CT Site Test Report Current Transformer: Pre-Commissioning Checklist
CT Site Test Report Current Transformer: Pre-Commissioning Checklist
Pre-Commissioning Checklist:
1. Check the erection of equipment is carried out as per the approved drawings
3. Check the primary terminals P1& P2 are connected to the bus as shown in the drawing
4. Check the position of the secondary terminal box is as per the approved drawing
6. Check the earth connections of the equipment are completed as per the drawing
7. Terminal Box:
a. Secondary connections are completed properly as per the drawing
And terminals are tightened
b. The tan delta terminal is connected properly to Earth
c. The cable tags, ferrules for all cores are provided
d. Cables are properly dressed and clamped
e. Unused holes are sealed properly
Make ABB
Type IMB 245
Highest System Voltage 245 KV
Rated Insulation 245/460/1050
Rated Primary Current 800 A
Core Details:
Primary – Earth 5 kV 41 18 36
2. Polarity Test:
Core R Y B
Core – 1 OK OK OK
Core – 2 OK OK OK
Resistance in Ohms
Core Sec. Terminals
R Y B
1S1 – 1S2
Core – 1 0.6 0.6 0.6
2S1 – 2S2
Core – 2 0.6 0.6 0.6
Magnetizing Current in Ma
Core Applied Volts
R Y B
1S1-1S5 500 5 4.6 5.1
2S1-2S5 500 5.6 4.6 4.9
3S1-3S5 48 232 2.4A [email protected]
4S1-4S2 500 4.5 5.1 4.6
5S1-5S2 500 4.9 4.1 4.5
5. Ratio Test:
Core1 Core2 Core1 Core2 Core1 Core2 Core1 Core2 Core1 Core2
199.97 199.97 0.9999 1.00005 -0.01* -0.03* 200:1.0001 200:1.0002 0.01% 0.01%
199.96 199.94 1.00006 0.9999 -0.04* -0.00* 200:1.0003 200:1.0002 0.03% 0.02%
199.95 199.94 1.00004 0.9999 -0.03* -0.01* 200:1.0003 200:1.0003 0.03% 0.02%
MODE R Ph Y Ph B Ph
VOLTAGE(KV)
CURRENT(mA)
Capacitance in pF
UST MODE Tan Delta in %
POWER
FREQUENCY
VDF%
MODE R Ph Y Ph B Ph
VOLTAGE(KV)
CURRENT(mA)
Capacitance in pF
GST GUARD
Tan Delta in %
MODE
POWER
FREQUENCY
VDF%
MODE R Ph Y Ph B Ph
VOLTAGE(KV)
CURRENT(mA)
Capacitance in pF
GST MODE Tan Delta in %
POWER
FREQUENCY
VDF%