300 40
PURCHASE 56 Manufacturer Yokogawa
57 Model EJA530E Series
NOTES:
1. Name Plate shall be included
STANDARD SPECIFICATIONS
Refer to GS 01C31T02-01EN for Fieldbus
communication type and GS 01C31T04-01EN for
PROFIBUS PA communication type for the items Specification Conformance
marked with “◊.” EJA-E series ensures specification conformance to at
least ±3σ.
□ SPAN AND RANGE LIMITS Reference Accuracy of Calibrated Span
(includes the effects of terminal-based linearity,
(For EJA510E, values are in absolute and lower
hysteresis, and repeatability)
range limits are 0.)
Measurement Reference Accuracy
Measurement psi bar kg/cm2
MPa span Span≥X Span<X
Span/Range (/D1) (/D3) (/D4)
10 to 200 A
Span 1.45 to 29 0.1 to 2 0.1 to 2
kPa B ±(0.0055 URL/ span)% of Span
A ±0.055%
−100 to −14.5 to
Range −1 to 2 −1 to 2 C of Span
200 kPa 29
14.5 to ±(0.0088 ∗50 MPa/ span)%
Span 0.1 to 2 1 to 20 1 to 20 D
290 of Span
B
−14.5 to
Range −0.1 to 2
290
−1 to 20 −1 to 20 [When /HAC is specified]
72.5 to Reference Accuracy
Span 0.5 to 10 5 to 100 5 to 100 Measurement
1450
C span Span≥X Span<X
−14.5 to
Range −0.1 to 10 −1 to 100 −1 to 100 A ±(0.004 URL/ span)% of Span
1450
720 to B ±(0.005+0.0035 URL/ span) %
Span * 5 to 50 50 to 500 50 to 500 ±0.04%
7200 C of Span
D of Span
−14.5 to
Range * −0.1 to 50 −1 to 500 −1 to 500 ±(0.0064 ∗50 MPa/ span)%
7200 D
of Span
*: Maximum value shall be 70 MPa, 10150 psi,
700 bar or 700 kgf/cm2 respectively when /HG is
specified. Measurement
A B C D
span
□ PERFORMANCE SPECIFICATIONS 20 kPa 0.2 MPa 1 MPa 8 MPa
X
Zero-based calibrated span, linear output, wetted (2.9 psi) (29 psi) (145 psi) (1160 psi)
parts material code ‘S’ and silicone oil, unless URL 200 kPa 2 MPa 10 MPa 50 MPa
otherwise mentioned. (Upper range limit) (29 psi) (290 psi) (1450 psi) (7200 psi)
For Fieldbus and PROFIBUS PA communication
types, use calibrated range instead of span in the
following specifications.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN June 1, 2017-00
<<Contents>> <<Index>> 3
Ambient Humidity Limits
0 to 100% RH
Maximum Over Pressure 100(14.5) Atmospheric
pressure
Working
Pressure pressure
Capsule EJA510E EJA530E kPa abs
A and B 4 MPa abs (580 psia) 4 MPa (580 psig) (psia)
C 20 MPa abs (2900 psia) 20 MPa (2900 psig) Applicable range
D 60 MPa abs (8700 psia) * 60 MPa (8700 psig) *
10(1.4)
*: 105 MPa (15200 psi) when /HG is specified.
Working Pressure Limits (Silicone oil)
Maximum Pressure Limits
2.7(0.38)
Pressure
Capsule EJA510E EJA530E 1(0.14)
A 200 kPa abs (29 psia) 200 kPa (29 psig) -40 0 40 80 120
B 2 MPa abs (290 psia) 2 MPa (290 psig) (-40) (32) (104) (176) (248)
C 10 MPa abs (1450 psia) 10 MPa (1450 psig) Process temperature °C (°F)
D 50 MPa abs (7200 psia) * 50 MPa (7200 psig) *
F02E.ai
*: 70 MPa (10150 psi) when /HG is specified.
Figure 1-2. Working Pressure and Process
Minimum Pressure Limit Temperature [For EJA530E]
See graph below
Supply & Load Requirements
100(750)
(Output signal code D and J. Optional features
or approval codes may affect electrical
requirements.)
With 24 V DC supply, up to a 550Ω load can be
used. See graph below.
10(75)
2.7(20) 600
Working
pressure Applicable range E-10.5
1(7.5) R=
kPa abs External 0.0244 Digital
(mmHg abs) load Communication
resistance range
BRAIN and HART
0.13(1)
0.1(0.75) 250
R (Ω)
0.013(0.1)
0.01(0.075) -40 10.5 16.6 25.2 42
0 40 80 120 (248)
(-40) (32) (104) (176) 85 Power supply voltage E (V DC)
F03E.ai
(185)
Process temperature °C(°F) Figure 2. Relationship Between Power Supply
F01E.ai
Voltage and External Load Resistance
Figure 1-1. Working Pressure and Process (Output signal code D and J)
Temperature [For EJA510E]
Supply Voltage “◊”
For 4 to 20 mA HART / BRAIN
(Output signal code D and J)
10.5 to 42 V DC for general use and flameproof type.
10.5 to 32 V DC for lightning protector
(option code A).
10.5 to 30 V DC for intrinsically safe, type n, non-
incendive or non-sparking type.
Minimum voltage limited at 16.6 V DC for digital
communications, BRAIN and HART
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN Oct. 24, 2014-00
<<Contents>> <<Index>> 4
For 1 to 5 V HART □ PHYSICAL SPECIFICATIONS
(Output signal code Q)
Power supply : Wetted Parts Materials
9 to 28 V DC for general use and flame proof type. Diaphragm, process connector
Power Consumption : Refer to “MODEL AND SUFFIX CODES.”
0.96 mA to 3 mA, 27 mW Non-wetted Parts Materials
Load for 4 to 20 mA HART / BRAIN Housing
(Output signal code D and J) • Low copper cast aluminum alloy
0 to 1290Ω for operation • Low copper cast aluminum alloy with corrosion
250 to 600Ω for digital communication resistance properties (copper content ≤ 0.03%,
Output Load for 1 to 5 V HART iron content ≤ 0.15%) (optional)
(Output signal code Q) • ASTM CF-8M Stainless steel (optional)
1 MΩ or greater (meter input impedance) Coating of housing
Note that with three-wire connection, the cable length [for aluminum housing]
may affect the measurement accuracy of the output Urethane curing type polyester resin powder coating
signal. Deep sea moss green paint (Munsell 0.6GY3.1/2.0 or
Communication Requirements “◊” its equivalent)
(Approval codes may affect electrical requirements.) [for option code /P or /X2]
BRAIN Epoxy and polyurethane resin solvent coating
Communication distance Degrees of protection
Up to 2 km (1.25 miles) when using CEV IP66/IP67, Type 4X
polyethylene-insulated PVC-sheathed cables. Pipe
Communication distance varies depending on type of Polypropylene
cable used. Cover O-rings
Load capacitance Buna-N, fluoro-rubber (optional)
0.22 µF or less Name plate and tag
Load inductance 316 SST
3.3 mH or less Fill fluid
Input impedance of communicating device Silicone, Fluorinated oil (optional)
10 kΩ or more at 2.4 kHz. Weight
EMC Conformity Standards Capsule A, B and C: 1.2 kg (2.6 lb)*
EN 61326-1 Class A, Table2 Capsule D: 1.4 kg (3.1 lb)*
EN 61326-2-3 *: Without integral indicator and mounting bracket.
EN 61326-2-5 (for fieldbus) Add 1.5 kg (3.3 lb) for Amplifier housing code 2.
European Pressure Equipment Directive Connections
2014/68/EU Refer to “MODEL AND SUFFIX CODES.”
Sound Engineering Practice (for all capsules)
< Related Instruments>
With option code /PE3 (for D capsule)
FieldMate Versatile Device Management Wizard:
Refer to GS 01R01A01-01E.
Category III, Module H, Type of Equipment: Pressure BRAIN TERMINAL: Refer to GS 01C00A11-00E
Accessory-Vessel, Type of Fluid: Liquid and Gas, Power Distributor: Refer to GS 01B04T01-02E or
Group of Fluid: 1 and 2 GS 01B04T02-02E
EU RoHS Directive
EN 50581 < Reference >
Safety Requirement Standards • is a registered trademark of Yokogawa
EN 61010-1, C22.2 No.61010-1 Electric Corporation.
• Installation category: I • FieldMate; Trademark of Yokogawa Electric
(Anticipated transient overvoltage 330 V) Corporation.
• Pollution degree: 2 • Hastelloy; Trademark of Haynes International Inc.
• Indoor/Outdoor use • HART®: Registered trademark of the FieldComm
Group.
• FOUNDATION Fieldbus; Trademark of the
FieldComm Group.
• PROFIBUS; Registered trademark of Profibus
Nutzerorganisation e.v., Karlsruhe, Germany.
Other company names and product names used in
this material are registered trademarks or trademarks
of their respective owners.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN June 1, 2017-00
<<Contents>> <<Index>> 5
MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJA510E ............................... Absolute pressure transmitter
EJA530E ............................... Gauge pressure transmitter
Output signal -D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC Output with digital communication (BRAIN protocol)
-J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC Output with digital communication
(HART 5/HART 7 protocol)*1
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol, refer to
GS 01C31T02-01EN)
-G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
GS 01C31T04-01EN)
-Q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Low Power, 1 to 5 V DC with digital communication (HART 7 protocol)
Measurement A . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 to 200 kPa (1.45 to 29 psi)
span (capsule) B . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.1 to 2 MPa (14.5 to 290 psi)
C . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 to 10 MPa (72.5 to 1450 psi)
D . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 to 50 MPa (720 to 7200 psi)*10
Wetted parts Process connector Diaphragm Others
material *2 S . . . . . . . . . . . . . . . . . . . . . . . . . 316L SST # Hastelloy C-276 *3# 316L SST #
H . . . . . . . . . . . . . . . . . . . . . . . . . Hastelloy C-276 *3# Hastelloy C-276 *3# Hastelloy C-276 *3#
Process connections 4 . . . . . . . . . . . . . . . . . . . . . . 1/2 NPT female
* For a diaphragm seal 7 . . . . . . . . . . . . . . . . . . . . . . 1/2 NPT male
system, refer to process 8 . . . . . . . . . . . . . . . . . . . . . . G1/2 DIN 16 288 male *4
connections code table 9 . . . . . . . . . . . . . . . . . . . . . . M20×1.5 DIN 16 288 male *4
(p.6).
─ N . . . . . . . . . . . . . . . . . . . Always N
─ -0 . . . . . . . . . . . . . . . . . Always 0
Amplifier housing ► 1 . . . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties *5
2 . . . . . . . . . . . . . . ASTM CF-8M stainless steel *6
Electrical connection 0 . . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . . G1/2 female, two electrical connections with a blind plug*7
7 . . . . . . . . . . . 1/2 NPT female, two electrical connections with a blind plug*7
9 . . . . . . . . . . . M20 female, two electrical connections with a blind plug*7
A . . . . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . . . Digital indicator *8
E . . . . . . . . Digital indicator with the range setting switch (push button) *9
► N . . . . . . . . (None)
Mounting bracket L . . . . . . 316 SST 2-inch pipe mounting
► N . . . . . . None
Optional Codes / Optional specification
The “►” marks indicates the most typical selection for each specification. Example: EJA530E-DAS4N-012NN/.
*1: HART 5 or HART 7 is selectable. Specify upon ordering.
*2: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm
and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium
hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the
wetted parts material.
*3: Hastelloy C-276 or ASTM N10276.
*4: Not applicable for combination of capsule code D and wetted parts material code H. Threads are based on the withdrawn
DIN 16 288.
*5: Not applicable for electrical connection code 0, 5, 7, 9 and A.
*6: Not applicable for electrical connection code 0, 5, 7 or 9.
*7: Material of a blind plug; aluminum alloy for code 5 and 9, and SUS304 for code 7.
*8: Not applicable for output signal code G.
*9: Not applicable for output signal code F.
*10: 5 to 70 MPa (720 to 10150 psi) when /HG is specified.
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR0175/ISO 15156.
Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN June 1, 2017-00
<<Contents>> <<Index>> 6
[Process Connections Code for Diaphragm Seal System]
Following table shows the code dedicated for EJAC50E Diaphragm Seal System. The code cannot be specified
without a diaphragm seal system. Please also refer to the GS 01C25W01-01EN for EJAC50E.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN June 1, 2017-00
<<Contents>> <<Index>> 7
Item Description Code
Canadian CSA Explosionproof Approval *1
Standards Certificate: 2014354
Association Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,
(CSA) C22.2 No.94, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1, C22.2 No.61010-2-030
Explosion-proof for Class I, Groups B, C and D.
Dustignition-proof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: Type 4X,
Temp. Code: T6...T4
CF1
Ex d IIC T6...T4 Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6 *2
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe Approval *1*3
Certificate: 1606623
[For CSA C22.2]
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157,
C22.2 No.213, C22.2 No.61010-1, C22.2 No.60079-0, C22.2 No.61010-2-030
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G,
Class III, Division 1, Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2,
Groups F & G, Class III, Division 1
Enclosure: Type 4X, Temp. Code: T4 Amb. Temp.: –50 to 60°C(–58 to 140°F) *2
Electrical Parameters: [Intrinsically Safe] Vmax=30V, Imax=200mA, Pmax=0.9W, Ci=10nF, Li=0 µH
[Nonincendive] Vmax=30V, Ci=10nF, Li=0 µH CS1
[For CSA E60079]
Applicable Standard: CAN/CSA E60079-11, CAN/CSA E60079-15, IEC 60529:2001
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP66/IP67
Amb. Temp.: –50 to 60°C(–58 to 140°F) *2, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: [Ex ia] Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0 µH
[Ex nL] Ui=30V, Ci=10nF, Li=0 µH
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1*3 CU1
IECEx IECEx Flameproof Approval *1
Applicable Standard: IEC 60079-0:2011, IEC60079-1:2007-4
Certificate: IECEx CSA 07.0008
Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66/IP67 SF2
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6
IECEx Intrinsically safe and Flameproof Approval *1*3
Intrinsically safe Ex ia
Certificate: IECEx DEK 11.0081X
Applicable Standard: IEC 60079-0:2011, IEC 60079-11:2011
Ex ia IIC T4 Ga Enclosure: IP66/IP67
Amb. Temp.: –50 to 60 °C(–58 to 140 °F), Max. Process Temp.: 120 °C(248 °F)
Electrical Parameters: Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 μH
Intrinsically safe Ex ic
Certificate: IECEx DEK 13.0061X
Applicable Standard: IEC 60079-0:2011, IEC 60079-11:2011
SU21
Ex ic IIC T4 Gc IP code: IP66
Amb. Temp.: –30 to 60°C(–22 to 140°F) *2, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: Ui=30V,Ci=27.6 nF, Li=0 μH
Flameproof
Certificate: IECEx CSA 07.0008
Applicable Standard: IEC 60079-0:2011, IEC60079-1:2007-4
Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6
*1: Applicable for Electrical connection code 2, 4, 7, 9, C and D.
*2: Lower limit of ambient temperature is –15°C (5°F) when /HE is specified.
*3: Not applicable for output signal code Q.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN June 1, 2017-00
<<Contents>> <<Index>> 8
OPTIONAL SPECIFICATIONS
Item Description Code
High accuracy type*16 High accuracy HAC
Painting Color change Amplifier cover only*2 P
Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating*1 X2
316 SST exterior parts 316 SST zero-adjustment screw and setscrews*14 HC
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature: –15°C (5°F) HE
Lightning protector Transmitter power supply voltage: 10.5 to 32 V DC ( 10.5 to 30 V DC for intrinsically safe type,
9 to 32 V DC for Fieldbus communication type.)
A
Allowable current: Max. 6000 A ( 1×40 µs ), Repeating 1000 A ( 1×40 µs ) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Oil-prohibited use Degrease cleansing treatment K1
Degrease cleansing treatment with fluorinated oilfilled capsule.
K2
Operating temperature −20 to 80°C (−4 to 176°F)
Capsule fill fluid Flourinated oil filled in capsule
K3
Operating temperature −20 to 80°C (−4 to 176°F)
Calibration units*3 P calibration (psi unit) D1
bar calibration (bar unit) (See Table for Span and Range Limits.) D3
M calibration (kgf/cm2 unit) D4
Output limits and failure Failure alarm down-scale : Output status at CPU failure and hardware error is −5%, 3.2mA DC
C1
operation*4 or less for 4 to 20 mA output type and −5%, 0.8V DC or less for 1 to 5 V output type.
Failure alarm down-scale: Output status at CPU
NAMUR NE43 Compliant C2
failure and hardware error is −5%, 3.2 mA DC or less.
Output signal limits:
3.8 mA to 20.5 mA*17 Failure alarm up-scale: Output status at CPU
C3
failure and hardware error is 110%, 21.6 mA or more.
Gold-plated diaphragm*13 Surface of isolating diaphragms are gold plated, effective for hydrogen permeation. A1
Wired tag plate 316 SST tag plate wired onto transmitter N4
Data configuration at factory*5 Software damping, Descriptor,
Data configuration for HART communication type CA
Message
Data configuration for BRAIN communication type Software damping CB
European Pressure PED 2014/68/EU
Equipment Directive*15*16 Category: III, Module: H, Type of Equipment: Pressure Accessory-Vessel, PE3
Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2
Material certificate*6 Process Connector M15
Pressure test/ Test Pressure: 200 kPa (29 psi) *7 T05
Leak test certificate*12 Test Pressure: 2 MPa (290 psi) *8 T06
Nitrogen(N2) Gas or Water*11
Test Pressure: 10 MPa (1450 psi) *9 T07
Retention time: one minute
Test Pressure: 50 MPa (7200 psi) *10 T08
Test Pressure: 70 MPa (10150 psi)*19 T15
High Pressure-proof
Maximum pressure limit and maximum span : 70 MPa. HG
structure*18
*1: Not applicable with color change option. Not applicable for amplifier housing code 2.
*2: Not applicable for amplifier housing code 2 and 3.
*3: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1,
D3, and D4.
*4: Applicable for output signal codes D and J. The hardware error indicates faulty amplifier or capsule.
*5: Also see ‘Ordering Information’.
*6: Material traceability certification, per EN 10204 3.1 B.
*7: Applicable for capsule code A.
*8: Applicable for capsule code B.
*9: Applicable for capsule code C.
*10: Applicable for capsule code D without /HG.
*11: Pure nitrogen gas or pure water is used for oil-prohibited use (option codes K1 and K2).
*12: The unit on the certificate is always kPa/MPa regardless of selection of option code D1, D3 and D4.
*13: Applicable for wetted parts material code S.
*14: 316 or 316L SST. The specification is included in amplifier code 2.
*15: Applicable for measurement span code D. If compliance with category III is needed, specify this option code.
*16: Not applicable for output signal code Q.
*17: The 1 to 5 V voltage output corresponding to 4 to 20 mA current output is applied to output signal code Q which is non-
compliant to NAMUR NE43.
*18: Applicable for capsule code D.
*19: Applicable for capsule code D with /HG specified.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN June 1, 2017-00
<<Contents>> <<Index>> 9
OPTIONAL SPECIFICATIONS (for Diaphragm Seal System)
Following table shows the option codes dedicated for EJXC50A Diaphragm Seal System. These codes cannot be
specified without a diaphragm seal system. Please also refer to the GS 01C25W01-01EN for EJXC50A.
DIMENSIONS
Unit: mm (approx.inch)
Model EJA510E and EJA530E
95(3.74) 188(7.40)
60(2.36)*2 Integral indicator Zero
(optional) adjustment 110(4.33)
Extenal indicator 12 39
Conduit connection Conduit connection
(0.47) (1.54)
(optional)
ø78(3.07)
(2.76)
54
ø70
126(4.96)
110(4.33)
(2.13)
159(6.26)
6
(6.50)
165
(0.24)
Ground terminal
Electrical connection
for code 5 and 9. Open to
atmosphere*1
2-inch pipe
Mounting bracket 12*3 (O.D. 60.5 mm) 129(5.08)
(optional) (0.47)
(6.77)
172
ø6
5(0.20)
(0.24)
F04E.ai
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN June 1, 2017-00
<<Contents>> <<Index>> 10
CHECK + 3
– 2
External indicator (ammeter) terminals*1*2
Ground terminal
Three or four wire connection. For four wire connection, both supply
and signal lines use SUPPLY - terminal.
F05E.ai
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN Oct. 24, 2014-00
<<Contents>> <<Index>> 11
< Ordering Information > “◊” < Factory Setting > “◊”
Specify the following when ordering
Tag number As specified in order
1. Model, suffix codes, and option codes
2. Calibration range and units Software
‘2.00 s’ or as specified in order
1) Calibration range can be specified with range damping *1
value specifications up to 5 digits (excluding any Calibration range
As specified in order
decimal point) for low or high range limits within lower range value
the range of -32000 to 32000. When reverse Calibration range
range is designated, specify Lower Range upper range As specified in order
Value (LRV) as greater than Upper Range Value value
(URV). [EJA530E]
2) Specify only one unit from the table, ‘Factory Selected from mmH2O, mmH2O(68°F),
mmAq*2, mmWG*2, mmHg, Pa, hPa*2,
Settings’ when shipped.’
kPa, MPa, mbar, bar, gf/cm2, kgf/cm2,
3. Display scale and units (for transmitters equipped inH2O, inH2O(68°F), inHg, ftH2O,
with integral indicator only) ftH2O(68°F) or psi. (Only one unit can be
Specify either 0 to 100 % or engineering unit scale specified)
Calibration range
and ‘Range and Unit’ for engineering units scale: units
Scale range can be specified with range limit [EJA510E]
Torr, Pa abs, hPa abs*2, kPa abs,
specifications up to 5 digits (excluding any decimal
MPa abs, mbar abs, bar abs, kgf/cm2 abs,
point) for low or high range limits within the range mmH2O abs, mmH2O abs(68°F),
of -32000 to 32000. The unit display consists of mmHg abs, inH2O abs, inH2O abs(68°F),
6-digit, therefore, if the specified unit is longer than inHg abs, ftH2O abs, ftH2O abs(68°F),
7 characters excluding ‘/’, the first 6 characters will psia, atm.
be displayed on the unit display. Designated value specified in order.
4. HART PROTOCOL Display setting
(%, or user scaled value.)
When output signal code is “J”, specify the HART
protocol revision “5” or “7”. *1: To specify these items at factroy, /CA or /CB
5. TAG NO (if required) option is required.
*2: Not available for HART protocol type.
Specified characters (up to 16 characters for
BRAIN, 22 characters for HART, or 16 characters
for /N4 tag) are engraved on the stainless steel tag < Material Cross Reference >
plate fixed on the housing.
ASTM JIS
6. SOFTWARE TAG (for HART only. if required)
Specified characters (up to 32 characters) are set grade 316 SUS316
as “Tag” (the first 8 characters) and “Long tag”*1 grade 316L SUS316L
(32 characters) in the amplifier memory. Use grade 304 SUS304
alphanumeric capital letters.
When the “SOFTWARE TAG” is not specified,
specified “TAG NO” is set as “Tag” (the first 8
characters) and “Long tag”*1 (22 characters) in the
amplifier memory.
*1: applicable only when HART 7 is selected.
7. Other factory configurations (if required)
Specifying option code CA or CB will allow further
configuration at factory. Following are configurable
items and setting range.
[/CA : For HART communication type]
1) Descriptor (up to 16 characters)
2) Message (up to 30 characters)
3) Software damping in second (0.00 to 100.00)
[/CB : For BRAIN communication type]
1) Software damping in second (0.00 to 100.00)
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31F01-01EN June 1, 2017-00
Subject to change without notice.
ATTACHMENT-2
CATALOGUE OF DIFF. PRESSURE
TRANSMITTER
<<Contents>> <<Index>>
General EJA110E
Specifications Differential Pressure Transmitter
GS 01C31B01-01EN
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 3
Static Pressure Signal Range and Accuracy Zero Adjustment Limits
(For monitoring via communication or on Zero can be fully elevated or suppressed, within the
indicator. Includes terminal-based linearity, lower and upper range limits of the capsule.
hysteresis, and repeatability) External Zero Adjustment
Range External zero is continuously adjustable with
Upper Range Value and Lower Range Value of the 0.01% incremental resolution of span. Re-range
static pressure can be set in the range between 0 can be done locally using the digital indicator with
and Maximum Working Pressure(MWP). The upper rangesetting switch.
range value must be greater than the lower range Integral Indicator (LCD display, optional) “◊”
value. Minimum setting span is 0.5 MPa(73 psi). 5-digit numerical display, 6-digit unit display and bar
Measuring either the pressure of high pressure side graph.
or low pressure side is user-selectable. The indicator is configurable to display one or up to
Accuracy four of the following variables periodically.;
Absolute Pressure Measured differential pressure, differential pressure
1 MPa or higher: ±0.5% of span in %, scaled differential pressure, measured static
Less than 1 MPa: ±0.5%×(1 MPa/span) of span pressure. See also “Factory Setting.”
Gauge Pressure Reference Local Parameter Setting
Gauge pressure reference is 1013 hPa (1 atm) (Output signal code D, J and Q)
Note: Gauge pressure variable is based on the above Parameter configuration by the external zero
fixed reference and thus subject to be affected by
the change of atomospheric pressure.
adjustment screw and push button (Integral indicator
code E) offers easy and quick setup for parameters of
□ FUNCTIONAL SPECIFICATIONS Tag number, Unit, LRV, URV, Damping, Output mode
(linear/square root), Display out 1, and Re-range by
Output “◊” applying actual pressure (LRV/URV).
For 4 to 20 mA HART / BRAIN Burst Pressure Limits
(Output signal code D and J) 69 MPa (10,000 psi) for wetted parts material S,
Two wire 4 to 20 mA DC output with digital except for Measurement span F.
communications, linear or square root programmable. 47 MPa (6,800 psi) for wetted parts material other
BRAIN or HART FSK protocol are superimposed on than S or Measurement span F.
the 4 to 20 mA signal.
Output range: 3.6 mA to 21.6 mA Self Diagnostics
Output limits conforming to NAMUR NE43 can be CPU failure, hardware failure, configuration error,
pre-set by option code C2 or C3. and over-range error for differential pressure, static
pressure and capsule temperature.
For 1 to 5 V HART User-configurable process high/low alarm for
(Output signal code Q) differential pressure and static pressure is also
Three or four wire low power 1 to 5 V DC output with available.
HART, linear or square root programmable.
HART protocol are superimposed on the 1 to 5 V DC Signal Characterizer (Output signal code D, J and Q)
signal. User-configurable 10-segment signal characterizer
Output range: 0.9 V to 5.4 V DC for 4 to 20 mA output.
Failure Alarm SIL Certification
For 4 to 20 mA HART / BRAIN EJA-E series transmitters except Fieldbus,
(Output signal code D and J) PROFIBUS PA and 1-5V DC with HART (Low Power)
Analog output status at CPU failure and hardware communication types are certified in compliance with
error; the following standards;
Up-scale: 110%, 21.6 mA DC or more (standard) IEC 61508: 2010; Part1 to Part 7
Down-scale: −5%, 3.2 mA DC or less Functional Safety of Electrical/electronic/
programmable electronic related systems; SIL 2
For 1 to 5 V HART capability for single transmitter use, SIL 3 capability
(Output signal code Q) for dual transmitter use.
Analog output status at CPU failure and hardware
error; □ NORMAL OPERATING CONDITION
Up-scale: 110%, 5.4 V DC or more (standard) (Optional features or approval codes may
Down-scale: −5%, 0.8 V DC or less
affect limits.)
Damping Time Constant (1st order)
Amplifier damping time constant is adjustable from Ambient Temperature Limits
0.00 to 100.00 s by software and added to response −40 to 85°C (−40 to 185°F)
time. −30 to 80°C (−22 to 176°F) with LCD display
Note: For BRAIN protocol type, when amplifier software Process Temperature Limits
damping is set to less than 0.5 s, communication −40 to 120°C (−40 to 248°F)
may occasionally be unavailble during the
operation, especially while output changes Ambient Humidity Limits
dynamically. The default setting of damping 0 to 100% RH
ensures stable communication. Working Pressure Limits (Silicone oil)
Update Period “◊” Maximum Pressure Limits (MWP)
Differential pressure: 45 ms 16 MPa (2300 psi)
Static pressure: 360 ms 25 MPa (3600 psi) for option code /HG
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN Feb. 10, 2017-00
<<Contents>> <<Index>> 4
Minimum Pressure Limit For 1 to 5 V HART
See graph below (Output signal code Q)
Power supply :
9 to 28 V DC for general use and flame proof type.
100(14.5) Atmospheric Power Consumption :
pressure 0.96 mA to 3 mA, 27 mW
Working
pressure
Load for 4 to 20 mA HART / BRAIN
kPa abs (Output signal code D and J)
(psi abs) 0 to 1290Ω for operation
250 to 600Ω for digital communication
Applicable range
10(1.4) Output Load for 1 to 5 V HART
(Output signal code Q)
1 MΩ or greater (meter input impedance)
Note that with three-wire connection, the cable length
2.7(0.38) may affect the measurement accuracy of the output
signal.
Communication Requirements “◊”
1(0.14) (Approval codes may affect electrical requirements.)
-40 0 40 80 120
(-40) (32) (104) (176) (248) BRAIN
Process temperature °C (°F) Communication distance
F01E.ai
Up to 2 km (1.25 miles) when using CEV
polyethylene-insulated PVC-sheathed cables.
Figure 1. Working Pressure and Process Temperature Communication distance varies depending on type of
cable used.
Supply & Load Requirements Load capacitance
(Output signal code D and J. Optional features 0.22 µF or less
or approval codes may affect electrical Load inductance
requirements.) 3.3 mH or less
With 24 V DC supply, up to a 550Ω load can be
used. See graph below. Input impedance of communicating device
10 kΩ or more at 2.4 kHz.
EMC Conformity Standards
EN 61326-1 Class A, Table2
EN 61326-2-3
600 EN 61326-2-5 (for fieldbus)
E-10.5 European Pressure Equipment Directive
R=
External 0.0244 Digital 2014/68/EU
load Communication
resistance Sound Engineering Practice (for all capsules)
range
BRAIN and HART With option code /PE3 and /HG (for M, H and V
250
capsules and wetted parts material code S.)
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 5
□ PHYSICAL SPECIFICATIONS < Related Instruments>
FieldMate Versatile Device Management Wizard:
Wetted Parts Materials Refer to GS 01R01A01-01E.
Diaphragm, cover flange, process connector, BRAIN TERMINAL: Refer to GS 01C00A11-00E
capsule gasket, and vent/drain plug Power Distributor: Refer to GS 01B04T01-02E or
Refer to “MODEL AND SUFFIX CODES.” GS 01B04T02-02E
Process connector gasket
PTFE Teflon < Reference >
Fluorinated rubber for option code N2 and N3 • is a registered trademark of Yokogawa
Non-wetted Parts Materials Electric Corporation.
• FieldMate; Trademark of Yokogawa Electric
Bolting Corporation.
B7 carbon steel, 316L SST or 660 SST • Teflon; Trademark of E.I. DuPont de Nemours & Co.
Housing • Hastelloy; Trademark of Haynes International Inc.
• Low copper cast aluminum alloy • HART®: Registered trademark of the FieldComm
• Low copper cast aluminum alloy with corrosion Group.
resistance properties (copper content ≤ 0.03%, • FOUNDATION Fieldbus; Trademark of the
iron content ≤ 0.15%) (optional) FieldComm Group.
• ASTM CF-8M Stainless steel (optional) • PROFIBUS; Registered trademark of Profibus
Coating of housing Nutzerorganisation e.v., Karlsruhe, Germany.
[for aluminum housing] Other company names and product names used in
Urethane curing type polyester resin powder coating this material are registered trademarks or trademarks
Deep sea moss green paint (Munsell 0.6GY3.1/2.0 or of their respective owners.
its equivalent)
[for option code /P or /X2]
Epoxy and polyurethane resin solvent coating
Degrees of protection
IP66/IP67, Type 4X
Cover O-rings
Buna-N, fluoro-rubber (optional)
Name plate and tag
316 SST
Fill fluid
Silicone, fluorinated oil (optional)
Weight
[Installation code 7, 8 and 9]
2.8 kg (6.2 lb) for measurement span code M, H and
V, wetted parts material code S and L without integral
indicator, mounting bracket, and process connector.
3.7 kg (8.2 lb) for measurement span code F without
integral indicator, mounting bracket, and process
connector.
Add 1.5 kg (3.3lb) for Amplifier housing code 2.
Connections
Refer to “MODEL AND SUFFIX CODES.”
Process connection of cover flange: IEC61518
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 6
MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJA110E ............................... Differential pressure transmitter
Output signal -D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
-J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)*1
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol, refer to
GS 01C31T02-01EN)
-G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
GS 01C31T04-01EN)
-Q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Low Power, 1 to 5 V DC with digital communication (HART 7 protocol)
Measurement F . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 to 5 kPa (2.0 to 20 inH2O) (For Wetted parts material code S)
span (capsule) L . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 to 10 kPa (2.0 to 40 inH2O)
(For Wetted parts material code M, H, T, A, D, B and W)
M . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 to 100 kPa (4 to 400 inH2O)
H . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 to 500 kPa (20 to 2000 inH2O)
V . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.14 to 14 MPa (20 to 2000 psi)
Wetted parts . . . . . . . . . . . . . . . . . . . . . . . . . Refer to “Wetted Parts Material” Table.
material *2
Process connections 0 . . . . . . . . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
See the table in the next1 . . . . . . . . . . . . . . . . . . . . . . with Rc1/4 female process connector
page for the codes for a 2 . . . . . . . . . . . . . . . . . . . . . . with Rc1/2 female process connector
diaphragm seal system. 3 . . . . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts materia J . . . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . . . 660 SST
Installation -7 . . . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection downside
-8 . . . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . . . . . . Bottom Process Connection, left side high pressure*3
-U . . . . . . . . . . . . . . . . . Universal flange*3
Amplifier housing 1 . . . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties*5
2 . . . . . . . . . . . . . . ASTM CF-8M stainless steel*6
Electrical connection 0 . . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . . G1/2 female, two electrical connections and a blind plug*7
7 . . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug*7
9 . . . . . . . . . . . M20 female, two electrical connections and a blind plug*7
A . . . . . . . . . . . G1/2 female, two electrical connections and a SUS316 blind plug
C . . . . . . . . . . . 1/2 NPT female, two electrical connections and a SUS316 blind plug
D . . . . . . . . . . . M20 female, two electrical connections and a SUS316 blind plug
Integral indicator D . . . . . . . . Digital indicator*8
E . . . . . . . . Digital indicator with the range setting switch (push button)*9
► N . . . . . . . . None
Mounting bracket ► B . . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . . 304 SST or SCS13A 2-inch pipe mounting, L type (for vertical piping)
J . . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . . 316 SST or SCS14A 2-inch pipe mounting, L type (for vertical piping)
M . . . . . . 316 SST or SCS14A 2-inch pipe mounting (for bottom process connection type)
N . . . . . . None
Optional Codes / Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: HART 5 or HART 7 is selectable. Specify upon ordering.
*2: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm
and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium
hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the
wetted parts material.
*3: Only applicable for Wetted parts material code S.
*4: Not applicable for measurement span code F.
*5: Not applicable for electrical connection code 0, 5, 7, 9 and A.
*6: Not applicable for electrical connection code 0, 5, 7 and 9.
*7: Material of a blind plug; aluminum alloy for code 5 and 9, and SUS304 for code 7.
*8: Not applicable for output signal code G.
*9: Not applicable for output signal code F.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 7
Table. Wetted Parts Materials
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 8
OPTIONAL SPECIFICATIONS (For Explosion Protected type) “◊”
For other agency approvals and marine approvals, please refer to GS 01C25A20-01EN.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 9
Item Description Code
Canadian CSA Explosionproof Approval *1
Standards Certificate: 2014354
Association Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,
(CSA) C22.2 No.94, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1, C22.2 No.61010-2-030
Explosion-proof for Class I, Groups B, C and D.
Dustignition-proof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: Type 4X,
Temp. Code: T6...T4
CF1
Ex d IIC T6...T4 Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6 *2
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe Approval *1 *3
Certificate: 1606623
[For CSA C22.2]
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157,
C22.2 No.213, C22.2 No.61010-1, C22.2 No.60079-0, C22.2 No.61010-2-030
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G,
Class III, Division 1, Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2,
Groups F & G, Class III, Division 1
Enclosure: Type 4X, Temp. Code: T4 Amb. Temp.: –50 to 60°C(–58 to 140°F) *2
Electrical Parameters: [Intrinsically Safe] Vmax=30V, Imax=200mA, Pmax=0.9W, Ci=10nF, Li=0 µH
[Nonincendive] Vmax=30V, Ci=10nF, Li=0 µH CS1
[For CSA E60079]
Applicable Standard: CAN/CSA E60079-11, CAN/CSA E60079-15, IEC 60529:2001
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP66/IP67
Amb. Temp.: –50 to 60°C(–58 to 140°F) *2, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: [Ex ia] Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0 µH
[Ex nL] Ui=30V, Ci=10nF, Li=0 µH
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1 *3 CU1
IECEx IECEx Flameproof Approval *1
Applicable Standard: IEC 60079-0:2011, IEC60079-1:2007-4
Certificate: IECEx CSA 07.0008
Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66/IP67 SF2
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6
IECEx Intrinsically safe and Flameproof Approval *1*3
Intrinsically safe Ex ia
Certificate: IECEx DEK 11.0081X
Applicable Standard: IEC 60079-0:2011, IEC 60079-11:2011
Ex ia IIC T4 Ga Enclosure: IP66/IP67
Amb. Temp.: –50 to 60 °C(–58 to 140 °F), Max. Process Temp.: 120 °C(248 °F)
Electrical Parameters: Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 μH
Intrinsically safe Ex ic
Certificate: IECEx DEK 13.0061X
Applicable Standard: IEC 60079-0:2011, IEC 60079-11:2011
SU21
Ex ic IIC T4 Gc IP code: IP66
Amb. Temp.: –30 to 60°C(–22 to 140°F) *2, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: Ui=30V,Ci=27.6 nF, Li=0 μH
Flameproof
Certificate: IECEx CSA 07.0008
Applicable Standard: IEC 60079-0:2011, IEC60079-1:2007-4
Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6
*1: Applicable for Electrical connection code 2, 4, 7, 9, C and D.
*2: Lower limit of ambient temperature is –15°C (5°F) when option code HE is specified.
*3: Not applicable for output signal code Q.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 10
OPTIONAL SPECIFICATIONS
Item Description Code
High accuracy type *1*20 High accuracy HAC
High pressure-proof structure Maximum working pressure for differential pressure measurement: 25MPa *18 HG
Painting Color change Amplifier cover only*2 P
Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating*3 X2
316 SST exterior parts 316 SST zero-adjustment screw and setscrews*4 HC
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature: –15°C (5°F) HE
Lightning protector Transmitter power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type.)
Allowable current: Max. 6000 A (1×40 µs), Repeating 1000 A (1×40 µs) 100 times A
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Oil-prohibited use*5 Degrease cleansing treatment K1
Degrease cleansing treatment and fluorinated oilfilled capsule.
K2
Operating temperature −20 to 80°C (−4 to 176°F)
Oil-prohibited use with Degrease cleansing and dehydrating treatment K5
dehydrating treatment*5 Degrease cleansing and dehydrating treatment with fluorinated oilfilled capsule.
K6
Operating temperature −20 to 80°C ( −4 to 176°F)
Capsule fill fluid Fluorinated oil filled in capsule
K3
Operating temperature −20 to 80°C (−4 to 176°F)
Calibration units*6 P calibration (psi unit) D1
bar calibration (bar unit) (See Table for Span and Range Limits.) D3
M calibration (kgf/cm2 unit) D4
Long vent*7 Total length: 119 mm (standard: 34 mm); Total length when combining with option code K1,
U1
K2, K5, and K6: 130 mm. Material: 316 SST
Gold-plated capsule gasket *8 Gold-plated 316L SST capsule gasket. Without drain and vent plugs. GS
Gold-plated diaphragm *9 Surface of isolating diaphragms are gold plated, effective Gold plate thickness: 3 μm A1
for hydrogen permeation. Gold plate thickness: 10 μm A2
Output limits and failure Failure alarm down-scale: Output status at CPU failure and hardware error is −5%, 3.2mA DC
C1
operation*10 or less for 4 to 20 mA output type and −5%, 0.8V DC or less for 1 to 5 V output type.
Failure alarm down-scale: Output status at CPU
NAMUR NE43 Compliant C2
failure and hardware error is −5%, 3.2 mA DC or less.
Output signal limits:
3.8 mA to 20.5 mA*21 Failure alarm up-scale: Output status at CPU
C3
failure and hardware error is 110%, 21.6 mA or more.
Body option*11 Right side high pressure, without drain and vent plugs N1
Terminal N1 and Process connection, based on IEC61518 with female thread on both sides of cover
Side N2
flange, with blind kidney flanges on back.
L H N2, and Material certificate for cover flange, diaphragm, capsule body, and blind kidney flange N3
F03E.ai
Wired tag plate 316 SST tag plate wired onto transmitter N4
Data configuration at factory*12 Software damping, Descriptor,
Data configuration for HART communication type CA
Message
Data configuration for BRAIN communication type Software damping CB
European Pressure PED 2014/68/EU
Equipment Directive*19 Category III, Module H, Type of Equipment: Pressure Accessory-Vessel,
PE3
Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2
Lower limit of ambient and process temperature: −29°C
Material certificate*13 Cover flange *14 M01
Cover flange, Process connector *15 M11
Pressure test/ Test Pressure: 16 MPa(2300 psi) Nitrogen(N2) Gas*17 T12
Leak test certificate*16 Test Pressure: 25 MPa(3600 psi) for option code HG Retention time: one minute T13
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN Feb. 10, 2017-00
<<Contents>> <<Index>> 11
*1: Applicable for capsule code M, H and V when combined with wetted parts material code S. Not applicable for /A2.
*2: Not applicable for amplifier housing code 2 and 3.
*3: Not applicable with color change option. Not applicable for amplifier housing code 2.
*4: 316 or 316L SST. The specification is included in amplifier housing code 2.
*5: Applicable for Wetted parts material code S, M, H and T.
*6: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1,
D3, and D4.
*7: Applicable for vertical impulse piping type (Installation code 7) and Wetted parts material code S, H, M and T.
*8: Applicable for wetted parts material code S; process connection code 0 and 5; and installation code 8 and 9.
Not applicable for option code U1, N2, N3 and M11. No PTFE is used for wetted parts.
*9: Applicable for wetted parts material code S or L. /A2 is not applicable with FM approval.
*10: Applicable for output signal codes D and J. The hardware error indicates faulty amplifier or capsule.
*11: Applicable for wetted parts material code S, M, H and T; process connection codes 3, 4, and 5; installation code 9; and
mounting bracket code N. Process connection faces on the other side of zero adjustment screw.
*12: Also see ‘Ordering Information’.
*13: Material traceability certification, per EN 10204 3.1B.
*14: Applicable for process connections codes 0 and 5.
*15: Applicable for process connections codes 1, 2, 3, and 4.
*16: The unit on the certificate is always Pa unit regardless of selection of option code D1, D3 or D4.
*17: Pure nitrogen gas is used for oil-prohibited use (option codes K1, K2, K5, and K6).
*18: Applicable for Measurement span code M, H, or V; and wetted parts material code S or L. The URL of static pressure range
is also extended to 25 MPa.
*19: Applicable for measurement span code M, H and V and wetted parts material code S. If compliance with category III is
needed, specify this option code with HG.
*20: Not applicable for output signal code Q.
*21: The 1 to 5 V voltage output corresponding to 4 to 20 mA current output is applied to output signal code Q which is non-
compliant to NAMUR NE43.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 12
DIMENSIONS
Unit: mm (approx.inch)
54 (0.24)
(Installation code 7)
6
242(9.53) 110(4.33)
(2.13)
175(6.89)
12 39
97 129(5.08) 2-inch pipe
(3.82) (0.47) (1.54) (O.D. 60.5 mm)
Mounting bracket External indicator
(L-type,optional) Conduit connection
(2.05)
(optional) Vent/Drain
52
ø78(3.07)
138(5.43)*2
95(3.74)
ø70(2.76)
(1.61)
67(2.64)
41
Process
Conduit connector
connection (optional)
41.3 Process connection 54
Zero adjustment High Low
(1.63) pressure (2.13) pressure
Ground terminal side*1 side*1 F04E.ai
(2.76)
(2.13)
ø70
6
175(6.89)
145(5.71)
129(5.08)
(0.24)
Vent plug, Ground
Drain plug*4 terminal Vent plug*4
41
54(2.13)
(1.61) Process Low
High
115(4.53) connection pressure pressure
side*1 side*1
(1.63)
41.3
Process connector
(1.85)
47
*1: When installation code 8 is selected, high and low pressure side on above figure are reversed.
(i.e. High pressure side is on the right side.)
*2: When option code K1, K2, K5 or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.
*3: When option code K1, K2, K5 or K6 is selected, add 30 mm (1.18 inch) to the value in the figure.
*4: Not available when option code GS is selected.
*5: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm from the conduit connection.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 13
Unit: mm (approx.inch)
(0.24)
6
256(10.10)
194(7.64) 110(4.33)
(2.13)
54
97 143(5.63) 9*4 39
2-inch pipe
(3.82) (0.35) (1.54)
(O.D. 60.5 mm)
Mounting bracket
(L-type,optional) External indicator Vent/Drain plugs
Conduit connection
(2.05)
(optional)
52
Integral indicator
(optional)
102(4.02)
234(9.21)
ø78(3.07)
148(5.83)*2
(3.74)
(2.76)
ø70
95
(1.81)
72(2.83)
46
Process
Conduit connector
connection (optional) 54
41.3 Process connection
Zero adjustment High (2.13) Low
(1.63) Ground terminal pressure pressure
side*1 side*1 F06E.ai
(2.13)
6
(2.76)
ø70
(0.24)
159(6.26)
143(5.63)
194(7.64)
Ground terminal
Electrical connection
for code 5, 9, A, and D.
Vent plug
Vent plug
Drain plug
124(4.88)
2-inch pipe
(1.85)
Mounting bracket
(Flat-type,optional)
133*3
(5.24) F07E.ai
*1: When Installation code 8 is selected, high and low pressure side on above figure are reversed.
(i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.
*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value in the figure.
*4: 15 mm (0.59 inch) for right side high pressure.
*5: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm from the conduit connection.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 14
Unit: mm (approx.inch)
ø78(3.07)
(2.13)
6
(2.76)
ø70
145(5.71)
(0.24)
129(5.08)
175(6.89)
Ground terminal
Electrical connection
for code 5, 9, A, and D.
Vent plug
Drain plug
41 54 Drain plug
High Low
Vent plug (1.61) (2.13)
(1.63)
pressure pressure
41.3
(2.13)
6
(2.76)
ø70
(0.24)
159(6.26)
143(5.63)
194(7.64)
Ground terminal
Electrical connection
for code 5, 9, A, and D.
Vent plug
Drain plug
46 Drain plug
54
(1.63)
*1: When Option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value.
*2: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm from the conduit connection.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 15
Unit: mm (approx.inch)
ø78(3.07)
for code 5, 9, A, and D.
(2.76)
ø70
109(4.29)
159(6.26)
Extenal indicator
Conduit connection
(optional)
Ground terminal
(optional) (1.63)
Vent plug
54
2-inch pipe Process connector
High (2.13) Low
(O.D. 60.5 mm) (optional) pressure pressure
side 130(5.12)*2 side
Process connection
129(5.08)
F10E.ai
(2.76)
ø70
159(6.26)
143(5.63)
238(9.37)
Ground terminal
Vent plug
79(3.11)
41.3
(1.63)
2-inch pipe
(O.D. 60.5 mm) Process connector 54
High (2.13) Low
(optional) pressure pressure
side 133(5.24)*2 side
Mounting bracket
54 (optional) 129(5.08)
(2.13)
6
(0.24)
Electrical connection
for code 5, 9, A, and D. F11E.ai
*1: A transmitter with SST housing is not applicable for mounting to horizontal 2-inch pipe.
*2: When Option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value.
*3: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm from the conduit connection.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
<<Contents>> <<Index>> 16
CHECK + 3
– 2
External indicator (ammeter) terminals*1*2
Ground terminal
Three or four wire connection. For four wire connection, both supply
and signal lines use SUPPLY - terminal.
F12E.ai
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN Nov. 7, 2016-00
<<Contents>> <<Index>> 17
< Ordering Information > “◊” < Factory Setting > “◊”
Specify the following when ordering
Tag number As specified in order
1. Model, suffix codes, and option codes
2. Calibration range and units Software
‘2.00 s’ or as specified in order
1) Calibration range can be specified with range damping *1
value specifications up to 5 digits (excluding Output mode ‘Linear’ unless otherwise specified in order
any decimal point) for low or high range limits Calibration range
As specified in order
within the range of -32000 to 32000. When lower range value
reverse range is designated, specify Lower Calibration range
Range Value(LRV) as greater than Upper Range upper range As specified in order
Value(URV). When square root output mode is value
specified, LRV must be “0 (zero) ”. Selected from mmH2O, mmH2O(68°F),
2) Specify only one unit from the table, ‘Factory mmAq*2, mmWG*2, mmHg, Pa, hPa*2,
setting.’ Calibration range kPa, MPa, mbar, bar, gf/cm2,
3. Select linear or square root for output mode and unit kgf/cm2, inH2O, inH2O(68°F), inHg, ftH2O,
ftH2O(68°F) or psi. (Only one unit can be
display mode. specified.)
Note: If not specified, the instrument is shipped set for
linear mode. Designated differential pressure value
4. Display scale and units (for transmitters equipped specified in order. (% or user scaled
Display setting
value.) Display mode ‘Linear’ or ‘Square
with the integral indicator only)
root’ is also as specified in order.
Specify either 0 to 100 % or ‘Range and Unit’ for
engineering units scale: Static pressure ‘0 to 16 MPa (25 MPa*3)’ absolute value.
display range Measuring high pressure side.
Scale range can be specified with range limit
specifications up to 5 digits (excluding any decimal *1: To specify these items at factory, option code CA
point) for low or high range limits within the range or CB is required.
of -32000 to 32000. Unit display consists of 6-digit, *2: Not available for HART protocol type.
therefore, if the specified scaling unit excluding ‘/’ is *3: Applicable for option code HG.
longer than 6-characters , the first 6 characters will
be displayed on the unit display. < Material Cross Reference >
5. HART PROTOCOL
When output signal code is “J”, specify the HART ASTM JIS
protocol revision “5” or “7”. 316 SUS316
6. TAG NO (if required) F316 SUSF316
Specified characters (up to 16 characters for 316L SUS316L
BRAIN, 22 characters for HART, and 16 characters
F316L SUSF316L
for /N4 tag) are engraved on the stainless steel tag
plate fixed on the housing. 304 SUS304
7. SOFTWARE TAG (for HART only. if required) F304 SUSF304
Specified characters (up to 32 characters) are set 660 SUH660
as “Tag” (the first 8 characters) and “Long tag”*1 B7 SNB7
(32 characters) in the amplifier memory. Use CF-8M SCS14A
alphanumeric capital letters.
When the “SOFTWARE TAG” is not specified,
specified “TAG NO” is set as “Tag” (the first 8
characters) and “Long tag”*1 (22 characters) in the
amplifier memory.
*1: applicable only when HART 7 is selected.
8. Other factory configurations (if required)
Specifying option code CA or CB will allow further
configuration at factory. Following are configurable
items and setting range.
[/CA : For HART communication type]
1) Descriptor (up to 16 characters)
2) Message (up to 30 characters)
3) Software damping in second (0.00 to 100.00)
[/CB : For BRAIN communication type]
1) Software damping in second (0.00 to 100.00)
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31B01-01EN June 1, 2017-00
Subject to change without notice.
ATTACHMENT-3
CATALOGUE OF TEMPERATURE
TRANSMITTER
<<Contents>> <<Index>>
General YTA710
Specifications Temperature Transmitter
GS 01C50G01-01EN
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 3
Safety Requirement Standards Communication Requirements (BRAIN type)
EN61010-1, C22.2 No.61010-1 Communication Distance
• Installation category: I Up to 2 km (1.25 miles) when using CEV
(Anticipated transient overvoltage 330 V) polyethylene-insulated PVC-sheathed cables.
• Pollution degree: 2 Communication distance varies depending on type
• Indoor/Outdoor use of cable used.
EN61010-2-030, C22.2 No.61010-2-030 Load Capacitance
• Measurement category: O (Other) 0.22 μF or less
(Measurement Input voltage: 150mVdc max) Load Inductance
EU RoHS Directive 3.3 mH or less
Applicable standard: EN 50581 Input Impedance of communicating device
10 kΩ or more at 2.4 kHz.
■ NORMAL OPERATING CONDITION Load Requirements (HART and BRAIN type)
(Optional features or approval codes may affect limits.) 0 to 1290Ω for operation
250 to 600Ω for digital communication
Ambient Temperature Limits
–40 to 85°C (–40 to 185°F) ■ PHYSICAL SPECIFICATIONS
–30 to 80°C (–22 to 176°F) (with indicator model)
Ambient Humidity Limits Enclosure
0 to 100% RH at 40°C (104°F) Material & coating
Supply Voltage Requirements • Low copper cast aluminum alloy
[for aluminum housing]
HART and BRAIN type Urethane-cured polyester powder coating
10.5 to 42 V DC for general use and flameproof type Mint-green paint (Munsell 5.6BG 3.3/2.9 or its
10.5 to 32 V DC for lightning protector (option code /A) equivalent)
10.5 to 30 V DC for intrinsically safe and [for option code /P or /X2]
non-incendive type Epoxy and polyurethane resin solvent coating
Minimum voltage limited at 16.6 V DC for digital • ASTM CF-8M Stainless steel
communications HART
With 24 V DC supply, up to a 550Ω load can be Degrees of protection
used. See graph below. IP66/IP67, TYPE 4X
Name plate and tag
316 SST
Mounting
600 Optional mounting brackets can be used either for
two-inch pipe or flat panel mounting.
E-10.5
R= Terminal screws
External 0.0244 Digital
load Communication M4 screws
resistance range Integral Indicator (with indicator model)
HART and BRAIN
5-digit numerical display, 6-digit unit display and bar
250 graph.
R (Ω)
Local Parameter Setting (with indicator model)
Parameter configuration by the push button offers
easy and quick setup for parameters.
Accessible parameters are different with each output
10.5 16.6 25.2 42 cord.
Power supply voltage E (V) Weight
F01E.ai Aluminum housing:
Figure 1. Relationship Between Power Supply 1.3 kg (2.9 lb) without integral indicator and mounting
Voltage and External Load Resistance Integral indicator: 0.2 kg (0.4 lb)
Bracket for horizontal pipe: 0.3 kg
Fieldbus type Bracket for vertical pipe: 1.0 kg
9 to 32V DC for general use, flameproof type, and Stainless housing:
non-incendive type 3.1 kg (6.8 lb) without integral indicator and mounting
9 to 30 V DC for intrinsically safe type Integral indicator: 0.3 kg (0.7 lb)
9 to 17.5 V DC for FISCO field device Connections
Communication Requirements Refer to “MODEL AND SUFFIX CODE.”
Supply Voltage: 9 to 32 V DC
Current Draw:
Steady state: 15 mA (max)
Software download state: 24 mA (max)
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 4
Table 1. Sensor type, measurement range, and accuracy
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Jan. 15, 2018-00
<<Contents>> <<Index>> 5
Table 2. Temperature coefficient
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 6
OPTIONAL SPECIFICATION
Item Description Code
Lightning protector *4 Allowable current: Max. 6000A(8×20µs), repeating 1000A(8×20µs), 100 times A
Painting*1*6 Color and coating change Color: Munsell code N1.5 Black
P1
Amplifier cover only*3 Coating: High anti-corrosion coating
Color: Munsell code 7.5BG4/1.5, Jade green
P2
Coating: High anti-corrosion coating
Color: Metallic silver
P7
Coating: High anti-corrosion coating
Color and coating change Color: Munsell code 7.5 R4/14, Red
PR
Amplifier and terminal Covers*3 Coating: High anti-corrosion coating
Coating change High anti-corrosion coating X2
Output signal low-side in Output signal Low-side: –5%, 3.2 mA DC or less.
C1
transmitter failure*2 Sensor burnout is also set to 'Low': –2.5%, 3.6 mA DC.
NAMUR NE43 compliant*2 Output signal limits: Failure alarm down-scale: output status at CPU failure and
3.8 mA to 20.5 mA hardware error is –5%, 3.2 mA or less. C2
Sensor burnout is also set to Low: –2.5%, 3.6 mA DC.
Failure alarm up-scale: output status at CPU failure and hardware
error is 110%, 21.6 mA or more. C3
In this case Sensor burnout is High: 110%, 21.6 mA DC.
Data configuration*9 Description into “Descriptor” parameter of HART protocol (max. 16 characters) CA
Wired tag plate SUS316 stainless steel tag plate wired onto transmitter N4
Sensor matching RTD sensor matching function CM1
Attached flameproof Electrical connection G1/2 female
2pc. V52
packing adapter*5*7 Applicable cable: O.D.8.0 to 12 mm
EAC approval and EAC approval and Russian pattern approval marking
Russian pattern approval VR
marking*8*10
EAC approval marking EAC approval marking without Russian pattern approval marking
without Russian pattern VE
approval marking*8*10
High ambient-temp Refer to Table 3 Temperature coefficient
R1
characteristic type*8
Note: The indication of the nameplate shows an initial shipment state.
*1: Not applicable for Stainless housing.
*2: Not applicable for Fieldbus type.
*3: Except for Amplifier and terminal cover, color and coating are general specification.
*4: Lightning protector (surge absorber) can be remove from, or added to the equipment.
*5: Combination with other Explosion protected other than TIIS flameproof is not possible.
*6: The combination of X2 and P is not possible.
*7: Applicable for Electrical Connection code 4. (The thread of connection between YTA and CABLE GLAND is M20,
and the thread of connection between CABLE GLAND and CABLE is G1/2.)
*8: Not applicable for BRAIN type.
*9: Applicable for only HART type.
*10: Combination with other Explosion protected other than EAC Explosion-proof type is not applicable.
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 7
Table 3. Temperature coefficient (R1 option)
Input Range
Sensor Type A/D Coefficient D/A Coefficient
°C
100 to 300 ±(0.586°C - 0.1433% of reading)
B 300 to 1000 ±(0.187°C - 0.0103% of reading)
1000 to 1820 ±(0.038°C + 0.0046% of reading)
-200 to 0 ±(0.007°C + 0.0158% of abs.reading)
E
0 to 1000 ±(0.007°C + 0.0065% of reading)
-200 to 0 ±(0.009°C + 0.0172% of abs.reading)
J
0 to 1200 ±(0.009°C + 0.0065% of reading)
-200 to 0 ±(0.011°C + 0.0218% of abs.reading)
K
0 to 1372 ±(0.011°C + 0.0078% of reading)
-200 to 0 ±(0.017°C + 0.0265% of abs.reading)
N
0 to 1300 ±(0.017°C + 0.0063% of reading)
-50 to 0 ±(0.088°C + 0.1273% of abs.reading)
R 0 to 200 ±(0.088°C - 0.0142% of reading)
T/C 200 to 1768 ±(0.048°C + 0.0058% of reading)
-50 to 0 ±(0.088°C + 0.0517% of abs.reading)
S 0 to 200 ±(0.088°C - 0.0106% of reading)
200 to 1768 ±(0.054°C + 0.0063% of reading)
-200 to 0 ±(0.011°C + 0.0195% of abs.reading)
T ±{0.0088% of span + 0.007%
0 to 400 ±(0.011°C + 0.0044% of reading)
of(reading − LRV)}
0 to 1400 ±(0.034°C + 0.0069% of reading)
C
1400 to 2315 ±( -0.157°C + 0.0205% of reading)
0 to 1400 ±(0.044°C + 0.0053% of reading)
W3
1400 to 2315 ±( -0.214°C + 0.0237% of reading)
-200 to 0 ±(0.009°C + 0.0117% of abs.reading)
L
0 to 900 ±(0.009°C + 0.0052% of reading)
-200 to 0 ±(0.011°C + 0.0148% of abs.reading)
U
0 to 400 ±(0.011°C + 0.0046% of reading)
Pt100 -200 to 850 ±(0.015°C + 0.005% of reading)
Pt200 -200 to 850 ±(0.023°C + 0.012% of reading)
Pt500 -200 to 850 ±(0.015°C + 0.005% of reading)
RTD Pt1000 -200 to 300 ±(0.015°C + 0.005% of reading)
JPt100 -200 to 500 ±(0.015°C + 0.005% of reading)
Cu10 -70 to 150 ±(0.320°C + 0.120% of reading)
Ni120 -70 to 320 ±(0.010°C + 0.005% of reading)
mV -10 to 120 [mV] ±(0.441uV + 0.0065% of abs.reading)
ohm 0 to 2000 [Ω] ±(0.040Ω + 0.0088% of reading)
Note: Temperature Effect = A/D coeffieicnt + D/A coefficient (The data in the table is the coeffcient per 10°C change.)
Example 1; Pt100Ω, 0 to 200°C calibration range, 50°C reading
(0.015°C + 50°C × 0.005%) + [200°C × 0.0088% + (50 - 0) × 0.007%]
= (0.015°C + 0.0025°C) + (0.0176°C + 0.0035°C )
= ± 0.0386°C [ per 10°C change ]
Example 2; T T/C, -100 to 100°C calibration range, -50°C reading
(0.011°C + | -50°C | × 0.0195%) + {200°C × 0.0088% + [-50 - (-100)] × 0.007%}
= (0.011°C + 0.00975°C) + (0.0176°C + 0.0035°C )
= ± 0.04185°C [ per 10°C change ].
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 8
OPTIONAL SPECIFICATION (For Explosion Protected type)
Item Description Code
ATEX [4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014
Certificate: KEMA 07ATEX0130
II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex tb IIIC T70°C/T90°C Db
KF2
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe ia approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T5…T4 Ga
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
Enclosure: IP66/IP67
Electrical parameters:
Supply/Output circuit: Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Intrinsically safe ic]
KU2
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012
Certificate: Not Applicable as per Annex VIII to ATEX 2014/34/EU
II 3 G Ex ic IIC T5...T4 Gc
Ambient Temperature: –30 to 70°C for T4, –30 to 50°C for T5
Enclosure: IP66/IP67
Overvoltage category: I
Electrical parameters:
Supply/Output circuit: Terminals: +, –
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Same as KF2
Fieldbus:
[Intrinsically safe ia approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T4 Ga
Ambient Temperature: –55 to 60°C
Enclosure: IP66/IP67
Electrical parameters:
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Intrinsically safe ic] KU25
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012
Certificate: Not Applicable as per Annex VIII to ATEX 2014/34/EU
II 3 G Ex ic IIC T4 Gc
Ambient Temperature: –30 to 70°C
Enclosure: IP66/IP67
Electrical parameters:
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Same as KF2
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 9
Item Description Code
IECEx [4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable standard: IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
Certificate: IECEx KEM 07.0044
Ex db IIC T6/T5 Gb, Ex tb IIIC T70°C/T90°C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C (–40 to 167°F) for T6,
SF2
–40 to 80°C (–40 to 176°F) for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C (–22 to 149°F) for T70°C,
–30 to 80°C (–22 to 176°F) for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe ia, ic pproval]
Applicable Standard: IEC 60079-0:2011, IEC 60079-11:2011
Certificate No. IECEx FMG 16.0014X
Ex ia IIC T5…T4 Ga
Ex ic IIC T5...T4 Gc
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5(Ex ia)
Ambient Temperature: –30 to 70°C for T4, –30 to 50°C for T5(Ex ic)
Enclosure: IP66/IP67
Over voltage category: I
Electrical parameters (Ex ia)
Supply/Output circuit: Terminal: +, – SU2
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Electrical parameters (Ex ic)
Supply/Output circuit: Terminal: +, –
Ui=30V, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Same as SF2
Fieldbus:
[Intrinsically safe ia approval]
Applicable Standard: IEC 60079-0: 2011, IEC 60079-11: 2011
Certificate No. IECEx FMG 16.0014X
Ex ia IIC T4 Ga
Ex ic IIC T4 Gc
Ambient Temperature: –55 to 60°C (Ex ia)
Ambient Temperature: –30 to 70°C (Ex ic)
Enclosure: IP66/IP67
Overvoltage category: I
Electrical parameters (Ex ia)
Supply/Output circuit: Terminals: +, –
FISCO field device or SU25
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Electrical parameters (Ex ic)
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit:Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Same as SF2
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 10
Item Description Code
FM (US) [4-20mA & Fieldbus: Explosionproof approval]
Applicable standard: FM Class 3600: 2011, FM Class 3615: 2006, FM Class 3810: 2005,
NEMA250: 2014
Class I, Division 1, Groups A, B, C and D.;
Class II/III, Division 1, Groups E, F and G.
FF1
"FACTORY SEALD, CONDUIT SEAL NOT REQUIRED."
Enclosure Ratings: TYPE 4X
Temperature Class: T6
Ambient Temperature: –40 to 60°C (–40 to 140°F)
Electrical Connection: 1/2NPT female*2
4-20mA:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: FM Class 3600:2011, FM Class 3610:2015, FM Class 3611:2004,
FM Class 3810:2005, ANSI/ISA-60079-0:2013, ANSI/ISA-60079-11:2014, NEMA 250:2003,
ANSI/IEC 60529:2004
Intrinsically safe for
Class I, II, III Division 1, Groups A, B, C, D, E, F, G, T5…T4
Class I Zone 0 AEx ia IIC T5…T4
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G, T5…T4
Class III, Division 1 T5…T4
Class I Zone 2 Group IIC T5…T4
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
Enclosure Type 4X, IP66/IP67
FU1
Electrical parameters:
Intrinsically safe for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ci=22nF, Li=0mH
Sensor circuit:Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Explosionproof approval]
Same as FF1
Fieldbus:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: FM Class 3600:2011, FM Class 3610:2015, FM Class 3611:2004,
FM Class 3810:2005, ANSI/ISA-60079-0:2013, ANSI/ISA-60079-11:2014, NEMA 250:2003,
ANSI/IEC 60529:2004
Intrinsically safe for
Class I, II, III Division 1, Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G T4
Class III, Division 1 T4 Class I Zone 2 Group IIC T4
Ambient Temperature: –55 to 60°C
Enclosure Type 4X, IP66/IP67
Electrical parameters:
FU15
Intrinsically safe for
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Terminals: +, –
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Explosionproof approval]
Same as FF1
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 11
Item Description Code
CSA*3*6 [4-20mA & Fieldbus: Explosionproof approval]
Applicable standard: C22.2 No. 0-10, C22.2 No. 0.4-04, C22.2 No. 25-M1966, C22.2 No. 30-M1986,
FM (Canada)*4*6 C22.2 No. 94-M1991, C22.2 No. 142-M1987, C22.2 No. 157-92, C22.2 No. 213-M1987,
C22.2 No.61010-1-12, C22.2 No. 61010-2-030-12
Class I, Groups B, C and D,
Class II, Groups E, F and G,
Class III. CF1
For Class I, Division2 Groups ABCD Locations “FACTORY SEALED, CONDUIT SEAL NOT
REQUIRED”
Enclosure TYPE 4X
Temperature Class: T6
Ambient Temperature: –40 to 60°C
Electrical Connection: 1/2 NPT female*2
4-20mA:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: CAN/CSA-C22.2 No. 94.2-07, C22.2 No.213:1987,
CAN /CSA-C22.2 No. 60079-0:11, CAN/CSA-C22.2 No. 60079-11:14,
CAN/CSA-C22.2 No. 60529:05, CAN/CSA-C22.2 No. 61010-1-12,
CAN/CSA-C22.2 No. 61010-2-030-12
Intrinsically safe for
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G, T5…T4
Ex ia IIC T5…T4 Ga
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G T5…T4
Class III Division 1 T5…T4
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
Enclosure Type: 4X, IP66/IP67
CU1
Electrical parameters:
Intrinsically safe for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Explosionproof approval]
Same as CF1
Fieldbus:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: CAN/CSA-C22.2 No. 94.2-07, C22.2 No.213:1987,
CAN /CSA-C22.2 No. 60079-0:11, CAN/CSA-C22.2 No. 60079-11:14,
CAN/CSA-C22.2 No. 60529:05, CAN/CSA-C22.2 No. 61010-1-12,
CAN/CSA-C22.2 No. 61010-2-030-12
Intrinsically safe for
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G T4
Ex ia IIC T4 Ga
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G T4
Class III Division 1 T4
Ambient Temperature: –55 to 60°C
Enclosure Type: 4X, IP66/IP67
Electrical parameters: CU15
Intrinsically safe for
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Explosionproof approval]
Same as CF1
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 12
Item Description Code
NEPSI 4-20mA and Fieldbus:
[Flameproof and Dust Ignition Proof Approval]
Applicable Standard: GB3836.1-2010, GB3836.2-2010, GB12476.1-2013, GB12476.5-2013
Certificate No. GYJ16.1396X
Ex d IIC T6/T5 Gb, Ex tD A21 IP66/IP67 T70°C/T90°C NF2
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe approval ]
Applicable Standard: GB 3836.1-2010, GB 3836.4-2010 GB 3836.20-2010
Certificate No. GYJ16.1423X
Ex ia IIC T4/T5 Ga
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
Enclosure: IP66/IP67 in accordance with only IEC 60529 NS2
Entity Parameters:
Supply/Output circuit: Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
Fieldbus:
[Intrinsically safe approval]
Applicable Standard: GB 3836.1-2010, GB 3836.4-2010, GB3836.20-2010
Certificate No. GYJ16.1423X
Ex ia IIC T4 Ga
Ambient Temperature: –55 to 60°C for T4
Enclosure: IP66/IP67 in accordance with only IEC 60529
NS25
FISCO field device
Entity Parameters:
Supply/Output circuit: Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min
[+, -, 1, 2, 3, 4, 5] to Earth terminal
[+, -] to [1, 2, 3, 4, 5]
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 13
Item Description Code
INMETRO*6 [4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable Standard: ABNT NBR IEC 60079-0:2013 Versão Corrigida 2: 2016,
ABNT NBR IEC60079-1:2016, ABNT NBR IEC 60079-31:2014
Certificate: DEKRA 16.0009
Ex db IIC T6/T5 Gb, Ex tb IIIC T70°C/ 90°C Db UF1
Ambient Temperature for Gas: –40 to +75°C for T6, –40 to +80°C for T5
Ambient Temperature for Dust: –30 to +65°C for T70°C, –30 to +80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe approval ]
Applicable Standard: ABNT NBR IEC 60079-0:2013 Versão Corrigida 2:2016,
ABNT NBR IEC 60079-11:2013
Certificate: ABNT 17.0001X
Ex ia IIC T5...T4 Ga
Ambient Temperature: –40 to 70 °C for T4, –40 to 50 °C for T5 US1
Enclosure: IP66/IP67
Supply/Output circuit:
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit:
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Fieldbus:
[Intrinsically safe approval "ia" ]
Applicable Standard: ABNT NBR IEC 60079-0:2013 Versão Corrigida 2:2016,
ABNT NBR IEC 60079-11:2013
Certificate: ABNT 17.0001X
Ex ia IIC T4 Ga
Ambient Temperature: –55 to 60 °C
Enclosure: IP66/IP67
Supply/Output circuit:
FISCO field device and
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit:
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
US15
[Intrinsically safe approval "ic" ]
Applicable Standard: ABNT NBR IEC 60079-0:2013 Versão Corrigida 2:2016,
ABNT NBR IEC 60079-11:2013
Certificate: ABNT 17.0001X
Ex ic IIC T4 Gc
Ambient Temperature: –30 to 70 °C
Enclosure: IP66/IP67
Overvoltage category: I
Supply/Output circuit:
FISCO field device and
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit:
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 14
Item Description Code
KOSHA [4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable Standard: Notice of Ministry of Labor No. 2016-54, harmorized with IEC
60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
Certificate: 17-AV4BO-0457 (Flameproof)
17-AV4BO-0458 (Dust Ignition Proof)
PF2
Ex d IIC T6/ T5, Ex tD A21 IP66/IP67 T70°C/ T90°C
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe approval]
Applicable Standard: Notice of Ministry of Labor No. 2016-54, harmorized with
IEC 60079-0: 2011, IEC 60079-11: 2011
Certificate: 17-AV4BO-0459X
Ex ia IIC T5…T4
Ambient Temperature: –40 to 70 °C for T4, –40 to 50 °C for T5
Enclosure: IP66/IP67
PS2
Supply/Output circuit:
Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit:
Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Electrical Connection: 1/2 NPT female and M20 female*1
Fieldbus:
[Intrinsically safe approval]
Applicable Standard: Notice of Ministry of Labor No. 2016-54, harmorized
with IEC 60079-0: 2011, IEC 60079-11: 2011
Certificate: 17-AV4BO-0459X
Ex ia IIC T4
Ambient Temperature: –55 to 60°C
Enclosure: IP66/IP67
Supply/Output circuit: PS25
Terminals: +, –
FISCO field device and
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit:
Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Electrical Connection: 1/2 NPT female and M20 female*1
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 15
Item Description Code
EAC*6 [4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable Standard: ГОСТ 31610.0-2014
ГОСТ IEC 60079-1-2013
ГОСТ IEC 60079-31-2013
Certificate: TC RU C-JP.ПБ98.B.00040
GF1*5
1Ex db IIC T6…T5 Gb, Ex tb IIIC T70 °C…T90 °C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe approval]
Applicable Standard: ГОСТ 31610.0-2014
ГОСТ 31610.11-2014
Certificate: TC RU C-JP.ПБ98.B.00040
0Ex ia IIC T4…T5 Ga X
Ambient Temperature: –40 to 70 °C for T4, –40 to 50 °C for T5
Enclosure: IP66/IP67
GS1*5
Supply/Output circuit:
Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit:
Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Electrical Connection: 1/2 NPT female and M20 female*1
Fieldbus:
[Intrinsically safe approval]
Applicable Standard: ГОСТ 31610.0-2014
ГОСТ 31610.11-2014
Certificate: TC RU C-JP.ПБ98.B.00040
0Ex ia IIC T4 Ga X
Ambient Temperature: –55 to 60°C
Enclosure: IP66/IP67
Supply/Output circuit: GS15*5
Terminals: +, –
FISCO field device and
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit:
Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Electrical Connection: 1/2 NPT female and M20 female*1
*1: Applicable for Electrical Connection Code 2 and 4.
*2: Applicable for Electrical Connection Code 2.
*3: For Explosionproof approval.
*4: For Intrinsically safe approval/non-incendive approval.
*5: GF1, /GS1 and /GS15 shall be combined with either /VE or /VR.
*6: Not applicable for BRAIN type.
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 16
DIMENSIONS
Unit: mm (Approx. inch)
2-inch horizontal pipe mounting
111(4.37) 65.4(2.57) 66.1(2.60)
Electrical Connection
Electrical Connection 47.1 18.5
(Input signal) Terminal Cover
(Output signal) (1.85) (0.73)
With Indicator
(Optional)
ø93(3.66)
102(4.02)
164(6.46)
(1.57)
(For Explosionproof type)
40
Tag Plate
Horizontal Pipe
(0.98)
25
Mounting Bracket
(Optional)
ø93(3.66)
Shrouding Bolt
(For Explosionproof type)
209.5(8.25)
191.5(7.54)
Ground Terminal
Tag Plate
Vertical Pipe
Mounting Bracket
(1.81)
(Optional)
46
2-inch pipe
64(2.52)
ø60.5(ø2.38) 101(3.98)
70(2.76)
98(3.86)
F02E.ai
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 17
Terminals
Terminal Configuration
Input Wiring
Thermocouple and RTD and resistance Thermocouple and RTD and resistance
DC voltage (2-wire) DC voltage (3-wire)
(A) (A) (A1)
1 1 1 (+) 1
(B) (A) (B1)
2 2 2 (–) 2
(B) (B)
3 3 3 (B2) 3
(B) (B2)
4 4 4 (B2) 4
(A2)
5 5 5 (A2) 5
RTD and resistance RTD and resistance Thermocouple + RTD and resistance
(3-wire) (4-wire) RTD and resistance (2-wire)
(3-wire)
(A1)
1 (B1)
2 (B1)
3 (–)
4
5 (+)
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 18
< Ordering Information > 6. Output scale unit
Specify the following when ordering Model, suffix Specify only one unit from the table, ‘Settings when
codes, and optional codes. shipped.’ For sensor input code-2, specify the unit
If not specified, the instrument is shipped with the for two inputs.
settings shown in Table A and B. Specify the following 7. Tag Number
when necessary. Specify Tag number (up to 16 Characters) to be
engraved on the tag plate.
8. Software Tag (PD_TAG)
4-20mA type (HART and BRAIN type) Specify software tag (up to 32 Characters) to be
1. Sensor type. written on the amplifier memory.
For RTD and resistance input, specify the number 9. Node Address
of wire as well. (Example: Pt100 3-wire system) 10. Operation Functional Class
For sensor input code-2, specify the type for two Select ‘BASIC’ or ‘LINK MASTER’.
inputs. In this case, PV (Sensor1 value) and SV 11. Sensor back up
(Sensor2 value) are alternately displayed on the Select ‘DISABLE’ or ‘ENABLE’.
integral indicator with sensor back up DISABLE.
2. Calibration range and unit
1) Calibration range can be specified within the < Factory Setting >
measurement range shown in Table 1. Also, set
the upper limit is larger than the lower limit. Table A. 4-20mA type (HART and BRAIN type)
2) Specify one range from °C, K, °F or °R for
temperature input. It is not necessary to specify Input sensor type *1 “Pt100” or as specified in order
the unit of mV and ohm inputs, for these units Wire connection “3-wire system” or as specified in
automatically will be mV or Ω. (For RTD) *1 order
3. Tag Number (if required) Calibration range “0 to 100” or as specified in order
Specify Tag number (up to 16 Characters) to be Calibration unit “°C” or as specified in order
engraved on the tag plate. The specified letters (TC and RTD)
are written on Tag (16 Characters) in the amplifier Sensor burnout *2 High (110%, 21.6 mA DC)
memory. Output in Transmitter High (110%, 21.6 mA DC or more)
4. Software tag (HART type) failure *2
Specified characters (up to 32 characters) are Sensor backup ‘DISABLE’ or as specified
set as “Tag” (the first 8 characters) and “Long
Tag No. “Blank” or as specified in order
tag (32 characters) in the amplifier memory.
Use alphanumeric capital letters. When the *1: For sensor input code-2, sensor 2 is set in
“SOFTWARE TAG” is not specified, “TAG NO” is set nonconnection.
as “Tag” (the first 8 characters) and “Long tag” (32 *2: Except when Optional code C1 or C2 is specified.
characters) in the amplifier memory.
5. Other factory configurations (HART type) Table B. Fieldbus type
Specifying option code CA will allow further
configuration at factory. Input sensor type *1 “Pt100” or as specified in order
Descriptor (up to 16 characters) Wire connection “3-wire system” or as specified in
6. Sensor back up (For RTD) *1 order
Select ‘DISABLE’ or ‘ENABLE’. Calibration range *1 “0 to 100” or as specified in order
Calibration unit “°C” or as specified in order
Fieldbus type (TC and RTD)
1. Sensor type. Output Scale *1 “0 to 100%”
For RTD and resistance input, specify the number Output mode “Direct”
of wire as well. For sensor input code-2, specify the
Node Address ‘0xF3’ unless otherwise specified in
type for two inputs. (Example: Pt100 3-wire system) (in hexadecimal) order
In this case, AI1 (Sensor1) value and AI2 (Sensor2)
Operation functional ‘BASIC’, or as specified in order
value are alternately displayed on the integral
Class
indicator with sensor back up DISABLE.
2. Calibration range (XD_SCALE) Sensor backup *2 ‘DISABLE’ or as specified in order
For sensor input code-2, specify the range for two Tag Number “Blank” or as specified in order
inputs. (Tag plate)
3. Units of calibration range: Software Tag ‘TT1001’ unless otherwise specified
Specify only one unit from the table, ‘Settings when (PD_TAG) in order.
shipped.’ For sensor input code-2, specify the unit *1: For sensor input code-2, sensor 2 is set in
for two inputs. nonconnection.
4. Output mode (L_TYPE) *2: Channel settings of AI function blocks depend on
Select ‘Direct’ or ‘Indirect .’ sensor backup setting.
5. Output scale (OUT_SCALE) Disable: AI1= Sensor1,
AI2= If Sensor2 type is specified then
For sensor input code-2, specify the scale for two
Sensor2 else Terminal temperature
inputs. Enable: AI1= Backup temperature,
AI2= Terminal temperature
All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50G01-01EN Mar. 2, 2018-00
Subject to change without notice.
ATTACHMENT-4
CATALOGUE OF THERMOWELL
Thermowells
Thermowells
Type TW.FL/TW10
WIKA Datasheet TW.FL/TW10
Applications
Standard Features
Process connections
Flanged
Bore diameter
.260”, .385”
Materials
Brass, AISI 304, AISI 316
(Other materials available upon request)
Surface finish
Brass: 60-100 Ra
AISI 304 & AISI 316: 60-100 Ra
Sanitary (AISI 304 & AISI 316):16-20 Ra
Ordering Information
See current WIKA Catalog or WIKA Price List for ordering
information
NOTES:
1. Flanges are manufactured in accordance with ANSI B16.5.
2. Raised face flange supplied as standard ANSI serrated.
125 RMS smooth face available.
3. Full penetration welds standard.
4. Wrench flats used on wells with a stem length of more than 21” long.
5. Bar diameter on flanged wells: 1.125” thru 600# rating.
1.375” for and over 900#.
18 - Certificates
1 Quality certificates
Z Without
Singapore
Ref. -No.: WFC-QU00060210-Rev.4
phone: +65 6844 5506
fax: +65 6844 5507
Calculation email: [email protected]
Tag-No.: TIT-001A/TW-001A
result:
good web: www.wika.com.sg
Note code /
Pipe data:
Inner diameter Di in.
Thermowell data:
WIKA model TW10 Name
Connection flanged
Shape straight Name
Material data:
Grade mat 316 Name
WIKA has made every reasonable attempt to validate the calculation procedure contained in this spread sheet, however, responsibility for validation rests solely with the user.
This WIKA ASME PTC 19.3 TW - 2016 spread sheet copyright © 2018 (compatible with Excel 2007/2010) is intended to assist the experienced designer of thermowells and should
not be considered as a replacement for professional engineering.The end user is responsible to assure that the calculation method is compatible to the process conditions.
For further information see Operation Instruction.
WIKA Instrumentation PTE. LTD.
Singapore
Ref. -No.: WFC-QU00060210-Rev.4
phone: +65 6844 5506
fax: +65 6844 5507
Calculation email: [email protected]
Tag-No.: TIT-001B/TW-001B
result:
good web: www.wika.com.sg
Note code /
Pipe data:
Inner diameter Di in.
Thermowell data:
WIKA model TW10 Name
Connection flanged
Shape straight Name
Material data:
Grade mat 316 Name
WIKA has made every reasonable attempt to validate the calculation procedure contained in this spread sheet, however, responsibility for validation rests solely with the user.
This WIKA ASME PTC 19.3 TW - 2016 spread sheet copyright © 2018 (compatible with Excel 2007/2010) is intended to assist the experienced designer of thermowells and should
not be considered as a replacement for professional engineering.The end user is responsible to assure that the calculation method is compatible to the process conditions.
For further information see Operation Instruction.