List of Data Sheet: Gujarat Water Supply & Sewerage Board Gandhinagar
List of Data Sheet: Gujarat Water Supply & Sewerage Board Gandhinagar
GANDHINAGAR
1. The Levels given in the Data Sheet are as per the Data available with GWSSB.
2. The Agency should confirm both the levels and layout of the Head Works as per the
requirement of the inter-related Structures and design accordingly. No Extra payment shall be
made by the Department to the Agency for the extra excavation or for the raised structure above
Ground Level.
DATA SHEET
Sr. Parameter 25.00 Lac Lit. Capacity Sump @ 30.00 Lac Lit. Capacity Sump @
No. Ganod HW Thaniyana HW
10) Inlet size of Pumping Main & Type 400 mm dia 300 mm dia
(D.I.D.F. PIPE)
Outlet size of Gravity main in case of ----- ------
HGLR
(D.I.D.F. PIPE)
Size of over flow pipe 300 mm dia 300 mm dia
(D.I.D.F. PIPE)
Size of Wash out pipe ------ ------
(D.I.D.F. PIPE)
No of Pumping Machinery attached Not Required Not Required
with Sump
11) Type of structure RCC As per design RCC As per design
Sr. Details DATA for RCC ESR DATA for RCC ESR
No.
1) Capacity 5.00 Lac. Lit. 5.00 Lac. Lit.
2) Approx Ground Level 100.00 Mtr. 100.00 Mtr
3) Approx OSL of ESR (Top of 118.00 Mtr. 120.00 Mtr
Outlet pipe)
4) Height 18.00 Mtr. 20.00 Mtr.
5) F.S.L. (As per design) (As per design)
6) Foundation depth below G.L. Minimum 3.0 M & required as Minimum 3.0 M &
per design. required as per design.
7) Type of foundation RCC foundation (as per RCC foundation (as per
design) design)
8) Free Board 0.30 meter 0.30 meter
9) Normal Water Table As per SBC Data As per SBC Data
10) Dia of pipe CI vertically cast Dia in mm
Double flange Inlet Outlet Overflow Wash out
250 300 300 200
11) Length of pipes Inlet:-From FSL+0.30 mtr to 1.0 Mtr. Below GL (vertically)
upto Duck foot Bend, and minimum 5.0 meter along ground
after edge of Shaft (Horizontally)
Outlet:-From OSL to 1.0 Mtr. Below GL (vertically) upto
Duck foot Bend, and minimum 5.0 meter along ground after
edge of shaft (Horizontally)
Overflow:-From FSL to 1.0 Mtr. Below GL (vertically)
upto Duck foot Bend, and minimum 5.0 meter along ground
after edge of shaft (Horizontally) & connected to 350mm dia
outlet pipe.
washout:-From top of bottom slab to 1.0 Mtr. Below GL
(vertically) upto Duck foot Bend, and minimum 5.0 meter
along ground after edge of shaft (Horizontally)
12) Size of (IS- 13095) & Sluice Valve Same size for Outlet & Washout pipe total 2 No of valves
for RCC ESR.
3.0.1 All internal masonry surfaces finish shall have 15 mm thick plain faced cement plaster in
cement mortar (1:3) with neat lime or neeru finish on top. Over this, one coat of primer and
two coats oil bound distemper of approved quality and shade shall be provided.
3.0.2 All external masonry surfaces shall have 20 mm thick sand faced cement plaster in cement
mortar (1:3) in two coats. Waterproofing compound of approved make and quality shall be
added to the cement mortar in proportions as specified by the manufacturer.
3.0.3 All external surfaces above ground level shall have one coat of primer and two coats of
waterproof cement based paint of approved quality and shade. A coat of silicone water
repellent paint shall also be applied thereon.
3.0.4 For pumping station construction shall be RCC frame and structure in M-200 where as all
external wall for super structure will be 230 mm thick in bella masonry in C.M. 1:6.
3.0.5 The flooring in all areas shall be in 600 mm x 450 mm x 25-mm thick polished kota stone
placed in C.M. to give overall thickness of 50mm.
3.0.6 The reinforced concrete roofs shall be made waterproof by application of an approved roof
polythene / bitumen membrane. The finished roof surface shall have adequate slope to drain
quickly the rainwater to R.W downtake inlet points.
3.0.7 Top surfaces of chajjas and canopies shall be made waterproof by providing a screed layer of
adequate slope or application of an approved roof membrane and sloped to drain the
rainwater. Chajjas, canopies and roof projections shall have drip moulds.
3.0.8 Building plinth shall be minimum 900 mm above average finished ground level around
building.
3.0.9 All windows and ventilators shall have 25 mm thick marble stone sills bedded in cement
mortar (1:3)
3.0.10 All Pump Houses shall be designed as Negative suction.
3.0.11 Steel door & window shall be made from frame of angle of size 40 mm x 40 mm x 6 mm and
shutter shall be of M.S. sheet of 20G thick with angle of appropriate size.
3.0.12 Unit wt. of steel door and window shall not be less than wt. given below
Door of size 1.00mt.x2.00mt. size – 95 kg.
window of size 1.00mt.x1.20mt. size – 65 kg.
Table No. I
Various requirements for construction of Chowkidar quarter
V Part – E : Paint
1 Acrylic emulsion
painting inside &
Weather-coat painting
outside
VI Part – F : Doors
1 Doors with Precast
RCC Frame with
Plywood and sun mica
finish Shutters including
Oil Painting with locking
arrangement etc. FRP
door for W/C and Bath