TECHNICAL DATA :
Nozzle flow Range 800 to 2000 GPM
(3030 to 7570 LPM)
Approval FM Approved
DESCRIPTION
VARSHA - 50, 50 is fixed gallonage master stream
nozzle, designed for heavy-duty use on fixed monitors.
The nozzle is factory set for required flow between 800
to 2000 GPM. The flow can be changed in the field by
replacing plunger or addition of spacer. The flow
pattern easily changeable under flowing condition. Under normal condition water must be flown through
Superior fog pattern with field changeable spinning the nozzle periodically and dirt, around exterior
teething. Excellent for AFFF application when used with moving parts must be cleaned, allowing nozzle to
premix water-faom solution. operate properly.
The nozzle is madeout of hard coat anodized Aluminum The nozzle must be inspected prior to and after each
or Bronze with stainless steel internals. use. Greasing the moving parts and 'O' ring is re-
quired periodically. Over a time the seals may need to
The performance data shown in this catalogue is be replaced.
effective stream trajectory in stand still air condition.
The maximum overall reach of last water drop is The owner is responsible for maintenance of the nozzle
approximately 3-5% more than the effective stream in proper operating condition.
performance data given. The effective stream After use with foam, nozzle should be flushed with fresh
decreases by about 10% when used as foam nozzle water.
with premixed water foam solution. The jet stream
may get effected considerably with tail or head wind. CAUTION
A trained personnel for fire fighting, with appropriate
MAINTENANCE guidance & training must use the product to reduce
The nozzle must be inspected regularly for possible the risk or injury. The nozzle must be fixed to the
damage or dirt around the moving parts. If any monitor carefully. The mismatched or damaged threads
abnormal conditions are observed such as poor may cause leakage or uncouple the nozzle during
discharge, excessive wear, water leak, corrosion effect, operation.
damage etc., then nozzle must be taken out of service
and repaired by qualified technician or replaced. Application of water or foam on an electric appliance
can cause serious injury by electrocution, as water is
The debris trapped in the nozzle may effect the nozzle a conductor of electricity.
performance. To remove trapped debris, the water
flow must be stopped and thereafter carefully unscrew The water supply to the nozzle must be gradual. Sudden
and remove the nozzle deflector. Clean the nozzle and surge of water supply must be avoided. The monitor
reassemble. While reassemblig the nozzle or as a mounting must be supported properly to support the
normal preventive maintenance, water proof lubricant nozzle reaction force.
must be used on seal and moving parts for smooth
operation. The nozzle must be operated periodically
under full flow straight stream and for fog pattern.
FOG
VERTICAL THROW IN %
50%
261
75
°
25%
60
°
45
°
30°
0%
0% 25% 50% 75% 100%
HORIZONTAL THROW IN %
PERFORMANCE DATA
SET FLOW RATE NOZZLE PRESSURE ACTUAL FLOW RATE STRAIGHT STREAM RANGE
LPM (GPM) KG/CM.SQ.(PSI) LPM (GPM) METERS (FEET)
3030 (800) 5.6 (80) 2710 (716) 64 (210)
7.0 (100) 3030 (800) 68 (223)
8.4 (120) 3319 (876) 70 (229)
3785 (1000) 5.6 (80) 3385 (894) 75 (246)
7.0 (100) 3785 (1000) 80 (262)
8.4 (120) 4146 (1095) 82 (267)
4165 (1100) 5.6 (80) 3725 (984) 76 (249)
7.0 (100) 4165 (1100) 81 (265)
8.4 (120) 4563 (1205) 83 (272)
4730 (1250) 5.6 (80) 4230 (1118) 82 (268)
7.0 (100) 4730 (1250) 88 (288)
8.4 (120) 5181 (1369) 90 (295)
5680 (1500) 5.6 (80) 5080 (1342) 82 (268)
7.0 (100) 5680 (1500) 89 (291)
8.4 (120) 6222(1643) 90 (295)
6625 (1750) 5.6 (80) 5925 (1565) 83 (272)
7.0 (100) 6625 (1750) 90 (295)
8.4 (120) 7257 (1917) 92 (301)
7570 (2000) 5.6 (80) 6775(1790) 89 (291)
7.0 (100) 7570 (2000) 93 (305)
8.4 (120) 8300 (2190) 94 (308)
PERFORMANCE DATA FOR WATER STREAM RANGE ARE BASED AT 32 DEG. NOZZLE ELEVATION IN STILL AIR CONDITION AND WITH HD
MONITOR. WHEN USED WITH PREMIXED WATER FOAM SOLUTION THE FOAM REACH WILL DECREASE BY APPROXIMATELY 10%.
LIMITED WARRANTY
Products manufactured by HD FIRE PROTECT PVT.LTD.. are warranted against defects in material and workmanship for a period of Two (2) years from the date of
shipment.
HD's obligation under this warranty is limited to replace or repair the products or its parts, which are shown to HD's examination to be in a defective condition
attributable to HD. No warranty is given for products or components which have been subject, to misuse, improper installation, corrosion, wear and tear,
improper storage, modification or repaired. If the defect attributable to HD cannot be rectified by repair or replacement, then HD may elect to refund the
purchase price of the equipment in complete discharge of its obligation under this Limited Warranty.
IN NO EVENT SHALL HD FIRE PROTECT PVT. LTD. BE LIABLE IN CONTRACT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY, FOR INCIDENTAL, IN-DIRECT, SPECIAL OR
CONSEQUENTIAL DAMAGES, INCLUDING DAMAGES. FOR INJURY TO PERSON OR DEATH OR DAMAGE TO PROPERTY AND OR PENALTIES RESULTING FROM ANY
PRODUCTS OR COMPONENT MANUFACTURED OR ASSEMBLED BY HD. THIS IS LIMITED WARRANTY ONLY. HD DISCLAIMS WITH RESPECT TO THE PRODUCTS ALL IMPLIED
WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. THERE IS NO WARRANTY OF ANY NATURE MADE BY
HD BEYOND AS STATED ABOVE.
NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also
with the provision of government codes or ordinances wherever applicable.
The information provided by us are to the best of our knowledge and belief, and are general guidelines only. Site handling and installation control is beyond our
reach. Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information,
recommendation or damages due to our product.
Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved
with the company.
C-3/6, THE NANDANVAN IND. ESTATE, L.B.S. MARG, THANE 400 604., INDIA.
PHONES : +(91) 22 2583 5434 2582 6958 2582 6793
FAX : +(91) 22 2581 2524 6796 9049
EMAIL : [email protected] WEBSITE : www.hdfire.com