FC 280 Profinet Programming Guide MG07G102
FC 280 Profinet Programming Guide MG07G102
Programming Guide
VLT® PROFINET
VLT® Midi Drive FC 280
vlt-drives.danfoss.com
Contents Programming Guide
Contents
1 Introduction 3
1.1 Purpose of the Manual 3
1.2 Additional Resources 3
1.3 Document and Software Version 3
1.4 Product Overview 3
1.5 Approvals and Certifications 4
1.6 Symbols, Abbreviations and Conventions 4
2 Safety 5
2.1 Safety Symbols 5
2.2 Qualified Personnel 5
2.3 Safety Precautions 5
3 Configuration 7
3.1 Configure the PROFINET Network 7
3.2 Configure the Controller 7
3.3 Configure the Frequency Converter 9
4 Control 10
4.1 PPO Types 10
4.2 Process Data 11
4.3 Control Profile 13
4.4 PROFIdrive Control Profile 14
4.5 FCDrive Control Profile 18
6 Parameters 26
6.1 Parameter Group 0-** Operation/Display 26
6.2 Parameter Group 8-** Communication and Option 26
6.3 Parameter Group 9-** PROFIdrive 28
6.4 Parameter Group 12-** Ethernet 32
6.5 PROFINET-specific Parameters 34
7 Application Examples 40
7.1 Example: Process Data with PPO Type 6 40
7.2 Example: Control Word Telegram Using Standard Telegram 1/PPO3 41
7.3 Example: Status Word Telegram Using Standard Telegram 1/PPO3 42
7.4 Example: PLC Programming 43
8 Troubleshooting 44
8.1 No Response to Control Signals 44
8.2 Warnings and Alarms 46
Index 53
1 Introduction 1 1
Software
Edition Remarks
version
MG07G1xx The first edition of this manual. 3.0x
Conventions
Numbered lists indicate procedures.
Bullet lists indicate other information and description of
illustrations.
Italicized text indicates:
• Cross reference.
• Link.
• Parameter name.
2 Safety
2 2
2.1 Safety Symbols WARNING
The following symbols are used in this guide: UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
WARNING time. Unintended start during programming, service, or
Indicates a potentially hazardous situation that could repair work can result in death, serious injury, or
result in death or serious injury. property damage. The motor can start with an external
switch, a fieldbus command, an input reference signal
CAUTION from the LCP or LOP, via remote operation using MCT 10
Set-up Software, or after a cleared fault condition.
Indicates a potentially hazardous situation that could
To prevent unintended motor start:
result in minor or moderate injury. It can also be used to
alert against unsafe practices. • Press [Off/Reset] on the LCP before
programming parameters.
WARNING
LEAKAGE CURRENT HAZARD
2 2 Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
• Ensure the correct grounding of the equipment
by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
• Ensure that only trained and qualified personnel
perform installation, start-up, and maintenance.
• Ensure that electrical work conforms to national
and local electrical codes.
• Follow the procedures in this document.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury when the frequency converter is not
properly closed.
• Ensure that all safety covers are in place and
securely fastened before applying power.
3 Configuration
130BE928.10
Ensure that all PROFINET devices connected to the same
bus network have a unique station name (host name).
3 3
Set the PROFINET host name of the frequency converter
via parameter 12-08 Host Name or hardware switches.
To configure a PROFINET controller, the configuration tool Illustration 3.2 Add a New GSDML File to the Simatic Manager
needs a GSDML file for each type of device on the Software Tool
network. The GSDML file is a PROFINET xml file containing
the necessary communication set-up data for a device.
Download the latest version of GSDML files for the FC 280
The FC 280 GSDML file is now imported and is accessible
frequency converter at www.danfoss.com/BusinessAreas/
via the following path in the hardware catalog:
DrivesSolutions/profinet. The name of the GSDML file may
differ from what is described in this manual.
130BE936.10
The following example shows how to configure the
controller for FC 280.
Illustration 3.1 Import the GSDML File in the Configuration To enter the device name, open the properties for the
Tool inserted frequency converter. See Illustration 3.4.
130BE932.10
130BE930.10
3 3
Illustration 3.6 Set up the Peripheral Input and Output Data
PPO type 6
NOTICE
The name must match the name in parameter 12-08 Host PCD word
0 1 2 3
Name. If the check mark Assign IP address via the IO number
controller is set, the controller downloads the IP address Input
to the IO device with the corresponding device name. 256–257 258–259 260–261 262–263
address
The IP address is stored in the non-volatile memory of Parameter 9-16 Parameter 9-16
the frequency converter. Set-up STW MAV PCD Read PCD Read
Configuration Configuration
130BE931.10
PCD word
0 1 2 3
number
Output
256–257 258–259 260–261 262–263
address
Parameter 9-15 Parameter 9-15
Set-up CTW MRV PCD Write PCD Write
Configuration Configuration
3 3
the frequency converter with a PROFINET interface.
NOTICE
When parameter 8-01 Control Site is set to [2] Control
word only, the settings from parameter 8-50 Coasting
Select to parameter 8-58 Profidrive OFF3 Select are
overruled and only act on bus control.
4 Control
4.1 PPO Types The setting in parameter 9-15 PCD Write Configuration
determines the signals for transmission (request) from the
The PROFINET profile for frequency converters specifies a master to the frequency converter.
number of standard telegrams and provides space for
The setting in parameter 9-16 PCD Read Configuration
vendor-specific telegrams. The PROFIdrive profile for
determines the signals for transmission (response) from the
4 4 frequency converters is suitable for data exchange
between a process controller (for example PLC) and a
frequency converter to the master.
frequency converter. All telegrams are defined for cyclic Select the PPO type in the master configuration. The
data transfer of high-priority data. selection is automatically recorded in the frequency
converter. No manual setting of PPO types in the
Pure process data objects frequency converter is required. Read the current PPO type
PPO types 3, 4, 6, 7, and 8 are pure process data objects in parameter 9-22 Telegram Selection. The setting [1]
for applications requiring no cyclic parameter access. The Standard telegram 1 is equivalent to PPO type 3.
PLC sends out process control data, and the frequency
converter then responds with a PPO of the same length, In addition, all PPO types can be set up as word-consistent
containing process status data. or module-consistent. The process data area can be word-
or module-consistent, whereas the parameter channel
Illustration 4.1 shows the available PPO types:
must always be module-consistent.
• PCD 1: The first 2 bytes of the process data area
(PCD 1) comprise a fixed part present in all PPO • Word-consistent data is transmitted as individual,
types. independent words between the PLC and the
• PCD 2: The next 2 bytes are fixed for PCD write frequency converter.
entries (see parameter 9-15 PCD Write Configu- • Module-consistent data is transmitted as sets of
ration [1]), but configurable for PCD read entries interrelated words transferred simultaneously
(see parameter 9-16 PCD Read Configuration [1]). between the PLC and the frequency converter.
• PCD 3–10: In the remaining bytes, the process
data can be parameterized with process signals,
see parameter 9-23 Parameters for Signals.
Standard telegram
130BE941.10
1 CTW/STW REF/MAV (The old PPO type 3)
Danfoss telegram
PCD 2 PCD 3
PPO 6 CTW/STW REF/MAV Read/ Read/
Write Write
4.2 Process Data The PCD part responds according to the state and parame-
terization of the frequency converter.
Use the process data part of the PPO to control and
monitor the frequency converter via the PROFIBUS. PCD part response:
• STW: 0F07 hex means that the motor is running
4.2.1 PCD and there are no warnings or faults.
• MAV: 2000 hex indicates that the output
Control word (CTW) according to PROFIdrive profile: frequency is 50% of the maximum reference.
Control words consist of 16 bits. The meaning of each bit
is explained in chapter 4.4.1 Control Word According to Table 4.3 shows a negative response to the request 4 4
PROFIdrive Profile (CTW) and chapter 4.4.2 Status Word example from Table 4.1.
According to PROFIdrive Profile (STW). The following bit
pattern sets all necessary start commands: Byte Value
0000 0100 0111 1111 = 047F hex.1) STW 9 0F
0000 0100 0111 1110 = 047E hex.1) STW 10 07
PCD
0000 0100 0111 1111 = 047F hex. MAV 11 20
MAR 12 00
1) For restart after power-up:
Table 4.3 Response Example: Negative Response
• Set bits 1 and 2 of the CTW to 1.
• Toggle bit 0 0–1. 4.2.3 Process Control Data
These values are for bytes 9 and 10 in Table 4.1.
Quick stop: 0000 0100 0110 1111 = 046F hex. Process control data (PCD) is the process data sent from
Stop: 0000 0100 0011 1111 = 043F hex. the PLC to the frequency converter.
Table 4.6 lists the reference (MRV) and the feedback (MAV)
formats.
The reference (MRV) and feedback (MAV) are always scaled Table 4.6 Reference/Feedback (MRV/MAV) Format
equally. The setting of parameter 3-00 Reference Range
determines the scaling of the reference and feedback NOTICE
(MAV), see Illustration 4.3. Negative numbers are formed as complement of 2.
NOTICE
The data type for MRV and MAV is an N2 16-bit
standardized value, expressing a range from -200% to
+200% (8001 to 7FFF).
Example NOTICE
The following settings determine the speed, as shown in To control the frequency converter via PROFIBUS, set
Table 4.7: parameter 8-50 Coasting Select to either [1] Bus or [2]
• Parameter 1-00 Configuration Mode set to [0] Logic AND. Then set parameter 8-01 Control Site to [0]
Speed open loop. Digital and ctrl.word or [2] Controlword only.
NOTICE
The setting of parameter 8-01 Control Site overrules the
settings in parameter 8-50 Coasting Select to
parameter 8-58 Profidrive OFF3 Select.
Illustration 4.4 shows the basic state transition diagram where control bits 0–3 control the transitions, and the corresponding
status bit indicates the actual state. The black bullets indicate the priority of the control signals where fewer bullets indicate
lower priority, and more bullets indicate higher priority. 4 4
130BD806.10
Illustration 4.4 PROFIdrive State Transition Diagram
4 4
Input) programmed to DC braking, coasting stop, 1 0
or reset and coasting stop. 2 1
An IO device consists of a number of physical or virtual slots. Slot 0 is always present and represents the basic unit. Each
slot contains a number of data blocks addressed by an index.
The master must address a variable in the slave as follows: /Slave address/Slot #/Index #
5 5
5 5
Initiate a read or write on a frequency converter parameter by an acyclic write service on slot 0, index 47. If this write
request is valid, a positive write response without data is returned from the frequency converter immediately. If not, a
negative write response is returned from the frequency converter.
The frequency converter now interprets the PROFIdrive parameter channel part of the data unit and starts to perform this
command internally in the frequency converter.
As the next step, the master sends a read request. If the frequency converter is still busy performing the internal parameter
request, a negative response without data is returned from the frequency converter. This request is repeated by the master,
until the frequency converter has the response data ready for the frequency converter parameter request.
The following example shows the details of the telegrams needed for the read/write service.
5 5
1 Header Request # Request ID Pointer to the index.
2 Header Axis # Param.
3 (Param. 1) Attribute # Elements
5.8 Data Block
4 (Param. 1) Parameter number
The data block is only needed for write commands. Set up
5 (Param. 1) Subindex number the data block information for each parameter to write.
6 (Param. 2) Attribute # Elements
7 (Param. 2) Parameter number
Format
8 (Param. 2) Subindex number The format of the information to write:
9 (Param. 3) Attribute # Elements 2: Integer 8
10 (Param. 3) Parameter number 3: Integer 16
11 (Param. 3) Subindex number 4: Integer 32
... 5: Unsigned 8
N (Data Param. 1) Format # Elements 6: Unsigned 16
N+1 (Data Param. 1) Data Data 7: Unsigned 32
N (Data Param. 2) Format # Elements 9: Visible string
N+1 (Data Param. 2) Data Data 33: Normalized value 2 bytes
N (Data Param. 3) Format # Elements 35: Bit sequence of 16 boolean variables
N+1 (Data Param. 3) Data Data 54: Time difference without date
N+1 (Data Param. 3) Data Data
For the individual frequency converter series, the
programming guide of the frequency converter contains a
N+1 (Data Param. 3) Data Data
table with parameter number, format, and other relevant
Table 5.1 Request Telegram information.
Data
5.6 Header The actual value to transfer. The amount of data has to be
exactly the size requested in the parameter block. If the
Request number size differs, the request generates an error.
The master uses request # to handle the response from the
IO device. The IO device mirrors this number in its On a successful transmission of a request command, the
response. master can read the response from the frequency
converter. The response does look very much like the
Request ID request command. The response only consists of 2 blocks,
1 = request parameter the header and the data block.
2 = change parameter
Axis 1 Header Request # Request ID
Always leave this to 0 (zero). 2 Header Axis # Param.
Only used in multi-axis system. 3 (Data Param. 1) Format Error code
Number of parameters 4 (Data Param. 1) Data Data
Number of parameters to read or write. 5 (Data Param. 2) Format Error code
6 (Data Param. 2) Data Data
5.7 Parameter Block
7 (Data Param. 3) Format Error code
Provide the following 5 values for each parameter to read. 8 (Data Param. 3) Data Data
9 (Data Param. 3) Data Data
Attribute 10 (Data Param. 3) Data Data
Attribute to be read
Table 5.2 Response Telegram
10 = Value
Error code
If the IO device discovers an error during the execution of
the command, it sets the error code to the following
values:
6 Parameters
Select the source of the control word: 1 of 2 serial [1] Freeze Freezes output frequency until communi-
interfaces or 4 installed options. During initial output cation resumes.
power-up, the frequency converter automatically
[2] Stop Stops with auto restart when communication
sets this parameter to [3] Option A if it detects a
resumes.
valid fieldbus option installed in slot A. When the
option is removed, the frequency converter detects [3] Jogging Runs the motor at jog frequency until
a configuration change, sets parameter 8-02 Control communication resumes.
Word Source to default setting [1] FC RS485, and [4] Max. speed Runs the motor at maximum frequency until
trips. If an option is installed after initial power-up, communication resumes.
the setting of parameter 8-02 Control Word Source
8-07 Diagnosis Trigger [0] Digital A digital input triggers the coasting function.
input
Option: Function:
6 6
[1] Bus A serial communication port or the fieldbus
Enables and controls the frequency converter
triggers the coasting function.
diagnosis function.
[2] Logic AND The fieldbus/serial communication port and a
[0] * Disable Extended diagnosis data is not sent even if
digital input trigger the coasting function.
the data appears in the frequency converter.
[3] * Logic OR The fieldbus/serial communication port or a
[1] Trigger on Extended diagnosis data is sent when 1 or
digital input triggers the coasting function.
alarms more alarms appear.
[2] Trigger Extended diagnosis data is sent if 1 or more 8-51 Quick Stop Select
alarm/warn. alarms/warnings appear.
Select the trigger for the quick stop function.
[2] Logic AND The fieldbus/serial communication port and a [2] Logic AND
digital input trigger the start function. [3] * Logic OR
[3] * Logic OR The fieldbus/serial communication port or a 8-58 Profidrive OFF3 Select
digital input triggers the start function. Option: Function:
[0] Digital input
8-54 Reversing Select
[1] Bus
Option: Function: [2] Logic AND
Select the trigger for the reversing function. [3] * Logic OR
[0] Digital A digital input triggers the reversing function.
6 6 input
8-90 Bus Jog 1 Speed
Range: Function:
[1] Bus A serial communication port or the fieldbus
triggers the reversing function. 100 RPM* [ 0 - 1500 Enter the jog speed. Activate this
RPM] fixed jog speed via the serial port or
[2] Logic AND The fieldbus/serial communication port and a
fieldbus option.
digital input trigger the reversing function.
[3] Logic OR The fieldbus/serial communication port or a 8-91 Bus Jog 2 Speed
digital input triggers the reversing function. Range: Function:
200 RPM* [ 0 - 1500 Enter the jog speed. Activate this
8-55 Set-up Select
RPM] fixed jog speed via the serial port or
Option: Function: fieldbus option.
Select the trigger for the set-up selection.
[0] Digital A digital input triggers the set-up selection. 6.3 Parameter Group 9-** PROFIdrive
input
9-15 PCD Write Configuration
[1] Bus A serial communication port or the fieldbus
triggers the set-up selection. Array [10]
Option: Function:
[2] Logic AND The fieldbus/serial communication port and a
digital input trigger the set-up selection. Select the parameters to be assigned to PCD 3-10 of
the telegrams. The number of available PCDs depends
[3] * Logic OR The fieldbus/serial communication port or a on the telegram type. The values in PCD 3-10 are then
digital input triggers the set-up selection. written to the selected parameters as data values.
Alternatively, specify a standard PROFIBUS telegram in
8-56 Preset Reference Select parameter 9-22 Telegram Selection.
Option: Function:
9-16 PCD Read Configuration
Select the trigger for the preset reference
selection. Array [10]
6 6
[105] PPO 5 [1609] Custom Readout
[106] PPO 6 [1610] Power [kW]
[107] PPO 7 [1611] Power [hp]
[108] PPO 8 [1612] Motor Voltage
[1613] Frequency
9-23 Parameters for Signals
[1614] Motor current
Array [1000]
[1615] Frequency [%]
Read only
[1616] Torque [Nm]
Option: Function: [1618] Motor Thermal
This parameter [1620] Motor Angle
contains a list of [1622] Torque [%]
signals available for [1630] DC Link Voltage
selection in [1633] Brake Energy /2 min
parameter 9-15 PCD
[1634] Heatsink Temp.
Write Configuration
[1635] Inverter Thermal
and
[1638] SL Controller State
parameter 9-16 PCD
[1639] Control Card Temp.
Read Configuration.
[1650] External Reference
[0] * [1652] Feedback[Unit]
[302] Minimum Reference [1653] Digi Pot Reference
[303] Maximum Reference [1657] Feedback [RPM]
[312] Catch up/slow Down Value [1660] Digital Input
[341] Ramp 1 Ramp Up Time [1661] Terminal 53 Setting
[342] Ramp 1 Ramp Down Time [1662] Analog input 53
[351] Ramp 2 Ramp Up Time [1663] Terminal 54 Setting
[352] Ramp 2 Ramp Down Time [1664] Analog input 54
[380] Jog Ramp Time [1665] Analog output 42 [mA]
[381] Quick Stop Ramp Time [1667] Pulse input 29[Hz]
[412] Motor Speed Low Limit [Hz] [1668] Pulse Input 33 [Hz]
[414] Motor Speed High Limit [Hz] [1669] Pulse Output 27 [Hz]
[416] Torque Limit Motor Mode [1671] Relay output
[417] Torque Limit Generator Mode [1672] Counter A
[553] Term. 29 High Ref./Feedb. Value [1673] Counter B
[558] Term. 33 High Ref./Feedb. Value [1674] Prec. Stop Counter
[590] Digital & Relay Bus Control [1680] Fieldbus CTW 1
[593] Pulse Out 27 Bus Control [1682] Fieldbus REF 1
[615] Terminal 53 High Ref./Feedb. Value [1684] Comm. Option STW
[625] Terminal 54 High Ref./Feedb. Value [1685] FC Port CTW 1
[696] Terminal 42 Output Bus Control [1690] Alarm Word
[748] PCD Feed Forward [1691] Alarm Word 2
[890] Bus Jog 1 Speed [1692] Warning Word
[9] * Active Set-up Follows the active set-up selected in Range: Function:
parameter 0-10 Active Set-up. 0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
9-71 Profibus Save Data Values PROFINET.
Option: Function:
9-83 Defined Parameters (4)
Parameter values changed via PROFINET are not
automatically stored in the non-volatile memory. Array [116]
Use this parameter to activate a function that No LCP access
stores parameter values in the EEPROM non- Read only
volatile memory, so changed parameter values Range: Function:
are retained at power-down. 0* [0 - 9999 ] This parameter displays a list of all the defined 6 6
[0] Off Deactivates the non-volatile storage function. frequency converter parameters available for
PROFINET.
[1] Store all Stores all parameter values for all set-ups in the
setups non-volatile memory. When all parameter values
9-84 Defined Parameters (5)
have been stored, the selection returns to [0] Off.
Array [115]
[2] Store all Stores all parameter values for all set-ups in the No LCP access
setups non-volatile memory. When all parameter values Read only
have been stored, the selection returns to [0] Off.
Range: Function:
9-72 ProfibusDriveReset 0* [0 - 9999] This parameter displays a list of all the defined
frequency converter parameters available for
Option: Function:
PROFINET.
[0] * No action
[1] Power-on Resets frequency converter upon power-up, 9-90 Changed Parameters (1)
reset as for power-cycle.
Array [116]
[3] Comm Resets the PROFINET option only, the No LCP access
option reset PROFINET option goes through a power-up Read only
sequence. Range: Function:
When reset, the frequency converter
0* [0 - 9999 ] This parameter shows a list of all the frequency
disappears from the fieldbus, which may
converter parameters deviating from default
cause a communication error from the
setting.
master.
Index [0] is used for port 1, and index [1] is used for port
12-03 Default Gateway
2.
Range: Function:
0* [0 - Configure the IP default gateway of the 12-10 Link Status
2147483647 ] option. Read-only, if parameter 12-00 IP Option: Function:
Address Assignment is set to DHCP or Read-only. Shows the link status of the Ethernet
BOOTP. In a non-routed network, this ports.
address is set to the IP address of the IO
[0] * No Link
Device.
[1] Link
6 6
is set to [1] On, this parameter is read-only and Option: Function:
displays the actual link speed. If no link is
present, None is displayed.
NOTICE
The cable diagnostics function is only
[0] * None
issued on ports where there is no link (see
[1] 10 Mbps parameter 12-10 Link Status, Link Status).
[2] 100
Mbps
Enables/disables advanced cable diagnosis
NOTICE function. If enabled, the distance to cable errors
can be read out in parameter 12-93 Cable Error
In POWERLINK, this parameter is locked to 100 Mbs.
Length. The parameter resumes to the default
setting of disable after the diagnostics have
12-14 Link Duplex finished.
Option: Function:
[0] * Disabled
NOTICE [1] Enabled
In POWERLINK, this parameter is locked
to half duplex. 12-91 Auto Cross Over
Option: Function:
Forces the duplex for each port to full or half [0] Disabled Disables the auto cross over function.
duplex. If parameter 12-12 Auto Negotiation is [1] * Enabled Enables the auto cross over function.
set to [1] On, this parameter is read-only.
[0] * Disabled Disables the built-in FTP server. [1] * Enabled Enables the IGMP snooping function.
parameter 12-05 Lease Expires. If lease time is set to 0 Parameter 12-13 Link Speed displays/sets the link speed for
(zero), the timer never expires. each port. If no link is present, None is displayed.
Parameter 12-09 Physical Address reads out the MAC Parameter 12-14 Link Duplex displays/sets the duplex mode
address of the option, which is also printed on the label of for each port.
the option.
NOTICE
It is only possible to assign valid class A, B, and C IP
addresses to the option. The valid ranges are shown in
Table 6.4.
6 6
Class A 1.0.0.1-126.255.255.254
Class B 128.1.0.1-191.255.255.254
Class C 192.0.1.1-223.255.254.254
Conversion
Parameter Default value Range Data type
index
Parameter 0-37 Display Text 1 0 [0-25] 0 Visible string 21
Parameter 8-01 Control Site [0] Dig. & ctrl. word [0-2] – Uint8
Parameter 8-02 Control Source – [0-3] – Uint8
Parameter 8-03 Control Timeout Time 1 0.1-6000 -1 Uint16
Parameter 8-04 Control Timeout Function [0] Off [0-5] – Uint8
Parameter 8-07 Diagnosis Trigger [0] Disable [0-2] – Uint8
Parameter 8-10 Control Word Profile [0] FC profile [0-7] – Uint8
Parameter 8-14 Configurable Control
[1] Profile default [0-6] – Uint8
Word CTW
Parameter 8-19 Product Code – 0-2147483647 0 Uint32
Conversion
Parameter Default value Range Data type
index
Parameter 12-09 Physical Address 0 0-17 – Visible string 17
Parameter 12-10 Link Status [0] No Link [0-1] – Uint8
Parameter 12-11 Link Duration – 0-0 – Time diff. w/date
Parameter 12-12 Auto Negotiation [1] On [0-1] – Uint8
Parameter 12-13 Link Speed [0] None [0-2] – Uint8
Parameter 12-14 Link Duplex [1] Full Duplex [0-1] – Uint8
Parameter 12-80 FTP Server [0] Disabled [0–1] – Uint8
Parameter 12-81 HTTP Server [0] Disabled [0–1] – Uint8
Parameter 12-82 SMTP Service [0] Disabled [0–1] – Uint8
Parameter 12-89 Transparent Socket
– 0-65535 0 Uint16
Channel Port
Parameter 12-90 Cable Diagnostic [0] Disabled [0-1] – Uint8
Parameter 12-91 Auto Cross Over
Parameter 12-92 IGMP Snooping
[1] Enabled
[1] Enabled
[0-1]
[0-1]
–
–
Uint8
Uint8
6 6
Parameter 12-93 Cable Error Length 0 0-65535 0 Uint16
Parameter 12-94 Broadcast Storm
-1% -1–20% 0 Int8
Protection
Parameter 12-95 Broadcast Storm Filter [0] Broadcast only [0-1] – Uint8
Parameter 12-96 Port Config – [0-255] – Uint8
Parameter 12-98 Interface Counters 4000 0-4294967295 0 Uint32
Parameter 12-99 Media Counters 0 0-4294967295 0 Uint32
The size index and the conversion index for each parameter can be taken from the parameter list in the respective operating
guide.
Physical unit Size index Measuring unit Designation Conversion index Conversion factor
0 No dimension
second s 0 1
6 6 -1
-2
0.1
0.01
Time 4 millisecond ms -3 0.001
minute min 70 60
hour h 74 3600
day d 77 86400
watthour Wh 0 1
Energy 8 kilowatthour kWh 3 1000
megawatthour MWh 6 106
milliwatt mW -3 0.001
watt W 0 1
Power 9
kilowatt kW 3 1000
megawatt MW 6 106
Rotation 11 rotation per minute RPM 67 1
newtonmetre Nm 0 1
Torque 16
kilonewtonmetre kNm 3 1000
Temperature 17 degree Celsius ºC 0 1
millivolt mV -3 0.001
Voltage 21 volt V 0 1
kilovolt kV 3 1000
milliampere mA -3 0.001
Current 22 ampere A 0 1
kiloampere kA 3 1000
milliohm mOhm -3 0.001
Resistance 23 ohm Ohm 0 1
kiloohm kOhm 3 1000
Ratio 24 per cent % 0 1
Relative change 27 per cent % 0 1
hertz Hz 0 1
kilohertz kHz 3 1000
Frequency 28
megahertz MHz 6 106
gigahertz GHz 9 109
7 Application Examples
0 1 2 3
CTW MRV PCD [2] PCD
From controller 04 7C 20 00 00 00 00 00
STW MAV PCD [2] PCD [3]
From frequency
0F 07 20 00 3F A6 00 08
converter
Byte # 1 2 3 4 5 6 7 8
7 7 The application requires monitoring of the motor torque Program the frequency converter as shown in Table 7.2:
and digital input, so PCD 2 is set up to read the current
motor torque. PCD 3 is set up to monitor the state of an Parameter Setting
external sensor via the process signal digital input. The Parameter 4-10 Motor Speed
sensor is connected to digital input 18. [2] Both directions
Direction
Parameter 5-10 Terminal 18
[0] No operation
An external device is also controlled via control word bit Digital Input
11 and the built-in relay of the frequency converter. Parameter 5-11 Terminal 19
Reversing is permitted only when the reversing bit 15 in [10] Reversing
Digital Input
the control word and the digital input 19 are set to high. Parameter 5-40 Function Relay [36/37] Control word bit 11/12
Parameter 8-03 Control Word
1s
For safety reasons, the frequency converter stops the Timeout Time
motor if the PROFINET cable is broken, the master has a Parameter 8-04 Control Word
[2] Stop
system failure, or the PLC is in stop mode. Timeout Function
Parameter 8-10 Control Word
[0] FC Profile
Profile
Parameter 8-50 Coasting Select [1] Bus
Parameter 8-51 Quick Stop Select [1] Bus
Parameter 8-52 DC Brake Select [1] Bus
Parameter 8-53 Start Select [1] Bus
Parameter 8-54 Reversing Select [2] Logic AND
Parameter 8-55 Set-up Select [1] Bus
Parameter 8-56 Preset Reference
[1] Bus
Select
[2] Sub-index
Parameter 9-16 PCD Read parameter 16-16 Torque [Nm]
Configuration [3] Sub-index
parameter 16-60 Digital Input
The control word telegram is sent from the PLC to the frequency converter. Standard telegram 1 is used in the example to
demonstrate the full range of modules. All the values shown are arbitrary and are provided for demonstration purposes
only.
0 1 2 3
CTW MRV PCD PCD
04 7C 20 00
Bit no.: 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 1 0 0 0 1 1 1 1 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
0 4 7 C 2 0 0 0
Table 7.4 indicates which bit functions and which corresponding bit values are active in this example.
The control word telegram is sent from the frequency converter to the controller. Standard telegram 1 is used in the
example to demonstrate the full range of modules. All the values shown are arbitrary and are provided for demonstration
purposes only.
0 1 2 3
STW MAV PCD PCD
0F 07 20 00
Bit no.: 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 1 0 0 0 1 1 1 1 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
0 F 0 7 2 0 0 0
7 7 Table 7.5 indicates the bits contained within the status word and how they are presented as process data in standard
telegram 1 in this example.
Table 7.6 indicates which bit functions and which corresponding bit values are active in this example.
130BE933.10
Input Output
256–257 258–259 260–261 262–263 256–257 258–259 260–261 262–263
address address
Motor Digital Control
Set-up Status word MAV Set-up Reference Not used Not used
torque input word
130BA110.10
Illustration 7.7 Network Activates Relay 02
8 Troubleshooting
the frequency converter for the full range of The effect of control mode on the function of
parameter 8-50 Coasting Select settings. parameter 8-53 Start Select and parameter 8-54 Reversing
Select:
The effect of control mode on the function of
parameter 8-50 Coasting Select, parameter 8-51 Quick Stop
If [0] Digital input is selected, the terminals control the start
Select, and parameter 8-52 DC Brake Select is as follows:
and reversing functions.
If [0] Digital input is selected, the terminals control the
coast and DC brake functions. Terminal Bits 06/15 Function
NOTICE 0 0 Stop/Counterclockwise
0 1 Stop/Counterclockwise
Coasting, quick stop, and DC brake functions are active
for logic 0. 1 0 Start/Clockwise
1 1 Start/Clockwise
NOTICE
Parameter 16-84 Comm. Option STW is not part of
extended diagnosis.
8.2.1 Warning and Alarm Messages Alarms that are triplocked offer additional protection,
meaning that the mains supply must be switched off
The LEDs on the LCP signal a warning or an alarm. A code before the alarm can be reset. After being switched back
in the display is also shown. on, the frequency converter is no longer blocked and can
be reset as described, once the cause has been rectified.
A warning remains active until its cause is no longer
present. Under certain circumstances, operation of the Alarms that are not triplocked can also be reset using the
motor can still be continued. Warning messages are not automatic reset function in parameter 14-20 Reset Mode.
necessarily critical. (Warning: automatic wake-up is possible!)
An alarm makes the frequency converter trip. Alarms must When a warning or alarm is marked against a code in
be reset to restart operation once their cause has been Table 8.17, this means that either a warning occurs before
rectified. an alarm, or that it is possible to specify whether it is a
warning or an alarm that is displayed for a given fault.
3 ways of resetting alarms
• By pressing [Reset]. For instance, this is possible in parameter 1-90 Motor
• Via a digital input with the Reset function. Thermal Protection. After an alarm or trip, the motor
• Via serial communication/optional fieldbus. continues coasting, and the alarm and warning flash. Once
the problem has been rectified, only the alarm continues
flashing until the frequency converter is reset.
NOTICE
8 8 After a manual reset pressing [Reset], press [Auto On] to
restart the motor.
8 8
40 Overload of digital output terminal 27 (X)
parameter 5-01 Terminal 27 Mode
Parameter 5-00 Digital I/O Mode,
41 Overload of digital output terminal 29 (X)
parameter 5-02 Terminal 29 Mode
Parameter 5-32 Term X30/6 Digi Out
42 Overload of digital output on X30/6 (X)
(MCB 101)
Parameter 5-33 Term X30/7 Digi Out
42 Overload of digital output on X30/7 (X)
(MCB 101)
46 Pwr. card supply X X
47 24 V supply low X X X
48 1.8 V supply low X X
49 Speed limit X
50 AMA calibration failed X
51 AMA check Unom and Inom X
52 AMA low Inom X
53 AMA motor too big X
54 AMA motor too small X
55 AMA parameter out of range X
56 AMA interrupted by user X
57 AMA timeout X
58 AMA internal fault X X
59 Current limit X
Parameter 4-30 Motor Feedback Loss
61 Tracking error (X) (X)
Function
62 Output frequency at maximum limit X
63 Mechanical brake low (X) Parameter 2-20 Release Brake Current
64 Voltage limit X
65 Control board overtemperature X X X
66 Heat sink temperature low X
67 Option configuration has changed X
68 Safe stop (X) (X)1) Parameter 5-19 Terminal 37 Safe Stop
69 Pwr. card temp X X
70 Illegal FC configuration X
71 PTC 1 safe stop X X1) Parameter 5-19 Terminal 37 Safe Stop
A trip is the action when an alarm has appeared. The trip Warning yellow
coasts the motor and can be reset by pressing [Reset] or Alarm flashing red
by making a reset by a [1] digital input (parameter group Triplocked yellow and red
5-1* Digital I/O Mode ). The event that caused an alarm
cannot damage the frequency converter or cause Table 8.18 LED Indication
dangerous conditions. A triplock is an action when an
alarm occurs, that can damage the frequency converter or
connected parts. A triplock situation can only be reset by a
power cycling.
10
000004
00
1024 DC undervolt. Start failed Reserved DC undervolt. Reserved Output freq. low DC brake 8 8
000008
11 2048 DC overvolt. Speed limit Reserved DC overvolt. Reserved Brake check OK Stop
00
000010 External
12 4096 Short circuit Reserved Reserved Reserved Braking max Reserved
00 interlock
000020 Freeze output
13 8192 Reserved Reserved Reserved Reserved Reserved Braking
00 request
000040 Mains ph.
14 16384 Reserved Reserved Mains ph. loss Reserved Reserved Freeze output
00 loss
000080 Auto DC
15 32768 AMA not OK Reserved Reserved No motor OVC active Jog request
00 braking
000100 Live zero
16 65536 Reserved Reserved Live zero error Reserved AC brake Jog
00 error
000200
17 131072 Internal fault Reserved Reserved Reserved Reserved Reserved Start request
00
000400 Brake Brake resistor
18 262144 Reserved Reserved Reserved Reserved Start
00 overload power limit
000800
19 524288 U phase loss Reserved Reserved Reserved Reserved Reference high Reserved
00
001000 Option
20 1048576 V phase loss Reserved Reserved Overload T27 Reference low Start delay
00 detection
002000
21 2097152 W phase loss Option fault Reserved Reserved Reserved Reserved Sleep
00
004000 Memory
22 4194304 Fieldbus fault Locked rotor Reserved Fieldbus fault Reserved Sleep boost
00 module
008000 24 V supply Position ctrl. 24 V supply
23 8388608 Reserved Reserved Reserved Running
00 low fault low
010000
24 16777216 Mains failure Reserved Reserved Mains failure Reserved Reserved Bypass
00
020000
25 33554432 Reserved Current limit Reserved Current limit Reserved Reserved Reserved
00
040000
26 67108864 Brake resistor Reserved Reserved Reserved Reserved Reserved External interlock
00
080000 13421772
27 Brake IGBT Reserved Reserved Reserved Reserved Reserved Reserved
00 8
100000 26843545 Option Feedback Feedback
28 Reserved Encoder loss Reserved FlyStart active
00 6 change fault fault
Frequency
200000 53687091 Back EMF too Heat sink clean
29 converter Encoder loss Reserved Reserved Reserved
00 2 high warning
initialized
400000 10737418 Safe Torque Safe Torque
30 Reserved Reserved Reserved Reserved Reserved
00 24 Off Off
800000 21474836 Mech. brake
31 Reserved Reserved Reserved Reserved Database busy Reserved
00 48 low
Table 8.19 Description of Alarm Word, Warning Word, and Extended Status Word
8 8
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for diagnosis.
See also parameter 16-94 Ext. Status Word.
Index
N
A Network................................................................................................... 34
Abbreviation............................................................................................. 4 No response to control signals........................................................ 44
Acyclic....................................................................................................... 21
Additional resources.............................................................................. 3
P
Alarm......................................................................................................... 48 Parameter......................................................................................... 34, 35
CTW........................................................................................................... 14
R
D Reference................................................................................................... 4
Discharge time......................................................................................... 5
S
E Safety........................................................................................................... 6
L
Leakage current....................................................................................... 6
LED............................................................................................................... 4
Load sharing............................................................................................. 5
M
MRV............................................................................................................ 11
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MG07G102*