Auto Transfer Switch & Mains Colour Control Module: Genset
Auto Transfer Switch & Mains Colour Control Module: Genset
dseGenset
dse8860
ENVIRONMENTAL TESTING STANDARDS
AUTO TRANSFER SWITCH & MAINS EMC Generic Immunity Standard for the
Industrial Environment
TEMPERATURE
BS EN 60068-2-1
The DSE8860 is an easy-to-use Comprehensive communications With all communication ports Ab/Ae Cold Test -30oC
single or multi-mains controller with are also available via RS232, capable of being active at the same BS EN 60068-2-2
Bb/Be Dry Heat +70oC
automatic transfer switch capability. RS485 & Ethernet for remote PC time, the DSE8000 Series is ideal
Designed to synchronise single or control and monitoring, and for a wide variety of demanding VIBRATION
load share applications. BS EN 60068-2-6
multiple DSE8810s with single or integration into building Ten sweeps in each of three major axes
multiple mains (utility) supplies, the management systems. 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
DSE8860 will automatically control KEY LOAD SHARE FEATURES:
The comprehensive event log will HUMIDITY
the change over from mains (utility) • Peak lopping
record up to 250 events to facilitate BS EN 60068-2-30
to generator supply or run generators • Sequential set start Db Damp Heat Cyclic 20/55oC @ 95% RH 48
maintenance.
in synchronisation with the mains • Manual voltage/frequency Hours
BS EN 60068-2-78
(utility) to provide no-break, peak An extensive number of fixed and adjustment Cab Damp Heat Static 40oC @ 93% RH 48
lopping and peak shaving power flexible monitoring and protection • R.O.C.O.F. and vector shift Hours
The module can indicate and alarms can be made using the • Mains (Utility) de-coupling Three shocks in each of three major axes
15gn in 11mS
operational status and fault DSE PC Configuration Suite • Mains (Utility) de-coupling
conditions on the LCD screen Software. Selected configuration is test mode DEGREES OF PROTECTION
• Bus failure detection PROVIDED BY ENCLOSURES
(multiple languages available), by also available via the module’s front BS EN 60529
illuminated LED, audible sounder panel. • Volts and frequency matching. IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
and SMS messaging.
DSE8860 MSC
7
8x60 8x10 8x80 8x10 8x60
OTHER
MAINS (UTILITY) SENSING N/C VOLT FREE LOAD N/O VOLT BUS
OUTPUTS CURRENT FREE OUTPUT SENSING
CURRENT VOLTS
ISSUE 1
®
dseGenset
dse8860
SPECIFICATION
DC SUPPLY
CONTINUOUS VOLTAGE RATING
AUTO TRANSFER SWITCH & MAINS 8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
FEATURES and supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUTS C & D
8 A at 250 V AC (Volt free)
DIMENSIONS
OVERALL
245 mm x 184 mm x 50 mm
9.6” x 7.2” x 2”
PANEL CUT-OUT
220 mm x 160 mm
8.7” x 6.3”
RELATED MATERIALS
TITLE PART NO’S
DSE8860 Installation Instructions 053-139
DSE8860 Operator Manual 057-173
DSE8860 PC Configuration Suite Software Manual 057-174
DSE8810 Data Sheet 055-116
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-139/7/12 (1)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457