List of Data Sheet: Gujarat Water Supply & Sewerage Board Gandhinagar

The document contains data sheets for various structures for the Augmentation of Bhadar-II RWSS project including: 1. A preamble explaining that agency should confirm levels and design structures accordingly, with no extra payment for excavation or raised structures. 2. Data sheets for sumps including design parameters like capacity, dimensions, materials and other requirements. 3. A data sheet for an RCC elevated storage reservoir including capacity, heights, pipe details, and construction requirements. 4. The data sheets provide design and construction guidance for key civil structures for the water supply project.

Uploaded by

Pratik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
173 views

List of Data Sheet: Gujarat Water Supply & Sewerage Board Gandhinagar

The document contains data sheets for various structures for the Augmentation of Bhadar-II RWSS project including: 1. A preamble explaining that agency should confirm levels and design structures accordingly, with no extra payment for excavation or raised structures. 2. Data sheets for sumps including design parameters like capacity, dimensions, materials and other requirements. 3. A data sheet for an RCC elevated storage reservoir including capacity, heights, pipe details, and construction requirements. 4. The data sheets provide design and construction guidance for key civil structures for the water supply project.

Uploaded by

Pratik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

GUJARAT WATER SUPPLY & SEWERAGE BOARD

GANDHINAGAR

Augmentation of Bhadar-II RWSS

TECHNICAL BID (DATA SHEETS)

LIST OF DATA SHEET

1. PREAMBLE TO DATA SHEET

2. DATA SHEETS FOR WTP

3. DATA SHEETS FOR RCC SUMP

4. DATA SHEETS FOR RCC ESR

5. DATA SHEETS FOR PUMP HOUSE

6. DATA SHEETS FOR CHOKIDAR QUARTER


PREAMBLE TO DATA SHEET:

1. The Levels given in the Data Sheet are as per the Data available with GWSSB.
2. The Agency should confirm both the levels and layout of the Head Works as per the
requirement of the inter-related Structures and design accordingly. No Extra payment shall be
made by the Department to the Agency for the extra excavation or for the raised structure above
Ground Level.

DATA SHEET

(A) Design requirements of Sump

Sr. Parameter 25.00 Lac Lit. Capacity Sump @ 30.00 Lac Lit. Capacity Sump @
No. Ganod HW Thaniyana HW

1) Average approx GL of Sump 100.00 m 100.00 m

2) Bottom level of sump 96.00 m 96.00 m

3) approx Bottom level of the As per design As per design


Sump/suction chamber
4) Avg. approx FSL of sump 100.60 m 100.60 m

5) approx Minimum water level in the 0.30 Mtr. 0.30 Mtr.


sump (m) dead storage
6) approx Maximum water level in the Not more than 5.0 Mt. depth
sump (m) RL of water column
7) Water depth minimum 4.0 meter 4.0 meter
8) Free board 0.30 meter minimum (below 0.30 meter minimum (below
beam bottom) beam bottom)
9) Capacity of sump( in litre) 25.00 lacs lit 30.00 lacs lit

10) Inlet size of Pumping Main & Type 400 mm dia 300 mm dia
(D.I.D.F. PIPE)
Outlet size of Gravity main in case of ----- ------
HGLR
(D.I.D.F. PIPE)
Size of over flow pipe 300 mm dia 300 mm dia
(D.I.D.F. PIPE)
Size of Wash out pipe ------ ------
(D.I.D.F. PIPE)
No of Pumping Machinery attached Not Required Not Required
with Sump
11) Type of structure RCC As per design RCC As per design

12) Grade of Concrete RCC -M300 RCC -M300


13) Steel TMT Steel Confirming to TMT Steel Confirming to
Relevant IS FE-415 Relevant IS FE-415
14) SBC To be carried out by Agency To be carried out by Agency
15) Shape of Sump Circular/ Flat slab Circular/ Flat slab
16) Water level Indicator To be provided To be provided
17) GI Pipe Railing of 25 mm dia 3 rows To be provided To be provided
18) Min.depth of foundation As per design As per design
19) C.I. M.H. Frame & Cover 0.90 x 0.60mt 0.90 x 0.60mt
4 Nos 4 Nos
20) 100 mm dia C.I. Cowl Ventilator 8 Nos 8 Nos
21) Lightening Arrestor Not required Not required
22) Valve Chamber (Butterfly Valve shall As per requirement As per requirement
be Provided where dia of valve more
than 300 mm dia)
23) MS ladder RCC Stair with Stair Room RCC Stair with Stair Room
24) GI Railing As Per Standard Design As Per Standard Design
25) Other requirement 5 HP Mud Pump 5 HP Mud Pump

OTHER REQUIREMENT FOR SUMP


1) Weather Coat paint of approved quality as per Inst. Of EIC should Be Provide On
Outside Surface
2) Maximum Water Table during rainy season will be considered.
DATA SHEET FOR RCC ESR

Sr. No. Staging Height in Mtr Location Location


1 18 Limbuda HW Jilana HW

Sr. Details DATA for RCC ESR DATA for RCC ESR
No.
1) Capacity 5.00 Lac. Lit. 5.00 Lac. Lit.
2) Approx Ground Level 100.00 Mtr. 100.00 Mtr
3) Approx OSL of ESR (Top of 118.00 Mtr. 120.00 Mtr
Outlet pipe)
4) Height 18.00 Mtr. 20.00 Mtr.
5) F.S.L. (As per design) (As per design)
6) Foundation depth below G.L. Minimum 3.0 M & required as Minimum 3.0 M &
per design. required as per design.
7) Type of foundation RCC foundation (as per RCC foundation (as per
design) design)
8) Free Board 0.30 meter 0.30 meter
9) Normal Water Table As per SBC Data As per SBC Data
10) Dia of pipe CI vertically cast Dia in mm
Double flange Inlet Outlet Overflow Wash out
250 300 300 200
11) Length of pipes Inlet:-From FSL+0.30 mtr to 1.0 Mtr. Below GL (vertically)
upto Duck foot Bend, and minimum 5.0 meter along ground
after edge of Shaft (Horizontally)
Outlet:-From OSL to 1.0 Mtr. Below GL (vertically) upto
Duck foot Bend, and minimum 5.0 meter along ground after
edge of shaft (Horizontally)
Overflow:-From FSL to 1.0 Mtr. Below GL (vertically)
upto Duck foot Bend, and minimum 5.0 meter along ground
after edge of shaft (Horizontally) & connected to 350mm dia
outlet pipe.
washout:-From top of bottom slab to 1.0 Mtr. Below GL
(vertically) upto Duck foot Bend, and minimum 5.0 meter
along ground after edge of shaft (Horizontally)

12) Size of (IS- 13095) & Sluice Valve Same size for Outlet & Washout pipe total 2 No of valves
for RCC ESR.

13) Size of Valve Chamber 1.30 x 1.30 x 1.00 mts. -2 Nos


i) Internal Dimension 1.0 mts. Depth (Average)
ii) Thickness of Masonry 23 cm
iii)Type of Masonry W.S. Bela Masonery in C.M. 1:6
iv) Plaster and pointing Inside plaster in C.M. 1:3 , 15 cm thick
v) Foundation 15 cm thick C.C. 1:3:6 or as per design
vi) Manhole Frame and Cover for As per requirement
chamber
vii)RCC Slab C.C. : 1:2:4 - 15 cm thick
14) Cowl type ventilator – 100 mm dia As per design
(Ventilation area shall not be less than of (A) 0.04% of the
free water surface when cowl type ventilators are provided.
(B) Cross sectional area of the inlet pipe. (C) Cross
sectional area of the outlet pipe.)
15) CI MH Frame and cover at top of 0.90 x 0.60 m (100 Kg) 2 Nos
Container
16) Lightening Arrester To be provided as per specification
17) Water level indicator To be provided as per specification
18) Type of Construction RCC (As per design)- M-300
19) Steel TMT Fe 500 steel to be used
20) Staging Only in Shaft with Staircase Inside
21) Other Requirement All other Requirement as per Price bid & specifications
Including all obligatory requirement of department.
22) SBC Tentative SBC of site is not less than 20 T/M2. But Agency
has to carry out SBC test at his own cost for design
purpose. If SBC carried out by agency comes out to be
greater than 20 T/M2. than design shall be prepared
considering SBC of 20 T/M2 . If Water table found within
foundation depth as per SBC than design must be done
with water table effect.
(B) Design requirement of pump house
1 Location Thaniyana HW
2 Size (tentative) 8.00 x 6.00x 4.50(With Gantry)
Positive Suction
3 Ground Level of Pump house 100.00 m
4 Plinth level of Pump house & 0.90 mt Above G.L
buildings (Average G.L. + 1 mt. Ht.)
5 Height of Pump House 3.00 M Minimum Or as required
6 Carpet area of the Pump House (Sq. 48.00 Sq.m
mt)
7 Live Load on the Pump Floor Level 1000
(kg/ sqm.)

8 Live load for non accessible pump 75 kg/sqm.


house roof (kg/sqm)
9 Flooring 25 mm th. Polished kota stone
10 Type of structure R.C.C. framed m-200 with White stone
bela Masonry in C.M. 1:6
11 Electrification work 5 Amp. - 5 Point
15 Amp. - 5 Point

12 Steel Door / window Door – 1 No. of 1 mt. x 2 mt. size


Window -1 mt. x 1.2 mt. size 6 No.
Rolling Shutter – 2.00 X2.50 M

3.0 Requirements of Construction details for pump house:


The construction requirements for pump house viz. flooring, ceiling, walls.

3.0.1 All internal masonry surfaces finish shall have 15 mm thick plain faced cement plaster in
cement mortar (1:3) with neat lime or neeru finish on top. Over this, one coat of primer and
two coats oil bound distemper of approved quality and shade shall be provided.

3.0.2 All external masonry surfaces shall have 20 mm thick sand faced cement plaster in cement
mortar (1:3) in two coats. Waterproofing compound of approved make and quality shall be
added to the cement mortar in proportions as specified by the manufacturer.

3.0.3 All external surfaces above ground level shall have one coat of primer and two coats of
waterproof cement based paint of approved quality and shade. A coat of silicone water
repellent paint shall also be applied thereon.

3.0.4 For pumping station construction shall be RCC frame and structure in M-200 where as all
external wall for super structure will be 230 mm thick in bella masonry in C.M. 1:6.
3.0.5 The flooring in all areas shall be in 600 mm x 450 mm x 25-mm thick polished kota stone
placed in C.M. to give overall thickness of 50mm.

3.0.6 The reinforced concrete roofs shall be made waterproof by application of an approved roof
polythene / bitumen membrane. The finished roof surface shall have adequate slope to drain
quickly the rainwater to R.W downtake inlet points.

3.0.7 Top surfaces of chajjas and canopies shall be made waterproof by providing a screed layer of
adequate slope or application of an approved roof membrane and sloped to drain the
rainwater. Chajjas, canopies and roof projections shall have drip moulds.
3.0.8 Building plinth shall be minimum 900 mm above average finished ground level around
building.

3.0.9 All windows and ventilators shall have 25 mm thick marble stone sills bedded in cement
mortar (1:3)
3.0.10 All Pump Houses shall be designed as Negative suction.
3.0.11 Steel door & window shall be made from frame of angle of size 40 mm x 40 mm x 6 mm and
shutter shall be of M.S. sheet of 20G thick with angle of appropriate size.
3.0.12 Unit wt. of steel door and window shall not be less than wt. given below
Door of size 1.00mt.x2.00mt. size – 95 kg.
window of size 1.00mt.x1.20mt. size – 65 kg.
Table No. I
Various requirements for construction of Chowkidar quarter

Sr. Items Living Kitchen Verandah Bath/WC


No. Room
I Part – A : Unit Size
1 Staff qtr Carpet area of    
62 sq.m.
II Part – B : Flooring
1 Vitrified Tiles flooring    
2 Ceramic tile – Class II 
ceramic tiles upto 2.0
mtr. Ht.in bath walls,
Flooring & 1.2 mt.
height in W/C
III Part – C : RCC Ceiling    
1 15 mm thick cement    
plaster in CM 1:3
IV Part – D : Walls
1 WS masonary in CM    
1:6 in foundation &
plinth, WS Bela
masonary in C.M. 1:6
for walls S/S.
2 15 mm thick (1:3)    
cement plaster inside
and 20 mm thk sand
faced plaster outside

V Part – E : Paint
1 Acrylic emulsion    
painting inside &
Weather-coat painting
outside
VI Part – F : Doors
1 Doors with Precast    
RCC Frame with
Plywood and sun mica
finish Shutters including
Oil Painting with locking
arrangement etc. FRP
door for W/C and Bath

VII Part – G : Windows


Sr. Items Living Kitchen Verandah Bath/WC
No. Room
1 Windows with    
Alluminium Section
including M.S.Grill & Oil
Painting with locking
arrangement.
VIII Part – H : Fan hook   
IX Part – I : Loft slab  
Part – J :
1 2400 long,, 830 high 
and 670 deep kitchen
plat form with Kota
stone top, sink of
approved quality
Kaddappah shelve
2 Std. quality of shower 
in bath.
Note: -
1. Indicates the provision of this item is to be made in the bidders offer.
2. Provide Electrical work 7/20 copper concealed wiring (20 points per staff quarter including
switches, point, 5 amp plug – 5 nos. and 15 amp – 2 nos. tube light – 4 Nos & ISI mark 48
inches fans 3 Nos )
3. For Sanitation purpose provide 24 cu mt soak pit per quarter with septic tank for ten users.
4. Varandah Grill should be provided with locking arrangements and painting etc. complete
5. 0.75 m height parapet and terrace water proofing by CC 1:2:4 50 mm thick and rain water pipe
should be fixed
6. RCC Lintel should be provided on walls @ 2.00 m height from plinth.