Iare Eei PPT
Iare Eei PPT
Instrumentation
Prepared By
Mr. A Sathish Kumar
Assistant professor
UNIT – I
INTRODUCTION TO
MEASURING
INSTRUMENTS
MEASURING INSTRUMENTS
“The device used for comparing the unknown quantity
with the unit of measurement or standard quantity
is called a Measuring Instrument.”
OR
“An instrument may be defined as a machine or
system which is designed to maintain functional
relationship between prescribed properties of
physical variables & could include means of
communication to human observer.”
CLASSIFICATION OF INSTRUMENTS
Electrical instruments may be divided into two categories,
that are;
1. Absolute instruments,
2. Secondary instruments.
- Absolute instruments gives the quantity to be
measured in term of instrument constant & its
deflection.
- In Secondary instruments the deflection gives the
magnitude of electrical quantity to be measured
directly. These instruments are required to be
calibrated by comparing with another standard
instrument before putting into use.
CLASSIFICATION OF INSTRUMENTS
CLASSIFICATION OF INSTRUMENTS
Electrical measuring instruments may also be classified
according to the kind of quantity, kind of current,
principle of operation of moving system.
- Indicating Instruments:
It indicate the magnitude of an
electrical quantity at the time when it is being
measured. The indications are given by a pointer
moving over a graduated dial.
CLASSIFICATION OF SECONDARY INSTRUMENTS
- Recording Instruments:
The instruments which keep a
continuous record of the variations of the magnitude
of an electrical quantity to be observed over a defined
period of time.
CLASSIFICATION OF SECONDARY INSTRUMENTS
- Integrating Instruments:
The instruments which measure the
total amount of either quantity of electricity or electrical
energy supplied over a period of time. For example
energy meters.
ESSENTIALS OF INDICATING INSTRUMENTS
1. Current transformers
2. Potential transformers
Instrument Transformers
Applications of Instrument Transformers:
• C.T. has a primary coil of one or more turns made of thick wire
connected in series with the line whose current is to be measured.
• The secondary consists of a large number of turns made of fine wire
and is connected across an a ete o a elay’s te i als.
Construction Types of Current Transformers
Window-type Bar-type
Current Transformers
Function of CT:
• The principal function of a CT is to produce a proportional current at a
level of magnitude, which is suitable for the operation of low-range
measuring or protective devices such as indicating or recording
instruments and relays.
• The primary and secondary currents are expressed as a ratio such as
100/5 or 1000/5 .
• With a 100/5 ratio CT, 100A flowing in the primary winding will result
in 5A flowing in the secondary winding, provided that the correct
rated burden is connected to the secondary winding.
Current Transformers
Class of a CT:
Single-Ratio CT Multi-Ratio CT
Multi-ratio CT:
• As indicated in the previous Figure, current transformers having a
center tapped secondary are referred to as a dual ratio CT.
• Dual ratio CT are used in applications where it is necessary to have
available two ratios of primary to secondary current from the same
secondary winding of the CT.
• This may be accomplished by adding a tap in the secondary
winding to get a second ratio.
• The ratio obtained by the tap is usually one-half the ratio obtained
by the full secondary winding.
• A schematic example is previously shown with 200 amperes flowing
in the primary, a connection X2 – X3 will produce 5 amperes out of
the secondary. As the load grows to 400 amperes, the secondary
circuit will be reconnected to X1 – X3 to still produce 5 amperes in
the secondary circuit.
Current Transformers
Working (Measurement):
Iron Core
• The `doughnut' fits over the primary conductor, which constitutes one primary turn. If
the toroid is wound with 240 secondary turns, then the ratio of the C.T. is 240 : 1 or
1200 : 5A
• This type of `doughnut' C.T. is most commonly used in circuit breakers and power
transformers. The C.T. fits into the bushing, and the porcelain bushing fits through the
centre of the `doughnut'.
• Up to four C.T.'s of this type can be installed around each bushing of an oil circuit
breaker. This arrangement is shown in a following diagram.
Substation Class Circuit Breakers' CTs
100
___ = 100:5 or 20:1
5
Polarity
Direction of
Secondary Current
Direction of
Primary Current
X1 IEEE Secondary
S1
IEC Polarity
Primary IEEE H1
Marks
Polarity
Marks IEC P1
X1 IEEE Secondary
S1
IEC Polarity
Primary IEEE H1
Marks
Polarity
Marks IEC P1
Direction of
Primary Current
Then:
E0.04, E0.2
CT accurate Burden Calculation
ZT = RCT + RL + ZB
ZT = Total burden in ohms (vector summation of
resistance and inductance components)
RCT = CT secondary resistance in ohms @75 deg C
RL = Resistance of leads in ohms (Total loop distance)
ZB = Device impedance in ohms
CT Saturation
Factors Affecting Degree and Time to Saturation
1. High DC offset
2. High fault current Magnitude (symmetrical current)
Example:
•100 to 5 CT@20 times= 2000 amps.
•Also @20,000 amps we have 200 times CT
Typical window CT
Power Transformers’ CT Connections
Slip over current transformer for installation over
exterior of outdoor bushing
Relay
Connections of 1-Phase Potential Transformers
Other PT and 3-Phase Typical Connections
Y – Broken Corner VT
Connection
damping resistor R
Other PT and 3-Phase Typical Connections
Return
Display of Waveforms
magnify
Return
Measurement of Short Time
Intervals
• Calibrate for the time base
• Measure a very small time interval, e.g.
measurement of sound speed in a metal rod
Return
Measurement of Frequency
• Signal applied to Y-plates
• ‘Lock’ the trace
• Choose a suitable time base
• Determine the period, T
• Calculate the frequency
Return
Display of Phase Relationships
Computer
Simulation
Return
Comparison of Frequencies
• Lissajous’ figures
• Frequency ratio