Diversity and Demand Factor
Diversity and Demand Factor
etc
DEMAND FACTOR, DIVERSITY FACTOR AND TRANSFORMER SIZE
CALCULATION
a) Demand factor - the ratio of the load that a piece of equipment actually
draws when it is in operation to the load it could draw (which we call full
load).
For example, we might have 10 air conditioning units that are 30 kW each at
a facility.
However, since the units are each thermostatically controlled, we do not
know exactly when each unit turns on.
If the 10 units are substantially bigger than the facility's actual peak A/C
load, then fewer than all ten units will likely come on at once. Say only 8
numbers are turned on at a time.
Thus, even though there are 10 units, they do not all come ON at the same
time to affect the facility's peak load. Thus we can use the diversity factor to
bring the kW into line with the facility's true peak load.
Demand factor can be applied to calculate the size of the sub-main which is
feeding a Sub panel.
If the panel (Say SSB 1) total load is 250 kVA , considering a Demand factor
of 0.8, we can size the feeder cable for 250 x 0.8= 200 kVA, which is equal
to 280 Ampere on 415 V 3 phase supply.
To calculate the Main incoming capacity and Transformer size, we can use
the Diversity factor which will take into account the fact that all the four
SSB’s above won’t attain their individual maximum simultaneously.
Assuming a Diversity factor of 0.7, the overall maximum demand would be
Transformer size= ( 568.75 / 0.8 ) x 1.2 = 853 kVA ( Choose the nearest
available standard size)