This document contains a load calculation for a power distribution circuit. It lists the connected loads including lighting outlets, convenience outlets, air conditioning units, and a range. It calculates the total connected load, demand current, and size of wire and circuit breaker needed. Based on the calculations, it specifies 2 x 14.0 mm2 copper wires, a 60A circuit breaker, and 15mm PVC conduits to satisfy the load requirements.

Uploaded by

ABCD EFG
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
374 views

Sample Load Computation

This document contains a load calculation for a power distribution circuit. It lists the connected loads including lighting outlets, convenience outlets, air conditioning units, and a range. It calculates the total connected load, demand current, and size of wire and circuit breaker needed. Based on the calculations, it specifies 2 x 14.0 mm2 copper wires, a 60A circuit breaker, and 15mm PVC conduits to satisfy the load requirements.

Uploaded by

ABCD EFG
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

PB 1

Ckt no P AT AF KAIC
LOAD DESCRIPTION VA VOLT A AB
1 2 20 50 10 8 Lighting Outlet 800 230 3.48 3.48
2 2 20 50 10 10 Lighting Outlet 1000 230 4.35 4.35
3 2 20 50 10 14 Lighting Outlet 1400 230 6.09 6.09
4 2 20 50 10 14 Lighting Outlet 1400 230 6.09 6.09
5 2 20 50 10 14 Lighting Outlet 1400 230 6.09 6.09
6 2 20 50 10 8 Convenience Outlet 1440 230 6.26 6.26
7 2 20 50 10 5 Convenience Outlet 900 230 3.91 3.91
6 2 20 50 10 9 Convenience Outlet 1620 230 7.04 7.04
7 2 20 50 10 10 Convenience Outlet 1000 230 4.35 4.35
8 2 30 50 10 1 ACU 1500 230 6.52
8 2 30 50 10 1 ACU 1500 230 6.52
8 2 30 50 10 1 ACU 1500 230 6.52
8 2 30 50 10 1 ACU 1500 230 6.52
9 2 30 50 10 1 Ref 1000 230 4.35
7 2 30 50 10 1 Range 1000 230 4.35
8 2 30 50 10 spare 1500 230 6.52
Total Connected Load, IFL 20460 88.96 47.65
Total Demand Current 85% 75.61
Size of Wire: Size of Circuit Breaker Protection:
IFL = 86.78 Amperes IFL = 108.03 Amps
at 85% demand = 73.77 Amps at 85% demand = 91.83
Use: 2- 14.0sqmm THHN Cu wire + 3.5sqmm TW grnd in 20 mm diam RSC Use: 60 AT/60 AF, 2P, Bolt-On Type
BC CA SIZE OF WIRE CONDUIT
2-3.5sqmm THHN +2.0 sqmm TW Cu 15mm Ø PVC
2-3.5sqmm THHN +2.0 sqmm TW Cu 15mm Ø PVC
2-3.5sqmm THHN +2.0 sqmm TW Cu 15mm Ø PVC
2-3.5sqmm THHN +2.0 sqmm TW Cu 15mm Ø PVC
2-3.5sqmm THHN +2.0 sqmm TW Cu 15mm Ø PVC
2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
6.52 2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
6.52 2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
6.52 2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
6.52 2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
4.35 2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
4.35 2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
6.52 2-5.5sqmm THHN +3.5 sqmm TW Cu 15mm Ø PVC
41.30 0.00

Amps
AT/60 AF, 2P, Bolt-On Type CB