Specifications: 5 Seconds
Specifications: 5 Seconds
Trickle use
Specifications
Nominal Voltage(V)
12V
Nominal Capacity
20 hour rate (0.35A to 10.50V) 7Ah
10 hour rate (0.63A to 10.50V) 6.3Ah
5 hour rate (1.131A to 10.20V) 5.65Ah
1 C (7A to 9.60V) 3.5Ah
3 C (21A to 9.60V) 2.1Ah
Weight
Approx. 2.0kg(4.4Lbs.)
(0.25)
4.75
6.35
(0.03)
0.8
0.8
F1 F2
Operating Temperature Range
65±1(2.56±0.04) 151±1(5.94±0.04)
Charge -15℃(5℉) to 40℃(104℉)
Discharge -15℃(5℉) to 50℃(122℉)
Storage -15℃(5℉) to 40℃(104℉)
102±1(4.02±0.04)
94±1(3.70±0.04)
Terminal
8.0
1 2 4 6 8 10 20 40 60 2 5 6 8 10 20
F1 or F2 (Faston Tab 187 or 250) minutes hours
Discharge Time
WPS7-12
Effect of Temperature on Capacity 25℃(77℉) Capacity Retention Characteristic Trickle (or float) Service Life
(%)
120 100 10
0.05CA 0℃(32℉)
100 0.1CA
Remaining Capacity
5
75
Life (years)
Capacity %
0.25CA
80 0.6CA 3
10℃(50℉)
1CA 2
60 2CA
50 20℃(68℉)
40 40℃(104℉) 30℃(86℉)
25
20 0.5
0
-20 -10 0 10 20 30 40 50 ℃ 0
-4 14 32 50 68 86 104 122 ℉ 3 6 9 12 15 18 20 30 40 50 (℃)
Storage Time (months) 68 86 104 122 (℉)
Temperature
Ambient Temperature
- PERFORMANCE DATA
Discharge Rates in Watts to Various End Voltages at 25℃(77℉)
End Voltage
1.85V 1.80V 1.75V 1.70V 1.67V 1.65V 1.60V
Time
2 min 48.9 67.6 83.2 93.2 97.0 99.1 102
4 min 33.4 43.5 51.7 56.8 58.7 59.8 61.5
6 min 26.3 33.2 38.6 41.9 43.2 44.0 45.1
8 min 22.3 27.5 31.5 33.9 34.9 35.4 36.2
10 min 19.3 23.3 26.4 28.3 29.0 29.4 30.1
15 min 15.8 18.5 20.5 21.7 22.2 22.4 22.9
20 min 13.4 15.3 16.7 17.5 17.9 18.1 18.4
30 min 10.7 11.8 12.6 13.1 13.3 13.4 13.6
60 min 7.38 7.72 7.92 7.99 8.03 8.06 8.06
90 min 5.35 5.58 5.70 5.76 5.78 5.80 5.86
120 min 4.26 4.43 4.52 4.56 4.58 4.60 4.63
180 min 3.26 3.37 3.44 3.46 3.48 3.49 3.51
240 min 2.60 2.68 2.73 2.75 2.76 2.77 2.79
300 min 2.18 2.24 2.28 2.29 2.30 2.31 2.32
480 min 1.50 1.53 1.56 1.57 1.57 1.58 1.58
600 min 1.26 1.28 1.30 1.31 1.31 1.32 1.32
1200 min 0.686 0.695 0.702 0.706 0.708 0.710 0.711