User Manual: PDS23 Plus Solar Pump Controller
User Manual: PDS23 Plus Solar Pump Controller
Preface
Thank you for using PDS23Plus solar pump controller. This manual provides you
with relevant operation instructions and detailed description of parameters. Please
read this manual carefully before installation, running, maintenance or inspection.
Please make sure the wiring and the pump’s rotation direction is correct before use.
- 1 -
Content
Preface ............................................................................................................... - 1 -
1.1 Features.................................................................................................................... - 7 -
- 2 -
- 3 -
■Before Installation
WARNING
Do not install or operate the controller that is damaged or has missing parts. Otherwise, it
may result in equipment damage or harm life.
■ Installation
CAUTION
WARNING
◎Ensure only qualified personnel to operate. Otherwise it can cause an electrical shock or
damage of the controller.
◎ Make sure the controller is isolated from power supply by the circuit breaker. Otherwise it
may cause a fire.
◎ Make sure that the ground terminal is grounded correctly.
◎ Do not touch the power input terminals of the controller and the pump’s terminals .
Otherwise it may cause an electrical shock.
- 4 -
■ Operation
CAUTION
◎ Do not open or remove the front cover when operation. Otherwise it may cause an
electrical shock.
◎Before testing the pump must be installed; can not make the pump dry-run for a long
time.In order to test the pump, the maximum dry-run time is not more than 15s
◎If the pump turning is reversed, it can change any two lines of the pump’s three power
lines.
◎ When the water pump is due to the light shadow, it will restart the operation after 120s.
◎ If a water level probe is installed in the well, when the water level is below the level of
water shortage, the water pump will stop. If there is no water level probe, it will need to be
short.If a water level probe is not used, the controller terminal must be short.
WARNING
◎ Only qualified or authorized professional personnel can maintain, replace and inspect the
controller. Otherwise it may cause damage and injury.
◎ Wait at least 10 minutes after the power failure, or make sure that no residual voltage
before carry out maintenance and inspection, otherwise it may cause damage.
■ Others
WARNING
◎ If failing to follow these instructions, resulting in damage to the machine, can not enjoy
the warranty service.
- 5 -
PDS23 Plus solar pumping system serves to provide water in remote applications
where electrical grid power is either unreliable or unavailable.PDS23 Plus solar
pump controller can convert DC from the PV array to AC, and drive kinds of pumps.
In sunny days, the pumping system can continuously pump water. The system
without batteries and other energy storage devices, it is recommended to take water
pumped to a reservoir for later use and water sources are those natural or special
such as river, lake, well or waterway, etc. A float switch can be installed in the water
tower to control the pump operation. And install a low-level probe in well to detect
the well water so thatwhen thewater shortagepump is stopped. Figure 1 shows a
typical diagram of the pumping system. The major parts and components in the
system are listed after the diagram
A. PV Array
B. DC Breaker
E. Well
Level Switch
D. Pump
- 6 -
Notice: In order to ensure maximum system reliability and water delivery, check
valves must be installed in the drop pipe. The first check valve must be installed at
the pump and additional check valves should be installed every 30m (100 ft) of
vertical pipe after the pump.
1.1 Features
System Diagnostics
Motor Soft-Start
Normally, when there is a demand for water and power is available, PDS23Plus
solar pump controller will be operating. Whenever the controller detects a need for
water, the controller always “ramps up” the motor speed while gradually
- 7 -
increasing motor voltage, resulting in a cooler motor and lower start-up current
compared to conventional water systems. Due to the controller’s soft-start feature
this will not harm the motor.
PDS23Plus solar pump controller is designed for full power operation from a solar
array in ambient temperatures up to 45 °C.In excess of45 ℃temperature conditions,
the controller will reduce output power in an attempt to avoid shutdown. Full pump
output is restored when the controller temperature cools to a safe level.
When the system is running on back-up AC power, please check for sufficient DC
primary source power every 30 minutes. If the primary DC power is available, shut
down the controller, switch back to primary power and attempt to run on DC
power supply.
NOTICE: A DC switch and aAC switch must be installed in the power switch box,
and these two switches must be mechanically interlocked each other to prevent
switching on together resulting the solar PV and the generator being connected to
the controller simultaneously! Please check if the design is in accordance with all
applicable national and local electrical codes.
- 8 -
PDS23Plus solar pump controller is a variable speed motor drive designed to run
any IEC three-phase asynchronous motor. PDS23Plus solar pumping system
provides water to remote locations by converting high voltage, direct current from a
solar array into alternating current to run a standard three-phase asynchronous motor.
When solar power is not available, the controller can be switched to an alternate
three-phase AC input such as a generator, if available. The controller provides fault
detection, motor soft start, and speed control. The controller is designed to provide
these features with the plug and play ease of installation.
The PDS23Plus solar pump controller is designed with the high standard of
reliability expected of products. The controller attempts to drive the pump and motor
to deliver water even under adverse conditions, reducing output as necessary to
protect the system components from damage, and only shutting down in extreme
cases. Full operation is restored automatically whenever abnormal conditions
subside.
2.1 Inspection
Before you begin, receive and inspect the controller unit. Verify that the part number
is correct and that no damage has occurred during transit.
NOTE: PDS23Plus solar pump controller is one component of the PDS23Plus solar
pumping system which has other two components, solar array and AC pump with
motor.
- 9 -
Thepumping system is optimized for pumping under adverse input power conditions
unique to solar arrays:
- 10 -
- 11 -
2.4.3 Input and Output Parametersof PDS23 Plus Solar Pump Controller
PDS23 PDS2Plus PDS23Pl PDS23Pl PDS23Pl
Controller Model
Plus 2.2K 4K us 5.5K us 7.5K us 11K
Input Data
PV Source
Max Input Voltage(Voc) DC800V
Recommended Voltage, at MPP DC500~700V
Recommended PV Array Power 13.2~
2.7~3.5 4.8~6.4 6.6~8.8 9~12
[kW] 17.6
Alternate AC Generator
Input Voltage 380/400/415/440VAC(±15%), Three Phase
Power and VA Capability[kVA] 4.0 5.9 8.9 11.0 17
Output Data
Output Power, Rated[kW] 2.2 4.0 5.5 7.5 11
Output Voltage, Rated 380/400/415/440VAC(±15%), Three Phase
Rated Output Amps(RMS)[A] 5.1 9.0 13.0 17.0 25.0
Max Amps(RMS)[A] 9.0 13.0 17.0 25.0 32.0
Output Frequency 0~50Hz/60Hz
Note: according to different regions, the recommended PV array power is 1.2 ~ 1.6 times the
power of the controller.
- 12 -
179 144.3
155.6
22
50
191.3
150
50
240
168
202 154
20
117.5
65
195
65
235
300
214
- 13 -
- 14 -
R/+ S T/- U V W
DC/AC INPUT PUMP
GROUND
The DC and AC can't To reverse direction,
input at the same reverse any two
time. wires.
Figure 5 Main terminals (The sequence may be different from actual product)
M1 M2 M3 COM M4 M5 M6 COM S+ S-
N0
NC RS485
No Function Interface
Low-water Remote Float Switch
sensor probe
Figure6 Control terminals (The sequence may be different from actual product)
- 15 -
WARNING
Before connect DC wiring, following the steps below to prevent hazardous electric shock
resulting in serious injury or device burning.
• Make sure that the external DC disconnect switch is off.
•Make sure that AC power is disconnected (If AC power supply is wired as backup
power,AC and DC power supply can not simultaneously put into the controller, otherwise it
will damage the controller.)
Correct grounding helps to prevent shock hazard if there is a fault in the motor.
- 16 -
It is recommended that use a wire tube to protect the electric wire from the
destruction of wildlife and natural weathering, and bury the wire tube into the
ground to strengthen protection. If you do not use a wire tube, you can use a higher
quality outdoor cable.
position
pump off
cable pumping
weight range
position
pump on
Figure 7FloatingBallDiagram
- 17 -
If the float switch is not used, the M6 and COM are kept short.
N0
M5 M6 COM
N0
Remote NC
NC
Float Float Switch
Switch
COM
COM
UP: closed
if cable is shielded, DOWN: open
ground this end only normal: open
3.2.8Electrical conduit
When the system installed in the outdoor, electricalconduit can be used to protect the
outdoor electric wires, so as to avoid the impact from the weather, human activities,
chewing animals. If you do not use the electrical conduit, use the higher quality
outdoor wire.
- 18 -
GROUND
The DC and AC To reverse direction,
can't input at the reverse any two
same time . wires
Low-water Remote Float
sensor probe Switch
NC
N0
Float Switch
(optional)
Submersible
Cable Splice
Low Water
Level Probe
(optional)
NOTE:
1. The float switch is optional; if not use, please keep the terminal M6 and COM
short.
2. Low water level probe is optional; if not use, please keep the terminal M4 and
COM short.
The PDS23Plus series controller is connected in series with the serial number of the
input components of the 18~20 block, and the 250W 500~700VDC (MPPT) is
satisfied.
- 19 -
Digital
Display 5 0 .0 0
Up increase
key
Program/exit ▼
key
PRGM SHIFT Shift key
ENT Data Enter Key Progressively enter menu and confirm parameter
RUN/STOP Run/stop key Start to run the controller in keypad control mode.
- 20 -
In order to set up the electric automatic start function FD.07=11 as an example, the
modified parameter flow chart is as follows:
Stand By Status
(Frequency/Hz) First Class First Class Second Class Third Class
Value N ow
Display f0 fd 10
Reading: 0.00 f d.07
Button: PRG M ▲ EN T EN T ▲
Run Status Third Class
(Frequency/Hz) First Class Second Class N ew Value
Display
Reading: 0.00 fd f d.10 11
Button: PRG M PRG M EN T
- 21 -
After the controller has failed, the controller will display the relevant fault code
information. The conventional fault code (E002/3/4/5/6/7/8/9/10/11/12/18) can
automatically reset after 10s operation, and can also choose to reset the RUN/STOP
on the keyboard. If the conventional failure persists, the controller will reset once
every 10s. Special fault code (E001/13/14) requires the user through theRUN/STOP
key on the keyboard to reset the fault; the controller can continue to run after the
reset.
For Example, if the motor which rated frequency is 60Hz, these parameters need
modification:
High limit of running frequency F0.12=60;
Other related parameters are: motor rated power F2.01, motor rated frequency
F2.02=60, motor rated speed F2.03, motor rated voltage F2.04, motor rated current
F2.05.
If the pump is in dry-run state, the maximum operating time can not exceed 15s,
otherwise it may cause damage to the pump.
- 22 -
If the pump is in dry-run, the maximum operating time can not exceed 15seconds;
otherwise it may cause damage to the pump. If the pump steering error, close the DC
switch, according to the pump / motor wiring to change the wiring of the motor
section of the two leads.
After the above parts are complete, you can try to run the system.
Let the system work for an hour, check the water supply capacity.
Commissioning finish
When the light is insufficient, the solar power module output power will be
reduced, and the pump operation speed will be very slow until stop. The controller
will attempt to start every120s, and during the trial run, the running indicator is
always on.
When a shadow suddenly passes through the battery array, the controller will lose
track of the input voltage, and the pump will stop working. But the controller does
not show the fault, the controller will try to restart the pump.
◎ The parameters which are actual-detecting record value and cannot be modified.
- 23 -
Function Modifica
Function Descriptions Unit Factory Setting
Code tion Type
F0 Group: Basic Parameters
High limit of
F0.12 30.00~60.00 Hz 50.00 〇
running frequency
Low limit of
F0.14 0.00~F0.12 Hz 20.00
running frequency
F0.18 Acceleration time 0.1 ~3600 s 10.0 〇
- 24 -
Function Modifica
Function Descriptions Unit Factory Setting
Code tion Type
Inverter firmware
F7.10 ◎
version
Accumulative
F7.11 0 ~9999 hour ◎
running time
FA Group: Protection and Malfunction Parameters
0: No fault
1: Inverter module protection
Fault record of the (E001)
FA.14 ◎
one before last 2. Over-current when accelerate
(E002)
3: Over-current when decelerate
(E003)
4: Over-current at constant
speed (E004)
5: Over-voltage when accelerate
(E005 )
FA.15 Last fault record 6: Over-voltage when decelerate 〇
(E006)
7: Over-voltage at constant
speed (E007)
8:Hardware overvoltage (E008)
9:Under voltage (E009)
10:Inverter overload (E010)
11:Motor overload (E011)
12:Phase-lack of input (E012)
13:Phase-lack of output (E013)
14:Heatsink overheating (E014)
Current fault 15:External fault (E015)
FA.16 16:Communication fault (E016) 〇
record
17:Reserved
18:Current detection fault
(E018)
20:Well level fault(E020)
21:Tank level fault(E021)
22:EEPROM fault (E022)
26:Water shortage fault (E026)
Running
FA.17 frequency when Hz ◎
fault occurs
- 25 -
Function Modifica
Function Descriptions Unit Factory Setting
Code tion Type
Output current
FA.18 A ◎
when fault occurs
DC bus voltage
FA.19 V ◎
when fault occurs
Parameter interpretation:
F0.14, Low limit of running frequency: this parameter defaults to 20Hz, when the
light becomes weak, and the controller output frequency is lower than F0.14, the
controller will be in standby mode. After the light becomes strong, the controller
will rerun. Can set this parameter artificially, in order to avoidpump at low speed
without water, reduce the pump abrasion at low speed.
F2.01~F2.05,Motor parameter: the user can be set according to the actual pump
motor nameplate parameters
F7.00 user password: the user can set a 5 digits password;after the password is set up
and confirmed, the password will be valid for a minute.
- 26 -
FD.07, Automatic start when power on: the factory defaults to 10 (disabled).Itcan be
set to 11 (enabled), then as long as the solar module power supply, the controller will
automatically start and achieve automatic operation of the whole day.
FD.10 water shortage detection time: when applied to a deep well pump, not using
the water level probe to detect the water shortage, the controller can use the built-in
water shortage detection function to complete the water shortage detection. When
this parameter is not 0, the software will start the function of water shortage.
Software shortage detection principle: If the water shortage happens, the controller
will still run FD.10 time, after that it will appear the water shortage fault E026.The
fault will be reset and the controller will restart automaticallyafter 20 minutes. If
there is no water shortage but fails E026, it may appear false; then you can simply
reduce FD.12 value.
WARNING :DO NOT touch any other piece inside the PDS23Plus Solar pump
controller while power is applied. To service any other areas of the controller,
disconnect ALL power sources and wait 5 minutes before continuing.
For the selection of PDS23Plus solar pump controller, it can be matched with the
power of the pump. If the length of cable is more than 100m, add an output reactor.
- 27 -
The PDS23Plus solar pump controller will attempt to drive the pump to deliver
water even under adverse conditions. To ensure years of reliable service, it must also
protect the system components from conditions that might result in equipment
damage. When adverse conditions arise, the controller will continue to deliver as
much water as possible at reduced output if necessary, and will shut down only in
extreme cases. Full operation will resume automatically whenever abnormal
conditions subside.
If the controller has stopped to indicate a fault code on the display, the associated
time-out delay will vary depending on the nature of the fault. The number following
the “E” symbol corresponds to the error code for the offending condition.
- 28 -
- 29 -
- 30 -
- 31 -
① If there is no enough sun light, and the controller's input power is not enough.
② Motor wiring errors cause the pump to reverse, change the wiring.
③ The motor shaft vibratesand can not rotate, it may be caused by the wiring
errors;Need to re check the motor wiring.
④ Pumps and pipes are clogged with mud and debris, and the pump can't run
②Check if the machine has a burning smell; if there is a burning smell, please
contact the agent to replace the controller
②Check if the machine has a burning smell; if there is a burning smell, please
contact the agent to replace the controller
- 32 -
• Controller
Periodically checking of Status display, error code display and fault record, long
term verification of cooling fan and cleaning of heat sink are needed.
• pump
The pump’s motor is permanently sealed, no need to maintain. Pump head is a
mechanical device, may be used for a period of time, due to the sand in the water,
and other impurities cause a certain wear, the performance of the pump needs to be
regularly detected. If the flow of the pump is less than the normal value, may need to
be replaced.
6.3 Cable
Need to regularly check the power cable and ground wire to make sure all the wires
are reliably connected and without being corroded.
- 33 -
In order to ensure continuous water supply, solar water pump system can be
manually switched to standby AC power supply when the light is insufficient or wet
days. When switching, the need to ensure that the DC and AC power supply reliable
mutual lock. Backup AC power source can be a local power grid, or a diesel
generator (please refer to the 2.4.3 technical form).
Warning: at any time, only one power supply can be entered, otherwise it may cause
the controller to damage.
Take three phase 380VAC backup AC power supply for example, the wiring is
shown in the following diagram:
R S T U V W COM M4 M5 M6 COM
Float Switch
(optional)
DC Switch AC
Switch
Pump Motor
PV Array Earth Ground
- 34 -
System Report
System and Components
Date ofPurchase
Distributor
(Contact details)
System
Controller
Serial Number
Motor Serial
Numberor
Power
Solar Power
Solar Module
Manufacturers
Type
PeakVoltage(V
mp)
Open Circuit
Voltage(Voc)
Quantity
- 35 -
Installation
Installation Date
Installer
(contact details)
Submersible Pump Surface Pump
Type Type
Type Type
- 36 -
V1.1
Inverter
- 37 -