CIPer Model 30 Controller

PRODUCT DATA

Features

• Full Niagara 4 stack with 12 points of on-board I/O


(including 9 monitored Hand-Off-Auto), expandable
to 312.
• 1Gbps 4-Port IP switch, integrates demanding IP
peripheral devices (like color cameras) 1000 times
faster than serial MSTP.
• Full Niagara N4 License included,
- 150 points (including data sharing points from
third party BACnet devices) and 3 devices.
- Expansion I/O capability support up to 15 modules
and 300 additional points.
• Rapid Spanning Tree protocol (IEEE 802.1w) supports
200+ controllers on a daisy-chain bus with fewer home
runs for faster and lower cost wiring.
- Up to 40 controllers in a redundant ring configura-
tion for enhanced fault tolerance.
-Supports Star network topology.
• Spyder Program and Venom conversion application
standard.
• BACnet B-BC listed product (pending).
• Sylk™ bus for use with Honeywell Sylk wall modules.
APPLICATION • Direct supervisor connectivity (Cloud or on premise);
simplifying system architecture and reducing
The WEB-C3036 controllers are part of the Honeywell
programming, commissioning & installation time.
WEBs CIPer family. CIPer MODEL 30 controllers are
- Open Niagara 4 Framework, eliminates extra cost
available in two models WEB-C3036EPUBNH and WEB-
proprietary software and tools.
C3036EPVBNH. These are Internet Protocol (IP) based
• SSL encrypted communications (FOXS PKI Certificate)
“edge” controllers that can be used for VAV, Unitary,
to protect the facility’s expensive assets and
equipment and Plant applications. Each is
infrastructure with world-class cyber-security.
programmable and configurable using the open Niagara
- FIPS 140-2 Level 1 compliance for critical high-risk
4 Framework.
facilities.
• Industry standard TCP/IP connectivity, enabling the
Each controller is equipped with a four-port Gigabit
use of CAT5 or CAT6 Ethernet cables.
network switch, that can integrate with broader IP
• VAV model includes on-board airflow sensor.
peripheral devices including cameras, variable frequency
• Live “real-time” programming; no time-consuming
drives, utility meters, lighting systems, etc. The CIPer
downloads.
MODEL 30 controllers can communicate over both TCP/
• Solid State Relay (SSR) outputs reduces the need for
IP (FOXS) and BACnet IP protocols. These controllers
external relays.
can be used to aggregate information (including real-
• Ready to use open-protocol Niagara 4 wire-sheet,
time data, alarms, trends, and history) and integrate this
alarming, history, schedules, web server, HTML
data to the Honeywell “FORGE” Cloud for value-added
graphics, standard tools and palettes, pre-configured
data analytics to maximize the efficiency and lifespan of
common application macro library, analytic points,
expensive facility equipment assets while helping
and Haystack Tagging.
prevent unplanned downtown. Additional physical I/O
points available using expansion IO modules WEB-
O9056H and WEB-O3022H.

© Honeywell 31-00236EFS-01
Controller Part Numbers
Table 1 Controller part number description
Model WEB-C3036EPUBNH / WEB C3036EPVBNH
WEB Brand Identifier
C Controller
3 Analog input
0 Digital input
3 Analog output
6 Digital output
E Ethernet
P Programmable
U/V U - Unitary & V- VAV
B BACnet
N No Actuator
H Hand off Auto

The CIPer Model 30 controller is compatible with two expansion or external I/O models—WEB-O9056H and WEB-
O3022H. The WEB-O9056H module is a large expansion module which adds 20 additional I/O points, and the
WEB-O3022H module is a small expansion module which adds 7 additional I/O points. A total of 15 expansion I/
O modules can be added to a controller.

Ordering part numbers


Table 2 Ordering Part numbers
OS Number (SKU) Description
WEB-C3036EPUBNH CIPer IP Unitary Controller, 150 Point/4-Device Niagara 4 License, SMA
WEB-C3036EPVBNH CIPer IP VAV Controller, 150 Point/4-Device Niagara 4 License, SMA
WEB-O9056H CIPer IP Large Expansion Module, 50-Point Niagara 4 License, 20 I/O, 9-UI, 6-BO, 5-UIO
WEB-O3022H CIPer Small Expansion Module, 50-Point Niagara 4 License, 7 I/O, 3-UI, 2-BO, 2-UIO

© Honeywell Page 2 31-00236EFS-01


Interfaces and Terminals

System overview

Fig. 1 CIPer 30 Controller Interfaces and Terminals

Table 3 Terminal Assignment


Type Legend Terminal Description
MAC Address 1 1, 2 Not Used
SYLK 2 3,4 2 wire Sylk™ bus to connect Honeywell Sylk modules.
Terminals 3 5, 7, 8 Universal inputs UI-1 to 3. Software controlled input type selection supports 10k
Thermistor (type II), Dry Contact, 0-10Vdc, 0-20mA, and Pulse (In-1, -2, -3), 20K
NTC. See specifications on the page 4.
Universal
Inputs/ Analog 6 COM terminal for UI-1 and UI-2.
Outputs 9 COM terminal for UI-3 and UI-4/AO-1.
10, 11, 13 Universal Inputs/Outputs as UI-4 to 6
Analog Outputs AO-1 to 3: selectable 0-10vDC or 4-20mA.
12 COM terminal for UI-5/AO-2 or UI-6/AO-3.
14 Supplies 20V DC out.
Input Power 4 15 24VAC Controller input supply voltage.
Supply 16 Supply voltage GND.
17 Electrical grounding / Earth.

© Honeywell Page 3 31-00236EFS-01


Table 3 Terminal Assignment
Type Legend Terminal Description
Terminals 5 18 24VAC output from controller's power (terminal 15) for DO devices.
19 HOT B. Supplies power to common side of controller's DO (For DO 5,6).
Digital Outputs 20 HOT A. Supplies power to common side of controller's DO (DO 1, 2, 3, 4).
21, 23, 24, 26 DO-1 to DO-4. See next page for specification.
22, 25, 28 COM terminal for DO-1&2, DO-3&4, DO-5&6 respectively.
27, 29 DO-5 to DO-6.
Air flow sensor 6 Differential pressure/ air flow sensor inputs.
H-O-A Switches 7 H-O-A switch for DO-1 to DO6 & AO-1 to AO-3:
1. If the switch is in the middle position it means that it is in OFF position for
digital outputs and 0% for modulating (PWM, FM, AO) outputs.
2 If the switch is moved to the left side/ HAND, it indicates that the input can
be given manually, and output can be collected from respective terminal. For
example, if the switch is indicating that input is manual for DO-1 then output
can be collected from terminal 21 manually and BAS logic will be disabled for
terminal 21. ON for digital outputs, 100% for PWM and Floating Motor
outputs, trim potentiometer value for Analog outputs (Voltage/Current).
3 If the switch is moved to Right side, it indicates the AUTO mode. The input
given to BAS logic will be enabled and the output will be received
automatically at the respective output terminal.
Trim pots 8 Trim pots for AO-1 to AO-3. For giving variable Analog input to AOs when the
respective H-O-A switch is in HAND position.
LEDs 9 Power LED: White/Blue color (See below table 4 for more details).
Status LED: Amber color (See below table 4 for more details).
Service Request Button.
A notification shall appear on the software tool when button is Pushed or when
the service request is cleared.
Ethernet 10 1 Giga bit 4 post Ethernet switch.
Interface
USB Interface 11 USB Type B to connect with laptops, mobile, and tablets.
12 USB Type A port to mount memory stick/flash drive for data transfer.
Serial 13 RS-485 RS-485 terminal to expand I/O by connecting to additional devices or Expansion
Expansion IO modules.
* Refer below RS-485 section for terminal details.

Below is the description of various LED states

Table 4 Power and Status LED States


Status or Condition LED State Blink Rate
No power to processor, LED damaged, Power LED OFF OFF
low voltage to board, first second of Status LED OFF OFF
power up, or loader damaged.
Baseboard bootloader running (approx. Power LED OFF OFF
first 10-15 seconds after power on or Status LED Blinks continuously 0.5 Second ON; 0.5 Second OFF
baseboard reset).
Bootloader completes and hands control Power LED ON ON steady
to main baseboard firmware. (stays ON as long as baseboard is
running)
Status LED ON ON steady
(Indicates station is NOT running)
Station starts up. Status LED Blinks continuously 1 Second ON; 1 Second OFF
(indicates baseboard is running
normally, presumably with a station
running in Niagara)

© Honeywell Page 4 31-00236EFS-01


Specifications Hardware Specifications
Table 5 Hardware Specifications
Electrical
Feature Specifications
Rated input voltage: 20-30 VAC; 50/60Hz MRAM 512 KB
Power consumption: RAM 1GB
- 100VA maximum for controller and all connected FLASH RAM 4GB
loads. Cortex A9 32-bit processor 1 GHz,
- 50 VA maximum for controller only load CPU Cortex-M4 227 MHz
Operating System QNX based
Operating Environment 24 hour, 365 day, multi-year
calendar including day of week
Ambient temperature: -4 to 131F (-20 to 55C) and configuration for automatic
Storage temperature: -4 to 150F (-20 to 65C) daylight savings time adjustment
Humidity: 5% to 95% non-condensing to occur at 2:00 a.m. local time on
Real-Time Clock configured start and stop dates.
Inputs and Outputs timekeeping accuracy Minimum 48 hours backup.

VAV 24 hours at 32°F to 100°F (0°C to


Air flow sensor range (VAV model): 0-2” WC (0 to 374 Power failure Memory 38°C), 22 hours at 100°F to
Pa) 32 to 122F (0 to 55C) backup 122°F (38°C to 50°C)

Universal Inputs (UI) ±1 minute per month at 77° F


Time Accuracy (25° C)
Universal Inputs: 6 UI / 3 configurable as AO.
Flexible UI’s to connect external sensors like 20KNTC,
PT1000 and other resistive sensors.

Mounting
Pulse Inputs: 100Hz max, minimum duty cycle: 5 mS This CIPer controller mounts on a standard DIN rail in
ON / 5 mS OFF
one of two ways:
•Vertically, with the connections on the right and left
Analog Outputs (AO) sides of the unit.
3 of the 6 UIs (UI 4,5,6) are configurable as AOs (AO •Horizontally, with the connections on the top and
1,2,3) AOs are individually configurable for current or bottom of the unit.
voltage.
This controller also has a locking clip, as do both type
Analog Current Outputs of I/O expansion modules. Mounting on DIN rail
Current Output Range: 4.0 to 20.0 mA ensures accurate alignment of connectors between all
Output Load Resistance: 550 Ohms maximum modules. The controller can also be screw-mounted
using the four mounting tabs, accessible under the
Analog Voltage Outputs covers. These mounting tabs may be broken off if
Voltage Output Range: 0.0 to 10.0 Vdc needed to save space when DIN rail mounting.
Maximum Output Current: 10.0 mA

Digital Outputs (DO) Note: Avoid mounting in areas where acid fumes or other
deteriorating vapors can attack the metal parts of the
6 Digital Outputs: Solid-State Relay
controller, or in areas where escaping gas or other explosive
Current rating: 1.5A Continuous, 3.5A in-rush for 100
vapors are present.
milliseconds
Voltage rating: 20 to 30 VAC @ 50/60Hz

© Honeywell Page 5 31-00236EFS-01


DIMENSIONS (H/W/D)

See Fig. 2 and Fig. 3 below for dimensional drawings.

Fig. 2 Dimensional view of Stacked Controller and Expansion IO modules

Fig. 3 Different views of CIPer Model 30 controller

© Honeywell Page 6 31-00236EFS-01


Standards and Approvals Safety Information as per EN60730-1
• UL/CUL (E87741) listed under UL 60730-1 and CSA The Open System is intended for residential,
E60730-1, UL 60730-2-9:2010.
• Meets FCC Part 15, Subpart B:2017, Class B (radiated commercial, and light-industrial environments.
emissions) requirements. The Open System is an independently mounted
• Meets Canada ICES-003:2016. electronic control system with fixed wiring.
• EMC Directive: 2014/30/EU. Standards Applied:
The WEB-C3036EPUBNH/WEB-C3036EPVBNH is
— EN 61000-6:2005
— EN 61000-6-3:2007 + A1 suitable for mounting in fuse boxes conforming with
— EN 60730-1: 2011, EN 60730-2-9: 2010 standard DIN43880, and having a slot height of max.
• RoHS Directive: 2011/65/EU. Standards Applied: 45 mm.
— EN 50581: 2012
It is suitable for panel rail mounting on 35 mm
standard panel rail (both horizontal and vertical rail
Conformance Statement
mounting possible).
This digital apparatus complies with CAN ICES-3 (B)/
NMB-3 (B). Table 6 Safety information as per EN-60730-1
FCC Notice Electric Shock PELV
This device complies with Part 15 of the FCC rules. Protection
Pollution Degree Pollution Degree 2, suitable for use in
Operation is subject to the following two conditions:
industrial environments.
(1) this device may not cause harmful interference,
Installation Class 3
and Overvoltage 24 V-powered controls: Category I
(2) this device must accept any interference received, Category
including interference that may cause undesired Rated Impulse 330 Vac for Category I (SELV)
operation. Voltage
Automatic Type 1
Action
Software Class Class A
Purpose of control Operating Control, Open Energy
Management Equipment.
Enclosure degree IP20
of protection
Ball-pressure >75 °C for all housing and plastic
Test parts.
Temperature >125 °C in the case of devices
applied with voltage-carrying parts,
connectors, and terminals.
Electromagnetic Tested at 230 Vac, with the
Interference modules in normal condition.
System Europe: safety isolating
Transformer transformers according to
IEC61558-2-6.
U.S.A. and Canada: NEC Class-2
transformers.

Honeywell Building Technologies


Honeywell International Inc.
1985 Douglas Drive North ® U.S. Registered Trademark
Golden Valley, MN 55422 © 2019Honeywell International Inc.
31-00236EFS
customer.honeywell.com