0% found this document useful (0 votes)
424 views106 pages

Aci Automation Components

This document provides a table of contents and product information for ACI's 2008/2009 product catalog. It lists various displays, temperature sensors, relative humidity sensors, pressure sensors, current sensors, air quality sensors, and accessories. It also discusses ACI's focus on customer satisfaction, product quality, knowledgeable staff, and trusted relationships.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
424 views106 pages

Aci Automation Components

This document provides a table of contents and product information for ACI's 2008/2009 product catalog. It lists various displays, temperature sensors, relative humidity sensors, pressure sensors, current sensors, air quality sensors, and accessories. It also discusses ACI's focus on customer satisfaction, product quality, knowledgeable staff, and trusted relationships.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 106

Table of Contents

Displays
A/LCD (4-20mA Input) DI-1
-LCD (Display Add-on for Temperature Sensors) DI- 3
A/TUC (Microprocessor Temperature) DI-5 .
A/TUCH (Microprocessor Temperature / RH) DI-7

Temperature
Temperature Configurations
A/100 & A/1K RTD
TE-1
TE-3
W elcome to ACI’s 2008/2009
Product Catalog! Please note that we
A/1K Nickel RTD TE-5 are updating our standard temperature
A/BALCO RTD TE-7 enclosures to a plastic type box. ACI
A/CP, A/AN, A/20K, & A/1.8K Thermistors TE-9
A/100KS, A/2252, A/CSI Thermistors TE-11 is dedicated to further enhance our
A/592 & A/592-10K Semiconductors TE-13 product offerings and this change will
A/34 Semiconductors TE-15 provide numerous benefits.
A/TT100, A/TT1K Temperature Transmitters TE-17
High and Low Temp. Sensors and Transmitters TE-19 Also, please check out our new web
page! It has a new look and several
Relative Humidity
A/RH (Relative Humidity) RH-1 new functions.
A/RH-TEMP (Relative Humidity/ Temperature)
A/ENT-CTRL & A/ENT-DIFF (Enthalpy)
RH-3
RH-5 Thank you!
A/ENT-TRAN (Enthalpy Transmitter only) RH-7

Pressure
A/LP (Low Differential Pressure) PR-1
A/DP (Differential Pressure) PR-3
A/PT, A/SPT, & A/VPT (Pitot Tubes)
A/GP (Gage Pressure)
PR-5
PR-7
“First in Sensor Quality”
A/629 (Wet to Wet Differential) PR-9
A/WP (Wet to Wet Differential) PR-11
A/AFS (Pressure Switches) PR-13
A/AFS-460 (Pressure Switch) PR-15

Current
A/CS (Status switch - Solid Core) CU-1
A/SCS (Status Switch - Split Core) CU-3
A/ACS (Adj. Status Switch - Solid Core) CU-5
A/ASCS (Adj. Status Switch - Split Core) CU-7
A/CTA & A/CTA-VFD (4-20mA Solid Core) CU-9
A/SCTA & A/SCTA-VFD (4-20mA Split Core) CU-11
A/CTE & A/CTV (0-5 & 0-10 VDC Solid Core) CU-13
A/SCTE & A/SCTV (0-5 & 0-10 VDC Split Core) CU-15

Air Quality
A/CO (Carbon Monoxide) AQ-1
A/CO2-010 (Carbon Dioxide 0 to 10VDC) AQ-3
A/CO2 (Carbon Dioxide 4 to 20mA) AQ-5
A/CO2-T (Carbon Dioxide with Temperature) AQ-7

Accessories
Power Supply AC-1
Light Level Sensors AC-3
Freeze Stats AC-5
Thermowells AC-7 Twice awarded
Shields and Covers AC-9
Mounting Plates AC-11 “Wisconsin Manufacturer of the Year”
Interface Devices AC-13

Price List PL-1 - PL-13


Please note: Product specifications are subject to change.
The ACI ADVANTAGE
ACI has been twice awarded the "Wisconsin Manufacturer
of the year." We take pride in these awards and in our

ACI
company. ACI employees are challenged on a daily basis
to maintain the "ACI Advantage". This advantage is based
Automation Components, Inc.
on the following principles:

CUSTOMER SATISFACTION
ACI has always focused on customer satisfaction. We have one of the lowest return rates in the
industry. Our highly skilled sales staff and customer service department are ready and willing to
help you with your next sensor application.

PRODUCT QUALITY
ACI has always focused on producing a quality product which exceeds that of the competition.
We test each product three separate times before it leaves our factory. We know that a defective
sensor costs you valuable time and money.

KNOWLEDGEABLE STAFF
ACI has over 120 years of combined industry sales experience and over 75 years of
combined engineering experience currently on staff. These individuals create the core
of the ACI Advantage. If you have conversed with someone on our staff, you have
experienced this first hand. If you haven't, we invite you to have your expectations
raised over that of your current supplier.

TRUSTED RELATIONSHIPS
ACI takes pride in the business relationships that we have forged with our customers.
We strive to create a long-term solution for your sensor needs. In addition, we appreciate
the kind words that our customers have shared with us regarding our products and level
of service.

For more information call 888-967-5224


Product Data LCD

A CI
A/LCD

DISPLAYS
Loop Powered
Display

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/LCD 4-20 mA is a low power, high accuracy, 3.5 digit LCD
display module that is available in an attractive wall mount enclosure. Attributes:
The A/LCD 4-20 mA may be used with any 4 to 20 mA loop powered Sleek looking enclosure
Temperature, Relative Humidity, and Differential or Gage Pressure
transmitter. Enclosure can accommodate
additional options such as
The display can be calibrated for any range between (-) 1999 and 1999 and setpoint and override

RELATIVE HUMIDITY
has factory set descriptors which include C, F, and a decimal point.
Another notable feature of the A/LCD 4-20 mA is its wide operating Loop powered
temperature range of 0 to 70oC (32 to 158oF).

Both setpoint and override options are available upon request. A separate Applications:
2 pole terminal block will be included for Tenant override. The setpoint Remote monitoring of any
options include a 2-wire, linear 4 to 20 mA current output or a resistive 4 to 20 output device
setpoint using a 400 Ohm, 1K, 2K, 3K, 5K, 8.5K, 10K, 20K, or 100K ohm
slide potentiometer. An optional series resistor allows for any offset of the

PRESSURE
setpoint potentiometer. The setpoint labels available are Cool|Warm, 55 to
85, 10 to 30oC, and - to +.

All of the units come with a two year factory warranty.

CURRENT
Product Specifications
Input 2-Wire, 4-20 mA current loop
Maximum Voltage Drop +7 VDC for LCD Display
Life Expectancy 100,000 hours or 11.5 years
Display Accuracy +/- 0.5% of span
Transmitter Operating Range 32 to 158oF (0 to 70oC)

AIR QUALITY
Enclosure Material Beige ABS plastic
Adjustable Setpoint Output 4 to 20mA or Resistive Output
Setpoint Accuracy:
Resistive Output +/- 10% of Resistive Range
4 to 20mA Output +/- 1% of span w/24 VDC supply
Setpoint Supply Voltage:
(4 to 20mA Output only) +24VDC +/-10%
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000097 Rev 1.pdf
DI-1
Dimensions
Room 1.15”
DISPLAYS

2.25” (2.9cm)
(5.7cm) 0.89”
(2.2cm)
0.78”
(1.9cm)

100.0
TEMPERATURE

o
F
o
C
RELATIVE HUMIDITY

3.84” 4.51”
(9.7cm) (11.4cm)
PRESSURE

0.60”
COOL | WARM (1.5cm)

2.75” 0.92”
(6.9cm) (2.3cm)
CURRENT

Ordering Information Only if


resistive
Only if
resistive
Span Configuration Setpoint Pot Action Pot Value Setpoint Indication
A/LCD- [ ] -[ ] -[ ] -[ ] -[ ] -[ ]

Please Specify R - Room (3) Resistive DA 400 Ohm Cool | Warm


AIR QUALITY

RS - Room w/ Setpoint (4) 4-20 mA RA 1K 55 to 85


RO - Room w/ Override 2K 10 to 30oC
RSO - Room w/ Setpoint & Override 3K - to +
5K
8.5K
10K
20K
100K
ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

DI-2
Product Data LCD

A CI
LCD Series

DISPLAYS
-DF
-DC
LCD Add-on for
“First in Sensor Quality” Temperature Sensors

Product Description

TEMPERATURE
Attributes:
The LCD option may be added to any resistive type temperature sensor in
Sleek looking enclosure
a room configuration. It is a low power, high accuracy, 3.5 digit LCD
display unit. The display has factory set descriptors which include C, F,
Enclosure can accommodate
mA, and a decimal point. Another notable feature of the -LCD option is
additional options such as
its wide operating temperature range of 0 to 50oC (32 to 122oF).
setpoint and override

RELATIVE HUMIDITY
The LCD may be powered with either 24 VAC or +8 to 35 VDC, since it
uses a half-wave bridge to convert the AC voltage to a usable DC voltage.
Customizable Logo’s
The heart of the LCD, is a precision semiconductor temperature sensor
calibrated to an accuracy of +/- 0.4oF. All of the units come with a two
year factory warranty. Please contact ACI for more information regarding
these products.

Please note: This option is added to room sensors by adding -DF or -DC

PRESSURE
to the end of the ordering information. The LCD option can be used in
conjunction with semiconductor type sensors; however, it may require
an additional board mounted on the back side of the room enclosure.

CURRENT
Product Specifications
Supply Voltage +8 to 35 VDC or 24 VAC +/- 10%
Supply Current 4 mA minimum
Display Accuracy +/- 0.4oF(0.22oC)
Life Expectancy 100,000 hours or 11.5 years
Transmitter Operating Range 32 to 122oF (0 to 50oC)

AIR QUALITY
Enclosure Material Beige ABS plastic
Enclosure Plastic Rating UL94-HB
Temperature Sensor See other Data Sheets
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C00000159 Rev 4.pdf
DI-3
DISPLAYS

Dimensions
Room 1.15”
2.25” (2.9cm)
(5.7cm) 0.89”
(2.2cm)
0.78”
TEMPERATURE

(1.9cm)

100.0 o
o
F
C
RELATIVE HUMIDITY

3.84” 4.51”
(9.7cm) (11.4cm)
PRESSURE

0.60”
COOL | WARM (1.5cm)

2.75” 0.92”
(6.9cm) (2.3cm)
CURRENT

Ordering Information
-DF (LCD in Degrees F)
-DC (LCD in Degrees C)

LCD Display
See ACI temperature cut sheets for complete ordering options
AIR QUALITY
ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407
DI-4
Product Data TUC

A CI
A/TUC

DISPLAYS
Microprocessor Based
Display with Temperature

“First in Sensor Quality”

Product Description

TEMPERATURE
Attributes:
The microprocessor based A/TUC comes with an LCD display that can
Microprocessor technology
indicate room temperature, setpoint, fan speed, and occupied status. The
unit can display temperature and setpoint using the F or C degrees scale. provides greater output
As an option, fan control can be provided for 2 to 5-speed fans with LCD flexibility
indication of fan speed. Also an option, an override and override feedback
Attractive enclosure with

RELATIVE HUMIDITY
support can be provided.
membrane keypad
This unit supports single sensor operation for several common sensor types,
and it provides the flexibility to choose from numerous sensor types and LCD displays multiple
setpoint output options. The unit can also be configured to display the functions
setpoint temperature only. Additionally, many options are field
programmable.
Applications:
All of these units come in an attractive beige colored ABS plastic Commercial Buildings
enclosure. The A/TUC comes with a two year factory warranty. Please

PRESSURE
contact ACI for more information regarding the A/TUC. Hotels

High Profile Residential

Schools /Universities

Operating Suites

CURRENT
Product Specifications
Supply Voltage +5 VDC (Resistance Outputs only)
+15-30VDC (Resistance, 0-5V, or 1-5V)
+18-30VDC (0-10V, 2-10V, 0-20mA, 4-20mA)
24 VAC
Power Consumption 0.4 to 2 VA max
Temperature Display Accuracy +/- 1oF (+/- 0.56oC)

AIR QUALITY
Operating Temp. Range 40oF to 104oF (5oC to 40oC)
Analog Temperature Sensor Resistive, 0-5V, 1-5V, 0-10V, 2-10V,
Outputs 0-20mA, 4-20mA
Resistive Setpoint Accuracy +/- 2% or better
Analog Setpoint Outputs Resistive, 0-5V, 1-5V, 0-10V, 2-10V, 0-20mA, 4-20mA
Temperature Sensor See Ordering Information
Communication Jack See Ordering Information
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000098 Rev 3.pdf
DI-5
ACCESSORIES AIR QUALITY CURRENT PRESSURE RELATIVE HUMIDITY TEMPERATURE DISPLAYS

DI-6
Ordering Information for A/TUC
Resistive
Sensor Supply Temp Setpoint Setpoint Setpoint Setpoint Override Override Fan Control Fan Speed Comm
Type Voltage Scale Offset Range Action Scale Option Feedback Output Indication Jack
A/TUC -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

o O
F X (Analog Output) DA (Direct) (A) -2 to +2 F XX (No Feedback) XXX (No Jack)
100 o O
C 0 Ohm RA (Reverse) (B) -3 to +3 F SW (Dry Contact) RJ4 4C (4-Pin 4 Cond. Jack)
1K-Nickel 5 (5VDC)
1K Ohm (C) -5 to +5OF 0V (Logic Low) RJ6 4C (6-Pin 4 Cond. Jack)
1K-Balco 24 (+15-30VDC/VAC)
2K Ohm (D) 50 to 90OF 5V (Logic High) RJ6 6C (6-Pin 6 Cond. Jack)
1K-Pt 375 R400 (400 Ohms)
4.75K Ohm (E) 55 to 85OF AC (24 VAC) RS-232 (3.5mm Stereo Jack)
1K-Pt 385 R1K (1K Ohms)
10K Ohm (F) 60 to 80OF
2K RTD (1) 2 speed On/Off
Custom (Specify) R2K (2K Ohms) (G) 60 to 85OF
1.8K R3K (3K Ohms) O (2) 2 speed Auto/On
2252 (H) 65 to 80 F
R5K (5K Ohms) O (3) 3 speed Off/Low/Hi
3K (I) 65 to 85 F
R8.5K (8.5K Ohms) (4) 3 speed Auto/Off/On
ASI (3K-ASI) (J) 55 to 90OF
R10K (10K Ohms) O (5) 4 speed Off/Low/Med/Hi
5K (K) 55 to 95 F
R20K (20K Ohms) O (6) 4 speed Auto/Off/Low/Hi
10K-AN (TYPE III) (L) 68 to 76 F
R100K (100K Ohms) (7) 5 speed Auto/Off/Low/Med/Hi
10K-CP (TYPE II) Custom (Specify)
C020 (Current 0-20mA)
10K-CSI C420 (Current 4-20mA) NO (No Override) 0-10K Ohms (0, 2.5K, 5K, 7.5K, 10K)
20K V05 (Voltage 0-5 VDC) ST (Short Sensor) 0-5V (0-5VDC)
100K V15 (Voltage 1-5 VDC) SS (Short Setpoint) 0-10V (0-10VDC)
C020 (0-20 mA) V010 (Voltage 0-10 VDC) DC (Dry Contact) 2-10V (2-10VDC)
C420 (4-20 mA) V210 (Voltage 2-10 VDC) 0-20mA (0-20mA)
V05 (0-5 VDC)
4-20mA (4-20mA)
V15 (1-5 VDC)
Custom (Upon Engineering Approval)
V010 (0-10 VDC)
V210 (2-10 VDC)
Note: All of the Setpoint Scales are also offered in oC for all of the
Notes: When using 4-20mA or 0-20mA outputs the ranges that are listed above.
unit must be powered with +18 to 30 VDC.

When using 0-10VDC or 2-10VDC outputs,


the unit must be powered with +18 to 30 VDC
or 24VAC

For Dimentional Drawings please see the A/LCD


Ordering Information

Examples: A/TUC -10K-AN -5 -oF -10K Ohm -R20K -DA -B -ST -SW - 0-10K -2 -XXX or A/TUC -10K-CP -24 - oC -X -C420 -DA -F -DC -SW -4-20mA -2 -RJ6C6
Product Data TUCH

A CI
A/TUCH

DISPLAYS
Microprocessor Based
Display with Temperature
and Relative Humidity
“First in Sensor Quality”

Product Description

TEMPERATURE
The microprocessor-based A/TUCH Room Unit combines temperature
and relative humidity space monitoring, with a temperature or relative Attributes:
humidity setpoint function, into one wall-mount package. The temperature Microprocessor technology
output can be configured to have a resistance signal or standard analog provides greater output
output signals. flexibility
The A/TUCH Room Unit uses the same technology as the A/RH series
Attractive enclosure with

RELATIVE HUMIDITY
for its relativity humidity sensor. Both the temperature and relative
humidity functions can be adjusted in the field using single-point offsets, membrane keypad
the temperature in 0.5° (F or C) steps and the relative humidity in 0.5%
RH steps. Field adjustable temperature
and RH offset
The A/TUCH Room Unit supports one setpoint function that can be
configured for either temperature or relative humidity. The setpoint output LCD displays RH, Temp,
is available in configurable resistance spans, or using one of the standard
analog output signals. An override function can be configured to short the and Setpoint
temperature output or the setpoint output. Additionally, the override can
be configured as a dry contact signal. An optional override-acknowledge Applications:

PRESSURE
input uses a feedback signal from the Building Automation System to Commercial Buildings
indicate the occupied mode on the LCD.
Hotels
The A/TUCH room unit is available in an attractive beige colored ABS
plastic enclosure and comes with a two-year limited warranty.
High Profile Residential

Schools /Universities

CURRENT
Product Specifications
Surgical Suites
Supply Voltage +12-30VDC (Resistance, 0-5V, 0.5-4.5V, 1-5V)
+18-30VDC (0-10V, 2-10V, 0-20mA, 4-20mA)
20-28 VAC (All)
Power Consumption 0.4 to 2 VA max
Temperature Accuracy +/- 1oF (+/- 0.56oC)
Operating Temp. Range 40oF to 104oF (4.5oC to 40oC)

AIR QUALITY
Analog Outputs 0-5V, 0.5-4.5V, 1-5V, 0-10V, 2-10V, 0-20mA, 4-20mA
(500 ohms maximum load resistance on current outputs)
RH Range 0% to 100% RH
RH Accuracy at 77oF 20% to 95% RH +/- 2%, +/-3%, +/-5%
Setpoint Range See ordering information
Setpoint Accuracy +/- 5% Full Scale Output (Resistance)
+/- 2% Full Scale Output (Analog)
Override Options See ordering information
ACCESSORIES

Storage Temperature -4oF to 131oF (-20oC to 55oC)


Automation Components, Inc.
2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000044 Rev 9.pdf
DI-7
ACCESSORIES AIR QUALITY CURRENT PRESSURE RELATIVE HUMIDITY TEMPERATURE DISPLAYS

DI-8
Ordering Information for A/TUCH
Resistive
Sensor Temp Setpoint Setpoint Setpoint Setpoint Override Override %RH Comm
Type Scale Offset Range Action Scale Option Feedback Accuracy %RH Output Jack
A/TUCH -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

o
F X (Analog Output) DA (Direct) (A) -2 to +2°F XX (No Feedback) XXX (No Jack)
100 o 2%
C 0 Ohm RA (Reverse) (B) -3 to +3°F 0V (Logic Low) RJ4 4C (4pin 4 Conductor Jack)
1K-Nickel 3%
51.1 Ohm NA (None) (C) -5 to +5°F 5V (Logic High) RJ6 4C (6 pin 4 Conductor Jack)
1K-Balco 5%
721 Ohm (D) 50°F to 90°F RJ6 6C (6 pin 6 Conductor Jack)
2K RTD R400 (400 Ohms)
750 Ohm (E) 55°F to 85°F RS-232 (3.5mm Stereo Phone Jack)
1.8K R1K (1K Ohms)
800 Ohm (F) 60°F to 80°F
2252 R2K (2K Ohms) C020 (0-20 mA)
1K Ohm (G) 60°F to 85°F
3K R3K (3K Ohms) C420 (4-20 mA)
2K Ohm (H) 65°F to 80°F
ASI(3K-ASI) R5K (5K Ohms) V05 (0-5 VDC)
3.57K Ohm (I) 65°F to 85°F
5K R8.5K (8.5K Ohms) V0545 (0.5-4.5 VDC)
4.75K Ohm (J) 55°F to 90°F
10K-AN (TYPE III) R10K (10K Ohms) V15 (1-5 VDC)
8.25K Ohm (K) 55°F to 95°F
10K-CP (TYPE II) R20K (20K Ohms) V010 (0-10 VDC)
10K Ohm (L) 68°F to 76°F
10K-CSI R100K (100K Ohms) V210 (2-10 VDC)
Custom (Specify) (M) 55°F to 80°F
20K V05 (Voltage 0-5 VDC) Custom**
(N) 5°C to 35°C
100K V0545 (0.5-4.5 VDC) (O) 5°C to 40°C NO (No Override)
C020 (Current 0-20mA) V15 (Voltage 1-5 VDC) (P) 10°C to 30°C ST (Short Sensor)
C420 (Current 4-20mA) V010 (Voltage 0-10 VDC) (Q) 10°C to 35°C SS (Short Setpoint)
V05 (Voltage 0-5 VDC) V210 (Voltage 2-10 VDC) (R) 10°C to 40°C DC (Dry Contact)
V15 (Voltage 1-5 VDC) None (S) 15°C to 25°C
V010 (Voltage 0-10 VDC)
(T) 15°C to 30°C
V210 (Voltage 2-10 VDC)
(U) 15°C to 35°C
(V) 20°C to 25°C
(W) 20°C to 30°C Certain configuration / options might not currently be available.
(AA) 0% to 100% Please contact ACI for further details.
(BB) 10% to 90%
(CC) 20% to 50%
(DD) 20% to 55%
(EE) 20% to 60%
Notes: When using 4-20mA or 0-20mA outputs the
(FF) 20% to 80%
unit must be powered with +18 to 30 VDC. (GG) 30% to 50%
(HH) 30% to 55%
When using 0-10VDC or 2-10VDC outputs, (II) 30% to 60%
the unit must be powered with +18 to 30 VDC (JJ) 30% to 70% Note: All of the Setpoint Scales are also
or 24VAC (KK) 40% to 50% Offered in oC for all of the
(LL) 40% to 55% ranges that are listed above
For Dimentional Drawings please see the A/LCD (MM) 40% to 60%
Ordering Information (NN) 45% to 55%
Temperature Sensor Configurations

DISPLAYS
Room
The ACI/Infinity II is the newest wall-mount enclosure from Automation Components,
Inc. The most important innovation is the development of four-way airflow capability.
This allows the enclosure to be fitted with numerous options, and no self-heating errors.

TEMPERATURE
Options include setpoint, override, communication jack, and LCD.

Duct

RELATIVE HUMIDITY
The ACI Duct Mount configuration has a built in mounting flange for quick installation
and a foam pad to dampen vibrations. The sensing element is double encapsulated to
avoid sensor failures caused by moisture infiltration. Most sensors come in lengths of
4”, 8”, 12” and 18”. Custom lengths may be available as upon requst. They can be
ordered with a standard plastic enclosure, a galvanized metal box, or upgraded
to a NEMA 3R or NEMA 4X enclosure.

Outside

PRESSURE
The ACI Outside Air Mount is based on a European Style Enclosure that locks out water
with a gasketed cover and watertight fitting. They are designed to be mounted flush to
an exterior wall.

CURRENT
Immersion
The ACI Immersion configuration incorporates the same high quality standards as the
ACI Duct configuration but adds a ½ inch NPSM fitting in place of the mounting
flange and includes a two part 304 stainless steel thermowell. This product can also be
ordered with an optional galvanized metal box, NEMA 3R or NEMA 4X enclosure.
AIR QUALITY

Strap
The ACI Strap On sensor comes with a plastic enclosure. It has a sensor potted to the
ACCESSORIES

back side of a copper plate and with a foam pad creates compression when the strap worm
drive is tightened. This creates a good therrmal transfer around pipes 2” to 5” in diameter.
Extra straps can be ordered for larger diameter pipes. This product can also be ordered
with a galvanized metal box or a NEMA 4X enclosure.

TE-1
Temperature Sensor Configurations
DISPLAYS

Averaging
ACI has several options for getting an average temperature reading. Most common is
the flexible copper tube type, which comes in lengths of 8’, 12’, and 24’. Flexible
Wire and Rigid Probe averaging sensors are also available in various lengths.
TEMPERATURE

Stainless Plate
RELATIVE HUMIDITY

The ACI Stainless Plate has a sensor potted to its backside and is thermally shielded
from temperatures inside the wall by an insulated foam pad. Options include an
override and RS232 communication port.

Submersible
PRESSURE

The ACI Submersible Sensors can be fully submersed in water and come in lengths
up to 30’. Please call for sensor type availability.
CURRENT

Button
The ACI Button Sensor is designed to be aesthetically pleasing for higher profile
applications. Due to its size and appearance, it is a perfect choice for applications
where you don’t want to notice a room sensor.
AIR QUALITY

Enclosure Types
ACI has several types of enclosures to choose from. They include plastic and metal
electrical box types, NEMA 3R, NEMA 4X, and Euro Style.
ACCESSORIES

TE-2
Product Data RTD

A CI

DISPLAYS
A/100 Series
A/1K Series
“First in Sensor Quality” Platinum RTD Temperature
Sensors
Product Description

TEMPERATURE
The A/100 and A/1K Series temperature sensors incorporate a Class A,
Attributes:
Thin Film Platinum RTD sensor which conforms to DIN-IEC-751
 Double Potting Process
platinum RTD standards. These sensors are available in either two or
to avoid Moisture Issues
three-wire configurations, incorporating high accuracy and
interchangeability throughout a wide operating temperature range.  European enclosure for
outside air

RELATIVE HUMIDITY
These units are offered in Room, Room with Set Point, Room with
Override, Room with Setpoint and Override, and Room with Setpoint,  Class A Standard exceeds
Override, and RJ11 Jack, Stainless Steel Duct and Duct without Box, most specifications
Immersion, Stainless Plate, Raw, Bendable Copper and Stainless Steel
Rigid Averaging, Strap-On, Bullet Probe and Outdoor Air Configurations.  Four-way Airflow design
for wall mount
All ACI Room sensors may be ordered with an optional setpoint (see
chart on the following page), override, or with a 4 pin RJ11 or 6 pin  Can be used with a
RJ12 communication jack with terminal blocks, for remote programming. transmitter to provide a

PRESSURE
These units are also available with a 1/8" RS232 Stereo Jack. 4 to 20mA signal

Applications:
 DDC Systems

 Refrigeration Systems

 OEM / Industrial

CURRENT
Product Specifications
Output 100 Ohms @ 32oF (0oC)  Light Industrial
1K Ohms @ 32oF (0oC)
Accuracy +/- 0.06% @ 32oF (0oC) Single Point
+/- 1.0 Ohm @ 70oF (Averaging)
Stability less than +/- 0.1oC drift

AIR QUALITY
Repeatability +/-0.2oC (+/-0.36oF)
Operating Temp Range:
Single Point -58 to 392oF (-50 to 200oC)
Averaging -50 to 275oF (-45.5 to 134.8oC)
Temp. Coefficient 0.00385 Ohm/Ohm/oC
Standardization DIN-IEC-751(formerly DIN 43760)
Resistance +/- 0.06% Class A (Standard)
Characteristics +/- 0.12% Class B (Averaging)
For sensors with Display option, see the LCD Series cut sheet
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000100 Rev 1.pdf
TE-3
DISPLAYS

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x
1/2" NPT (PG16)
CONDUIT KNOCKOUTS Duct Insertion (U-Dimension)
5.5" (89 mm)
7.5" (191 mm)
11.5" (292 mm)
17.5" (445 mm)
PROBE LENGTH
(U-DIMENSION)
Averaging
8' (2.4 m)
12' (3.7 m)
4.060" [103.12mm] 24' (7.3 m)
TEMPERATURE

PROBE Ø 0.250" [6.35mm]


Ø0.743" [18.87 mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm]
CONDUIT KNOCKOUTS
RELATIVE HUMIDITY

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x Well Insertion (U-Length)
1/2" NPT (PG16)
CONDUIT KNOCKOUTS
2.50" (64 mm)
4.00" (102 mm)
6.25" (158.75 mm)

4.060" [103.12mm]
PRESSURE

Ø0.743" [18.87mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm] U-LENGTH
CONDUIT KNOCKOUTS
CURRENT

Ordering Information 1 1
Sensor # Wires Configuration Communication Jack1 Pot Value1 Setpoint Indicator Pot Action Display1 Housing Type2
A/ [ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

100 2W (2-Wire) R - Room RJ4 (4 Pin RJ11) 400 Cool | Warm DA (Direct) ( ) No Display ( ) Plastic Housing
1K 3W (3-Wire) RS - Room w/ Setpoint RJ6 (6 Pin RJ12) 1K 55 to 85 RA (Reverse) (Standard) (Standard)
RO - Room w/ Override RS232 (Stereo Jack) 2K 10 to 30o C (DF) LCD Display (GD) Galvanized
RSO - Room w/ Setpoint & Override 3K (Degrees F) (BB) NEMA 3R
AIR QUALITY

D - Duct 4”, 8”, 12”, 18” 5K (DC) LCD Display (4X) NEMA 4X
DO -Duct without box 4”, 8”, 12”, 18” 8.5K (Degrees C)
I - Immersion 2.5”, 4”, 6” 10K
A - Bendable Copper Averaging 12', 24'
20K
RA - Rigid Averaging 18", 24", 36"
S - Strap On 100K
O - Outdoor Air 1
These Options are only available on ACI’s Room Configurations.
RP - Remote Probe w/6’Leads
2
SP - Stainless Plate Duct, Immersion, Bendable Copper and Rigid Averaging available with optional
BP - Bullet Probe NEMA 3R (BB), NEMA 4X (4X) enclosures or Galvanized Junction Box (GD).
W - Raw
ACCESSORIES

BBS - Brass Button Sensor Strap-On Sensors are available with an optional NEMA 4X (4X) or
SBS - Stainless Button Sensor Galvanized Junction Box (GD)

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

TE-4
Product Data RTD

A CI

DISPLAYS
A/1K Nickel
“First in Sensor Quality”
Series
Nickel Temperature
Sensor
Product Description

TEMPERATURE
The A/1K-Nickel Series temperature sensors incorporate a thin film RTD
Attributes
sensor, which provides a predictable output over the specified temperature
 Positive Temp. Coefficient
range of -40 to 300oF. These sensors are available in a two-wire (PTC)
configuration incorporating high accuracy and interchangeability
throughout a wide operating temperature range. (See web page for  Two Year Warranty
complete curve/chart specifications)

RELATIVE HUMIDITY
 Double Potting Process
These units are offered in Room, Room with Set Point, Room with avoids moisture issues
Override, Room with Setpoint and Override, and Room with Setpoint,
Override, and RJ11 Jack, Stainless Steel Duct and Duct without Box,  Non-polarity sensitive
Immersion, Stainless Plate, Raw, Strap-On, Bullet Probe, Button Sensor
and Outdoor Air Configurations.
Applications
All ACI Room sensors may be ordered with an optional setpoint (see chart  OEM/Industrial
on the following page), override, or with a 4 pin RJ11 or 6 pin RJ12

PRESSURE
communication jack with terminal blocks, for remote programming. These  Commercial
units are also available with a 1/8" RS232 Stereo Jack.
 Process Control

 DDC Control Systems

CURRENT
Product Specifications
Output 1K Ohms @ 70oF (21oC)
Temp. Coefficient 0.00527 Ohm/Ohm/oC
Accuracy Temp Resistance Accuracy
-50oF 674 Ohms +/- 1.4oF
-30oF 725 Ohms +/- 1.2oF

AIR QUALITY
32oF 892 Ohms +/- 0.5oF
70oF 1000 Ohms +/- 0.4oF
170oF 1314 Ohms +/- 1.3oF
250oF 1597 Ohms +/- 1.7oF
Tolerance T<0oC (32oF) +/-0.4 + 0.028 * T(oC)
Tolerance T>0oC (32oF) +/-0.4 + 0.007 * T(oC)
Operating Temp. Range -40 to 300oF (0 to 148.9oC)
Operating RH Range 0 to 95% RH, non condensing
ACCESSORIES

For sensors with Display option, see the LCD Series cut sheet Automation Components, Inc.
2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000101 Rev 1.pdf
TE-5
DISPLAYS

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x
1/2" NPT (PG16)
CONDUIT KNOCKOUTS Duct Insertion (U-Dimension)
5.5" (89 mm)
7.5" (191 mm)
11.5" (292 mm)
17.5" (445 mm)
PROBE LENGTH
(U-DIMENSION)
Averaging
8' (2.4 m)
12' (3.7 m)
4.060" [103.12mm] 24' (7.3 m)
TEMPERATURE

PROBE Ø 0.250" [6.35mm]


Ø0.743" [18.87 mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm]
CONDUIT KNOCKOUTS
RELATIVE HUMIDITY

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x Well Insertion (U-Length)
1/2" NPT (PG16)
CONDUIT KNOCKOUTS
2.50" (64 mm)
4.00" (102 mm)
6.25" (158.75 mm)

4.060" [103.12mm]
PRESSURE

Ø0.743" [18.87mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm] U-LENGTH
CONDUIT KNOCKOUTS
CURRENT

Ordering Information 1 1
Sensor Configuration Communication Jack1 Pot Value1 Setpoint Indicator Pot Action Display1 Housing Type2
A/ [ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

1K-NI R - Room RJ4 (4 Pin RJ11) 400 Cool | Warm DA (Direct) ( ) No Display ( ) Plastic Housing
RS - Room w/ Setpoint RJ6 (6 Pin RJ12) 1K 55 to 85 RA (Reverse) (Standard) (Standard)
RO - Room w/ Override RS232 (Stereo Jack) 2K 10 to 30o C (DF) LCD Display (GD) Galvanized
RSO - Room w/ Setpoint & Override 3K (Degrees F) (BB) NEMA 3R
AIR QUALITY

D - Duct 4”, 8”, 12”, 18” 5K (DC) LCD Display (4X) NEMA 4X
DO -Duct without box 4”, 8”, 12”, 18” 8.5K (Degrees C)
I - Immersion 2.5”, 4”, 6” 10K
A - Bendable Copper Averaging 12', 24'
20K
S - Strap On
O - Outdoor Air 100K
RP - Remote Probe w/6’Leads 1
These Options are only available on ACI’s Room Configurations.
SP - Stainless Plate
2
BP - Bullet Probe Duct, Immersion, Bendable Copper and Rigid Averaging available with optional
W - Raw NEMA 3R (BB), NEMA 4X (4X) enclosures or Galvanized Junction Box (GD).
ACCESSORIES

BBS - Brass Button Sensor


SBS - Stainless Button Sensor Strap-On Sensors are available with an optional NEMA 4X (4X) or
Galvanized Junction Box (GD)

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

TE-6
Product Data RTD

A CI

DISPLAYS
A/BALCO Series
Temperature
“First in Sensor Quality” Sensor

Product Description

TEMPERATURE
The A/1K-Balco Series temperature sensors incorporate a thin film RTD
Attributes
sensor, which provides a predictable output over the specified temperature
 Specialized Temp. Sensor
range of -40 to 240ºF.
 Double Potting Process
These sensors are available in a two-wire configuration incorporating high avoids moisture issues
accuracy and interchangeability throughout a wide operating temperature

RELATIVE HUMIDITY
range.  Non-polarity sensitive

These units are offered in Room, Room with Set Point, Room with
Override,Room with Setpoint and Override, and Room with Setpoint, Applications
Override, and RJ11 Jack, Stainless Steel Duct and Duct without Box,  OEM/Industrial
Immersion, Stainless Plate, Raw, Strap-On, Bullet Probe, Button Sensor
and Outdoor Air Configurations.  Light Industrial

All ACI Room sensors may be ordered with an optional setpoint (see chart  DDC Systems

PRESSURE
on the following page), override, or with a 4 pin RJ11 or 6 pin RJ12
communication jack with terminal blocks for remote programming.

CURRENT
Product Specifications
Sensor Output 1000 Ohms @ 70ºF (21ºC)
Temp. Coefficient 2.2 Ohms /deg F
Temp. Operating Range -40 to 240ºF (-40 to 116ºC)
Accuracy +/- 0.1%
For sensors with Display option, see the LCD Series cut sheet

AIR QUALITY
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000117 Rev 1.pdf
TE-7
DISPLAYS

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x
1/2" NPT (PG16)
CONDUIT KNOCKOUTS Duct Insertion (U-Dimension)
5.5" (89 mm)
7.5" (191 mm)
11.5" (292 mm)
17.5" (445 mm)
PROBE LENGTH
(U-DIMENSION)
Averaging
8' (2.4 m)
12' (3.7 m)
4.060" [103.12mm] 24' (7.3 m)
TEMPERATURE

PROBE Ø 0.250" [6.35mm]


Ø0.743" [18.87 mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm]
CONDUIT KNOCKOUTS
RELATIVE HUMIDITY

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x Well Insertion (U-Length)
1/2" NPT (PG16)
CONDUIT KNOCKOUTS
2.50" (64 mm)
4.00" (102 mm)
6.25" (158.75 mm)

4.060" [103.12mm]
PRESSURE

Ø0.743" [18.87mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm] U-LENGTH
CONDUIT KNOCKOUTS
CURRENT

Ordering Information 1 1
Sensor Configuration Communication Jack1 Pot Value1 Setpoint Indicator Pot Action Display1 Housing Type2
A/ [ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

Balco R - Room RJ4 (4 Pin RJ11) 400 Cool | Warm DA (Direct) ( ) No Display ( ) Plastic Housing
RS - Room w/ Setpoint RJ6 (6 Pin RJ12) 1K 55 to 85 RA (Reverse) (Standard) (Standard)
RO - Room w/ Override RS232 (Stereo Jack) 2K 10 to 30o C (DF) LCD Display (GD) Galvanized
RSO - Room w/ Setpoint & Override 3K (Degrees F) (BB) NEMA 3R
AIR QUALITY

D - Duct 4”, 8”, 12”, 18” 5K (DC) LCD Display (4X) NEMA 4X
DO -Duct without box 4”, 8”, 12”, 18” 8.5K (Degrees C)
I - Immersion 2.5”, 4”, 6” 10K
S - Strap On 20K
O - Outdoor Air
100K
RP - Remote Probe w/6’Leads
SP - Stainless Plate 1
These Options are only available on ACI’s Room Configurations.
BP - Bullet Probe 2
W - Raw Duct, Immersion, Bendable Copper and Rigid Averaging available with optional
BBS - Brass Button Sensor NEMA 3R (BB), NEMA 4X (4X) enclosures or Galvanized Junction Box (GD).
ACCESSORIES

SBS - Stainless Button Sensor


Strap-On Sensors are available with an optional NEMA 4X (4X) or
Galvanized Junction Box (GD)

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

TE-8
Product Data Thermistor

ACI

DISPLAYS
A/AN Series
A/CP Series
“First in Sensor Quality”
A/3K Series
A/1.8K Series
Product Description A/20K Series

TEMPERATURE
The A/10K-AN (Type III), A/10K-CP (Type II), A/3K, A/1.8K and Attributes
A/20K Series temperature sensors are thermistor type sensors. These
sensors provide a predictable output over a specified temperature range  Offer high accuracy and
to meet each manufacturer’s required input values. (See web page for interchangeability over a
complete curve chart specifications) wide temperature range.

These units are offered in Room, Room with Set Point, Room with  Higher resistance output

RELATIVE HUMIDITY
Override, Room with Setpoint and Override, and Room w/ Setpoint, relative to Platinum RTD's
Override, and RJ11 Jack, Stainless Steel Duct and Duct without Box,
Immersion, Stainless Plate, Raw, Bendable Copper and Stainless Steel
Rigid Averaging, Strap-On, Bullet Probe, Button Sensor, and Outdoor  Non-polarity sensitive
Air Configurations.
Applications
All ACI Room sensors may be ordered with an optional setpoint (see  OEM / Industrial
chart on the following page), override, or with a 4 pin RJ11 or 6 pin
RJ12 communication jack with terminal blocks, for remote  Light Industrial
programming. These units are also available with a 1/8" RS232 Stereo
Jack.

PRESSURE
 DDC Systems

CURRENT
Product Specifications
Sensor Output 10K Ohms @ 77oF (25oC) Type III
10K Ohms @ 77oF (25oC) Type II
3K Ohms @ 77oF (25oC)
1.8K Ohms @ 77oF (25oC)
20K Ohms @ 77oF (25oC)

AIR QUALITY
Accuracy (0 to 70oC) +/-0.2oC (+/-0.36oF)
Stability +/- 0.13oC (0.23oF)
Operating Temperature Range -40 to 302oF (-40 to 150oC)
Operating Humidity 0 to 90% RH non-condensing
Interchangeability +/- 0.2oC (+/-0.36oF)
Power Dissipation Constant 3 mW / oC
For sensors with Display option, see LCD Series Temp display cut sheet
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
c0000102rev1.pdf
TE-9
DISPLAYS

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x
1/2" NPT (PG16)
CONDUIT KNOCKOUTS Duct Insertion (U-Dimension)
5 .5" (89 mm)
7.5" (191 mm)
11.5" (292 mm)
17.5" (445 mm)
PROBE LENGTH
(U-DIMENSION)
Averaging
8' (2.4 m)
12' (3.7 m)
4.060" [103.12mm] 24' (7.3 m)
TEMPERATURE

PROBE Ø 0.250" [6.35mm]


Ø0.743" [18.87 mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm]
CONDUIT KNOCKOUTS
RELATIVE HUMIDITY

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x Well Insertion (U-Length)
1/2" NPT (PG16)
CONDUIT KNOCKOUTS
2.50" (64 mm)
4.00" (102 mm)
6.25" (158.75 mm)

4.060" [103.12mm]
PRESSURE

Ø0.743" [18.87mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm] U-LENGTH
CONDUIT KNOCKOUTS
CURRENT

Ordering Information 1 1
Sensor Configuration Communication Jack1 Pot Value1 Setpoint Indicator Pot Action Display1 Housing Type2
A/ [ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

CP (Type II) R - Room RJ4 (4 Pin RJ11) 400 Cool | Warm DA (Direct) ( ) No Display ( ) Plastic Housing
AN (Type III) RS - Room w/ Setpoint RJ6 (6 Pin RJ12) 1K 55 to 85 RA (Reverse) (Standard) (Standard)
3K RO - Room w/ Override RS232 (Stereo Jack) 2K 10 to 30o C (DF) LCD Display (GD) Galvanized
1.8K RSO - Room w/ Setpoint & Override 3K (Degrees F) (BB) NEMA 3R
AIR QUALITY

20K D - Duct 4”, 8”, 12”, 18” 5K (DC) LCD Display (4X) NEMA 4X
DO -Duct without box 4”, 8”, 12”, 18” 8.5K (Degrees C)
I - Immersion 2.5”, 4”, 6” 10K
A - Bendable Copper Averaging 12', 24'
20K
RA - Rigid Averaging 18", 24", 36"
100K
FA - Flexible Averaging (Cable)18", 24", 36"
S - Strap On
1
O - Outdoor Air These Options are only available on ACI’s Room Configurations.
RP - Remote Probe w/6’Leads 2
Duct, Immersion, Bendable Copper and Rigid Averaging available with optional
SP - Stainless Plate
NEMA 3R (BB), NEMA 4X (4X) enclosures or Galvanized Junction Box (GD).
ACCESSORIES

BP - Bullet Probe
W - Raw
BBS - Brass Button Sensor Strap-On Sensors are available with an optional NEMA 4X (4X) or
SBS - Stainless Button Sensor Galvanized Junction Box (GD)

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

TE-10
Product Data Thermistor

ACI

DISPLAYS
A/100KS Series
A/2252 Series
“First in Sensor Quality”
A/CSI Series
A/5K Series
Temperature
Product Description Sensor

TEMPERATURE
The A/100KS, A/2252, A/CSI and A/5K Series temperature sensors are Attributes
thermistor type sensors. These sensors provide a predictable output over
a specified temperature range to meet each manufacturer’s required input  Offer high accuracy and
values. (See web page for complete curve chart specifications) interchangeability over a
wide temperature range.
These units are offered in Room, Room with Set Point, Room with
Override, Room with Setpoint and Override, and Room w/ Setpoint,  Higher resistance output

RELATIVE HUMIDITY
Override, and RJ11 Jack, Stainless Steel Duct and Duct without Box, relative to Platinum RTD's
Immersion, Stainless Plate, Raw, Bendable Copper and Stainless Steel
Rigid Averaging, Strap-On, Bullet Probe, Button Sensor, and Outdoor
Air Configurations.  Non-polarity sensitive

All ACI Room sensors may be ordered with an optional setpoint (see Applications
chart on the following page), override, or with a 4 pin RJ11 or 6 pin  OEM / Industrial
RJ12 communication jack with terminal blocks, for remote
programming. These units are also available with a 1/8" RS232 Stereo  Light Industrial
Jack.

PRESSURE
 DDC Systems

CURRENT
Product Specifications
Output 100K Ohms @ 77oF (25oC)
10K Ohms @ 77oF (25oC) CSI
2252 Ohms @ 77oF (25oC)
5000 Ohms @ 77oF (25oC)
Operating Temperature Range -40 to 302oF (-40 to 150oC)
+/- 0.2oC (+/-0.36oF)
AIR QUALITY
Interchangeability
Power Dissipation Constant 3 mW / oC
Stability +/- 0.13oC (0.23oF)
o
Accuracy (0 to 70 C) +/-0.2oC (+/-0.36oF)
Operating Humidity 0 to 90% RH non-condensing
For sensors with Display option, see the LCD Series cut sheet
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
c0000102rev1.pdf
TE-11
DISPLAYS

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x
1/2" NPT (PG16)
CONDUIT KNOCKOUTS Duct Insertion (U-Dimension)
5.5" (89 mm)
7.5" (191 mm)
11.5" (292 mm)
17.5" (445 mm)
PROBE LENGTH
(U-DIMENSION)
Averaging
8' (2.4 m)
12' (3.7 m)
4.060" [103.12mm] 24' (7.3 m)
TEMPERATURE

PROBE Ø 0.250" [6.35mm]


Ø0.743" [18.87 mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm]
CONDUIT KNOCKOUTS
RELATIVE HUMIDITY

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x Well Insertion (U-Length)
1/2" NPT (PG16)
CONDUIT KNOCKOUTS
2.50" (64 mm)
4.00" (102 mm)
6.25" (158.75 mm)

4.060" [103.12mm]
PRESSURE

Ø0.743" [18.87mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm] U-LENGTH
CONDUIT KNOCKOUTS
CURRENT

Ordering Information 1 1
Sensor Configuration Communication Jack1 Pot Value1 Setpoint Indicator Pot Action Display1 Housing Type2
A/ [ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

100KS R - Room RJ4 (4 Pin RJ11) 400 Cool | Warm DA (Direct) ( ) No Display ( ) Plastic Housing
2252 RS - Room w/ Setpoint RJ6 (6 Pin RJ12) 1K 55 to 85 RA (Reverse) (Standard) (Standard)
CSI RO - Room w/ Override RS232 (Stereo Jack) 2K 10 to 30o C (DF) LCD Display (GD) Galvanized
5K RSO - Room w/ Setpoint & Override 3K (Degrees F) (BB) NEMA 3R
AIR QUALITY

D - Duct 4”, 8”, 12”, 18” 5K (DC) LCD Display (4X) NEMA 4X
DO -Duct without box 4”, 8”, 12”, 18” 8.5K (Degrees C)
I - Immersion 2.5”, 4”, 6” 10K
A - Bendable Copper Averaging 12', 24'
20K
RA - Rigid Averaging 18", 24", 36"
S - Strap On 100K
O - Outdoor Air 1
These Options are only available on ACI’s Room Configurations.
RP - Remote Probe w/6’Leads
2
SP - Stainless Plate Duct, Immersion, Bendable Copper and Rigid Averaging available with optional
BP - Bullet Probe NEMA3R (BB), NEMA 4X (4X) enclosures or Galvanized Junction Box (GD).
ACCESSORIES

W - Raw
BBS - Brass Button Sensor Strap-On Sensors are available with an optional NEMA 4X (4X) or
SBS - Stainless Button Sensor Galvanized Junction Box (GD)

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

TE-12
Product Data Semiconductor

A CI

DISPLAYS
A/592 Series
A/592-10K Series
Temperature
“First in Sensor Quality” Sensor

Product Description

TEMPERATURE
The A/592 Series semiconductor type temperature sensors provide
accurate temperature measurement and control. Attributes
 System Specfic Sensor
The A/592 provides a 248 to 378 uA output throughout the temperature
range of -25 to 105ºC (-13 to 221ºF).  uA and mV output
The A/592-10K uses a precision 10K (0.1%) resistor to convert the Applications

RELATIVE HUMIDITY
current output to a three-wire 2.48 to 3.78 VDC output.
 OEM / Industrial
These units are calibrated using a NIST traceable thermometer to ensure
the highest possible accuracy. Each unit will be individually calibrated  Light Industrial
and labeled with its offset never to exceed 2.2ºC (4ºF).
 DDC Systems
These units are offered in Room, Room with Setpoint, Room with
Override, Room with Setpoint and Override, Duct, Immersion, Stainless
Plate, Raw, Averaging, Strap-On, and Outside Air configurations.

PRESSURE
CURRENT
Product Specifications
Supply Voltage +4 to 30 VDC
Output A/592 - 248 to 378 uA
Output A/592-10K - 2.48 to 3.78 VDC
Temperature Coefficient A/592 - 1 uA/ºC (0.556 uA/ºF)
Temperature Coefficient A/592-10K - 10 mV/C (5.556 mV/ºF)

AIR QUALITY
Sensor Accuracy +/- 1.26ºF @ 77ºF (+/- 0.70C @ 25C)
Repeatability +/- 0.18ºF (+/- 0.10ºC)
Linearity +/- 0.27ºF max from 32 to 158ºF
Temperature Range -13 to 221ºF (-25 to 105ºC)
Offset +/- 4ºF max (+/- 2.2ºC max)
For sensors with Display option, see the LCD Series cut sheet
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000120 Rev 1.pdf
TE-13
DISPLAYS

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x
1/2" NPT (PG16)
CONDUIT KNOCKOUTS Duct Insertion (U-Dimension)
5.5" (89 mm)
7.5" (191 mm)
11.5" (292 mm)
17.5" (445 mm)
PROBE LENGTH
(U-DIMENSION)
Averaging
8' (2.4 m)
12' (3.7 m)
24' (7.3 m)
TEMPERATURE

4.060" [103.12mm]

PROBE Ø 0.250" [6.35mm]


Ø0.743" [18.87 mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm]
CONDUIT KNOCKOUTS
RELATIVE HUMIDITY

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x Well Insertion (U-Length)
1/2" NPT (PG16)
CONDUIT KNOCKOUTS
2.50" (64 mm)
4.00" (102 mm)
6.25" (158.75 mm)

4.060" [103.12mm]
PRESSURE

Ø0.743" [18.87mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm] U-LENGTH
CONDUIT KNOCKOUTS
CURRENT

Ordering Information 1 1
Sensor Configuration Communication Jack1 Pot Value1 Setpoint Indicator Pot Action Display1 Housing Type2
A/ [ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

592 R - Room RJ4 (4 Pin RJ11) 400 Cool | Warm DA (Direct) ( ) No Display ( ) Plastic Housing
592-10K
RS - Room w/ Setpoint RJ6 (6 Pin RJ12) 1K 55 to 85 RA (Reverse) (Standard) (Standard)
RO - Room w/ Override RS232 (Stereo Jack) 2K 10 to 30o C (DF) LCD Display (GD) Galvanized
RSO - Room w/ Setpoint & Override 3K (Degrees F) (BB) NEMA 3R
AIR QUALITY

D - Duct 4”, 8”, 12”, 18” 5K (DC) LCD Display (4X) NEMA 4X
DO -Duct without box 4”, 8”, 12”, 18” 8.5K (Degrees C)
I - Immersion 2.5”, 4”, 6” 10K
A - Bendable Copper Averaging 12', 24'
S - Strap On 20K
O - Outdoor Air 100K
RP - Remote Probe w/6’Leads 1
These Options are only available on ACI’s Room Configurations.
SP - Stainless Plate
2
BP - Bullet Probe Duct, Immersion, Bendable Copper and Rigid Averaging available with optional
W - Raw NEMA 3R (BB), NEMA 4X (4X) enclosures or Galvanized Junction Box (GD).
ACCESSORIES

Strap-On Sensors are available with an optional NEMA 4X (4X) or


Galvanized Junction Box (GD)

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

TE-14
Product Data Semiconductor

A CI

DISPLAYS
A/34 Series
Temperature
Sensor
“First in Sensor Quality”

Product Description

TEMPERATURE
The A/34 Series semiconductor type temperature sensors provide
accurate temperature measurement that is linear and proportional to Attributes
Degrees Fahrenheit.  System Specific Sensor

The A/34 sensor provides a -400 to 2300 mV output throughout the  mV output equal to ooF
temperature range of -40 to 230ºF.
Applications

RELATIVE HUMIDITY
These units are offered in Room, Room with Set Point, Room with
Override, Room with Setpoint and Override, and Room w/ Setpoint,  OEM / Industrial
Override, and RJ11 Jack, Stainless Steel Duct and Duct without Box,
Immersion, Stainless Plate, Raw, Strap-On, Bullet Probe, Button Sensor,  Light Industrial
and Outdoor Air Configurations.
 DDC Systems
All ACI Room sensors may be ordered with an optional setpoint (see
chart on the following page), override, or with a 4 pin RJ11 or 6 pin
RJ12 communication jack with terminal blocks, for remote programming.
These units are also available with a 1/8" RS232 Stereo Jack.

PRESSURE
CURRENT
Product Specifications
Supply Voltage +5 to 30 VDC
Output -3 wire, -400 to 2300 mV
Accuracy +/- 1.0ºF @ 77ºF (+/- 0.55ºC @ 25ºC)
Temperature Range -40 to 230ºF (-40 to 110ºC)
Temperature Coefficient 10 mV/ºF or 18 mV/ºC

AIR QUALITY
For sensors with Display option, see the LCD Series cut sheet
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000119 Rev 1.pdf
TE-15
DISPLAYS

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x
1/2" NPT (PG16)
CONDUIT KNOCKOUTS Duct Insertion (U-Dimension)
5.5" (89 mm)
7.5" (191 mm)
11.5" (292 mm)
17.5" (445 mm)
PROBE LENGTH
(U-DIMENSION)
Averaging
8' (2.4 m)
12' (3.7 m)
4.060" [103.12mm] 24' (7.3 m)
TEMPERATURE

PROBE Ø 0.250" [6.35mm]


Ø0.743" [18.87 mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm]
CONDUIT KNOCKOUTS
RELATIVE HUMIDITY

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x Well Insertion (U-Length)
1/2" NPT (PG16)
CONDUIT KNOCKOUTS
2.50" (64 mm)
4.00" (102 mm)
6.25" (158.75 mm)

4.060" [103.12mm]
PRESSURE

Ø0.743" [18.87mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm] U-LENGTH
CONDUIT KNOCKOUTS
CURRENT

Ordering Information 1 1
Sensor Configuration Communication Jack1 Pot Value1 Setpoint Indicator Pot Action Housing Type2
A/ [ ] -[ ] -[ ] -[ ] -[ ] -[ ] -[ ]

34 R - Room RJ4 (4 Pin RJ11) 400 Cool | Warm DA (Direct) ( ) Plastic Housing
RS - Room w/ Setpoint RJ6 (6 Pin RJ12) 1K 55 to 85 RA (Reverse) (Standard)
RO - Room w/ Override RS232 (Stereo Jack) 2K 10 to 30o C (GD) Galvanized
RSO - Room w/ Setpoint & Override 3K (BB) NEMA 3R
AIR QUALITY

D - Duct 4”, 8”, 12”, 18” 5K (4X) NEMA 4X


DO -Duct without box 4”, 8”, 12”, 18” 8.5K
I - Immersion 2.5”, 4”, 6” 10K
S - Strap On 20K
O - Outdoor Air
100K
RP - Remote Probe w/6’Leads
SP - Stainless Plate 1
These Options are only available on ACI’s Room Configurations.
BP - Bullet Probe 2
W - Raw Duct, Immersion, Bendable Copper and Rigid Averaging available with optional
NEMA 3R (BB), NEMA 4X (4X) enclosures or Galvanized Junction Box (GD).
ACCESSORIES

Strap-On Sensors are available with an optional NEMA 4X (4X) or


Galvanized Junction Box (GD)

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

TE-16
Product Data Transmitter

ACI
A/TT100 Series

DISPLAYS
A/TT1K Series
A/TTM100 Series
“First in Sensor Quality” A/TTM1K Series
Temperature Transmitters
Product Description

TEMPERATURE
ACI temperature transmitters are a cost effective solution for all of your Attributes:
temperature measurement needs. The transmitters are accurate, durable, Not polarity sensitive
and reliable. Numerous mounting configurations are offered.
Class A RTD
ACI produces two temperature transmitters, the A/TT100 for use with a
100 Ohm Platinum RTD and the A/TT1K for use with a 1K Ohm
Double Potting Process

RELATIVE HUMIDITY
Platinum RTD. The transmitters produce a linear 4-20 mA output
carried on a two-wire system. Optional output voltage ranges of (+1-5 or avoids moisture issues
+2-10 VDC) can also be ordered. The transmitter is supplied factory
calibrated, and supplied with zero and span potentiometers for field Custom calibration ranges
calibration. The transmitter is linear from -50 to 392oF. are available

The A/TTM Series transmitters are calibrated using a high accuracy Applications:
NIST traceble digital thermometer and temperature chamber at three Data acquisition
points standard. Additional options include current limiting and AC
power. All temperature transmitters have a two year product warranty. OEM

PRESSURE
Process Control

Clean Rooms

CURRENT
Product Specifications
Transmitter Supply Voltage 8 to 35 VDC, No Polarity Sensitivity
249 Ohm Load: +12 to 35VDC
499 Ohm Load: +17 to 35VDC
Temp. Transmitter Input 2-wire Platinum 100/1K Ohm Class A RTD
Temp. Transmitter Output 2-wire, Linear 4 to 20mA DC Current (Std.)
1 to 5 VDC or 2 to 10VDC

AIR QUALITY
Temp. Transmitter Accuracy +/- 1% of Calibrated span (Standard)
NIST Accuracy Specified by customer down to +/-0.5oF
Temp. Sensor Operating Range
Single Point -58 to 392oF (-50 to 200oC)
Averaging -50 to 275oF (-45.5 to 135oC)
Transmitter Operating Temp. Range 32 to 158oF (0 to 70oC)
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000104 Rev 2.pdf
TE-17
DISPLAYS

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x
1/2" NPT (PG16)
CONDUIT KNOCKOUTS Duct Insertion (U-Dimension)
5.5" (89 mm)
7.5" (191 mm)
11.5" (292 mm)
17.5" (445 mm)
PROBE LENGTH
(U-DIMENSION)
Averaging
8' (2.4 m)
12' (3.7 m)
24' (7.3 m)
TEMPERATURE

4.060" [103.12mm]

PROBE Ø 0.250" [6.35mm]


Ø0.743" [18.87 mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm]
CONDUIT KNOCKOUTS
RELATIVE HUMIDITY

2.200" [55.88mm]
Ø0.896" [22.76mm] 4x Well Insertion (U-Length)
1/2" NPT (PG16)
CONDUIT KNOCKOUTS
2.50" (64 mm)
4.00" (102 mm)
6.25" (158.75 mm)

4.060" [103.12mm]
PRESSURE

Ø0.743" [18.87mm] 2x
3/8" NPT (PG11) 2.000" [50.8mm] U-LENGTH
CONDUIT KNOCKOUTS
CURRENT

Ordering Information
Sensor Type Span Configuration Output LCD Display Housing Type2
A/ [ ] [ ] [ ] [ ] [ ] -[ ]

( ) Plastic Housing
TT100 (100 Ohm RTD) (1) 40 to 90o R - Room (1) 1 to 5 VDC ( ) No Display
RS - Room w/Setpoint (Standard)
TT1K (1000 Ohm RTD) (2) 30 to 100o (2) 2 to 10 VDC (Standard)
RO - Room w/Override (GD) Galvanized
(3) 20 to 120o
AIR QUALITY

(4) 4 to 20 mA (DF) LCD Display


(BB) NEMA 3R
RSO - Room w/Setpoint & Override
TTM100 (100 Ohm RTD) (4) 40 to 140o D - Duct 4”, 8”, 12”, 18”
(Degrees F)
(4X) NEMA 4X
TTM1K (1000 Ohm RTD) (5) 40 to 240o (DC) LCD Display
I - Immersion 2.5”, 4”, 6”
(6) -30 to 130o (Degrees C)
Matched Calibration A - Averaging 12', 24'
with 3 point NIST (7) 0 to 150o RA - Rigid Averaging 18”, 24”, 36”
certificate (8) Specify S - Strap - On 2
O - Outdoor Air Duct, Immersion, Bendable Copper and Rigid Averaging available
For added accuracy 5 point RP - Remote Probe 6' Lead wires with optional NEMA 3R (BB), NEMA 4X (4X) enclosures or
SP - Stainless Plate Galvanized Junction Box (GD).
calibration is also available
ACCESSORIES

A/5PT NIST (5 Point NIST Calibration certificate) Strap-On Sensors are available with an optional NEMA 4X (4X) or
Galvanized Junction Box (GD)

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

TE-18
Product Data High and Low Temp

A CI

DISPLAYS
High and Low
Temperature
“First in Sensor Quality” Sensors and
Transmitters
Product Description

TEMPERATURE
ACI has a full line of high and low temperature sensors that are available
as stand alone sensors or sensor/transmitter combinations. The transmitters Attributes:
come standard with 100 or 1,000 Ohm platinum RTD’s and provide a 100/1000 Ohm RTD
linear 4 to 20 mA output signal.
Stable outputs in extreme
ACI High Temperature sensors are air encapsulated. This allows the sensor Temperature Environments
to have a more stable output since the sensing element isn't subjected to

RELATIVE HUMIDITY
the constant expansion and contraction of the encapsulation materials.
The sensors are mounted in a 1/4" diameter stainless steel probe with 3-Wire Sensors w/ 8 foot
Nickel Plated Fiberglass lead wires. Nickel Fiberglass or Teflon
lead wires.
ACI Low Temperature sensors use a strain-free element. This allows the
sensor to have a more stable output, since the sensing element is not
subjected to the constant expansion and contraction of the encapsulation Applications:
materials. The sensors are mounted in a 1/4" diameter stainless steel
probe with Teflon lead wires. High Temp: Stacks, Boilers,
Commercial Ovens
Both the ACI High and Low Temperature sensors are available in duct,

PRESSURE
immersion and remote probe mounting configurations. All of the units Low Temp: Freezers, Meat
come with a two year factory warranty. Packing Plants, Laboratories

CURRENT
Product Specifications
Supply Voltage 8 to 35 VDC, No Polarity Sensitivity
249 Ohm Load: +12 to 35VDC
499 Ohm Load: +17 to 35VDC
Sensor Output 3-wire Platinum 100/1000 Ohm RTD
Sensor Accuracy +/- 0.012% @ 32oF (0oC)
Sensor Temperature Coefficient 0.00385 Ohms/ Ohms /oC

AIR QUALITY
Transmitter Output 2-wire, Linear 4 to 20 mA DC Current
Transmitter Accuracy +/- 1.0% of span
Sensor Operating Range Low Temp: -328 to 392oF (-200 to 200oC)

High Temp: -40 to 743oF (-40 to 395oC)


Transmitter Operating Range 32 to 158oF (0 to 70oC)
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000104 Rev 2.pdf
TE-19
Dimensions
DUCT IMMERSION
DISPLAYS

1.70”
(4.3cm)

5.75” (14.6cm) X 0.25” (0.6cm) DIA 0.25”


8” (20.3cm) X 0.25” (0.6cm) DIA (0.6cm)
0.25”
12” (30.4cm) X 0.25” (0.6cm) DIA (0.6cm)
18” (45.7cm) X 0.25” (0.6cm) DIA

4.00”
(10.2cm)
½” (1.2cm) Male NPT
TEMPERATURE

1/8" (0.3cm) mnpt Stainless Threads


Fitting

2.00” 1.70”
(5.08cm) (4.3cm)
0.85”
(2.1cm) 2.00” ½” (1.2cm) Conduit
(5.0cm) Knockouts
(10 Total)
RELATIVE HUMIDITY

½” (1.2cm) Male NPT


4.0” Stainless Fitting
(10.2cm)

0.175” DIA x 0.600”


(0.4cm DIA x 1.5cm)

OUTDOOR AIR REMOTE PROBE


2.00” 2.75”
(5.0cm) 0.50" x 0.25” Slot
(1.2cm x 0.6cm) (6.9cm)

8’ (2.43m)Teflon Leads
PRESSURE

4.5”
(11.4cm) 1” (2.54cm) Long x
0.25” (0.6cm) O.D.
Bullet Probe

1.70”
(4.3cm)

2.00”
(5.0cm)
½” (1.2cm) Conduit
Knockouts
CURRENT

(10 Total)

3.0” 4.0”
(7.6cm) (10.2cm)

0.250” O.D.(0.6cm)
Stainless Steel
Probe

Ordering Information
Sensor Span* Configuration Output*
AIR QUALITY

A/ [ ] [ ] -[ ] [ ]

100-LT ( ) Specify D - Duct 4”, 8”, 12”, 18” (1) 1 to 5 VDC


1K-LT DO - Duct without Box 4”,8”,12”,18” (2) 2 to 10 VDC
100-HT I - Immersion 2.5”, 4”, 6” (4) 4 to 20 mA
1K-HT RP - Remote Probe (8’ leads)
TT100-LT* O - Outside Air - Only Available for Low Temperature Sensors.
TT1K-LT*
TT100-HT*
ACCESSORIES

TT1K-HT* *Specify Span and Choose Output Options on Temperature Transmitters

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407
TE-20
Product Data Relative Humidity

A CI

DISPLAYS
A/RH Series
Relative Humidity Transmitters

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/RH Series Relative Humidity transmitters, convert a resistance Attributes:
change to a linear 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC output. The Single point Field Calibration
current signal may be transmitted over long distances on twisted-pair wire
and will not be affected by the lead wire resistance or electrical noise.
Field selectable output signals
The Advanced Ceramic Technology design overcomes the limitations of
other resistance-based humidity sensors that utilize water-soluble polymer 1%, 2%, 3%, and 5%

RELATIVE HUMIDITY
coatings. The Advanced Ceramic Technology enables these sensors to Accuracies
recover fully from condensation. This also allows the sensor to maintain
its accuracy over a longer period of time. Despite its high accuracy, the Low Drift
Advanced Ceramic Technology sensor and related circuitry is economical.
Highly Repeatable
Accuracy is maintained over the entire operating range, using a thermistor
for temperature compensation. Calibration Certificates
Available
Each A/RH Series humidity transmitter is calibrated using a NIST

PRESSURE
Traceable Temperature /Humidity Chamber. Both three and five point
calibration certificates are avalable for 1% and 2% RH accuracies but Applications:
they must be ordered separately.
Building Automation Systems
All A/RH Series transmitters have a limited 2 year warranty.
Light Industrial

Pharmaceutical

CURRENT
Product Specifications Humidity Chambers
Supply Voltage 250 Ohm Load: +15 to 36 VDC / 21.6-26.4 VAC
0-5VDC: +15-36 VDC / 21.6-26.4 VAC Data acquisition
500 Ohm Load: +18 to 36 VDC / 21.6-26.4 VAC
0-10VDC: +18-36 VDC / 21.6-26.4 VAC OEM
Power Consumption 1 VA max.
RH Measurement Range 0 to 100%

AIR QUALITY
RH Output 2-wire, 4 to 20mA (Factory Standard)
3-wire, 0-5, 0-10 VDC or 4 to 20mA
Accuracy @ 77oF +/- 1% over 20% span (between 20 to 90%)
+/- 2%, 3%, or 5% from 20 to 95%
Long Term Stability Less than 2% drift / 5 years
Hysteresis Less than 0.4% RH
Repeatablity 0.5% RH
Sensitivity 0.1 % RH
Response Time 110 seconds for 63% Step
ACCESSORIES

Operating Temperature Range -10 to 122oF (-23.3 to 50oC)


Operating Humidity Range 0 to 95 % RH non-condensing Automation Components, Inc.
Saturation Response Time 10 minutes for 63% Step 2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000105 rev 3.pdf
RH-1
Dimensions
DISPLAYS

Room Outside
2.75" 3.60"
(70 mm) 1.15" (4) PG11 1/2" (91 mm)
(29 mm) (127 mm) NPT
Knockouts
TEMPERATURE

0.18"
3.84" (5 mm)
4.51"
(98 mm) O.D. Ref.
(115 mm)

Mounting Hole
RELATIVE HUMIDITY

Separation:
2.25" 2.69" (68 mm)
(57 mm)

Duct Stainless Plate


0.65" dia.
(17 mm)

Plastic
PRESSURE

0.75" dia. Washer


1.00"
7.15" (19 mm) 4.50" (25 mm)
(182 mm)
(114 mm)

60 Micron S.S. 0.75" dia.


Sintered
(19 mm)
0.75" Filter
(19 mm) 2.25"
CURRENT

(57 mm) 2.75"


(70 mm)

Ordering Information
AIR QUALITY

Accuracy Range if 1% Configuration


A/ [ ] -[ ] -[ ]
RH1 (+/- 1%) Please Specify (R) Room
RH2 (+/- 2%) a 20% Span (D) Duct
RH3 (+/- 3%) (i.e. 40-60%) (O) Outdoor Air
RH5 (+/- 5%) (SP) Stainless Plate
3 PT NIST Certificate (3 point Calibration Certificate @ 20, 50 and 80% RH)
ACCESSORIES

5 PT NIST Certificate (5 point Calibration Certificate w/standard points choosen by ACI)


Example: A/RH3-R or A/RH5-D or A/RH2-O or A/RH1-(40 to 60%)-SP
2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407

RH-2
Product Data RH-TEMP

A CI

DISPLAYS
A/RH-TEMP Series
Relative Humidity/
Temperature Combinations
“First in Sensor Quality”

Product Description

TEMPERATURE
The A/RH-TEMP Series Relative Humidity transmitters, convert a
resistance to a linear 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC output. Attributes:
The current signal may be transmitted over long distances on unshielded Low Drift
twisted-pair wire and will not be affected by the lead wire resistance or
electrical noise. Highly Repeatable
The Advanced Ceramic Technology design overcomes the limitations of
other resistance-based humidity sensors that utilize water soluble polymer Temperature Sensor Ouput

RELATIVE HUMIDITY
coatings. The Advanced Ceramic Technology enables these sensors to
recover fully from condensation. This allows the sensor to maintain its Field Selectable Output
accuracy over a longer period of time. Despite its accuracy, the Advanced Signals
Ceramic Technology sensor and related circuitry is economical.
Accuracy is maintained over the entire operating range, using a thermistor Single Point Field Calibration
for temperature compensation. using DIP Switches
Each A/RH-TEMP Series humidity transmitter is calibrated using an NIST Lowers Inventory Cost
Traceable Temperature and Humidity Chamber.

PRESSURE
Any ACI thermistor, RTD, or temperature transmitter may be ordered with Applications:
the A/RH transmitter. All A/RH-TT Room combination units will have a Light Industrial
board mounted on the back of the enclosure. All A/RH-Temp Series
transmitters have a limited 2 year warranty. Pharmaceutical

Humidity Chambers

CURRENT
Product Specifications Pool Environments

Supply Voltage 250 Ohm Load: +15 to 36 VDC / 24 VAC Process Control
500 Ohm Load: +18 to 36 VDC / 24 VAC
Power Conumption 1 VA max.
RH Measurment Range 0 to 100% RH
RH Output Signal 2-wire, 4-20mA, 3-wire 0-5 or 0-10 VDC
Temperature Sensor Output 2-Wire Resistive, or 2-wire uA Output

AIR QUALITY
Temperature Transmitter Output 2-wire, 4 to 20mA, or 3-wire, 1-5, 2-10 VDC
Accuracy @ 77oF (25oC) +/- 1% over 20% Span between 20-95% RH
+/- 2, 3, or 5% from 20 to 95% RH
Repeatability 0.5% RH
Hysteresis Less than 0.4% RH
Long Term Stability Less than 2% RH Drift / 5 Years
Response Time 110 seconds for 63% Step
Saturated Response Time 10 minutes for 63% Step
Operating Temp. Range -10 to 122oF (-23.3 to 50oC)
ACCESSORIES

Operating RH Range 0 to 100% RH Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000106 Rev 2.pdf
RH-3
Dimensions
Room Outside
DISPLAYS

2.75" 3.60"
(70 mm) 1.15" (4) PG11 1/2" (91 mm)
(29 mm) (127 mm) NPT
Knockouts
TEMPERATURE

0.18"
3.84" (5 mm)
4.51"
(98 mm) O.D. Ref.
(115 mm)

Mounting Hole
Separation:
RELATIVE HUMIDITY

2.25" 2.69" (68 mm)


(57 mm)

Duct Stainless Plate


0.65" dia.
(17 mm)

Plastic
PRESSURE

0.75" dia. Washer


1.00"
7.15" (19 mm) 4.50" (25 mm)
(182 mm)
(114 mm)

60 Micron S.S. 0.75" dia.


Sintered
(19 mm)
0.75" Filter
(19 mm) 2.25"
2.75"
CURRENT

(57 mm)
(70 mm)

Ordering Information
Accuracy Temp Sensor Configuration Temp Transmitter Output (if needed)
AIR QUALITY

A/ [ ] [ ] [ ] [ ]
RH1 (+/- 1%)* 100 1K 1.8K (R) Room (4) 4 to 20mA Output
RH2 (+/- 2%) 2.2K ASI 3K (RO) Room w/Override (1) 1-5 VDC Output
RH3 (+/- 3%) AN(Type III) (RS) Room w/Set Point* (2) 2-10VDC Output
RH5 (+/- 5%) CP(Type II) (RSO) Room w/Set Point
CSI 20K 100K &Override*
(D) Duct
1K Nickel * See Temperature Cut sheet for
(O) Outdoor Air
ACCESSORIES

TT1K** TT100** (SP) Stainless Plate additional information on setpoint specs

*Specify a 20 % RH Range when ordering an A/RH1%


**Specify a Temperature span for TT100 and TT1K Units
2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407

RH-4
Product
ProductData
Data Enthalpy

A CI

DISPLAYS
A/ENT-CTRL
Enthalpy Controller

“First in Sensor Quality” A/ENT-DIFF


Differential Enthalpy

Product Description

TEMPERATURE
The A/ENT-CTRL and A/ENT-DIFF are low cost Enthalpy controllers that
measure both temperature and humidity and converts them into a sourced Attributes:
relay output. The supply voltage to the A/ENT-CTRL/DIFF is common to 1/4” Spade Connectors
the N/O or N/C contacts of the 10A Form 1C Relay. The relay is
controlled or switched by selecting the proper mode switch within the unit. Conformally Coated PCB

The Advanced Ceramic Technology overcomes the limitations of other High Accuracy

RELATIVE HUMIDITY
resistance-based humidity sensors that utilize water-soluble polymer
coatings. This technology enables these sensors to fully recover from RoHS Compliant
condensation and enables the sensor to maintain its accuracy over time.
Despite its accuracy, the Advanced Ceramic Technology sensor and Ashrae 90.1 Compliant
related circuitry is economical. (A/ENT-CTRL only)
All of the A/ENT-CTRL and A/ENT-DIFF are calibrated using a NIST
Switched Relay Output
Traceable temperature and humidity controlled environmental chamber.
Factory selectable calibration can be achieved for elevations of 0, 1000,
Selectable Control Curves

PRESSURE
2000, 3000, 4000, 6000, 8000, and 10000 feet. Use reverse action in the
A/ENT-CTRL/DIFF unit to change the NO/NC switch action.
Applications:
All of the A/ENT series units come with a 2 year factory warranty. Economizer Control

OEMS

CURRENT
Product Specifications
Supply Voltage +24 to 36 VDC or 24 VAC +/- 10%
Supply Current 0.85 VA minimum
Output 10A Form 1C Relay w/ Sourced Supply Voltage
External Input (A/ENT-DIFF only) 4-20mA (0 to 50 BTU’s) from A/ENT-TRAN
Enthalpy Accuracy +/- 1 BTU @ 77oF (25oC)

AIR QUALITY
Long Term Stability Less than 2% RH Drift / 5 Years
Sensitivity 0.1% RH
Repeatability 0.5% RH
Hysteresis Less than 0.4% RH
Operating RH Range 0 to 95% RH (non-condensing)
Operating Temperature Range -40oF to 140oF (-40oC to 60oC)
Standard Elevation 1000’ above sea level (standard)
Environmental Compliance RoHS Compliant
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000152 Rev 2.pdf
RH-5
Dimensions
DISPLAYS

Enthalpy Controller
4.25"
(108 mm)
End View
Temp. Sensor in
Brass Snap Relative Humidity Sensor
TEMPERATURE

N/O N/C GND 24 4-20 Vout

1.37"
mA In
3.35"
(35 mm) (85 mm)
Enthalpy Controller
Model #: ACI/DIFF
Power: 24 VAC
Output: 10 A Form 1C Relay

Mounting Holes
RELATIVE HUMIDITY

Elevation Effect Chart


Feet Above Sea Level BTU Output Change(BTU’s)
0 29.3027 - 0.4044
250 29.4069 - 0.3002
500 29.5052 - 0.2019
750 29.6052 - 0.1019
1,000 29.7071 0.0000
1,500 29.9248 + 0.2177
2,000 30.134
PRESSURE

+ 0.4269
2,500 30.351 + 0.6439
3,000 30.5762 + 0.8691
4,000 31.0533 + 1.3462
5,000 31.5268 + 1.8197
6,000 32.0373 + 2.3302
10,000 34.4084 + 4.7013

Ordering Information
CURRENT

Elevation Curve Output Action


A/ENT-CTRL [ ] [ ] [ ]
or
A/ENT-DIFF ( ) 1,000’ Elevation (Standard) ( ) No Curve (For A/ENT-DIFF only) ( ) Direct Action
(A) 0’ Elevation (A) 28 BTU/lb and 75oF (Standard) (R) Reverse Action
(B) 2,000’ Elevation (B) 24 BTU/lb and 70oF
(C) 3,000’ Elevation (C) 23 BTU/lb and 67oF
AIR QUALITY

(D) 4,000’ Elevation (D) 21.5 BTU/lb and 63oF


(E) 6,000’ Elevation
(F) 8,000’ Elevation
(G) 10,000’ Elevation
CTRL: Mode #1 has been designed to switch at a fixed set point (standard; Curve A) 28 BTU/lb or 75oF., or is
field selectable, by 2 switches under the cover, selecting curves A, B, C or D.
ACCESSORIES

DIFF: Mode #2 has been designed to measure (typically) the Outdoor Enthalpy and, when used in conjunction
with the A/ENT-TRAN, determine if the local Enthalpy is greater than the remote (normal condition), and
switch if the local is less.
2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407

RH-6
Product Data Enthalpy

A CI

DISPLAYS
A/ENT-TRAN
4-20mA Enthalpy Transmitter

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/ENT-TRAN is a low cost Enthalpy transmitter that converts a
resistive type humidity sensor into a linear 2-wire, 4 to 20 mA output Attributes:
signal proportional to a scale of 0 to 50 BTU’s. The Advanced Ceramic 1/4” Spade Connectors
Technology overcomes the limitations of other resistance-based humidity
sensors that utilize water-soluble polymer coatings. This technology Conformally Coated PCB
enables these sensors to fully recover from condensation and enables the
sensor to maintain its accuracy over time. Despite its accuracy, the High Accuracy

RELATIVE HUMIDITY
Advanced Ceramic Technology sensor and related circuitry is economical.
Excellent Repeatability
Each A/ENT-TRAN is calibrated at 3 different points, using an NIST
Traceable temperature and humidity controlled environmental chamber. RoHs Compliant
Factory selectable calibration can be achieved for elevations of 0, 1000,
2000, 3000, 4000, 6000, 8000, and 10000 feet. Reverse Action makes the
slope negative, from 20 down to 4 mA. All of the A/ENT-TRAN Enthalpy
Transmitters come with a 2 year factory warranty. Applications:
Economizer Control

PRESSURE
OEM’s

CURRENT
Product Specifications
Supply Voltage +24 to 36 VDC
Supply Current 0.85 VA minimum
Enthalpy Measurement Range 0-50 BTU’s
Output Signal 2-wire, 4-20mA (0 to 50 BTU’s)
Accuracy +/- 1 BTU @ 77oF (25oC)

AIR QUALITY
Long Term Stability Less than 2% RH Drift / 5 Years
Repeatability 0.5% RH
Hysteresis Less than 0.4% RH
Sensitivity 0.1% RH
Standard Elevation 1000’ above sea level (standard)
Operating Temperature Range -40oF to 140oF (-40oC to 60oC)
Operating RH Range 0 to 100% RH (condensing)
Enclosure Flammability Rating UL94-5VA
ACCESSORIES

Enviroamental Compliance RoHS Compliant


Automation Components, Inc.
2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000107 Rev 7.pdf
RH-7
Dimensions
DISPLAYS

Enthalpy Controller
4.25"
(108 mm)
End View
Temp. Sensor in
Brass Snap Relative Humidity Sensor
+ -
TEMPERATURE

Vin 4-20
Out
3.35"
1.37" ACI (85 mm)
(35 mm)
Automation Components, Inc.

Enthalpy Transmitter
Model #: A/ENT-TRAN
Input: 24 to 36 VDC
Range: 0 to 50 BTU’s
Output: 4 to 20mA

Mounting Holes
RELATIVE HUMIDITY

Elevation Effect Chart


Feet Above Sea Level BTU Output Change(BTU’s)
0 29.3027 - 0.4044
250 29.4069 - 0.3002
500 29.5052 - 0.2019
750 29.6052 - 0.1019
1,000 29.7071 0.0000
1,500 29.9248 + 0.2177
2,000 30.134
PRESSURE

+ 0.4269
2,500 30.351 + 0.6439
3,000 30.5762 + 0.8691
4,000 31.0533 + 1.3462
5,000 31.5268 + 1.8197
6,000 32.0373 + 2.3302
10,000 34.4084 + 4.7013

Ordering Information
CURRENT

Elevation Output Slope


A/ENT-TRAN [ ] [ ]

( ) 1,000’ Elevation (Standard) ( ) Direct Acting / Positive Slope (Standard)


(A) 0’ Elevation (R) Reverse Acting / Negative Slope
(B) 2,000’ Elevation
(C) 3,000’ Elevation
AIR QUALITY

(D) 4,000’ Elevation


(E) 6,000’ Elevation
(F) 8,000’ Elevation
(G) 10,000’ Elevation
ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

RH-8
Product Data Air Pressure

A CI
A/LP Series

DISPLAYS
Low Differential
Pressure Transmitter

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/LP Series transmitters are a low cost alternative to the A/DP series
pressure transmitters. The A/LP Series is a 4-20 mA transmitter with uni- Attributes:
directional spans.  Optional Internal or
External Terminal blocks
These pressure transmitters incorporate a durable piezoresistive, silicon
micro-machined sensing element to enable very low-pressure ½” NPT Knockout (When
measurements. Integrated temperature compensation with offset and Cord Grip Removed)

RELATIVE HUMIDITY
span calibration extends the performance of these devices to provide
excellent long term reliability. Euro Housing Option w/
Cord Grip
The transmitters must be powered by a +24 to 36 VDC or 24VAC supply.
The electronics provide a two-wire, linear 4-20 mA current loop or an UL 94-V0 Rated Enclosure
optional 3-wire voltage output. The uni-directional spans range from 0-1”
to 0-10” of Water Column or 0-300 to 0-2500 Pascals. All units are
RoH’S Compliant
calibrated with a 4-20 mA output as standard. If a voltage output as
required, they must be ordered as such from the factory. The A/LP is now
available with a Cord Grip and ½” NPT Knockout when ordering the

PRESSURE
“Euro” Enclosure option. Applications:
Monitoring Building Static
All A/LP Series Transmitters come with a limited 2-year warranty. Pressure
Please contact ACI for more information regarding this product.
Leak Detection

Monitoring Filter Blockage

CURRENT
Product Specifications
Measuring flow when used
Supply Voltage +24 to 36 VDC / 24 VAC (+/-10%) in conjunction with a Pitot
Supply Current 23 mA minimum Tube or Orifice Plate
Output 2-wire, Linear 4 to 20mA DC Current or
3-wire, 1-5 or 2-10 VDC
Sensor Accuracy* +/-1.1% F.S.O.
Repeatablity +/- 0.3% F.S.O. nominal

AIR QUALITY
Operating Temperature Range -13 to 185oF (-25 to 85oC)
Compensated Temperature Range 32 to 122oF (0 to 50oC)
Full Scale Shift (0oC to 50oC) +/-2.0% F.S.O.
Media Dry air or inert non-conductive gases
Environmental Compliance RoHS-Directive 2002/95/EC
WEEE-Directive 2002/96/EC
* Accuracy includes linearity, hysteresis and repeatability
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000058 Rev 5.pdf
PR-1
DISPLAYS

Dimensions
All Dimensions are in Inches

Terminals Exposed Version Terminals Enclosed Version


*Add (E) Euro to your ordering information
Top View 0.25" Top View
0.25" (6.35 mm)
(6.35 mm)
TEMPERATURE

+
ACI
Ground
Output

ACI
1.677" 1.677" Automation Components, Inc.
(95 mm) (95 mm)
2305 Pleasant View Rd.
Automation Components, Inc.
Middleton, WI 53562
2305 Pleasant View Rd.
3.355" Ph: (608) 831-2585 3.355"
Middleton, WI 53562 Fax: (608) 831-7407
Ph: (608) 831-2585
(85 mm) (85 mm)
Fax: (608) 831-7407
Pressure Transmitter
Model: LP Series
RELATIVE HUMIDITY

Model: LP Series
Supply Voltage: 24 VAC / 24-36 VDC Supply Voltage: 24 VAC / 24-36 VDC 1.05"
27mm
HI LO HI LO

Ø0.190" Ø0.190"
(5 mm) (5 mm)
TYP. 3.750" TYP. 4.886"
(95 mm) (95 mm)
4.250"
5.538"
(108 mm)
(108 mm)

Front View Front View


PRESSURE

Ø0.3125" Ø0.3125"
0.125" 0.125"
(TYP.) (TYP.)
(3 mm) 1.357" (3 mm) 1.357"
0.839" 0.739" TYP. (34 mm) 0.839" 0.739" TYP. (34 mm)
(21 mm) (19 mm) (21 mm) (19 mm)

1.821" 1.821"
(35 mm) Ø0.188" (5 mm) (35 mm) Ø0.188" (5 mm)
2.603" Mounting Holes 2.603" Mounting Holes
(TYP.) (TYP.)
(51 mm) (51 mm)
CURRENT

Ordering Information (See Above)


Span Output *Scale *Enclosure
A/LP -[ ] -[ ] -[ ] -[ ]

(1) 0 to 1.0” (5) 1 to 5 VDC ( ) “ H20 (Standard) (E) Euro


AIR QUALITY

(2) 0 to 2.0” (10) 2 to 10 VDC (P) Pascals


(3) 0 to 3.0” or 0 to 300 pa (20) 4 to 20 mA
(4) 0 to 4.0”
(5) 0 to 5.0” or 0 to 500 pa
(10) 0 to 10.0” or 0 to 1000 pa
(16) 0 to 1600 pa
(25) 0 to 2500 pa
(Please Specify)
ACCESSORIES

Example: A/LP-1-20 or A/LP-3-20-E or A/LP-16-5-P

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

PR-2
Product Data Air Pressure

A CI

DISPLAYS
A/DP Series
Low Differential
Pressure Transmitter

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/DP series is a line of low differential pressure transmitters that are
capable of sensing full scale ranges down to 0.25” of water column. Each Attributes:
ACI pressure transmitter utilizes a high quality ceramic capacitive sensor Field Selectable Pressure
to provide long term stability and performance. Variable capacitance Ranges
sensors have a good signal to noise ratio and are not plagued by
temperature drift. Field Selectable Output
Signals

RELATIVE HUMIDITY
The transmitter electronics provide either a two-wire, linear 4 to 20 mA
or a three-wire, 0 to 5 or 0 to 10 VDC output signal. Accuracy is +/- 1% Accepts AC/DC Supply
of full scale over the compensated temperature range. The transmitter Voltages
may be powered by a regulated, +15-36 VDC or 24 VAC supply, and is
polarity sensitive. In addition to the requested span, each transmitter is User Friendly / Lowers
capable of being field adjusted to a maximum of three additional spans
Inventory
by resetting the internal jumpers. A slight zero offset may be needed.
This feature provides greater flexibility in the field. Commonly available
spans are 0 to 0.25”, -0.5 to 0.5”, 0 to 1”, 0 to 2.0”, and 0 to 5”.
Applications:

PRESSURE
When used in combination with an A/PT, A/SPT, or A/VPT style pitot Static Pressure Control in
tubes, flow can be measured and controlled in ducts. All A/DP low Rooms
differential pressure transmitters come factory calibrated with a 2 year
warranty. Leak Detection

Monitoring Filter Blockage

CURRENT
Product Specifications Pneumatic Control

Supply Voltage 250 Ohm Load: +15-36 VDC / 24VAC Variable Air Volume Systems
500 Ohm Load: +19-36 VDC / 24 VAC (VAV’s)
Output Ranges 2-wire, Linear 4 to 20mA DC Current or
3-wire, 0-5, 0-10 VDC, or 4-20mA
Response Time 15 msec - 63% full scale step
Position effect 2% Null shift from vertical to horizontal

AIR QUALITY
Transmitter Accuracy +/-1 of span
Operating Temperature Range -10 to 60oC (14 to 140oF)
Compensated Temperature Range 10 to 40oC (50 to 104oF)
Linearity +/- 0.5% of span
Pressure Fittings 1/4” barbed fitting (Brass)
Pressure Overload Span < 2” H2O
Positive Pressure 5X
Negative Pressure 3X
Span > 2” H2O
ACCESSORIES

Positive Pressure 5X Automation Components, Inc.


Negative Pressure 3X 2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000109 Rev 3.pdf
PR-3
DISPLAYS

Dimensions

0.533”
(4.6cm)

(4) 0.193” Mounting Holes


(0.5cm)
TEMPERATURE

(2) ¼” Brass Barbed Fittings


(0.6cm)

Pressure Transmitter 5.78”


Model: DP Series (14.7cm) LO
RELATIVE HUMIDITY

Input: 24 VAC/+15-36 VDC 5.25”


Range: -0.25 to +0.25” WC (13.3cm) HI
Output: 4 to 20 mA

3.120”
(7.9cm)
Lo (Front)
3.66”
(9.3cm)
HI
PRESSURE

2.250”
(5.7cm)

Ordering Information
CURRENT

Model# Factory Set SPAN Output


A /DP -[ ] -[ ] -[ ] Table of Jumper Selectable Ranges
for all DP Model# to the left
(1) +/- 1.0” (5) 0 to 5 VDC DP1 +/- 2.0” N/A N/A
(2) +/- 0.5” (10) 0 to 10 VDC DP2 +/- 0.3” N/A N/A
(3) +/- 0.25” (20) 4 to 20 mA DP3 +/- 0.5” N/A N/A
(4) 0 to 0.25” DP4 0 to 0.5” 0 to 0.4” 0 to 0.3”
AIR QUALITY

(5) 0 to 0.5” DP5 0 to 0.4” 0 to 0.3” 0 to 0.25”


(6) 0 to 1.0” DP6 0 to 0.8” 0 to 0.6” 0 to 0.5”
(7) 0 to 2.0” DP7 0 to 2.5” 0 to 1.5” 0 to 1.25”
(8) 0 to 3.0” DP8 0 to 5.0” 0 to 4.0” 0 to 2.5”
(9) 0 to 5.0” DP9 0 to 4.0” 0 to 3.0” 0 to 2.5”
(10) 0 to 10.0” DP10 0 to 8.0” 0 to 6.0” 0 to 5.0”
(11) +/- 5.0” DP11 +/- 2.5” N/A N/A
DP12 +/- 5.0” N/A N/A
ACCESSORIES

(12) +/- 10.0”

Example: A/DP-1-10 or A/DP-1-20 or A/DP-1-5


2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407

PR-4
Product Data Pitot Tubes

A CI

DISPLAYS
A/PT Series
A/SPT Series
“First in Sensor Quality”
A/VPT Series
Pitot Tubes

Product Description

TEMPERATURE
The A/PT is designed to sense the differential inlet pressure in the inlet
section of VAV and Fan Terminal Boxes. They can also be used to measure Applications:
the differential pressure at any other location in the main or branch duct  Used with Pressure Switches
systems. and Differential Pressure
Transmitters
The "H" port senses the overall pressure and the "L" port senses the static
pressure on the A/PT.
 Velocity Pressure

RELATIVE HUMIDITY
These sensors require a 7/8" diameter hole for insertion into the duct and
should be mounted horizontally to assure the accuracy of the velocity  Monitoring Building Static
readings. Two pilot holes should be used to attach the flange to the duct Pressures
with either rivets or sheet metal screws.
The A/SPT and A/VPT are aluminum pitot tubes that may be used to  Monitoring Differential
measure the static or velocity pressure in ducts. The A/SPT has a 4" long Pressures
insertion length and can be used to measure the static pressure in the duct.
The A/VPT has a 4" insertion length and a pointed tube that can be used
to measure the velocity pressure when mounted facing into the air stream.

PRESSURE
Please contact ACI for more information regarding any of these products.

CURRENT
Product Specifications
Connections A/PT 1/4” Nipples for 3/8” OD. Tubing
A/SPT, A/VPT 1/8” to 1/4” I.D. Tubing
Operating Temperature Range 40oF to 120oF (4oC to 49oC)
Sensing Lengths & Sensing Points 3 5/32” - One set
5 13/32” - Two sets
7 21/32” - Three sets

AIR QUALITY
9 29/32” - Four sets
Mounting Material Integral Flange with Gasket
A/PT - ABS/Polycarbonate (UL94-5V)
A/VPT - Aluminum
A/SPT - Aluminum
Recommended Air Flow A/PT = 200 fpm minimum
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000047 Rev 1.pdf
PR-5
Dimensions
ACI/PT
DISPLAYS

0.80

3 1/2” 0.70
(8.89cm)
0.60
H L
1 1/4”
3 5/32”(8.0cm)
5 13/32”(13.7cm)
(3.1cm) 0.50
FLOW
7 21/32”(19.4cm)
2 3/4”
9 29/32”(25.1cm) 0.40
TEMPERATURE

(6.9cm)

0.30

0.20

0.10
7/16” Push on Nipples for
1/4” I.D. Tubing
(0.4cm)
(0.6cm) 0
RELATIVE HUMIDITY

1000 2000 3000


VELOCITY -FEET PER MINUTE
A/PT 3 5/32"
A/PT 5 13/32"
A/PT 7 21/32" & A/PT 9 29/32"

ACI/SPT
PRESSURE

ACI/VPT
CURRENT

Ordering Information
Model#
[ ]
AIR QUALITY

A/PT 3 5/32”
A/PT 5 13/32"
A/PT 7 21/32”
A/PT 9 29/32”
A/SPT (Static)
A/VPT (Velocity)
ACCESSORIES

Example: A/PT or A/PT 9 29/32” or A/VPT

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

PR-6
Product Data Gage Pressure

ACI
A/GP Series

DISPLAYS
Gage Pressure Transducer

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/GP is a two-wire, 4-20 mA gage pressure transducer. These
units have been designed to provide excellent accuracy and reliability Attributes:
in commercial, industrial, and process control applications.  +/-1% FS Accuracy entire
operating Temp. range
The A/GP pressure transducers are compatible with a wide range of
gases and liquids. They are available in ranges from 0 to 15 PSIG up to
0 to 3000 PSIG. Other options and ranges may be available upon request  Laser-welded stainless steel
and might have a minimum order quantity. design (No O-Rings)

RELATIVE HUMIDITY
All units are accurate to +/- 0.5% or +/- 1% of full scale. The A/GP  Compatible with wide range
pressure transmitter offers a combined repeatability, hysteresis, and of gases and liquids
non-linear factor that is typically below +/- 0.15% of full scale. The A/GP
pressure transducers are both EMC compliant and Reverse Polarity
Protected.  CE compliant

The pressure port is a 1/4”-18 NPT Male fitting made of 304L stainless Applications:
steel. Each unit is approximately 2.60” inches long and weighs
approximately .206lbs (.093Kg). A 2’ shielded cable is supplied for  HVAC and Refrigeration
making all of the proper connections. All of the transducers may also be Equipment

PRESSURE
ordered mounted in an optional NEMA 4 rated enclosure.
 Pump and Compressor
Control

 Industrial Equipment

 Hydraulic Systems

CURRENT
Product Specifications
 Level Depth Instrumentation
Supply Voltage +8-30VDC
Output Signal 4 to 20mA  Process Control
Accuracy (Non-linearity, Hysteresis, 75 to 3000 psi: +/- 0.5% of FSO
Repeatability) 15 to 60 psi: +/- 1.00% of FSO
Thermal Error 75 to 3000 psi: +/- 0.5% of FSO
15 to 50 psi: +/- 1.00% of FSO

AIR QUALITY
Stability +/-1% FS
Operating Temp. Range -40 to 221oF (-40 to 105oC)
Response Time < 1ms
Burst Pressure 3X Full Scale
Proof Pressure 3X Full Scale
Process Fitting 1/4”-18NPT Male 304L Stainless Steel
Case 304L Stainless Steel
EMC Compliance 100 V/M
ACCESSORIES

Weight < 0.206 lbs. (0.093Kg)


Automation Components, Inc.
2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000047 Rev 2.pdf
PR-7
DISPLAYS

Dimensions
2.56" (65.02 mm)

1.03" (5.56 mm)


24" (609.6 mm)
0.71" (18.03 mm)
TEMPERATURE

0.157" (4.0 mm) Dia.


Thread Size
1/4"-18 NPT
0.875" (22.22 mm) Max.
0.866" (22.00 mm) Min.
RELATIVE HUMIDITY

3.35" (85.09 mm)


1.15" (29.21 mm)

5.00" (127.0 mm)


5.57" (141.48 mm)
6.27" (159.26 mm)

1/2" NPT Threads


PRESSURE

1/4"-18 NPT Threads

For 1/2" conduit


Remove plug
CURRENT

Ordering Information
Pressure Range Enclosure Option Output Signal
A/GP - [ ] -[ ] -[ ]

(15) 0-15 psig ( ) No NEMA 4 Enclosure (Std) (20) 4 to 20mA


(50) 0-50 psig (4) Mounted in NEMA 4 Enclosure(Optional)
(100) 0-100 psig
(200) 0-200 psig
AIR QUALITY

(300) 0-300 psig


(500) 0-500 psig
(1000) 0-1000 psig
(1500) 0-1500 psig
(2000) 0-2000 psig
(3000) 0-3000 psig

Example: A/GP-50-20 or A/GP-50-4-20 or A/GP-50-20 or A/GP3000-4-20


ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX (608) 831-7407

PR-8
Product Data Wet to Wet

ACI
A/629 Series

DISPLAYS
Wet to Wet Differential
Pressure Transmitter

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/629 Differential Pressure Transmitter monitors differential
pressure of air and compatible gases and liquids with 0.5% accuracy. Attributes:
The design employs dual pressure sensors converting pressure changes  Gas and liquid Compatible
into a standard 4-20 mA output signal for two wire circuits. Small
internal volume and minimum moving parts result in exceptional  Optional 3 way valve
response and reliability. package

RELATIVE HUMIDITY
Terminal block, zero and span adjustments are easily accessed under the  NEMA 4X (IP 66)
top cover. The Series 629 Wet to Wet Differential Pressure Transmitter is construction
designed to meet NEMA 4X (IP 66) construction.
Applications:
The A/629 series transducers come with a 2 year warranty.
Monitor Differential
Pressures Across:

 Flow Elements

PRESSURE
 Heat exchangers

 Filters

 Pumps

 Coils

CURRENT
Product Specifications
Supply Voltage +13 to 30 VDC
Output Signal 4 to 20 mA. Optional 0-5, 0-10 VDC
Accuracy +/- 0.5% F.S.
Loop Resistance 0-1300 ohms maximum for current output.
Voltage outputs, min load resistance: 2000 Ohms
Response Time 50 msec.

AIR QUALITY
Operating Temp. Range 0 to 200°F (-18 to 93°C)
Compensated Temp. Limits 0 to 175°F (-18 to 79°C)
Electrical Connections 1/2” NPT conduit Terminal Block
Process Connections 1/4” Female NPT
Wetted Material Connections 316, 316L Stainless Steel
Agency Approvals CE
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000156 rev 1.pdf
PR-9
DISPLAYS

Dimensions
Optional LED Display

Top View
43/64
[17.07] 1-11/32
[34.13]

3-9/32
TEMPERATURE

[83.34]
LIQUID TIGHT FITTING 3 Valve Manifold
CORD DIAMETER RANGE:
.200 TO .350 [5.06 TO 8.89] 6-29/32 Ø13/64 [5.64] DIA
[175.42] MOUNTING HOLES
9/32 2.400 TYP 4 PLACES
[7.14] [60.69]
1-5/8
[41.28]
RELATIVE HUMIDITY

5-25/32 [146.84]
1/4 NPT FEMALE FITTING 5-7/16
[138.11]
6-1/64
[152.81]

2.400 2-1/16
[60.69] [52.39]
3
[76.20]
PRESSURE

Pressure Limits
Range Working* Over
Model Number (psid) BLEED SCREW
Pressure (psid) Pressure (psi)
A/629-10 Series 10 20 100
A/629-25 Series 25 50 250
A/629-50 Series 50 100 250
A/629-100 Series 100 200 500
CURRENT

* Pressures exceeding the working pressure limit may cause a calibration


shift of up to ±3% of full scale.

Ordering Information
Pressure Ranges Output 3-Valve Manifold (Optional) LED Display (Optional)
A/629 -[ ] -[ ] -[ ] -[ ]
AIR QUALITY

(10) 0 to 10 psid* (5) 0 to 5 VDC* ( ) No Manifold (Standard) ( ) No LED Display (Standard)


(25) 0 to 25 psid* (10) 0 to 10 VDC* (3V) Assembled on (D) with LED Display*
(50) 0 to 50 psid (20) 4 to 20 mA 3 Valve Manifold
(100) 0 to 100 psid

*Non-stocked options. Please contact ACI for estimated lead time.


ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

PR-10
Product Data Wet to Wet

A CI
A/WP Series

DISPLAYS
Wet to Wet Differential
Pressure Transducers

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/WP Series is a two-wire wet to wet differential pressure
transducer. The A/WP is ideally suited for use with any harsh media, Attributes:
wet or dry, that is compatible with 17-4 PH and 300 series stainless steel. Gas and Liquid Compatible
The A/WP may be powered with a 9 to 30 VDC supply voltage and
outputs a linear 4 to 20 mA, 0 to 5, or 0 to 10 VDC output signal. To Fast Response
ensure an accurate linear analog output, the WP contains circuitry to
provide signal conditioning, reverse polarity protection, and temperature
Available with pre-assembled

RELATIVE HUMIDITY
compensation as an integral part of the device.
3-Valve Manifold Option
Built for remote installation, the A/WP is a rugged unit, housed in a
splash and dust proof NEMA 4/IP65 rated stainless steel enclosure. NEMA 4/IP65 Rating
Both of the input pressure ports will accept a 1/4” NPT Male fitting. Each
unit is approximately 3.01” long x 3.05” tall x 2.15” in depth and weighs
approximately 0.75 lbs. (.34Kg)
Applications:
The A/WP pressure transducers are available in ranges from 0 to 1 PSID Chiller and Boiler Systems
all the way up to 0 to 100 PSID. Bi-Directional ranges are available.
Optional pressure snubbers are also avilable upon request. Pumps and Compressors

PRESSURE
(part # A/SS-4-SA-EW)
Environmental Control
All of the A/WP Series transducers have a 2 year warranty. Systems

Level Monitoring

Refrigerant Systems

CURRENT
Product Specifications
Supply Voltage 4-20mA Min: 9 + 0.02 x (Load + Line)
Max: 30+ 0-004 x (Load + Line)
0 to 5 VDC +9 to 30 VDC
0 to 10 VDC +13 to 30 VDC
Analog Output Signal 4 to 20mA or 0 to 10 VDC
Accuracy +/-0.25% of FSO @ Constant Temp

AIR QUALITY
Long Term Stability +/-0.50% FS / 1 Year
External Load 4-20 mA : 1K Ohms Max.
0 to 5 & 0 to 10 VDC: > 5K Ohms Min.
Output Impedance 100 Ohms
Compensated Temperature Range -1 to 65oC (30 to 150oF)
Thermal Effects +/- 1.8% / 50oC(+/-2% / 100oF)
Operating Temperature Range -18 to 80oC (0 to 175oF)
Max. Working Pressure 250 PSIG
ACCESSORIES

Response Time 30 to 50 msecs.


Agency Approvals CE Automation Components, Inc.
2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C00000108Rev1.pdf
PR-11
DISPLAYS

Dimensions
Top V iew Side View 3.01”
2.15” (7.6cm)
(5.4cm)

PRESSURE TRANSMITTER
MODEL ACI /WP
TEMPERATURE

SERIAL #: 997826
RANGE
: 0 to 100 PSI D
EXCIT.: 24 VDC
OUTPUT: 4-20 mA
OP TIONS :

¼” (0.6cm) ¼” (0.6cm)
End View -18 NPT -18 NPT
Internal (Low
Internal (High
RELATIVE HUMIDITY

Pressure Port) Pressure Port)


Bleed Scr ews

3-Valve Manifold Assembly


3.05”
(7.7cm)
½” Conduit
Knockout
1.00”
V3
(2.5cm)
5.63"
Mounting (14.3cm)
Bracket V1 V2 6.25"
5.00"
MODEL 230 (12.7cm) (15.8cm)
DIFFERENTIAL PRESSURE
PRESSURE

TRANSDUCER
Shunt Valves

4X TYP 0.52" (1.3cm)


0.16"
Shut
(0.4cm)
off
Valves 2.13"
0.38" (5.4cm)
3.25" 0.31"
(0.9cm)
(8.2cm) 4.00" (0.7cm)
7.05" (10.1cm)
High Process Low Process (17.9cm)
Connection 1/4" NPT
(0.6cm) Connection 1/4" NPT
CURRENT

(0.6cm)

Unidirectional Spans Bidirctional Spans


Pressure Range Proof Pressure Proof Pressure Pressure Range Proof Pressure Proof Pressure
(PSID) High Side Low Side (PSID) High Side Low Side
(PSI) (PSI) (PSI) (PSI)
0 to 1 20 2.5 +/-1 40 2.5
0 to 5 100 12.5 +/-5 100 12.5
0 to 10 100 25 +/-10 200 25
0 to 25 250 62.5 +/-25 250 62.5
AIR QUALITY

0 to 50 250 125 +/-50 250 125


0 to 100 250 250 n/a n/a n/a

Ordering Information Pressure Ranges Output 3-Valve Manifold (Optional)


A/WP [ ] -[ ] -[ ] -[ ]

( ) Unidirectional Span (1) 0 to 1 psid or +/-1 PSID (5) 0 to 5 VDC


(Standard) (5) 0 to 5 psid or +/-5 PSID (10) 0 to 10 VDC ( ) No Manifold (Standard)
(B) Bi-Directional Span (10) 0 to 10 psid or +/-10 PSID (20) 4 to 20 mA (3) Assembled on
ACCESSORIES

(25) 0 to 25 psid or +/-25 PSID 3 Valve Manifold


(50) 0 to 50 psid or +/-50 PSID
(100) 0 to 100 psid Note: +/-100 PSID NOT available
2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407

PR-12
Product Data Pressure Switches

ACI

DISPLAYS
A/AFS-222
A/AFS-262
Pressure Switches
“First in Sensor Quality”

Product Description

TEMPERATURE
The A/AFS Series differential pressure switches are general purpose
proving switches designed for both HVAC and Energy Management Attributes:
applications. These pressure switches can be used to sense positive, Field Adjustable Setpoints
negative, or differential air pressures.
 2 Year Warranty
The A/AFS-222 has a field adjustable operating range of 0.07" to 12.0"
wc The A/AFS-222 has a field adjustable setpoint range of 0.05" +/- 0.02"
 RoHS compliant

RELATIVE HUMIDITY
to 12" wc with a field adjustable release range of 0.04" to 11.2" of w.c..

The A/AFS-262 has a field adjustable operating range of 0.07" to 2.0" Applications:
wc. It also has a setpoint range of 0.05" +/- 0.02" to 2" wc with a field  General Purpose Proving
adjustable "release range" of 0.04" to 1.9" w.c. The sampling connections Switch
are located on each side of the diaghram.

Both the A/AFS-222 and A/AFS-262 will accept a 0.25" O.D. rigid metallic  Monitor Flow
tubing via the integral compression ferrule and nut. The enclosure cover
guards against accidental contact with the live switch terminal screws and  Monitor Filter Blockage
the setpoint adjusting screw. Both units also contain a 1/2" conduit

PRESSURE
knockout in the cover of the enclosure as well as a diagraphm, calibration May be used to sense:
spring, and a snap acting SPDT switch. positive air pressure
negative air pressure
differential pressure

CURRENT
Product Specifications
Input Pressure Range AFS-222 (0.07” to 12” w.c.)
AFS-262 (0.07” to 2” w.c.)
Output 1 set SPDT Contacts
Operating Temperature Range -40 to 180oF (-40 to 82oC)
Electrical Rating 300 VA pilot duty @ 115 to 277 VAC
15 amps non-inductive to 277 VAC, 60 HZ

AIR QUALITY
Maximum Pressure 0.5 psi (0.03 Bar)
Switch Differential increasing from 0.02” +/- 0.01”wc to Approx
0.8” wc @ Maximum setpoint.
Setpoint +0.08” wc @ Maximum Setpoint
Measured Media Air, or combustion by-products that will not
degrade silicon
Mounting Direction Any Vertical Plane
Agency Approval UL, FM, CSA, CE
ACCESSORIES

Shipping Weight 1.2 lbs


Environmental Compliance RoHS Compliant Automation Components, Inc.
2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000122Rev 2.pdf
PR-13
DISPLAYS

Dimensions

Side View
6.25”
(15.8 cm)
TEMPERATURE

1.44”
(3.6 cm)

3.18”
(8.0 cm)

1.38” 0.71”
(3.5 cm) (1.8 cm)
RELATIVE HUMIDITY

0.5”
(1.2 cm)
0.44”
(1.1 cm)

3.34”

End View (8.4 cm)


2.313”
(5.8 cm)
PRESSURE

Low Pressure Inlet

High Pressure Inlet


CURRENT

4.46”
(11.3 cm)
AIR QUALITY

Ordering Information
Pressure Switch
A /AFS [ ]

222
262
ACCESSORIES

Example: A / AFS-222 or A /AFS-262

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

PR-14
Product Data Pressure Switches

A CI

DISPLAYS
A/AFS-460
Pressure Switches

“First in Sensor Quality”

Product Description

TEMPERATURE
The A/AFS-460 series differential pressure switches are general purpose
proving switches designed to require a manual operator reset following Attributes:
actuation. These pressure switches can be used to sense either positive, Field Adjustable Setpoints
negative, or differential air pressure in HVAC and Energy Management
applications which require operator interface.  2 Year Warranty
The A/AFS-460 has an input operating range of 0.40” to 12.0” w.c. with
 RoHS compliant

RELATIVE HUMIDITY
an adjustable setpoint range of 0.40” +/- 0.06” to 12” of w.c.. Each unit
contains a diaghram, calibration spring, and a snap-acting SPST-NC
(Manual Reset) switch. Applications:
 General Purpose Proving
The sampling connections are located on each side of the diaghram. They Switch
will accept a 0.25” O.D. rigid metallic tubing via the integral compression
ferrule and nut. The enclosure cover guards against accidental contact with
the “live switch” terminal screws and the setpoint adjustment screw. The  Monitor Flow
A/AFS-460 also contains a 1/2” conduit knockout in the cover of the
enclosure. Other options may be available upon request.  Monitor Filter Blockage

PRESSURE
All of the A/AFS-460 Series differential pressure switches come with a two May be used to sense:
year factory warranty. Please contact ACI for more information regarding positive air pressure
the A/AFS-460 differential pressure switches. negative air pressure
differential pressure

CURRENT
Product Specifications
Input Pressure Range AFS-460 (0.40” to 12” w.c.)
Output SPST -NC Contacts (Manual Reset)
Operating Temperature Range -40 to 180oF (-40 to 82oC)
Electrical Rating 300 VA pilot duty @ 115 to 277 VAC
15 amps non-inductive to 277 VAC, 60 HZ
Maximum Pressure 0.5 psi (0.03 Bar)

AIR QUALITY
Switch Differential increasing from 0.02” +/- 0.01”wc to Approx
0.8” wc @ Maximum setpoint.
Setpoint +0.08” wc @ Maximum Setpoint
Measured Media Air, or combustion by-products that will not
degrade silicon
Mounting Direction Any Vertical Plane
Agency Approval UL, FM, CSA, CE
Shipping Weight 1.2 lbs
ACCESSORIES

Environmental Compliance RoHS Compliant


Automation Components, Inc.
2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000160 Rev 1.pdf
PR-15
DISPLAYS

Dimensions

Side View
6.25”
(15.8 cm)
TEMPERATURE

1.44”
(3.6 cm)

3.18”
(8.0 cm)

1.38” 0.71”
(3.5 cm) (1.8 cm)
RELATIVE HUMIDITY

0.5”
(1.2 cm)
0.44”
(1.1 cm)

3.34”

End View (8.4 cm)


2.313”
(5.8 cm)
PRESSURE

Low Pressure Inlet

High Pressure Inlet


CURRENT

4.46”
(11.3 cm)
AIR QUALITY

Ordering Information
Pressure Switch
A /AFS-460
ACCESSORIES

Example: A/AFS-460

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

PR-16
Product
Product Data
Data Current
Current

A CI
A/CS Series

DISPLAYS
A/CSX Series
Solid-Core Fixed
Current “Status” Switches
“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/CS and A/CSX series current switches are available in a solid-core
with either Normally-Open (N/O) or Normally-Closed (N/C) output Attributes:
configurations. All of these sensors will have a solid-state output with a ”Go/NoGo” Status Switch
fixed trip point (setpoint). These current switches are ideal for providing
status information on any type of AC current using equipment. The A/CS Integral Din-rail mounting
and A/CSX current switches are accurate, reliable, easy to install, and require
less servicing than differential pressure switches, flow switches, and paddle flange

RELATIVE HUMIDITY
wheels.
Rated up to 250 Amps
These current switches should be used in applications in which a
“Go/No Go” current switch is required. A change in the operating current Limited 5 year warranty
may indicate mechanical failure or that the unit has been turned off.
UL94-5VB
The A/CS and A/CSX series current switches can be used to monitor devices
with a maximum continuous operating current of up to 250 Amps. These (enclosure rating)
current switches will not need to be externally powered, since the power for
the switch is induced from the conductor being monitored. Another great LED Indication
feature of the A/CS and A/CSX series current switches is that they include a

PRESSURE
Red “Status” LED that will indicate whether the current is above or below
the fixed trip point. Applications:
Monitoring Fans, pumps,
and other electrical
equipment for status

Rated for industrial use

CURRENT
Product
Product Specifications
Specifications
Sensor Power Induced from monitored conductor
Amperage Rating 0 to 250 Amps continuous
Operating Frequency 40 to 1 kHz
Max. Sensing Current Voltage 600VAC
Isolation Voltage 2,200 VAC
Output Switch Rating A/CS (N/O): 0.3A @ 200 VAC/VDC

AIR QUALITY
A/CSX (N/C): 0.15A @ 300 VAC/VDC
Status LED Indication Red LED - Above Trip Point
Aperture (Hole) Size 0.75”, Accepts up to 350 MCM Cables
DIN Rail Size 35mm
Unit Weight 0.21 lbs
Operating Temperature Range -15 to 40oC (5 to 104oF)
Operating Humidity Range 0 to 95% RH, non-condensing
Note: DO NOT use the LED’s to indicate whether the sensors have power applied to them.
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
c0000001rev11.pdf
CU-1
Dimensions
DISPLAYS

Solid-Core
TEMPERATURE

0.78" Dia.
(20 mm)

2.27"
(58 mm)
0.14" 0.21" Dia. TYP.
(4 mm) ACI A/CS
Automation Components, Inc.
(5 mm)
Middleton, WI
RELATIVE HUMIDITY

0.98"
(25 mm)

1.38"
(35 mm) 0.40"
(10 mm)
2.84"
(72 mm) L to CL
C

3.38"
(86 mm)
PRESSURE

C US
LISTED
IND.CONT.EQ.
3JHX
CURRENT

Ordering Information
AIR QUALITY

ACI Model # Description Fixed Trip Point Output Switch Rating


A/CS Solid-Core Current Switch, N/O, 0-250A 0.50 Amps 0.30A @ 200 VAC/VDC
A/CS-L Solid-Core Current Switch, N/O, 0-250A 0.20 Amps 0.30A @ 200 VAC/VDC
A/CSX Solid-Core Current Switch, N/C, 0-250A 1.00 Amps 0.15A @ 300 VAC/VDC
A/CSX-L Solid-Core Current Switch, N/C, 0-250A 0.50 Amps 0.15A @ 300 VAC/VDC
ACCESSORIES

! Warning: Not intended to be used in Life & Safety Applications or for use in any hazardous locations.

CU-2
Product
Product Data
Data Current
Current

ACI
A/SCS Series

DISPLAYS
Split-Core Fixed Current
“Status” Switches

“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/SCS and A/SCSX series current switches are available in a split-core
with either Normally-Open (N/O) or Normally-Closed (N/C) output Attributes:
configurations. All of these sensors will have a solid-state output with a Split-Core design is suited for
fixed trip point (setpoint). These current switches are ideal for providing
status information on any type of AC current using equipment. Both the retrofit applications
A/SCS and A/SCSX series current switches are an excellent choice for
retrofit or existing installations, since you will not have to power down the Integral Din-rail mounting
unit and disconnect any wires during the installation process. The A/SCS flange

RELATIVE HUMIDITY
and A/SCSX current switches are accurate, reliable, easy to install, and
require less servicing than differential pressure switches, flow switches, and
paddle wheels. Limited 5 year warranty
These current switches should be used in applications in which a UL94-5VB
“Go/No Go” current switch is required. The “Go/No Go” Current switches
should be used to monitor the “on/off” status of any equipment that uses (enclosure rating)
AC current.
LED Indication
The A/SCS and A/SCSX series current switches can be used to monitor
devices with a maximum continuous operating current of up to 250 Amps
depending on the model number ordered. These current switches will not Models rated to 200 and

PRESSURE
need to be externally powered since the power for the switch is induced 250 amps
from the conductor being monitored. Another great feature of the A/SCS
and A/SCSX series current switches is that they include a Red “Status”
LED that will indicate whether the current is above the fixed trip point.
Applications:
Monitoring fans, pumps and
other electrical equipment
for status

CURRENT
Product
Product Specifications
Specifications
Rated for industrial use
Sensor Power Induced from monitored conductor
Amperage Rating See ordering info on back
Operating Frequency 40 to 1 kHz
Isolation Voltage 2,200 VAC
Max. Sensing Current Voltage 600 VAC
Output Switch Rating A/SCS (N/O): 0.3A @ 200 VAC/VDC

AIR QUALITY
A/SCSX (N/C): 0.15A @ 300 VAC/VDC
Status LED Indication Red LED - Above Trip Point
Aperture (Hole) Size 0.75”, Accepts up to 350 MCM Cables
DIN Rail Size 35mm
Unit Weight 0.21 lbs
Operating Temperature Range -15 to 40oC (5 to 104oF)
Operating Humidity Range 0 to 95% RH, non-condensing
Note: DO NOT use the LED’s to indicate whether the sensors have power applied to them.
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000002 Rev 10.pdf
CU-3
Dimensions
DISPLAYS

Split-Core

ACI A/SCS
Automation Components, Inc.
Middleton, WI
TEMPERATURE

2.70"
(69 mm) 0.76"
(19 mm)

0.14" 0.22" Dia. TYP.


(4 mm) (6 mm)
0.74"
(19 mm) 1.08"
(27 mm)
RELATIVE HUMIDITY

1.38"
(35 mm) 0.50"
(13 mm)
2.84"
(72 mm) L to CL
C

3.33"
(85 mm)
PRESSURE

C US
LISTED
CURRENT

IND.CONT.EQ.
3JHX
AIR QUALITY

Ordering Information
ACI Model # Description Fixed Trip Point Output Switch Rating
A/SCS Split-Core Current Switch, N/O, 0-200A 2.50 Amps 0.30A @ 200 VAC/VDC
A/SCS-L Split-Core Current Switch, N/O, 0-200A 1.50 Amps 0.30A @ 200 VAC/VDC
A/SCSX Split-Core Current Switch, N/C, 0-250A 2.50 Amps 0.15A @ 300 VAC/VDC
ACCESSORIES

! Warning: Not intended to be used in Life & Safety Applications or for use in any hazardous locations.

CU-4
Product
Product Data
Data Current
Current

ACI
A/ACS Series

DISPLAYS
Solid-Core Adjustable Current
“Status” Switches

“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/ACS and A/ACSX series current switches are available in a solid-core
with either Normally-Open (N/O) or Normally-Closed (N/C) output Attributes:
configurations. All of these sensors will have a solid-state output with an Red and Green status LED’s
adjustable trip point (setpoint). These current switches are ideal for
providing status information on any type of AC current using equipment. Integral Din-rail mounting
These current switches should be used in applications where a current flange

RELATIVE HUMIDITY
switch with an adjustable trip point is required. A change in the operating
current may indicate motor failure, belt loss/slippage, or mechanical failure. Rated up to 250 Amps
Any time one of these events occurs, the current can significantly increase
or decrease, thus tripping the sensor, and notifying the Building Management Limited 5 year warranty
System of an alarm condition.
UL94-5VB
The A/ACS and A/ACSX series current switches can be used to monitor
devices with a maximum continuous operating current of up to 250 Amps. (enclosure rating)
These current switches will not need to be externally powered, since the
power for the switch is induced from the conductor being monitored. Applications:
Another great feature of the A/ACS and A/ACSX series current switches is Monitoring overloads,

PRESSURE
that they include a Red and Green LED that will indicate the “Status” of the underloads and normal
switch contacts. operating conditions

Monitoring belt loss or


slippage

Monitoring Filter Status

CURRENT
Product
Product Specifications
Specifications
Rated for industrial use
Sensor Power Induced from monitored conductor
Amperage Rating 0 to 250 Amps continuous
Operating Frequency 40 to 1 kHz
Isolation Voltage 2,200 VAC
Max. Sensing Current Voltage 600 VAC
Output Switch Rating A/ACS (N/O): 0.3A @ 200 VAC/VDC

AIR QUALITY
A/ACSX (N/C): 0.15A @ 300 VAC/VDC
Status LED Indication Red LED - Above Trip Point
Green LED - Below Trip Point
Aperture (Hole) Size 0.75”, Accepts up to 350 MCM Cables
DIN Rail Size 35mm
Unit Weight 0.21 lbs
Operating Temperature Range -15 to 40oC (5 to 104oF)
Operating Humidity Range 0 to 95% RH, non-condensing
ACCESSORIES

Hysteresis (Dead Band) 10% Setpoint, Typical Automation Components, Inc.


Note: DO NOT use the LED’s to indicate whether the sensors have power applied to them. 2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000003 Rev 10.pdf
CU-5
Dimensions
DISPLAYS

Solid-Core
TEMPERATURE

0.78" Dia.
(20 mm)

2.27"
(58 mm)
0.14" 0.21" Dia. TYP.
(4 mm) ACI A/CS
(5 mm)
RELATIVE HUMIDITY

Automation Components, Inc.


Middleton, WI

0.98"
(25 mm)

1.38"
(35 mm) 0.40"
(10 mm)
2.84"
(72 mm) L to CL
C

3.38"
(86 mm)
PRESSURE

C US
LISTED
CURRENT

IND.CONT.EQ.
3JHX

Ordering Information
ACI Model # Description Adjustable Output Switch Rating
AIR QUALITY

Trip Point
A/ACS Solid-Core, Current Switch, N/O, 0-250A 1.0-250 Amps 0.30A @ 200 VAC/VDC
A/ACS-L Solid-Core Current Switch, N/O, 0-250A 0.50-250 Amps 0.30A @ 200 VAC/VDC
A/ACSX Solid-Core Current Switch, N/C, 0-250A 1.0-250 Amps 0.15A @ 300 VAC/VDC
ACCESSORIES

! Warning: Not intended to be used in Life & Safety Applications or for use in any hazardous locations.

CU-6
Product
Product Data
Data Current

ACI
A/ASCS Series

DISPLAYS
Split-Core Adjustable Current
“Status” Switches

“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/ASCS and A/ASCSX series current switches are available in a
split-core with either Normally-Open (N/O) or Normally-Closed (N/C) Attributes:
output configurations. All of these sensors will have a solid-state output Split-Core design is suited for
with an adjustable trip point (setpoint). These current switches are ideal for retrofit applications
providing status information on any type of AC current using equipment.
Red and Green status LED’s
These current switches should be used in applications in which a current

RELATIVE HUMIDITY
switch with adjustable trip point is required. A change in the operating
current may indicate motor failure, belt loss/slippage, or mechanical failure. Integral Din-rail mounting
Any time one of these events occurs, the current can significantly increase flange
or decrease, thus tripping the sensor, and notifying the Building Management
System of an alarm condition. Models rated to 200 and
250 Amps
The A/ASCS and A/ASCSX series current switches can be used to monitor
devices with a maximum continuous operating current of 200 to 250 Amps
depending on the model. These current switches will not need to be Limited 5 year warranty
externally powered, since the power for the switch is induced from the
conductor being monitored. Another great feature of the A/ASCS and UL94-5VB

PRESSURE
A/ASCSX series current switches is that they include a Red and Green (enclosure rating)
LED that will indicate the “Status” of the switch contacts.
Applications:
Monitoring overload,
underloads, and normal
operating conditions

CURRENT
Product Monitoring belt loss/ slippage
Product Specifications
Specifications
Sensor Power Induced from monitored conductor Monitoring Filter Status
Amperage Rating See Ordering Info on Back
Operating Frequency 40 to 1 kHz Rated for industrial use
Isolation Voltage 2,200 VAC
Max. Sensing Current Voltage 600 VAC
Output Switch Rating A/ASCS (N/O): 0.3A @ 200 VAC/VDC

AIR QUALITY
A/ASCSX (N/C): 0.15A @ 300 VAC/VDC
Status LED Indication Red LED - Above Trip Point
Green LED - Below Trip Point
Aperture (Hole) Size 0.75”, Accepts up to 350 MCM Cables
DIN Rail Size 35mm
Unit Weight 0.21 lbs
Operating Temperature Range -15 to 40oC (5 to 104oF)
Operating Humidity Range 0 to 95% RH, non-condensing
ACCESSORIES

Hysteresis (Dead Band) 10% Setpoint, Typical


Automation Components, Inc.
Note: DO NOT use the LED’s to indicate whether the sensors have power applied to them. 2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000004 Rev 9.pdf
CU-7
DISPLAYS

Dimensions
Split-Core

ACI
TEMPERATURE

A/SCS
Automation Components, Inc.
Middleton, WI

2.70"
(69 mm) 0.76"
(19 mm)

0.14" 0.22" Dia. TYP.


(4 mm) (6 mm)
RELATIVE HUMIDITY

0.74"
(19 mm) 1.08"
(27 mm)

1.38"
(35 mm) 0.50"
(13 mm)
2.84"
(72 mm) L to CL
C

3.33"
(85 mm)
PRESSURE
CURRENT

C US
LISTED
IND.CONT.EQ.
3JHX

Ordering Information
AIR QUALITY

ACI Model # Description Adjustable Output Switch Rating


Trip Point
A/ASCS Split-Core, Current Switch, N/O, 0-200A 3.00-200 Amps 0.30A @ 200 VAC/VDC
A/ASCS-L Split-Core Current Switch, N/O, 0-200A 2.00-200 Amps 0.30A @ 200 VAC/VDC
A/ASCSX Split-Core Current Switch, N/C, 0-250A 3.00-250 Amps 0.15A @ 300 VAC/VDC
A/ASCSX-L Split-Core Current Switch, N/C, 0-250A 2.50-250 Amps 0.15A @ 300 VAC/VDC
ACCESSORIES

! Warning: Not intended to be used in Life & Safety Applications or for use in any hazardous locations.

CU-8
Product
Product Data
Data Current
Current

ACI

DISPLAYS
A/CTA Series
Solid-Core 4-20 mA Output
“First in Sensor Quality” Current Sensor

Product
Product Description
Description

TEMPERATURE
The A/CTA Series current sensors monitor the current flowing to electrical
equipment or buildings. The magnitude of this current is then converted into Attributes:
a linear and proportional 4 to 20 mA output signal, which can be monitored Integral 35mm Din-rail
by your Building Management, DDC, or PLC controller. The A/CTA Series mounting flange
current sensors are available in either an Average or True RMS output
version. All of these sensors have jumper selectable input ranges except for
the 0 to 5 Amp input range on the A/CTA-05 series sensors. Rated up to 250 Amps

RELATIVE HUMIDITY
The A/CTA series current sensors are fast acting and extremely accurate Limited 5 year warranty
from 1 to 100% of the Full Scale Output. All of the A/CTA series
current sensors are factory calibrated using an NIST Traceable standard and True RMS Versions available
shipped with the jumper placed in the largest jumper selectable range. (VFD models)
In applications where the maximum current is larger than 250 Amps, ACI
recommends the use of a traditional ratio:5 (5A) current transformer and the High Accuracy
A/CTA-5 for best results. The A/CTA must be externally powered using a
+12 to 30 VDC power supply. UL94-5VB
(enclosure rating)

PRESSURE
Applications:
Load trending Equipment
(current monitoring)

Monitoring Building Loads

CURRENT
Product
Product Specifications
Specifications
Monitoring VFD Drives
Sensor Supply Voltage (Vs) +12 to 30 VDC
Amperage Rating 0-250 Amps (See Ordering Information) Rated for industrial use
Supply Current 36 mA max.
Output 4-20mA, 2-wire Loop Powered
Accuracy (from 1-100% of FSO) A/CTA: +/- 0.5%
A/CTA-VFD: +/- 0.5%

AIR QUALITY
Maximum Load Resistance A/CTA: 700 Ohms @ 24VDC (Vs-9)/0.02-40.2
A/CTA-VFD: 650 Ohms @ 24VDC (Vs-10)/0.02-40.2
Response Time A/CTA: < 75mS
A/CTA-VFD: <200mS
Operating Frequency Range 30 to 1 kHz
Isolation Voltage 2,200 VAC
Max. Sensing Current Voltage 600 VAC
Aperture (Hole) Size 0.75”, Accepts up to 350 MCM Cables
ACCESSORIES

Operating Temp Range A/CTA -15 to 40oC (5 to 104oF)


o o
A/CTA-VFD 0 to 40 C (32 to 104 F) Automation Components, Inc.
Operating Humidity Range 0 to 95% RH, non-condensing 2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
c0000005rev12.pdf
CU-9
Dimensions
DISPLAYS

Solid-Core

0.78" Dia.
TEMPERATURE

(20 mm)

2.27"
(58 mm)
0.14" 0.21" Dia. TYP.
(4 mm) ACI A/CS
Automation Components, Inc.
(5 mm)
Middleton, WI

0.98"
(25 mm)
RELATIVE HUMIDITY

1.38"
(35 mm) 0.40"
(10 mm)
2.84"
(72 mm) L to CL
C

3.38"
(86 mm)
PRESSURE

C US
LISTED
IND.CONT.EQ.
3JHX
CURRENT

Ordering Information
AIR QUALITY

ACI Model # Description Jumper Selectable Range CE Compliant


A/CTA-5 Loop Powered, Solid-Core, 4-20 mA Average Output 0-5 Amps (Not Selectable) Yes
A/CTA-50 Loop Powered, Solid-Core, 4-20 mA Average Output 0-10, 0-20, 0-50 Amps Yes
A/CTA-250 Loop Powered, Solid-Core, 4-20 mA Average Output 0-100, 0-200, 0-250 Amps Yes
A/CTA-5-VFD Loop Powered, Solid-Core, True RMS, 4-20 mA Output ** 0-5 Amps (Not Selectable) No
A/CTA-50-VFD Loop Powered, Solid-Core, True RMS, 4-20 mA Output ** 0-10, 0-20, 0-50 Amps No
A/CTA-250-VFD Loop Powered, Solid-Core, True RMS, 4-20 mA Output ** 0-100, 0-200, 0-250 Amps No
**Note: All -VFD options should be used with VFD’s (Variable Frequency Drives)
ACCESSORIES

! Warning: Not intended to be used in Life & Safety Applications or for use in any hazardous locations.

CU-10
Product
Product Data
Data Current
Current

ACI
A/SCTA Series

DISPLAYS
Split-Core 4-20 mA
Output Current Sensors

“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/SCTA Series current sensors monitor the current flowing to
electrical equipment or buildings. The magnitude of this current is Attributes:
then converted into a linear and proportional 4 to 20 mA output signal, Split-Core design for retrofit
which can be monitored by your Building Management, DDC, or PLC applications
controller. The A/SCTA Series current sensors are available in either
an Average or True RMS output version. All of these sensors have Integral 35mm Din-rail
jumper selectable input ranges except for the 0 to 5 Amp input range.
mounting flange

RELATIVE HUMIDITY
The A/SCTA series current sensors are fast acting and extremely
accurate from 1 to 100% of the Full Scale Output. All of the Limited 5 year warranty
A/SCTA series current sensors are factory calibrated using an NIST
Traceable standard and shipped with the jumper placed in the largest True RMS versions Available
jumper selectable range. (VFD models)
In applications where the maximum current is larger than 200 Amps,
ACI recommends the use of a traditional ratio:5 (5A) current High Accuracy
transformer and the A/SCTA-5 for best results. The A/SCTA must be
externally powered using a +12 to 30 VDC power supply. UL94-5VB

PRESSURE
(enclosure rating)

Applications:
Load trending equipment
(current monitoring)

CURRENT
Product Load Trending building
Product Specifications
Specifications
current consumption
Sensor Supply Voltage (Vs) +12 to 30 VDC
Amperage Rating 0-200 Amps (See Ordering Information) Rated for industrial use
Supply Current 36 mA max.
Output 4-20mA, 2-wire Loop Powered
Accuracy (from 1-100% of FSO) A/SCTA: +/- 0.5%
A/SCTA-VFD: +/- 0.5%

AIR QUALITY
Maximum Load Resistance A/SCTA: 700 Ohms @ 24VDC (Vs-9)/0.02-40.2
A/SCTA-VFD: 650 Ohms @ 24VDC (Vs-10)/0.02-40.2
Response Time A/SCTA: < 75mS
A/SCTA-VFD: <200mS
Operating Frequency Range 30 to 1 kHz
Isolation Voltage 2,200 VAC
Max. Sensing Current Voltage 600 VAC
Aperture (Hole) Size 0.75”, Accepts up to 350 MCM Cables
ACCESSORIES

Operating Tem Range A/CTA -15 to 40oC (5 to 104oF)


o o
A/CTA-VFD 0 to 40 C (32 to 104 F) Automation Components, Inc.
Operating Humidity Range 0 to 95% RH, non-condensing 2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000006 Rev 11.pdf
CU-11
Dimensions
DISPLAYS

Split-Core

ACI A/SCS
TEMPERATURE

Automation Components, Inc.


Middleton, WI

2.70"
(69 mm) 0.76"
(19 mm)

0.14" 0.22" Dia. TYP.


(4 mm) (6 mm)
RELATIVE HUMIDITY

0.74"
(19 mm) 1.08"
(27 mm)

1.38"
(35 mm) 0.50"
(13 mm)
2.84"
(72 mm) L to CL
C

3.33"
(85 mm)
PRESSURE

C US
CURRENT

LISTED
IND.CONT.EQ.
3JHX

Ordering Information
ACI Model # Description Jumper Selectable Range CE Compliant
AIR QUALITY

A/SCTA-5 Loop Powered, Split-Core, 4-20 mA Average Output 0-5 Amps (Not Selectable) Yes
A/SCTA-50 Loop Powered, Split-Core, 4-20 mA Average Output 0-10, 0-20, 0-50 Amps Yes
A/SCTA-200 Loop Powered, Split-Core, 4-20 mA Average Output 0-100, 0-150, 0-200 Amps Yes
A/SCTA-5-VFD Loop Powered, Split-Core, True RMS, 4-20 mA Output ** 0-5 Amps (Not Selectable) No
A/SCTA-50-VFD Loop Powered, Split-Core, True RMS, 4-20 mA Output ** 0-10, 0-20, 0-50 Amps No
A/SCTA-200-VFD Loop Powered, Split-Core, True RMS, 4-20 mA Output ** 0-100, 0-150, 0-200 Amps No
**Note: All –VFD options should be used with VFD’s (Variable Frequency Drives)
ACCESSORIES

! Warning: Not intended to be used in Life & Safety Applications or for use in any hazardous locations.

CU-12
Product
Product Data
Data Current
Current

ACI
A/CTE Series

DISPLAYS
Solid-Core 0-5VDC
Output Current Sensor

“First in Sensor Quality”


A/CTV Series
Solid-Core 0-10VDC
Output Current Sensor
Product
Product Description
Description

TEMPERATURE
The A/CTE and A/CTV Series current sensors monitor the current flowing
to electrical equipment or buildings. The magnitude of this current is then Attributes:
converted into a linear 0 to 5 or 0 to 10 VDC output signal, which can be Fast response time
monitored by your Building Management, DDC, or PLC controller. All
of these sensors have jumper selectable input ranges except for the 0 to Integral 35mm Din-rail
5 Amp input range. mounting flange

RELATIVE HUMIDITY
The A/CTE and A/CTV series current sensors are fast acting and
extremely accurate from 2% or 5% up to 100% of the Full Scale Rated up to 250 Amps
Output depending on the model being ordered. All of the A/CTE and
A/CTV series current sensors are factory calibrated using an NIST Limited 5 year warranty
Traceable standard and shipped with the jumper placed on the largest
jumper selectable range. Induced Power
The power for the A/CTE and A/CTV series current transmitter is
induced from the conductor being monitored. This means that no UL94-5VB
external power supply is necessary for the installation of these sensors. (enclosure rating)

PRESSURE
Applications:
Load Trending Equipment
(current monitoring)

Monitoring Building loads

CURRENT
Product Rated for industrial use
Product Specifications
Specifications
Sensor Power Induced from monitored conductor
Output Voltage A/CTE Series: 0 to 5 VDC
A/CTV Series: 0 to 10 VDC
Amperage Ranges 0 to 250 Amps (See ordering information)
Accuracy A/CTE: +/- 1.0% (2 to 100% FSO)
A/CTV: +/- 1.0% (5 to 100% FSO)

AIR QUALITY
Response Time A/CTE: < 100 mS
A/CTV: < 100 mS
Operating Frequency Range 50 to 600 Hz
Isolation Voltage 2,200 VAC
Max. Sensing Current Voltage 600 VAC
Aperture (Hole) Size 0.75”, Accepts up to 350 MCM Cables
DIN Rail Size 35mm
Operating Temperature Range -15 to 40oC (5 to 104oF)
Operating Humidity Range 0 to 95% RH, non-condensing
ACCESSORIES

Enclosure Rating UL94-5VB Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
c0000007rev10.pdf
CU-13
Dimensions
DISPLAYS

Solid-Core
TEMPERATURE

0.78" Dia.
(20 mm)

2.27"
(58 mm)
0.14" 0.21" Dia. TYP.
(4 mm) ACI A/CS
Automation Components, Inc.
(5 mm)
Middleton, WI
RELATIVE HUMIDITY

0.98"
(25 mm)

1.38"
(35 mm) 0.40"
(10 mm)
2.84"
(72 mm) L to CL
C

3.38"
(86 mm)
PRESSURE

C US
CURRENT

LISTED
IND.CONT.EQ.
3JHX

Ordering Information
AIR QUALITY

ACI Model # Description Jumper Selectable Ranges


A/CTE-50 Solid-Core, 0 to 5 VDC Output 0-10, 0-20, 0-50 Amps
A/CTE-250 Solid-Core, 0 to 5 VDC Output 0-100, 0-200, 0-250 Amps
A/CTV-50 Solid-Core, 0 to 10 VDC Output 0-10, 0-20, 0-50 Amps
A/CTV-250 Solid-Core, 0 to 10 VDC Output 0-100, 0-200, 0-250 Amps
ACCESSORIES

! Warning: Not intended to be used in Life & Safety Applications or for use in any hazardous locations.

CU-14
Product
Product Data
Data Current

ACI
A/SCTE Series

DISPLAYS
Split-Core 0-5VDC
Output Current Sensor

“First in Sensor Quality”


A/SCTV Series
Split-Core 0-10VDC
Output Current Sensor
Product
Product Description
Description

TEMPERATURE
The A/SCTE and A/SCTV Series current sensors monitor the current flowing
to electrical equipment or buildings. The magnitude of this current is then Attributes:
converted into a linear 0 to 5 VDC or 0 to 10 VDC output signal, which can Split-Core design is suited for
be monitored by your Building Management, DDC, or PLC controller. All retrofit applications
of these sensors have jumper selectable input ranges except for the 0 to
5 Amp input range.
Integral 35mm Din-rail
mounting flange

RELATIVE HUMIDITY
The A/SCTE and A/SCTV series current sensors are fast acting and
extremely accurate from 5% to 10% up to 100% of the FSO (Full Scale
Output) depending on the model being ordered. All of the A/SCTE and Rated up to 250 Amps
A/SCTV series current sensors are factory calibrated using a NIST
Traceable standard and shipped with the jumper placed in the largest Limited 5 year warranty
jumper selectable range.

The power for the A/SCTE and A/SCTV series current transmitter is Induced Power
induced from the conductor being monitored. This means that no
external power supply is necessary for the installation of these sensors. UL94-5VB
(enclosure rating)

PRESSURE
Applications:
Load Trending Equipment
(current monitoring)

CURRENT
Product Monitoring Building Loads
Product Specifications
Specifications
Sensor Power Induced from monitored conductor Rated for industrial use
Output Voltage A/SCTE Series: 0 to 5 VDC
A/SCTV Series: 0 to 10 VDC
Amperage Ranges 0 to 250 Amps See ordering information table
Accuracy A/SCTE: +/- 1.0% (5 to 100% FSO)
A/SCTV: +/- 1.0% (10 to 100% FSO)

AIR QUALITY
Response Time A/SCTE: < 100 mS
A/SCTV: < 100 mS
Operating Frequency Range 50 to 600 Hz
Isolation Voltage 2,200 VAC
Max. Sensing Current Voltage 600 VAC
Aperture (Hole) Size 0.75”, Accepts up to 350 MCM Cables
DIN Rail Size 35mm
Operating Temperature Range -15 to 40oC (5 to 104oF)
Operating Humidity Range 0 to 95% RH, non-condensing
ACCESSORIES

Enclosure Rating UL94-5VB Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000008 Rev 12.pdf
CU-15
Dimensions
DISPLAYS

Split-Core

ACI A/SCS
Automation Components, Inc.
Middleton, WI
TEMPERATURE

2.70"
(69 mm) 0.76"
(19 mm)

0.14" 0.22" Dia. TYP.


(4 mm) (6 mm)
0.74"
(19 mm) 1.08"
RELATIVE HUMIDITY

(27 mm)

1.38"
(35 mm) 0.50"
(13 mm)
2.84"
(72 mm) L to CL
C

3.33"
(85 mm)
PRESSURE
CURRENT

C US
LISTED
IND.CONT.EQ.
3JHX

Ordering Information
AIR QUALITY

ACI Model # Description Jumper Selectable Ranges


A/SCTE-50 Split-Core, 0 to 5 VDC Output 0-10, 0-20, 0-50 Amps
A/SCTE-250 Split-Core, 0 to 5 VDC Output 0-100, 0-200, 0-250 Amps
A/SCTV-50 Split-Core, 0 to 10 VDC Output 0-10, 0-20, 0-50 Amps
A/SCTV-250 Split-Core, 0 to 10 VDC Output 0-100, 0-200, 0-250 Amps
ACCESSORIES

! Warning: Not intended to be used in Life & Safety Applications or for use in any hazardous locations.

CU-16
Product
Product Data
Data Carbon
Carbon Monoxide
Monoxide

A CI
A/CO Series

DISPLAYS
Carbon Monoxide Sensor

“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/CO transmitters monitor carbon monoxide (CO) levels in industrial
environments. The A/CO transmitters are intended to be used for the Attributes:
continuous monitoring of vehicle exhaust in non-hazardous areas. Field Configurable
Guidelines provided by OSHA and the UL2034 STD rating state that
current danger levels are 50 ppm on a Time Weighted Average over an 8 Addressable RS-485 digital
hour Period or 35 Minutes at a 200 ppm level. Indoor concentrations
above 35 ppm indicate the need for additional ventilation. communication

RELATIVE HUMIDITY
The A/CO uses a wide spectrum, long life electrochemical sensor to Two optional SPDT relays
measure the amount of carbon monoxide in the environment. It is offered and audible alarm
with an operating range of 0 to 125 ppm. The carbon monoxide transmitter
provides a linear 4 to 20 mA or 2 to 10 VDC output on a 4-wire system LCD display
when using an AC or DC supply voltage to power the transmitter.

Both the Room and Duct CO transmitters are offered in a standard NEMA RoH’s Compliant
1 rated ABS Polycarbonate plastic enclosure. An optional NEMA 4X
watertight and dust proof enclosure is only available with the CO room Applications:
transmitter. Other options include an LCD display with (2) SPDT Form Parking Garages

PRESSURE
1C relays and a buzzer.
Arenas

Kitchens

Laundry Rooms

CURRENT
Product Warehouses
Product Specifications
Specifications
Supply Voltage +24VDC or 24 VAC Floating or One side ground Loading Docks
Outputs 4-20mA, +2-10VDC, Digital RS-485
Accuracy / Repeatability +/- 2.5% of Reading / +/- 1.0% of Reading Service Garages
Operating Range 0 to 125 ppm (standard) / 0-250ppm (max)
Temperature Range -20o to 40oC (-4o to 104oF)
Operating Humidity 15 to 90%, non-condensing, 0 to 99% Intermittent
AIR QUALITY
Coverage Area 7,500 Sq. Ft. (max)
Indicators Two line 8 digit Alpha Numberic LCD (standard)
(2) Red LED’s for Relay Status
Sensor Type Electrochemical
Supply Current 100mA nominal / 250mA maximum
Response Time Less than 60 seconds typical for a 90% step change
Mounting Height 4 to 6’ above floor (1.5 to 2.0 meters)
Sensor Life Span 2 to 3 years typical (under normal conditions)
ACCESSORIES

Relay Rating (2) SPDT Form 1C rated @1 Amp dry contact Automation Components, Inc.
Buzzer Rating Rated for 85 dB @ one foot 2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000099 Rev 1.pdf
AQ-1
Dimensions
DISPLAYS

Room All Dimensions are in Inches


Front Right Side
1.09"

3.50"
0.80"
TEMPERATURE

ACI
Automation
Components
Inc.

Switch One (Up)

Switch Two (Down)

Switch Three (Enter / Accept)


RELATIVE HUMIDITY

6.00"
PRESSURE
CURRENT

Ordering Information
Model Display
A/CO -[ ] -[ ]

(R) - Room Configuration ( ) - No Display (Standard)


(D) - Duct Configuration w/ Pitot Tube (D) - LCD Display, (2) SPDT Form 1C Relays, and Buzzer
(R-4X) - Room Configuration in NEMA 4X Housing*
(R-4X-RB)- Room Configuration in NEMA 4X Housing*
AIR QUALITY

with relays and buzzer

*Not available with external LCD


Example: A/CO-R or A/CO-R-D
ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

AQ-2
Product
Product Data
Data Carbon
Carbon Dioxide
Dioxide

A CI
A/CO2-010 Series

DISPLAYS
Carbon Dioxide Sensor
(0 to 10 VDC output)

“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/CO2-010 room and duct transmitters monitor the carbon dioxide
(CO2) levels in industrial and office type environments. The concentration
of CO2 is a good indication of the overall indoor air quality (IAQ).

All units come with a 0-10 VDC analog output as well as the patented
ABC LogicTM self-calibration system (Automatic Background
Calibration). The concentration of CO2 is measured using a Single Beam

RELATIVE HUMIDITY
Absorption Infrared Diffusion or Flow Through sampling method
depending on the mounting configuration. Attributes:
0 to 10VDC Output
These units should not be used in environments such as greenhouses,
wineries, breweries, or any other applications where industrial sources No field calibration
of CO2 are present.

The ABC LogicTM software eliminates the need for manual calibration in CO22 Level LED Indication
applications where the indoor CO2 level drops to outside levels during (Room Only)
unoccupied periods (ie. During evening hours). Also the ABC LogicTM
will not work properly in applications where the space is left unoccupied 15 year design life

PRESSURE
for less than 4 hours a day or where there are industrial sources of CO2
present. Upon initial installation, a warm-up period of more than two CE and FCC part 15 Class B
minutes is required and up to 5 minutes for full operating accuracy. An
optional three color LED is available for CO2 level indication on the room
version only. All room units include a 20K NTC thermistor for monitoring RoH’s and WEEE Compliant
the room temperature.
Applications:
All A/CO2-010 transmitters come with a two year factory warranty. Large Office Buildings

CURRENT
Product
Product Specifications
Specifications Schools/Gymnasiums
Supply Voltage 18 to 30 VAC RMS, 50/60 Hz or 18 to 42 VDC
Power Consumption Duct: Typical, 1.65 W Pek, 0.65 W Avg. @ 42 VDC Shopping Malls
Room: 2.75 VA Peak, 1.75 VA Avg.
Measurement Range 0 to 2000ppm
Output Signal CO2 Duct: 0 to 10 VDC (100 Ohms output impedance)
Room: 0 to 10VDC (100 Ohms output impedance)

AIR QUALITY
Digital RS-232 communication w/UIP Software
Temperature 20K NTC Thermistor
Accuracy Duct: +/- 40 ppm +3% of Reading @ 72oF (22oC)
Room: +/- 75 ppm @ 72oF (22oC)
Non-Linearity < 1% of FS @ 72oF (22oC)
Stability < 2% FS over life of sensor (15 Yrs Typical)
Temperature Dependence 0.2% of Full Scale per oC
Pressure Dependence 0.13% of reading per mm Hg
Response Time Duct: 3 min. typical for 90% Step change
ACCESSORIES

Room: 3 to 5 min. typical for 90% Step Change


Operating Temp/ RH Range 32 to 122oF (0 to 50oC) / 0 to 95%, non-condensing Automation Components, Inc.
2305 Pleasant View Rd.
Sensor Coverage Area 7,500 sq. ft. maximum
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
c0000112rev1.pdf
AQ-3
Dimensions
Front View: Right Side View: Back Plate, Front View:
DISPLAYS

1.63" [41.28mm]
3.25" [82.55mm] 0.97" [24.64mm]
0.13" [3.18mm] 4x 0.37" [9.33mm]

SENSOR
INDICATOR
(LED)
0.15" [3.81mm] 4x
0.15" [3.81mm] 4x
TEMPERATURE

4.65" [118.11mm] 4.39" [111.57mm]


1.10" [27.94mm]
4.05" [102.74mm]

1.44" [36.58mm] 0.16" [4.06mm]


RELATIVE HUMIDITY

0.67" [16.89mm]

0.33" [8.25mm]
COVER SCREW AND
RELEASE BUTTON
Bottom View: 1.09" [27.69mm] 0.98" [24.77mm]
1.63" [41.28mm]

Top View: Right Side View:


PRESSURE

3.05" [77.47mm] 5.70" [144.78mm]

�0.22" [�5.52mm] 2x

PRODUCT
1.15" [29.21mm] LABEL 3.05" [77.47mm] Ø1.24" [31.50mm]

LOCATION
CURRENT

4.94" [125.54mm]
5.66" [143.76mm] 1.60" [40.64mm] 4.10" [104.14mm]
AIR QUALITY

Ordering Information
Configuration Displays
A/CO2-010-R (Room) ( ) -No LED Indication (Standard)
(L) -Green/Yellow/Red LED Indication
(Available on Room units only)
A/CO2-010-D (Duct)
ACCESSORIES

Example: A/CO2-010-R or A/CO2-010-RL or A/CO2-010-D

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

AQ-4
Product
Product Data
Data Carbon
Carbon Dioxide
Dioxide

A CI
A/CO2 Series

DISPLAYS
Carbon Dioxide Sensor
4 to 20 mA
0 to 10 VDC
“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/CO2 transmitters monitor carbon dioxide (CO2) levels in industrial
and living environments from 0 to 10,000 ppm. The concentration of CO2 Attributes:
is a good indication of the indoor air quality (IAQ). All units come with LCD Display
both a 4-20 mA and 0-10 VDC analog output as well as a relay output with
an adjustable setpoint and deadbank (Hysersis). An optional LCD display Analog and Relay outputs
may be added to the room unit while all the duct configurations come
standard with the LCD display.
Self calibration system

RELATIVE HUMIDITY
The concentration of CO2 is measured using a Single Beam Absorption
Infrared sensing method. The CO2 transmitter is also equipped CE, FCC part 15 class B
with a patented ABC LogicTM (Automatic Background Calibration) California Energy
software. The ABC LogicTM software virtually eliminates the need for Commission Compliant
manual calibration in applications where the indoor CO2 level drops to
outside levels during unoccupied periods. The ABC LogicTM will not work
properly in applications where the space is left unoccupied for less than 4 Long life span
hours a day or where there are industrial sources of CO2. (15 years typical)

The room transmitter is encased in a white enclosure while the duct sensor

PRESSURE
is enclosed in a black case that is UL94-5V rated and includes a pitot tube. Applications:
Schools
All units come with a two year factory warranty.
Large Office Buildings

Auditoriums/Gymnasiums

CURRENT
Product Shopping Malls
Product Specifications
Specifications
Supply Voltage 18 to 30 VAC, 50/60 Hz Half-Wave Rectified Residential
+18 to 42 VDC, Polarity Protected
Power Consumption 1.75 VA average power, 2.75 VA peak power
Theatres
CO2 Analog Output Signals 4 to 20 mA (RL max = 500 Ohms)
0 to 10 VDC (100 Ohms output impedance)
Accuracy @ 72oF (22oC) +/- 40 ppm + 3% of reading

AIR QUALITY
Response Time 0 to 90% < 2 minutes
Operating Temperature Range 60 to 90oF (15 to 32oC)
Operating RH Range 0 to 95% RH, non-condensing
CO2 Measurement Range 0 to 2000 ppm (Factory Set), Adjustable to 10,000 ppm
Digital I/O RS232 Interface for use with optional PC UIP Kit #2072
Relay Output N/O or N/C 2A max @ 24VAC contact Rating, Factory
Set at 1000 ppm with 50 ppm Hysteresis
Calibration Time 5 Years / Zero ppm with a 50 ppm Hysteresis
ACCESSORIES

Sampling Method Room: Single Beam Infrared Diffusion


Digital Display 0 to 10,000 ppm (Optional) Automation Components, Inc.
2305 Pleasant View Rd.
Operating Temperature 32 to 122oF (0 to 50oC) Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000113 rev 2.pdf
AQ-5
Dimensions
DISPLAYS

Room Mount Duct Mount


Back Mounting Plate
Fittings for Pitot
2 7/8"
Tube Mounting
2 3/8"
3.25”

2 3/8"

3 1/4"
TEMPERATURE

4 1/4"

6.125” 5 1/16"
5.625”
8 76 5 4 3 2 1

AC/GND
AC/DC+
RELATIVE HUMIDITY

LCD Display
Side View
0.75”
Pitot Tube for Duct
0.8125 Side View
Air Intake Air Intake
Louvres for Air Intake

5.50”
PRESSURE

0.250” Foam Pad


End View
2.75”

H L
1.25”
36” Clear Tubing FLOW
CURRENT

1.100”

Ordering Information
Configuration Display Option (Room Only)
A/CO2-R (Room Mount) -[ ]
AIR QUALITY

( )- No Display (Standard)
(D)- LCD Display (Optional)
A/CO2-D (Duct Mount with Display)
A/CO2-Software (Calibration Software)
(UIP Kit #2072)
ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

AQ-6
Product
Product Data
Data CO
CO22 w/
w/ Temp
Temp

A CI
A/CO2-T Series

DISPLAYS
Carbon Dioxide Sensors with
Temperature Sensor

“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/CO2-T transmitters monitor both the temperature and carbon dioxide
(CO2) levels in industrial and living environments. The concentration of Attributes:
CO2 is a good indication of the indoor air quality (IAQ). No Field Calibration
(Self calibration)
All units come with both a 4-20 mA and 0-10 VDC analog output. A
resistive type temperature sensor is available with options including
Override, Setpoint, and RJ-14 Communication Jack. By combining both the “After Hours” override
option (Standard)

RELATIVE HUMIDITY
temperature and CO2 sensors in one package, installation and maintenance
is greatly simplified. The concentration of CO2 is measured using a Single
Beam Absorption Infrared Diffusion sampling method. The CO2 RJ14 Communication Jack
transmitter is also equipped with a patented ABC LogicTM (Automatic (Standard)
Background Calibration) software. The ABC LogicTM software virtually
eliminates the need for manual calibration in applications where the indoor CO2 and Temp in one
CO2 level drops to outside levels during unoccupied periods. The ABC
LogicTM will not work properly in applications where the space is left Enclosure
unoccupied for less than 4 hours per day or where there are industrial
sources of carbon dioxide. Upon initial installation, a warm up period of Setpoint option (Optional)
more than 2 minutes is required to get an accurate reading.

PRESSURE
Applications:
The A/CO2-T series carbon dioxide transmitters are only offered in room Office Buildings
configurations. The room transmitter will mount directly to a standard 2”
x 4” junction box and is encased in a beige enclosure. All units come with
a two year warranty. Schools

Shopping Malls

CURRENT
Product Auditoriums/Gymnasiums
Product Specifications
Specifications
Supply Voltage 18 to 30 VAC, 50/60 Hz Half-Wave Rectified Restaurants
+18 to 42 VDC, Polarity Protected
Power Consumption 1.75 VA average power, 3.25 VA peak power
CO2 Measurement Range 0 to 2000 ppm
CO2 Output Signal 4 to 20 mA (RL max=500 Ohms)
0 to 10 VDC (source 100 mA, Sink 10 mA)

AIR QUALITY
Accuracy @ 72oF (22oC) +/- 100 ppm or +/- 7% whichever is greater
Stability < 2% of FS over 15 years, Typical
Response Time 0 to 90% < 2 minutes
Operating RH Range 0% to 95% RH, non-condensing
Sensor Life 15 Years Typical
Operating Temperature Range 59 to 90oF (15 to 32oC)
Resistive Temperature Sensor See Ordering Information on back
“Night Setback” Override Shorts the temperature when depressed
ACCESSORIES

Setpoint Option See ordering Information on back


Agency Approvals CE, FCC Port 15 Class B, CA Energy Commission Automation Components, Inc.
2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000114 Rev. 2.pdf
AQ-7
DISPLAYS

Dimensions

Front View Left Side Right Side


3.20” 1.18”
(81.3mm) (30mm)
TEMPERATURE

5.50”
(139.7mm)
RELATIVE HUMIDITY

6 Pin RJ14
Communication Jack

“After Hours" N/O


Override Pushbutton

Setpoint Adjus tment


PRESSURE

Ordering Information
Configuration Temperature Sensor Setpoint Value
CURRENT

A/CO 2-T [ ] -[ ] -[ ]

RO-Room with Override and 6 pin RJ12 Jack 100 RTD (385) 400 Ohm
RSO-Room with Setpoint, Override and 6 pin RJ12 Jack 1K RTD (385) 1K
1K-NI (Nickle) 2K
1.8K 3K
2K RTD 5K
AIR QUALITY

3K 8.5K
ASI (3K) 10K
2252 20K
5K 100K
AN (10K-Type III)
*All Optional Series Offset Resistors
CP (10K-Type II)
must be Installed at the controller.
CSI (10K-CSI)
20K
100K
ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

AQ-8
Product
Product Data
Data Power
Power Supply
Supply

A CI
A/PS1.5

DISPLAYS
1.5 Amp Power Supply

“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/PS1.5 adjustable power supply is a low cost, dependable external
power supply. This unit will accept an input of up to 28 VAC or 35 VDC, Attributes:
and provides an adjustable 1.2 to 27 VDC output. The A/PS1.5 will Half and Full-Wave jumper
supply 1.5A continuous when (Vin- Vout < 15V). The maximum power selectable
dissipation is internally limited to 20W.
Adjustable Voltage output
All A/PS1.5's are jumper selectable between Half-Wave and Full-Wave and

RELATIVE HUMIDITY
are factory set in the Half-Wave mode. If a Full-Wave power supply is 1.5A @ 24VDC
needed, change the two on board selection jumpers. When using the power
supply in the Full-Wave mode, a grounded DC minus terminal and a Snap Track Mountable
grounded 24 VAC input transformer will blow the unit's fuse.
Applications:
The A/PS1.5 also features a potentiometer adjustment, auto reset thermal
protection, and LED power indication. This unit is available in a Whenever a DC power
convenient snap track mount configuration along with a two year factory source is not available
warranty. Please contact ACI for more information regarding the
A/PS1.5 adjustable power supplies.

PRESSURE
CURRENT
Product
Product Specifications
Specifications
Supply Voltage Regulated +30 to 35 VDC or 22 to 28 VAC
Output Voltage Adjustable from +1.2 to 27 VDC
Current Output 1.5A max
Overload Protection Internally Regulated Thermal Shutdown
Fuse Protected for ground loop protection
Power Dissipation 20 Watts Max.

AIR QUALITY
Operating Humidity Range 0 to 95% non-condensing
Operating Temperature Range 30 to 185oF (0 to 70oC) ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
c0000123rev1.pdf
AC-1
Dimensions
DISPLAYS

All Dimensions are in Inches

2.14”
TEMPERATURE

2.14”

- +
24 VAC VDC output
RELATIVE HUMIDITY
PRESSURE
CURRENT
AIR QUALITY

Ordering Information

A/PS1.5

Example: A/PS1.5
ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

AC-2
Product
Product Data
Data Light Level

A CI
A/LLS

DISPLAYS
A/LLS-T
Light Level Sensors
and Transmitter
“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The light level sensor and transmitter is to be used for applications such
as turning on or off indoor or outdoor lighting based upon the amount of Attributes:
available light. These sensors are not to be used in applications such as  Indoor and Outdoor
green houses where the actual amount of light is monitored. This unit is ranges available
mounted in either the end of a waterproof conduit box or as a snap track
mount.  NEMA 3R weatherproof
enclosure for all transmitters

RELATIVE HUMIDITY
The A/LLS has a resistance in darkness in excess of 1M ohm and a
resistance in bright light of less than 1.5K ohm. The A/LLS-T
incorporates a transmitter with the sensor to produce a non-linear Applications:
4-20 mA output signal. The A/LLS-T is calibrated for 4 mA in darkness  Illuminated Outdoor Signs
and 20 mA in bright Light.
 Outdoor Lighting

 Security Lighting

PRESSURE
CURRENT
Product
Product Specifications
Specifications
Supply Voltage +24 to 35 VDC
Input Impedance 150K Ohms
2 Foot Candle Resistance 17K Ohms
Output LLS - See Resistance Graph
LLS-T - 4 to 20 mA (non-Linear)
Operating Temp. Range -40 to 70ºC (-40 to 158ºF)

AIR QUALITY
Maximum Current Draw 22mA
Operating RH Range 0-95% RH, non-condensing ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000124 Rev. 2.pdf
AC-3
DISPLAYS

Dimensions
ACI/LLS-T
TEMPERATURE

2.15”

+24 COM I/V +IN -IN

2.15”
RELATIVE HUMIDITY

ACI/LLS
1/2” NPT

18”

0.89”

Typical Resistance vs.


Illumination Characteristics
PRESSURE

Resistance (Ohms)
10Meg

1Meg

100K
CURRENT

10K

1K
0.1 1 10 100 1000
Illumination - LUX (2850K)
AIR QUALITY

Ordering Information
Model# Enclosure
A / -[ ] -[ ]

LLS ( ) - No Enclosure (standard)


LLS-T (0 to 100 Foot Candles) Indoor Lighting (BB) - Bell Box (NEMA 3R)
LLS-T (0 to 500 Foot Candles) Outdoor Lighting This option is for sensors only the Transmitter
ACCESSORIES

comes standard with the Bell Box option

Example: A /LLS or A/LLS-T (0 to 100 Foot Candles) or A/LLS-BB


2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407

AC-4
Product
Product Data
Data Freeze Stats

A CI

DISPLAYS
A/FS Series
Freeze Stats
“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/FS Series controllers are Low Limit controllers also known as
"Freeze Stats". These devices were designed for use on HVAC Attributes:
equipment requiring low-temperature cutout protection and in all ducts to 6, 10 and 20 foot lengths
prevent the cooling coils from freezing. The Freeze Stats should be
mounted between the heating and cooling coils on the supply side of the Adjustable Setpoint
fan unit.
Manual Reset Versions

RELATIVE HUMIDITY
The A/FS-1, A/FS-3 and A/FS-5 are available in both manual and automatic
reset versions. These units are responsive to the lowest temperature sensed
along any 1 foot section of the sensing element. They also have (one) set Automatic Reset Versions
of SPDT contacts with an adjustable setpoint range of 14 to 54ºF. The
sensing element is made up of a vapor-filled, copper capillary tube CE Approval
measuring 5/64 inches in diameter (2mm) with an overall length of 6, 10,
and 20 feet depending on the model number being ordered.
RoH’s Compliant
The A/FS-2, A/FS-4, and A/FS-6 are available in both manual and automatic
reset versions. These units are responsive to the lowest temperature sensed Applications:
along any 1 foot section of the sensing element. The A/FS-2, A/FS-4, and Low Limit temperature

PRESSURE
A/FS-6 model number each have (2) sets of SPDT contacts with an protection for HVAC
adjustable setpoint range of 14 to 54ºF. The sensing element is made up of equipment and cooling coils
a vapor-filled, copper capillary tube measuring 5/64 inches (2mm) in
diameter with an overall length of 6, 10, or 20 feet depending on the model
number being ordered.

CURRENT
Product
Product Specifications
Specifications
Sensing Element Vapor Filled, Copper Capillary Tube
Output A/FS-1, A/FS-3, A/FS-5 one SPDT Form 1C Relay
A/FS-2, A/FS-4, A/FS-6 two SPDT Form 1C Relays
Contact Rating 250 VAC, 15 (8) A
Setpoint Range 14 to 54ºF (-10 to 12 ºC) Field Adj.
Setpoint Differential 1.8ºF (1ºC), Fixed for Auto Reset

AIR QUALITY
Setpoint Safety Lock 35.6ºF (Factory Set), Field Adj.
Housing Rating NEMA 1 (IP40)
Operating Temp. Range 14 to 194ºF (-10 to 65 C)
Operating Humidity Range 0 to 95%, non-condensing
Agency Approvals CE Approved
Environmental Approvals RoH’s Compliant
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000094 Rev 3.pdf
AC-5
DISPLAYS

Dimensions

2.10”
4.25”
TEMPERATURE

+oF
15
20
30
40
50 3.40”
RELATIVE HUMIDITY

Conduit Opening PG13.5

Copper Sensing Element


6', 10', and 20'
PRESSURE

Ordering Information
Model#
A/ [ ]
CURRENT

FS-1 ((1 set) SPDT Contacts, 20ft capillary, Manual reset)


FS-1A ((1 set) SPDT Contacts, 20ft capillary, Auto reset)
FS-2 ((2 sets) SPDT Contacts, 20ft capillary, Manual reset)
FS-2A ((2 sets) SPDT Contacts, 20ft capillary, Auto reset)
FS-3 ((1 set) SPDT Contacts, 10ft capillary, Manual reset)
FS-3A ((1 set) SPDT Contacts, 10ft capillary, Auto reset)
FS-4 ((2 sets) SPDT Contacts, 10ft capillary, Manual reset)
FS-4A ((2 sets) SPDT Contacts, 10ft capillary, Auto reset)
AIR QUALITY

FS-5 ((1 set) SPDT Contacts, 6ft capillary, Manual reset)


FS-5A ((1 set) SPDT Contacts, 6ft capillary, Auto reset)
FS-6 ((2 sets) SPDT Contacts, 6ft capillary, Manual reset)
FS-6A ((2 sets) SPDT Contacts, 6ft capillary, Auto reset)
DBZ-05 Capillary Mounting Clips (Set of 6)
DBZ-07 Housing Mounting Bracket

Example: A/FS1 or A/FS-1A or A/FS-2 or A/FS-2A


ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

AC-6
Product
Product Data
Data Thermowells

A CI
A/2.5”

DISPLAYS
A/4”
A/6”
“First in Sensor Quality” Two Part Thermowells
Thermal Grease
Product
Product Description
Description

TEMPERATURE
The A/2.5", 4", and 6" thermowells are made of 300 series stainless
steel to ensure long lasting reliability and stability. These units are milled Attributes:
to high tolerances, so there is no gap between the thermowell sheath and  Compatible with a wide
the probe, to provide maximum heat transfer. range of medias
The A/2.5", 4", and 6" thermowells are a two part thermowell. The  Economical
sheath is set into the nut (see dimensional drawing on back) and then

RELATIVE HUMIDITY
welded with an automated tig weld for consistency and from its own
material to provide the strongest possible joint.  RoH’s Compliant

If preferred, thermal grease may be used with all of the thermowells. ACI
offers the thermal grease in both a silicone and non-silicone compound. Applications:
The silicone compound is available in a 8 oz. tube and the non-silicone  Hot & Chilled Water Systems
compound is available in a 2 oz. tube.

For more information on specifications and pricing, please contact ACI.  Cooling Towers

 Process Control

PRESSURE
 Boilers

CURRENT
Product
Product Specifications
Specifications
Material Tube 304 Series Stainless Steel
Process Thread 1/2” NPT (National Pipe Tapor)
Instrument Thread 1/2” NPS (National Pipe Straight)
Pressure vs. Temp Ratings Max PSI oF
1600 70

AIR QUALITY
1500 200
1400 400
1200 600
1000 800
900 1000
700 1200
Environmental Compliance RoH’s Compliant
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000125 Rev 2.pdf
AC-7
DISPLAYS

Dimensions

1 1/8” Hex Nut


Automated Tig Weld
TEMPERATURE

1/2” Male NPT threads

0.8” 1.0” 2.5”, 4.0” or 6.25” 0.375”


RELATIVE HUMIDITY

(Cross Sectional View)


1/2” Female NPSM Threads

*Note: All of our standard thermowells have a 0.260" bore and


will accept probe diameters up to 0.250" diameter
PRESSURE
CURRENT

Ordering Information
Model#
A/ [ ]
AIR QUALITY

2.5” (2.5” Thermowell)


4” (4” Thermowell)
6” (6” Thermowell)
SG (-40 - 400oF) Silicone Grease
NSG (-40 - 392oF) Non-Silicone Grease

Example: A/2.5" or A/4" or A/6" or A/SG or A/NSG


ACCESSORIES

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

AC-8
Product
Product Data
Data Shields/Covers

ACI
Locking Cover
A/Locking Cover

DISPLAYS
A/PS
Plexi Shield
“First in Sensor Quality” A/WS
Weather Station
Product
Product Description
Description

TEMPERATURE
ACI has some options when your application calls for additional security
or protection. Plexi Shield
Product Description
The A/Locking Cover can be used to protect any ACI Room mounted
enclosure from physical damage or tampering. It comes with a clear vented
cover and two keys.

RELATIVE HUMIDITY
The A/PS is a clear lucite shield that is designed to cover a wall thermostat
or temperature sensor. Not only will it protect the thermostat or sensor, but
it can also be used to stabilize the temperature in rooms where large fans or
extreme environmental changes are present.

The A/WS is designed to provide protection in both indoor and outdoor


environments. It will provide protection from rain, sleet, snow, or against Weather Station
dripping water. It is made of 16 gauge G-90 grade galvanized steel and is
coated with white enamel.

PRESSURE
Attributes:
Offer varying levels of

CURRENT
protection against vandalism,
tampering, and the elements.

Applications:
Schools, Universities, and
various commercial bldgs.
AIR QUALITY
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm

AC-9
This page left intentionally blank
Product
Product Data
Data Accessories

ACI

DISPLAYS
Mounting Plate
A/Mounting Plate
A/Mounting Plate-10
“First in Sensor Quality”

Product
Product Description
Description

TEMPERATURE
The A/Mounting Plate may be used to mount any ACI Room
enclosure over a much larger electrical enclosure or hole in the
wall. The A/Mounting Plate is made up of a plastic material and
contains numerous mounting holes to match most of the standard Mounting Plate-10
electrical boxes used in the industry today. It may be mounted
either vertically or horizontally. (Dimensions 7" long X 5.25" wide)

RELATIVE HUMIDITY
The A/Mounting Plate-10 is slightly larger than the standard
Mounting Plate and is made from 20 Gauge Commercial Steel.
It is painted to match the color of the ACI Room enclosure.
(Dimensions 7.875” long X 5.875” wide)

PRESSURE
CURRENT
AIR QUALITY
ACCESSORIES

Automation Components, Inc.


2305 Pleasant View Rd.
Middleton, WI 53562
PH: (608) 831-2585
FAX: (608) 831-7407
Wiring Diagrams available at www.workaci.com/instructions.htm
C0000128 Rev 2.pdf
AC-11
DISPLAYS

Dimensions
A/Mounting Plate Front View: Side View: Back View:
0.997" [25.32mm] 3.231" [82.05mm]
1.439" [36.55mm] 2.205" [56.01mm]

2.508" [63.69mm]
TEMPERATURE

5.063" [128.61mm]

1.985" [50.42mm] 7.000" [177.80mm] 4.498" [114.25mm] 3.275" [83.19mm]


RELATIVE HUMIDITY

2.508" [63.69mm]

1.875" [47.63mm] 2.125" [53.98mm]


0.312" [7.92mm] 1.831" [46.49mm]
1.250" [31.75mm] 2.639" [67.04mm]
5.250" [133.35mm] 3.495" [88.78mm]

A/Mounting Plate-10 0.225" [5.72mm]


PRESSURE

0.188" [4.76mm]
MOUNTING HOLE

1.500" [38.10mm] 0.300" [7.62mm]


MOUNTING SLOT
7.563" [192.09mm]
CURRENT

1.000" [25.40mm]

0.188" [4.76mm]

3.781" [96.04mm]
3.281" [83.34mm]
AIR QUALITY

1.143" [29.02mm]

2.035" [51.69mm]
4.428" [112.46mm]
5.570" [141.48mm]

Ordering Information
ACCESSORIES

A/Mounting Plate
A/Mounting Plate-10

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562


PH: (608) 831-2585 FAX: (608) 831-7407

AC-12
Interface Devices

DISPLAYS
Analog Input to Pneumatic Output
The A/PXP converts an analog input signal into a proportional pneumatic output ranging
from 0 to 15 psig. The A/PXP will automatically modulate its control valve to control
the branch line pressure to the selected setpoint as determined by the input signal. The

TEMPERATURE
input signal may be either a 0 to 5, 0 to 10, 0 to 15 VDC or a 4 to 20 mA signal.

Analog Input to Pneumatic Output

RELATIVE HUMIDITY
The A/EPC converts an analog input signal into a proportional pneumatic output. The
output pressure ranges are jumper selectable for 0-10, 0-15 or 0-20 psi and are adjustable
in all ranges. The EPC will automatically modulate its control valve to control the branch
line pressure to the selected setpoint as determined by the input signal. The input signal
may be a 0 to 5, 0 to 10, 0 to 15VDC, or a 4 to 20 mA signal.

PWM Input to Pneumatic Output

PRESSURE
The A/EPW converts a pulse, phase cut, or digital PWM signal into a proportional
pneumatic signal ranging from 0 to 20 psig. The pneumatic output is proportional to the
signal input, either direct or reverse acting. The A/EPW offers four jumper-selectable
input timing ranges. Output pressure ranges are jumper-shunt selectable for 0 to 10,
0 to 15 or 0 to 20 psig, and adjustable in all ranges.

CURRENT
Pneumatic Sensor to Current Output
The A/PTP will accept either a 0 to -7.5, 3 to 15, or 3 to 30 psig pneumatic input and
convert it into a proportional 4 to 20 mA current output. By adding one of the supplied
external load resistors, the A/PTP will output a proportional 1 to 5, 2 to 10, or 3 to 15

AIR QUALITY
VDC signal. It is a positive current output device that is fully temperature compensated.

Floating Point Input to Pneumatic Output


The A/EFP converts a floating point signal into a proportional pneumatic signal ranging
ACCESSORIES

from 0-20 psig. The pneumatic output is proportional to the signal input. The A/EFP has
a manual override switch with terminal strip contacts to indicate its status and a
potentiometer to vary the pneumatic output.

AC-13
Interface Devices
DISPLAYS

Analog Rescaling Modules


The A/ARM is an analog re-scaling module, which will accept any analog voltage or
current input signal and re-scales it to another voltage or current output range. Several
preset ranges are jumper selectable. Trimmer potentiometers can then be used to
TEMPERATURE

attenuate an input signal up to 100% or to make fine adjustments on output ranges for
maximum flexibility.

Pulse/Analog/Floating Pt Input to Resistance Output


RELATIVE HUMIDITY

The A/DRN Series modules accept an Analog, Pulse, Floating Point, or Tri-state input
signal and converts it into a proportional resistance output. The output directly replaces
a variable resistance controller and simulates the action of a potentiometer.

PWM Input to Analog Output


PRESSURE

The A/PTA converts a single pulse-width modulated input to an analog current or


voltage output. There are two LED indicators that designate power and signal. A timed
contact or solid state closure from the controlling microprocessor controller is converted
to a linear analog output signal with 256 steps of resolution.
CURRENT

Analog Isolation Module


The A/AIM1 optically isolates the analog input signal from its output signal. The
A/AIM1 is factory calibrated having an output that is linear and proportional (1:1 ratio)
to the input signal. Inputs of 0 to 5 or 0 to 10 volts, and 0 to 20 mA are available. The
A/AIM1 isolates analog inputs up to 600 VAC or 1500 VDC.
AIR QUALITY

Analog Input to Relay Output Modules


The A/AAR controls two “Form C” 10A relays with a single analog voltage or current
ACCESSORIES

input. Analog input ranges available are 0 to 12 VDC, 0 to 24 VDC, or a 0 to 20mA.

AC-14
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List
LCD Indicators
A/LCD-R 4 to 20 mA Loop Powered Display $105.00
-LCD 8 to 35 VDC/24 VAC Display add on $105.00
A/TUC-R Microprocessor LCD Display Consult Factory
A/TUCH-R Microprocessor LCD Display Consult Factory
A/FAN LCD-R LCD Display w/ 4 Speed Switch Consult Factory
-TI Thermometer Indicator add on $18.00

100 Ohm Platinum Resistance Temperature Detectors (PRTD)


A/100-2w-R Room Sensor $34.00
A/100-2w-RS Room w/ Setpoint $42.00
A/100-2w-RO Room w/ Override $42.00
A/100-2w-RSO Room w/ Setpoint & Override $50.50
A/100-2w-RSO-RJ11 Room w/ Set, O/R & RJ11 $60.00
-(DF) or -(DC) LCD Can be added to above sensors $105.00
A/100-2w-D-( ) *Duct (4”, 8”, 12”, 18”) $36.50
A/100-2w-I-( ) *Immersion (2”, 4”, 6”) $61.50
A/100-2w-S *Strap-On $42.00
A/100-2w-O Outdoor Air $43.25
A/100-2w-W Raw $26.00
A/100-3w-A-( ) *Averaging (12', 24') Only available in 3 Wire $160.00
A/100-2w-RA-18" *Rigid Averaging (18", 24”, 36”) $150.00
A/100-2w-SP Stainless Plate $34.00
A/100-2w-BP Bullet Probe $28.00
A/100-2w-DO-( ) Duct without Box (4”, 8”, 12”, 18”) $33.00
A/100-2w-BBS Brass Button Sensor $73.00
A/100-2w-SBS Stainless Button Sensor $78.00
These sensors are also available in a 3 wire configuration

1000 Ohm Platinum Resistance Temperature Detectors (PRTD)


A/1K-2w-R Room $38.00
A/1K-2w-RS Room w/ Setpoint $46.00
A/1K-2w-RO Room w/ Override $46.00
A/1K-2w-RSO Room w/ Setpoint & Override $52.50
A/1K-2w-RSO-RJ11 Room w/ Set, O/R & RJ11 $62.00
-(DF) or -(DC) LCD Can be added to above sensors $105.00
A/1K-2w-D-( ) *Duct (4”, 8”, 12”, 18”) $42.00
A/1K-2w-I-( ) *Immersion (2”, 4”, 6”) $67.00
A/1K-2w-S *Strap-On $46.00
A/1K-2w-O Outdoor Air $47.00
A/1K-2w-W Raw $29.00
A/1K-3w-A-( ) *Averaging (12', 24') Only available in 3 Wire $180.00
A/1K-2w-RA-( ) *Rigid Averaging (18”, 24”, 36”) $170.00
A/1K-2w-SP Stainless Plate $38.00
A/1K-2w-BP Bullet Probe $32.00
A/1K-2w-DO-( ) Duct without Box (4”, 8”, 12”, 18”) $37.00
A/1K-2w-BBS Brass Button Sensor $76.00
A/1K-2w-SBS Stainless Button Sensor $81.00
These sensors are also available in a 3 wire configuration

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
* Add $10.00 for Polycarbonate NEMA 4X Enclosure PL-1
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List
100 Ohm Cryogenic Platinum Resistance Temperature Detectors (PRTD)
A/100-LT-3w-D-( ) *Duct (4”, 8”, 12”, 18”) $120.00
A/100-LT-3w-I-( ) *Immersion (2”, 4”, 6”) $150.00
A/100-LT-3w-RP *Remote Probe $120.00
A/100-LT-3w-O) Outdoor Air $130.00

1000 Ohm Cryogenic Platinum Resistance Temperature Detectors (PRTD)


A/1K-LT-3w-D-( ) *Duct (4”, 8”, 12”, 18”) $124.00
A/1K-LT-3w-I-( ) *Immersion (2”, 4”, 6”) $154.00
A/1K-LT-3w-RP *Remote Probe $124.00
A/1K-LT-3w-O Outdoor Air $134.00

100 Ohm High Temperature Platinum Resistance Temperature Detectors (PRTD)


A/100-HT-3w-D-( ) *Duct (4”, 8”, 12”, 18”) $125.00
A/100-HT-3w-I-( ) *Immersion (2”, 4”, 6”) $155.00
A/100-HT-3w-RP *Remote Probe $125.00

1000 Ohm High Temperature Platinum Resistance Temperature Detectors (PRTD)


A/1K-HT-3w-D-( ) *Duct (4”, 8”, 12”, 18”) $129.00
A/1K-HT-3w-I-( ) *Immersion (2”, 4”, 6”) $155.00
A/1K-HT-3w-RP *Remote Probe $129.00

1,000 Ohm Nickel Resistance Temperature Detectors


A/1K-NI-R Room $36.00
A/1K-NI-RS Room w/ Setpoint $44.00
A/1K-NI-RO Room w/ Override $44.00
A/1K-NI-RSO Room w/ Setpoint & Override $52.50
A/1K-NI-RSO-RJ11 Room w/ Set,O/R&RJ11 $60.00
-(DF) or -(DC) LCD can be added to above sensors $105.00
A/1K-NI-D-( ) *Duct (4”, 8”, 12”, 18”) $38.50
A/1K-NI-I-( ) *Immersion (2”, 4”, 6”) $63.50
A/1K-NI-S *Strap-On $44.00
A/1K-NI-A-( ) *Averaging (12', 24') $180.00
A/1K-NI-O Outdoor Air $45.00
A/1K-NI-W Raw $32.00
A/1K-NI-RP Remote Probe 6' Leads $38.00
A/1K-NI-SP Stainless Plate $38.00
A/1K-NI-BP Bullet Probe $34.00
A/1K-NI-BBS Brass Button Sensor $85.00
A/1K-NI-SBS Stainless Button Sensor $85.00
A/1K-NI-DO-( ) Duct without box (4”, 8”, 12”) $36.00

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
PL-2 * Add $10.00 for Polycarbonate NEMA 4X Enclosure
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List
1,000 Ohm Balco Resistance Temperature Detectors
A/1K-Balco-R Room $45.00
A/1K-Balco-RS Room w/ Setpoint $53.00
A/1K-Balco-RO Room w/ Override $53.00
A/1K-Balco-RSO Room w/ Setpoint & Override $59.00
A/1K-Balco-RSO-RJ11 Room w/ Set, O/R & RJ11 $67.50
-(DF) or -(DC) LCD can be added to above sensors $105.00
A/1K-Balco-D-( ) *Duct (4”, 8”, 12”, 18”) $47.00
A/1K-Balco-I-( ) *Immersion (2”, 4”, 6”) $75.00
A/1K-Balco-S *Strap-On $53.00
A/1K-Balco-O Outdoor Air $55.00
A/1K-Balco-W Raw $37.00
A/1K-Balco-RP Remote Probe 6' Leads $46.50
A/1K-Balco-SP Stainless Plate $46.00
A/1K-Balco-BP Bullet Probe $41.50
A/1K-Balco-BBS Brass Button Sensor $85.00
A/1K-Balco-SBS Stainless Button Sensor $85.00

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
* Add $10.00 for Polycarbonate NEMA 4X Enclosure PL-3
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List
ACI Thermistor Series
Sensor types
AN (10,000 Ohm Type III Thermistor) CP (10,000 Ohm Type II Thermistor)
1.8K (1.8K Ohm Thermistor) 2252 (2,252 Ohm Thermistor)
3K (3K Ohm Thermistor) 5K (5K Ohm Thermistor)
20K (20K Ohm Thermistor) 100KS (100,000 Ohm Thermistor)
Configurations
A/( )-R (Room Sensors) $20.00
A/( ) -RS (Room w/ Setpoint) $28.75
A/( ) -RO (Room w/ Override) $28.75
A/( )-RSO (Room w/ Setpoint & Override) $35.00
A/( )-RSO-RJ11 (Room w/ Set, O/R & RJ11) $44.50
-(DF) or -(DC) LCD can be added to above sensors $105.00
A/( )-D-( ) *Duct (4”, 8”, 12”, 18”) $27.00
A/( )-I-( ) *Immersion (2”, 4”, 6”) $52.00
A/( )-S *Strap-On $28.75
A/( )-O Outdoor Air $32.00
A/( )-W Raw $15.75
A/( )-RP Remote Probe $22.25
A/( )-SP Stainless Plate $20.00
A/( )-A-8' *Averaging 8 Foot-Copper $105.00
A/( )-A-12' *Averaging 12 Foot-Copper $125.00
A/( )-A-24' *Averaging 24 Foot-Copper $175.00
A/( )-FA-8' *Averaging 8 Foot-Flexible Cable $105.00
A/( )-FA-12' *Averaging 12 Foot-Flexible Cable $125.00
A/( )-FA-24' *Averaging 24 Foot-Flexible Cable $175.00
A/( )-RA-18" *Rigid Averaging 18" $85.00
A/( )-RA-24" *Rigid Averaging 24" $90.00
A/( )-RA-36" *Rigid Averaging 36" $90.00
A/( )-BP) Bullet Probe $18.50
A/( )-DO-( ) Duct without Box (4”, 8”, 12”, 18”) $24.50
A/( )-BBS Brass Button Sensor $70.00
A/( )-SBS Stainless Button Sensor $75.00

Example: A/AN-D-4”

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
PL-4 * Add $10.00 for Polycarbonate NEMA 4X Enclosure
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List

AD592 & AD592-10K Series Semiconductor Type Sensors


A/592-R Room $36.00
A/592-RS Room w/ Setpoint $43.00
A/592-RO Room w/ Override $43.00
A/592-RSO Room w/ Setpoint & Override $51.00
-(DF) or -(DC) LCD can be added to above sensors $105.00
A/592-D-( ) *Duct (4”, 8”, 12”, 18”) $42.00
A/592-I-( ) *Immersion (2”, 4”, 6”) $74.00
A/592-S *Strap-On $43.00
A/592-O Outdoor Air $46.00
A/592-W Raw $28.50
A/592-RP Remote Probe $38.50
A/592-SP Stainless Plate $36.00
A/592-A-8' *Averaging 8' $175.00
A/592-A-12' *Averaging 12' $187.00
A/592-A-24' *Averaging 24' $300.00
A/592-BP Bullet Probe $32.00
A/592-DO Duct without Box $39.50

LM34 Series Semiconductor Type Temperature Sensor


A/34-R Room $50.00
A/34-RS Room w/ Setpoint $58.00
A/34-RO Room w/ Override $58.00
A/34-RSO Room w/ Setpoint & Override $64.00
A/34-D-( ) *Duct (4”, 8”, 12”, 18”) $55.00
A/34-I-( ) *Immersion (2”, 4”, 6”) $80.00
A/34-S *Strap-On $58.00
A/34-O Outdoor Air $60.00
A/34-SP Stainless Plate $50.00

LM334 Series Semiconductor Type Temperature Sensor


A/334-R Room $35.00
A/334-RS Room w/ Setpoint $40.00
A/334-RO Room w/ Override $40.00
A/334-RSO Room w/ Setpoint & Override $43.00
A/334-D- ( ) *Duct (4”, 8”, 12”, 18”) $42.00
A/334-I-( ) *Immersion (2”, 4”, 6”) $67.00
A/334-S *Strap-On $40.00
A/334-O Outdoor Air $43.00
A/334-SP Stainless Plate $35.00

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
* Add $10.00 for Polycarbonate NEMA 4X Enclosure PL-5
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List

100 & 1000 Ohm Temperature Transmitters


A/TT100-R Room $90.00
A/TT100-RS Room w/ Setpoint $96.00
A/TT100-RO Room w/ Override $96.00
A/TT100-RSO Room w/ Setpoint & Override $101.75
-(DF) or -(DC) LCD can be added to above sensors $105.00
A/TT100-D-( ) *Duct (4”, 8”, 12”, 18”) $97.20
A/TT100-I-( ) *Immersion (2”, 4”, 6”) $122.20
A/TT100-S *Strap-On $97.20
A/TT100-O Outdoor Air $107.50
A/TT100-A-( ) *Averaging (12', 24') $231.25
A/TT100-RA-( ) *Rigid Averaging (18" 24”, 36”) $221.25
A/TT100-SP Stainless Plate $91.00

A/TT1K-R Room $96.50


A/TT1K-RS Room w/ Setpoint $102.50
A/TT1K-RO Room w/ Override $102.50
A/TT1K-RSO Room w/ Setpoint & Override $108.25
-(DF) or -(DC) LCD can be added to above sensors $105.00
A/TT1K-D-( ) *Duct (4”, 8”, 12”, 18”) $103.50
A/TT1K-I-( ) *Immersion (2”, 4”, 6”) $128.50
A/TT1K-S *Strap-On $103.50
A/TT1K-O Outdoor Air $113.50
A/TT1K-A-( ) *Averaging (12', 24') $256.25
A/TT1K-RA-( ) *Rigid Averaging (18", 24”, 36”) $246.25
A/TT1K-SP Stainless Plate $97.50

100 & 1000 Ohm Matched Temperature Transmitters


A/TTM100-R Room $120.00
A/TTM100-RS Room w/ Setpoint $126.00
A/TTM100-RO Room w/ Override $126.00
A/TTM100-RSO Room w/ Setpoint & Override $131.75
-(DF) or -(DC) LCD can be added to above sensors $105.00
A/TTM100-D-( ) *Duct (4”, 8”, 12”, 18”) $127.20
A/TTM100-I-( ) *Immersion (2”, 4”, 6”) $152.20
A/TTM100-S *Strap-On $127.20
A/TTM100-O Outdoor Air $137.50
A/TTM100-A-( ) *Averaging (12', 24') $261.25
A/TTM100-RA-( ) *Rigid Averaging (18", 24”, 36”) $251.25
A/TTM100-SP Stainless Plate $121.00

A/TTM1K-R Room $126.50


A/TTM1K-RS Room w/ Setpoint $132.50
A/TTM1K-RO Room w/ Override $132.50
A/TTM1K-RSO Room w/ Setpoint & Override $138.25
-(DF) or -(DC) LCD can be added to above sensors $105.00
A/TTM1K-D-( ) *Duct (4”, 8”, 12”, 18”) $133.50
A/TTM1K-I-( ) *Immersion (2”, 4”, 6”) $158.50
A/TTM1K-S *Strap-On $133.50
A/TTM1K-O Outdoor Air $143.50
A/TTM1K-A-( ) *Averaging (12', 24') $286.25
A/TTM1K-RA-( ) *Rigid Averaging (18", 24”, 36”) $276.25
A/TTM1K-SP Stainless Plate $127.50

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
PL-6 * Add $10.00 for Polycarbonate NEMA 4X Enclosure
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List

High Temperature Transmitters


A/TT100-HT-D-( ) *Duct (4”, 8”, 12”, 18”) $230.00
A/TT100-HT-I-( ) *Immersion (2”, 4”, 6”) $255.00
A/TT100-HT-RP) *Remote Probe $230.00

A/TT1K-HT-D-( ) *Duct (4”, 8”, 12”, 18”) $235.00


A/TT1K-HT-I-( ) *Immersion (2”, 4”, 6”) $260.00
A/TT1K-HT (RP) *Remote Probe $235.00

Low Temperature Transmitters


A/TT100-LT-D-( ) *Duct (4”, 8”, 12”, 18”) $230.00
A/TT100-LT-I-( ) *Immersion (2”, 4”, 6”) $255.00
A/TT100-LT-RP *Remote Probe $230.00
A/TT100-LT-O Outdoor Air $240.00

A/TT1K-LT-D-( ) *Duct (4”, 8”, 12”, 18”) $235.00


A/TT1K-LT-I-( ) *Immersion (2”, 4”, 6”) $260.00
A/TT1K-LT-RP *Remote Probe $235.00
A/TT1K-LT-O Outdoor Air $245.00

Submersible Cryogenic Temperature Sensors and Transmitters


A/1K-LTS-RP Remote Probe w/ 6' Leads $135.00
A/TT1K-LTS-RP Remote Probe w/ 6' Leads $240.00
A/TTM1K-LTS-RP Remote Probe w/ 6' Leads $260.00
A/GLYCOL BOTTLE Matched Nalgene TM Bottle 4 oz $15.00

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
* Add $10.00 for Polycarbonate NEMA 4X Enclosure PL-7
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List
5% Relative Humidity Transmitters
A/RH5-R Room $187.20
A/RH5-D *Duct $192.40
A/RH5-O Outdoor $192.40
A/RH5-SP Stainless Plate $192.40
3% Relative Humidity Transmitters
A/RH3-R Room $270.00
A/RH3-D *Duct $280.00
A/RH3-O Outdoor $290.00
A/RH3-SP Stainless Plate $290.00
2% Relative Humidity Transmitters
A/RH2-R Room $350.00
A/RH2-D *Duct $360.00
A/RH2-O Outdoor $370.00
A/RH2-SP Stainless Plate $370.00
1% Relative Humidity Transmitters
A/RH1-R-( ) Room (Choose 20% Span) $550.00
A/RH1-D-( ) *Duct (Choose 20% Span) $560.00
A/RH1-O-( ) Outdoor (Choose 20% Span) $570.00
A/RH1-SP Stainless Plate (Choose 20% Span) $570.00

Humidity/Temperature Sensor Combinations


A/RH5-(Any Thermistor)-R Room $197.20
A/RH5-(Any Thermistor)-D *Duct $206.40
A/RH5-(Any Thermistor)-O Outdoor $206.40
A/RH5-(Any Thermistor)-SP Stainless Plate $206.40
A/RH3-(Any Thermistor)-R Room $280.00
A/RH3-(Any Thermistor)-D *Duct $294.00
A/RH3-(Any Thermistor)-O Outdoor $304.00
A/RH3-(Any Thermistor)-SP Stainless Plate $304.00
A/RH2-(Any Thermistor)-R Room $360.00
A/RH2-(Any Thermistor)-D *Duct $374.00
A/RH2-(Any Thermistor)-O Outdoor $384.00
A/RH2-(Any Thermistor)-SP Stainless Plate $384.00

Humidity/Temperature Transmitter Combinations


A/RH5-TT100-R Room $277.20
A/RH5-TT100-D *Duct $289.40
A/RH5-TT100-O Outdoor $301.00
A/RH5-TT1K-R Room $283.70
A/RH5-TT1K-D *Duct $296.00
A/RH5-TT1K-O Outdoor $306.00
A/RH3-TT100-R Room $360.00
A/RH3-TT100-D *Duct $377.20
A/RH3-TT100-O Outdoor $397.50
A/RH3-TT1K-R Room $366.50
A/RH3-TT1K-D *Duct $383.50
A/RH3-TT1K-O Outdoor $403.50
A/RH2-TT100-R Room $440.00
A/RH2-TT100-D *Duct $457.20
A/RH2-TT100-O Outdoor $477.50
A/RH2-TT1K-R Room $446.50
A/RH2-TT1K-D *Duct $463.50
A/RH2-TT1K-O Outdoor $483.50

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
PL-8 * Add $10.00 for Polycarbonate NEMA 4X Enclosure
Price
Price List
List

ACI
AC I
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List

Pressure Transmitters
A/LP Low Differential Pressure Transmitter $166.00
A/DP Field Selectable Low Differential Pressure Transmitter $320.00

Pitot Tubes
A/PT 3 5/32" Pitot Tube w/1 sensing point $36.00
A/PT 5 13/32" Pitot Tube w/2 sets of sensing points. $40.00
A/PT 7 21/32" Pitot Tube w/3 sets of sensing points $48.00
A/PT 9 29/32" Pitot Tube w/4 sets of sensing points $56.00

For use with AFS Pressure Switches:


A/SPT 3” Pitot Tube for sensing Static Pressure $8.00
A/SPT 8" Pitot Tube for sensing Static Pressure $20.00
A/VPT Pitot Tube for sensing Velocity Pressure $8.00

Gage Pressure and Wet to Wet


A/GP Series 4 to 20 mA Gage Pressure Transmitters $285.00
A/GP-4 above sensor in NEMA 4 Housing $410.00
A/629 Wet to Wet Differential Pressure Transducer $815.00
A/629-3V above sensor w/3 Valve Manifold $1,145.00
A/629-D A/629 w/LED Display $1,100.00
A/WP Wet to Wet Differential Pressure Transducer Consult Factory
A/WP-3V above sensor w/3-Valve Manifold Consult Factory
A/Snubber 316 Stainless Steel Snubber (Gauge Protector) $74.00

Pressure Switches
A/AFS-222 0.07 to 12" H2O w/ Automatic Reset $52.00
A/AFS-262 0.07 to 2" H2O w/ Automatic Reset $56.00
A/AFS-460 0.06 to 12" H2O w/ Manual Reset $90.00

* Add $5.00 for Aluminum Weatherproof NEMA 3R Enclosure (Not available for strap-on configurations)
* Add $10.00 for Polycarbonate NEMA 4X Enclosure PL-9
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List

Current Sensors
Solid Core, N/O, "Go/No Go" Current Switch
A/CS 0.5A Trip, 0-250 Amp Operating Range $58.00
A/CS-L 0.1A Trip, 0-250 Amp Operating Range $64.00
A/CSX 0.5 A Trip, 0-250 Amp Operating Range $58.00
A/CSX-L 0.1 A Trip, 0-250 Amp Operating Range $64.00

Split Core, "Go/No Go" Current Switch


A/SCS N/O Trip = 1.5 Amps $65.00
A/SCS-L N/O Trip = 1.0 Amps $71.00
A/SCSX N/C Trip = 1.5 Amps $65.00

Solid Core Adjustable Current "Status" Switch


A/ACS N/O, 0.80-250A $97.00
A/ACS-L N/O, 0.35-250A $103.00
A/ACSX N/C, 0.80-250A $97.00

Split Core, Adjustable Current Switch


A/ASCS N/O, Trip = 2.0 - 250 Amps $100.00
A/ASCS-L N/O, Trip = 1.7 - 250 Amps $106.00
A/ASCSX N/C, Trip = 2.0 - 250 Amps $100.00
A/ASCSX-L N/C, Trip = 1.7 to 250 Amps $106.00

Solid Core Loop Powered Current Sensor


A/CTA-5 4-20mA output, 0-5 Amps Fixed Input $120.00
A/CTA-50 4-20mA output, 0-10/0-20/0-50 Amps $100.00
A/CTA-250 4-20mA output, 0-100/0-200/0-250 Amps $100.00

Split Core Loop Powered Current Sensor


A/SCTA-5 4-20mA Output, 0-5 Amps Fixed Input $130.00
A/SCTA-50 4-20mA Output, 0-10/0-20/0-50 Amps $110.00
A/SCTA-200 4-20mA Output, 0-100/0-150/0-200 Amps $110.00

Solid Core Loop Powered, True RMS, Current Sensor


A/CTA-5-VFD 4-20mA Output 0-5 Amps Fixed Input $160.00
A/CTA-50-VFD 4-20mA Output, 0-10/0-20/0-50 Amps $140.00
A/CTA-250-VFD 4-20mA Output, 0-100/0-200/0-250 Amps $140.00

Split Core Loop Powered, True RMS, Current Sensor


A/SCTA-5-VFD 4-20mA Output, 0-5 Amps Fixed Input $170.00
A/SCTA-50-VFD 4-20mA Output, 0-10/0-20/0-50 Amps $150.00
A/SCTA-200-VFD 4-20mA Output, 0-100/0-150/0-200 Amps $150.00

Solid Core Current Sensor


A/CTE-50 0-5VDC Output, 0-10/0-20/0-50 Amps $83.00
A/CTE-250 0-5VDC Output, 0-100/0-200/0-250 Amps $83.00
A/CTV-50 0-10VDC Output, 0-10,0-20, 0-50 Amps $83.00
A/CTV-250 0-10VDC Output, 0-100, 0-200, 0-250 Amps $83.00

Split Core Current Sensor


A/SCTE-50 0-5VDC Output, 0-10/0-20/0-50 Amps $100.00
A/SCTE-250 0-5VDC Output, 0-100/0-200/0-250 Amps $100.00
A/SCTV-50 0-10VDC Output, 0-10/0-20/0-50 Amps $100.00
A/SCTV-250 0-10VDC Output, 0-100/0-200/0-250 Amps $100.00

PL-10
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List

Gas/Smoke Detectors
Electrochemical CO Transmitter
A/CO-R Room $450.00
A/CO-R-4X Room w/NEMA 4X ENC $525.00
A/CO-R-LCD Includes Buzzer Alarm and two SPDT Relay's $550.00
A/CO-D Duct w/ Pitot Tube $525.00
A/CO-R-4X-RB Room w/NEMA 4X, Relays and Buzzer $675.00
Other Gas Transmitters available: Oxygen, Nitrogen Dioxide, Nitric Oxide and Ammonia. Consult Factory

CO2 Transmitter (0-10VDC only)


A/CO2-010-R Room $340.00
A/CO2-010-R-L Room w/ LED $355.00
A/CO2-010-D Duct $360.00

Analog CO2 Transmitter w/ Relay, 0-10 VDC and 4 to 20 mA ouputs


A/CO2-R Room $500.00
A/CO2-R-LCD Room w/ LCD Display $540.00
A/CO2-D Duct w/ Pitot Tube and LCD $550.00
-1508 1508 Enclosure add $105.00
A/CO2-T-RO CO2 w/ Temperature & Override $550.00
A/CO2-T-RSO CO2 w/ Temp.,Set, & Override $565.00

A/SM501 Series Duct Smoke Detectors $195.00


A/SL-2000 Series Duct Smoke Detectors $195.00
A/STS-1.0' 1.0' Sampling Tube for Duct Smoke Detector $9.50
A/STS-2.5' 2.5' Sampling Tube for Duct Smoke Detector $12.00
A/STS-5.0' 5.0' Sampling Tube for Duct Smoke Detectors $16.00
A/STS-10' 10.0' Sampling Tube for Duct Smoke Detectors $22.00

PL-11
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List

Accessories
A/PS 1.5 Adjustable Power Supply $43.00
A/LLS Resistive Light Level Sensor 1/2" NPT Clear Head $37.50
A/LLS-T Light Level Transmitter NEMA 4 Bell Box $120.00
A/FS-1 (1) SPDT, 20', Manual Reset Freeze Stat $150.00
A/FS-1A (1) SPDT, 20', Auto Reset Freeze Stat $138.00
A/FS-2 (2) SPDT, 20', Manual Reset Freeze Stat $184.00
A/FS-2A (2) SPDT, 20', Auto Reset Freeze Stat $173.00
A/FS-3 (1) SPDT, 10', Manual Reset Freeze Stat $146.25
A/FS-3A (1) SPDT, 10', Auto Reset Freeze Stat $134.00
A/FS-4 (2) SPDT, 10', Manual Reset Freeze Stat $179.00
A/FS-4A (2) SPDT, 10', Auto Reset Freeze Stat $168.00
A/FS-5 (1) SPDT, 6', Manual Reset Freeze Stat $144.00
A/FS-5A (1) SPDT, 6', Auto Reset Freeze Stat $133.00
A/FS-6 (2) SPDT, 6', Manual Reset Freeze Stat $177.00
A/FS-6A (2) SPDT, 6', Auto Reset Freeze Stat $165.00
A/DBZ-05 Capillary Mounting Brackets $11.00
A/DBZ-07 Housing Mounting Bracket $8.50
A/2.5" Stainless Steel Two-Piece Thermowell $24.00
A/4" Stainless Steel Two-Piece Thermowell $26.00
A/6" Stainless Steel Two-Piece Thermowell $30.00
A/M4" Machined Stainless Steel Thermowell $65.00
A/M6" Machined Stainless Steel Thermowell $75.00
A/SG Silicon Thermal Grease 8oz Tube $87.82
A/NSG Non-Silicon Thermal Grease 2oz Tube $33.00
A/WS Weather Station $170.00
A/WSMP Weather Station Mounting Plate $6.50
A/PS Clear Plexishield $45.00
A/LOCKING COVER Locking Cover for room enclosures $15.00
A/MOUNTING PLATE Plastic Wall Mounting Plate $22.00
A/MOUNTING PLATE 10 Steel Wall Mounting Plate $18.00

PL-12
Price
Price List
List

ACI
List Pricing from
Automation Components, Inc.
Effective June 1st 2008
“First in Sensor Quality”
Model No. List

Interface Devices
Pressure to Current/Voltage
A/PTP 3 to 15 or 3 to 30 psi* $90.00
A/PTP-G 3 to 15 or 3 to 30 psi w/Gauge* $100.00

Analog to Pressure
A/PXP 0,1,5,7.3 Single Valve Control* $141.00
A/PXP0,1,5,7.3-G Above w/Gauge* $154.00
A/PXP2.3 Dual Valve Control* $178.00
A/PXP2.3-G Above w/Gauge* $191.00
A/PXP2.3 FS A/PXP2.3 w/"Fail Safe"* $248.00
A/PXP2.3 FSG Above w/Gauge* $259.00
A/EPC Field Adjustable Single Valve Control* $148.00
A/EPC-G Field Adjustable Single Valve Control w/Gauge* $160.00
A/EPC2 Field Adjustable Dual Valve Control* $184.00
A/EPC2-G Field Adjustable Dual Valve Control w/Gauge* $195.00
A/EPC2 FS A/EPC2 "Fail Safe" Control* $238.00
A/EPC2 FS-G Above w/Gauge* $252.00

Pulse to Pressure
A/EPW Single Valve Control* $207.00
A/EPW-G Above w/Gauge* $218.00
A/EPW2 Dual Valve Control* $254.00
A/EPW2-G Above w/Gauge* $265.00
A/EPW2 FS "Fail Safe" Dual Valve Control* $298.00
A/EPW2 FS-G Above w/Gauge* $308.00

Interface Devices
A/ARM Analog Re-Scaling Module* $90.00
A/ARM2 Dual Output Analog Re-Scaling Module* $118.00
A/AIM1 Analog Isolation Module* 1:1 Input/Output Ratio $186.00

A/AIM2 Re-Scaleable Isolation Module* $215.00


A/AAR Analog Input to (2) Adjustable Relay Outputs* $98.00
A/ATL Analog Input to (4) Adjustable Relay Outputs* $142.00
A/PTA Digital Pulse Input to Analog Output* $112.00
A/PTA2 Digital Pulse Input to 0-10VDC Output Only* $90.00
A/DRN3.1 Multiple Input/Resistive Output* $260.00
A/DRN4 Multiple Input/Resistive Output -Motor Mount $304.00
(0 to 135 Ohm Only)

* Snap Track Mount standard Add $12.00 for Optional ENC1 Enclosure