2/2-Way Solenoid Valve With Servo-Diaphragm, G 3/8 - G 1
2/2-Way Solenoid Valve With Servo-Diaphragm, G 3/8 - G 1
www.burkert.com p. 1/4
6211
Response times
1)
Pressure data [bar]: Overpressure with respect to
Orifice Kv value Port Pressure Response times Weight atmospheric pressure
water connection range 2) Closing 2)
For opening the full cross-section, a pressure
Opening Closing difference of 0.5 bar is required.
1)
[kg] [m³/h] [mm] [bar] [ms] [ms] [kg]
10 1.9 G3/8, G1/2 0.5-10 20-25 100-120 0.31
13 3.6 G1/2, G3/4 0.5-10 100-200 200-250 0.44
20 8.3 G3/4, G1 0.5-10 400 500-700 1.03
• Kv value [m³/h]: Flow rate value for water, measured at +20 °C and 1 bar1) pressure differential
over a fully opened valve.
• Response times [ms]: measured at valve outlet at 6 bar1) and +20 °C
Opening: pressure build-up 0 ... 90%, Closing: pressure relief 100 ... 10%
Materials
1 Body Brass
2 O-ring NBR, FKM, EPDM
3 Diaphragm support PPS
4 Spring St. st. 1.4310
5 Body cover PPE/PA
6 Plunger St. st. 1.4105
7 Spring St. st. 1.4310
8 Coil
DIN EN 175301-803*) C PA (on request)
DIN 43650
(industrial standard) Form B Epoxy
9 Diaphragm holder Brass, PPS
10 Bolt Brass
11 Diaphragm NBR, FKM, EPDM
12 Flange Steel
(thick-film passivated acc. to Rohs)
13 Shading ring Cu
14 Locknut Steel
(thick-film passivated acc. to Rohs)
p. 2/4
6211
Port connection
Circuit function
Pressure range
110/50-60
230/50-60
24/50-60
Kv value
Orifice
24/DC
[m³/h]
[bar]1)
water
[mm]
DN
Item no.
Voltage
I &URTHERôVERSIONSôONôREQUEST
Electrical Connection
Coil with cable plug acc. to DIN EN 175301 Form C
Coil with flying leads
Port Connection
Threaded port NPT, Rc
Approvals
UR/CSA
p. 3/4
6211
Dimensions [mm]
35.5
33.5
3
12
29.7 16.3
22
A
51
B
49.5
P P
F F
E
L
10.5
G
SW
30.3
Form C for cable plug 2506 (industrial standard) for cable plug
Type 2507
20
D
1)
For port connection G thread F1 and G1 applies;
port connection NPT thread F2 and G2;
port connection Rc thread F3 and G3. *)
so far DIN 43650
1) 1) 1) 1) 1) 1)
DN [mm] A B C D E F1 G1 F2 G2 F3 G3 L SW
To find your nearest Bürkert facility, click on the orange box www.burkert.com
In case of special application conditions, We reserve the right to make technical changes without notice.
please consult for advice. © Christian Bürkert GmbH & Co. KG 1310/3_EU-en_00891748
p. 4/4