CPM1300
CPM1300
CPM
Communication Platform
Copyright© 2019 BTG Instruments AB
The contents of this document are subject to revision without notice due to continued progress
in methodology, design, and manufacturing. BTG shall have no liability for any error or
damages of any kind resulting from the use of this document.
All rights reserved. No part of this document may be copied, photocopied, published,
reproduced, translated or converted into electronic or machine-readable form
without written permission of BTG Instruments AB.
Original Instructions
1 Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Dimensions and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Type Plate Explanations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5 CE-Declaration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Assembly of Product Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.3 Mounting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4 Cabling Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.5 Connection Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.5.1 AC Connection to Power Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.5.2 HCM-8000 / 8010 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.5.2.1 HCM-8000 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5.2.2 HCM-8010 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.5.3 FCM-8000 / 8010 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.5.3.1 FCM-8000 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.5.3.2 FCM-8010 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.5.4 Sensor Control Module SCM-8000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.5.5 Connection to Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.5.6 24 V On/Off Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.6 Backup Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.7 RS-485 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3 Service Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.1 Maintenance Routines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4 Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.1 CPM Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
NOTE!
Always read the safety instructions before installation and service of the
instrument!
NOTE!
If the CPM is used in a manner not specified by BTG the protection provided
by the equipment may be impaired.
For operation instructions, see the CPM operation manual for the appropriate
instrument. CPM operation manuals are available for the following
instruments:
1 Product Introduction
1.1 General
The CPM is delivered as a complete unit from BTG, normally in conjunction with an
instrument.
The CPM has the following functions:
• Local display and console for full configuration and operation of the
instrument
• Large illuminated display for easy reading
• Protected from splash and sun
Fig 1 CPM overview
1 Protective cover 1
2 Front cover
3 Scroll keys
4 LCD display with
backlight 2
5 Function keys
6 Closing screw 3
7 Cable glands
8 Transmitter cable 4
Function Specifications
Communication Modules:
HCM-8000/8010
Hart communication module using HART® protocol.
Equipped with slot for SD memory card.
Analog output (AO1- AO5)
4 - 20 mA. Galvanic isolated. Current limited to min. 3.9 and max. 20.5 mA.
Loop load signal: Voltage supply/load 24 V DC
Active or passive output for HCM-8000
Active output only for HCM-8010
Superimposed signal over 4 - 20 mA current loop according to standard HART® protocol.
Analog input (AI1 - AI4)
4 - 20 mA 250 Ω input resistance
Digital input (DI1 - DI4)
Galvanic isolated
High-ohmic = logical 0
+24 V ≥ 12 mA = logical 1
Digital output (DO1 - DO2)
Galvanic isolated
Maximum 120 mA
Maximum 30 V DC
Solenoid valve (SV1 - SV5)
Open drain output for solenoids
Maximum 500 mA
Maximum 30 V DC
FCM-8000/8010
Fieldbus communication module programmed for PROFIBUS.
Equipped with slot for SD memory card.
Output / Input signal
PROFIBUS (PA)
User Interface
Illuminated display. Key pad for adjustment of instrument settings.
Physical Specifications
Materials
Casing: Polycarbonate thermo plastic
Cable fittings: Polyamide thermo plastic
Storage Temperature
Max. 80 °C (176 °F)
Min. -25 °C (-13 °F)
Operation Temperature
Max. 50 °C (122 °F)
Min. 0 °C (32 °F)
Degree of Protection
IP 65, comparable to NEMA 4x and better, the CPM is intended for use indoors.
Weight
CPM: 2 - 2.5 kg (4.4 - 5.5 lbs) depending on configuration
Cables
Power supply flexible cable: 0.3 - 2.5 mm2 (AWG = 28-12)
Signalling cable: 0.2 - 2.5 mm2 (AWG = 24-12)
Transmitter Cable
CPM-1300: Standard length: 10 m [33 ft] (option up to 55 m [180 ft])
Cable diameter: 5.5 mm [0.22"]
Connector diameter: 15 mm [0.6"]
CPM-1400: Standard length: 10 m [33 ft] (option up to 20 m [66 ft])
Cable diameter: 13 mm [0.5"]
No fixed connector
CPM-1500: Standard length: 10 m [33 ft] (option up to 20 m [66 ft])
Cable diameter: 5.5 mm [0.22"]
No fixed connector
Cable Inlets
There are cable glands for signal cables (diameter 4-8 mm) and for power supply cable
(diameter 4-12 mm) in the bottom of the CPM.
0.4"
10
Quick Guide
10.8"
270
7.2"
180
7.2"
180
5 (4x)
0.2"
10 (4x) 180 50
0.4" 7.2" 210 2" 152
8.4" 6" 162
240
9.6" 6.5" 222
8.9"
Fig 3 Recommended
clearances
200
8"
300
12"
Quick Guide
200
8"
200
8"
PRODUCT TYPE 15
6 CPM-1300 HA/Q0/C0/S/10/I230 A
NiMH
NO VOLTAGE 14
7 123456 100-240 V AC 13
8 9 10 11
1. Manufacturer
2. CE-marking
The CPM is approved in accordance with CE directives.
3. C-TIC marking
The CPM is approved in accordance with Australian C-TIC N1619
directives.
4. ETL-marking
The CPM is approved by ETL.
5. Warning sign
The CPM is designed for industrial use. Installation, handling and service
must only be carried out by trained and authorized personnel and in
accordance with relevant standards. Read the manual for detailed
information and pay particular attention to the warning signs!
6. Product
The instrument model is specified according to the code system explained
below:
CPM-1300
A B C
A Product Group
CPM Communication platform
B Power type
13 50 W Power supply
14 240 W Power supply
15 80 W Power supply
C Input/Output Unit
If field D = Hx:
1x analog output, 1x analog input
1x digital output, 3x digital inputs
00
If field D = PA or FF:
1x Fieldbus output
1x digital output, 1x digital input
If field D = HA
10 5x analog outputs, 4x analog inputs
7x digital outputs, 4x digital inputs
7. Manufacturing number
BTG internal product identification number.
8. Frequency
The CPM operates at both 50 and 60 Hz.
9. Apparent power
Maximum power consumption (W).
10. Installation category
In accordance with CE-Directive. Fixed installation. Resistant to
transients.
11. Factory identification
12. Voltage
100-240 V AC to power supply.
13. Recycling
The CPM should be recycled in accordance with local regulations.
HA/Q0/C0/S/10/I230 A
D E F G H I
D Communication Protocol
HA Analog 4-20 mA with HART®, Active output
Analog 4-20 mA with HART®, Standard is: Active output
Hx
but can be set by customer from menu to: Passive output
PA Profibus PA
FF Foundation Fieldbus
F0 Foundation Fieldbus supplied with FCI-1000
E Sensor Control Module
Q0 No module
Q1 Sensor control module SCM-8000
F Communication Connector
C0 No serial connector
C1 One serial connector
C2 Two serial connectors
G Housing
S Standard housing with protecting cover
T Standard housing without protecting cover
L Large housing without protecting cover
H Cable length
10 10 m [32.8 ft]
20 20 m [65.6 ft]
30 30 m [98.4 ft]
40 40 m [131.2 ft]
55 55 m [180.4 ft]
I Other options
Blank = no option
I012 Interlock interface relay 12 V DC
I024 Interlock interface relay 24 V AC/DC
I048 Interlock interface relay 48 V DC
I060 Interlock interface relay 60 V DC
I120 Interlock interface relay 120 V AC/ 110 V DC
I230 Interlock interface relay 230 V AC/ 220 V DC
A Alarm relay max 230 V AC / 220 V DC
1.5 CE-Declaration
When using the units in combinations other than those tested for, BTG can not
guarantee CE-directive conformity.
The units in combination with customer-installed external devices may conform
with EMC and safety requirements when properly installed and CE-marked
equipment is used.
The system operator is responsible for CE-directive conformity.
Conformity must be verified by inspection.
Declaration of Conformity
CE mark
COMMUNICATION PLATFORM
TYPE: CPM-1300
CPM-1400
CPM-1500
BTG INSTRUMENTS AB
P.O. Box 602
661 29 Säffle
Sweden
This declaration of conformity is issued under the sole responsibility of the manufacturer.
EN ISO 12100:2010 Safety of machinery - General principles for design - Risk assessment and risk
reduction
EN 61326-1:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements
Part 1: General requirements
Page 1
2 Installation Instructions
2.1 Unpacking
The following is included in a CPM delivery:
1. 1 x CPM box with transmitter cable
2. 1 x Protection cover (not when pre-assambled on a base unit)
3. 1 x Quick reference guide card
Quick Guide
Quick Reference
Guide card
Tools required:
Screwdriver
Drilling machine
1. Mount the CPM in the selected location by fastening the protective cover
to a flat surface. Use four suitable screws.
• See Fig 6 for recommended clearances.
• The top of the protective cover can be used as a holder for a
HART-terminal.
Fig 6 Recommended
clearances
200
8"
300
12"
Quick Guide
200
8"
200
8"
DANGER
Hazardous voltage
in the equipment NOTE!
BTG recommends that separate cables be used for analog and digital signals.
Multi conductor cables can be used.
NOTE!
Unused cable glands must be sealed in order to fulfill the IP 65 requirement.
NOTE!
Secure all cables with cable ties to avoid short circuit.
NOTE!
Overcurrent protection is included in the power supply unit.
NOTE!
An external 2-pole switch close to the CPM is required as shown in Fig 7
(Not delivered from BTG).
The switch should be marked "Disconnecting device".
NOTE!
The connection cable must be able to withstand an ambient temperature of at
least 75 °C (167 °F).
- -
+
+
+ + - -
- - AC
+
+
100-120/
200-240 V
N L
+ + - -
100-240 V AC
N L
50W
N L PE
Fuse
PE N L
100-240 V AC
Min. 4 A (200-240 V)
N L
Fuse Min. 6 A (100-120 V)
Min. 2 A
AC
100-120/
200-240 V
N L
NOTE!
Fig 8 shows resistance as a function of supply voltage. The grey area is
accepted. The resistance is the sum of cable- and power source- resistance in
the current loop. The HART® communication requires a minimum resistance of
250
730
250
V
0
8 14 24 35 (Max)
NOTE!
The connection blocks can be released from the connection module for easier
access, as shown in Fig 9 below.
3. Connect the shield to the upper connection point on the shield filter module
(SFM-8000).
CAUTION!
The cable shield must always be connected to the upper connection point on
the shield filter module, and kept separated from the transmitter cable shield.
NOTE!
The functions of the connections for each instrument type can be found in the
connection tables for HCM-8000 in section 5: Appendix
P3
P2
P1
DI3 DO
8000 cable Digital In 3
+24 V
Digital Out
P1
P1 LOAD
-
+
P2 +24 V
DI1 DI2
Digital In 1
P3 +24 V
Digital In 2
P2
CAUTION -
Supplied with 14 - 35 V DC
+
LOAD
Note the polarity for +24 V P3
Always connect Analog In 4-20 mA
the cable shield!
Passive or Active
Analog Out (AO).
Alternative 2: AO = Active
If the analog output
signal (4-20 mA) is
AO1 AI1
NOTE!
The functions of the connections for each instrument type can be found in the
connection tables for HCM-8010 in section 5: Appendix
P6
P5
P4
P3
P2
P1
DI3 DO
HCM-8010 cables Digital In 3
P7 P1 P4
+24 V
Digital Out
P1
LOAD
-
+
P8 P2 P5 +24 V
DI1 DI2
Digital In 1
P9 P3 P6 +24 V P2
Digital In 2
NOTE!
For HCM-8010, only active Active Analog Out 4-20 mA
AO1 AI1
analog output is available. +24 V
Analog In 4-20 mA
P3
AO2 AO3
+24 V
DI4 DO2
Solenoid Valve 5
P8 Active Analog Out 5 (4-20 mA)
P5
CAUTION!
SV 1 2 3
AI 2 3 4
Transmitter
cable SFM-8000
DANGER NOTE!
Hazardous voltage Before installation, ensure that all power to the system has been turned off.
in the equipment Cable connections must be made by authorized personnel.
NOTE!
The connection blocks can be released from the connection module for easier
access, as shown in Fig 14 below.
3. Connect the shield to the upper connection point on the shield filter module.
CAUTION!
The cable shield must always be connected to the upper connection point on
the shield filter module, and kept separated from the transmitter cable shield.
NOTE!
The functions of the connections for each instrument type can be found in the
connection tables for FCM-8000 in section 5: Appendix
P3
P2
P1
Fig 16 Connection of
FCM-8000 cables FCM-8000
DO DI3
Digital Out
P1 Digital In 3
P1
CAUTION
P2
Always connect 1 23 4
FF / PROFIBUS PA
the cable shield! P3
Shield P2
S
NOTE!
The functions of the connections for each instrument type can be found in the
connection tables for FCM-8010 in section 5: Appendix
P6
P5
P4
P3
P2
P1
DO DI3
Digital Out
FCM-8010 cables
P7 P1 P4 Digital In 3
P1
P8 P2 P5
1 23 4
FF / PROFIBUS PA
P9 P3 P6 Shield P2
S
Software update
P3
Cable shield
AO2 AO3
+24 V
DI4 DO2
Solenoid Valve 5
P8 Active Analog Out 5 (4-20 mA)
P5
CAUTION!
SV 1 2 3
AI 2 3 4
Transmitter
cable SFM-8000
DANGER NOTE!
Hazardous voltage These connection instructions are only valid for DRT-5500. Other instruments
in the equipment equipped with the SCM-8000 have all connections to the SCM unit pre-wired
at delivery.
NOTE!
Before installation, ensure that all power to the system has been turned off.
Cable connections must be made by authorized personnel.
SCM-8000 P5
P6
P4 P5 P6
- - + -
P6
+ -- - + -- - + -- - P5
- - + -
P4
red
HCM SCM black
8000 8000 blue
Solenoid valve 1
Solenoid valve 2
Solenoid valve 3
Solenoid valve 4
Solenoid valve 5
Solenoid valve 6
Solenoid valve 7
Solenoid valve 8
Solenoid valve 9
white
RS-485
HCM-8000
SCM-8000
P1 DI3 DO P1
Common
+ - + - + - + -
P2 DI1 DI2 P2
+ - + - + - + -
P3 AO AI P3
+ - + - + - + -
SCM-8000
P1 P2 P3
+ -+ - + -+ - + -+ -
P1
brown
white
black
P2
blue
P3
Sensor Cable
Sample button
DANGER NOTE!
Hazardous voltage Before installation, ensure that all power to the system has been turned off.
in the equipment Cable connections must be made by authorized personnel.
Brown 24 V DC
Black or Green
White RS-485
Blue or Yellow
1kΩ
Cable shield
transmitter
A B S
2 3 4 S
AC
100-120/
200-240 V
N L
Red
Black
Blue
White
+ + - -
On/Off
A B S
2 3 4 S
AC
100-120/
200-240 V
N L
d
ar
yC
m SD
or
Me
++ - -
n
tio
+- +-
ic a
un ule
m
o m mod
C
RS
-48
5
3 Service Instructions
4 Parts List
Most spare parts are delivered in kits. Each kit includes instructions.
6 7 2 4
3
++ - -
Pulptec TM
5 HCM-8000
SUPPLY
POWER
HCM-8000
Com
Power PE N L
CPU
Rec.
Kit spare Qty Part No. Spare Part Description
No.
parts
Without electronics Including:
1 1 PB0011007 Console kit Protective cover, Display holder, Front
tape, Attachments
Hart communication module Including:
2 1 PB0011015 HCM-8000 kit Bottom socket, Contact for transmitter
(5 pin)
Standard 10 m
PB0011023 Transmitter cable kit (CPM-1300)
(other length on request)
3 1
MEK-3000 up to 20 m
P46033742 Transmitter cable (CPM-1400) (not shown in figure)
4 1 HB0011031 50 W power supply kit Including: Cable, Contact (2 pin)
5 1 PB0011049 Display card kit Including: Cable
6 1 PB0011056 SFM-8000 kit Shield filter module kit
7 1 HB0011171 4-20 mA Active output kit
8 9 10 11 12 13
+ + - -
HCM-8000
HCM-8010
HCM-8010 SCM-8000
SCM-8000
On/Off
FCM-8000 HCM-8000
SV1
DO2 SV2
DO3 SV3
DI4 SV4
DI51 SV5
SV1 SV6
SV2
SV3
A B S POWER 3.3
Com Com POWER 5.0 Com2
POWER 24
Power Com1
2 3 4 S Power
Power
CPU CPU CPU
AC
100-120/
200-240 V
N L
Kit Rec.
spare Qty Part No. Spare Part Description
No.
parts
Fieldbus communication module,
programmed for PROFIBUS (PA)
PB0011551 FCM-8000 kit Including: Bottom socket, Contact for
8 1 transmitter (5 pin).
Fieldbus communication module,
PA0113415 FCM-8010 Unit programmed for PROFIBUS (PA) for
extended in- and outputs
PB0021741 240 W Power Supply kit For CPM-1400 (MEK-3000)
9 1
P46036133 80 W Power Supply unit For CPM-1500 (SPK-5500)
10 1 P46033965 24 V Switch 24 V Switch
11 1 Terminal Block kit For CPM-1400 (MEK-3000)
Hart Communication Module with
12 1 PB0021774 HCM-8000/8010 kit 8010 card for extended in- and outputs
Including: Bottom sockets 5 pin x2
Sensor Control Module
13 1 KB0021782 SCM-8000 kit Including: Bottom socket 5 pin
14 1 HA0111674 Communication cable RS-485 Serial (not in figure)
15 1 HA0112953 Communication cable RS-485 USB (not in figure)
16 1 PA0150151 RS485 service connector (not in figure)
Memory card for back-up
17 * 1 P00X20418 SD card 512 MB Industrial
(not in figure)
18 1 PA0174573 Alarm relay Kit (not in figure)
19 1 PA0119867 Interlock relay Kit (not in figure)
5 Appendix
Interlock
DI3 Digital In 3 Sample Input (1=Interlock) Sample Input Sample Input
P1
DO Digital Out Alarm Output Data Ready Alarm Output Alarm Output
Sample Input
DI3 Digital In 3 Sample Input Sample Input Sample Input
or Interlock
P1
DO Digital Out Alarm Output Alarm Output Alarm Output Alarm Output
DI1 Digital In 1 Calibration set Calibration set Calibration set Calibration set
Input A Input A Input A Input A
P2
DI2 Calibration set Calibration set Calibration set Calibration set
Digital In 2 Input B Input B Input B Input B
Total Total
Consistency Consistency
AO Analog Out output value output value Consistency Consistency
output value output value
P3 4 - 20 mA 4 - 20 mA 4 - 20 mA 4 - 20 mA
P1 Alarm Output
DO Digital Out Alarm Output or PCD-1000
control
Total Total
Consistency Consistency
AO Analog Out output value output value
P3 4 - 20 mA 4 - 20 mA
1 0 0
2 1 0
3 0 1
4 1 1
BT-5500
Connection Block BLT-5500 DLT-5500 RET-25x2 RET-55xx
DI3 Digital In 3 Initiate lab sample Sample Input Sample Input Interlock
P1
Alarm Output or PCD-
DO Digital Out 1 Alarm Output Alarm Output 1000 control Alarm Output
DI1 Digital In 1 Calibration set Input A Calibration set Input A Calibration set Input A Calibration set Input A
P2
DI2 Digital In 2 Calibration set Input B Calibration set Input B Calibration set Input B Calibration set Input B
AO3 Analog Out 3 Channel 3 output value Not used Not used Not used
4 - 20 mA
AI2 Analog In 2
Analog input signals
P6 AI3 Analog In 3 from external equipment Not used Not used Not used
4 - 20 mA
AI4 Analog In 4
DI4 Digital In 4
P7 Not used Not used Not used Internally pre-wired(a)
DO2 Digital Out 2
P9 SV2 Sol. valve 2 Not used Not used Not used Internally pre-wired(a)
(a) For more information about internally pre-wired connections, see the installation drawing for the transmitter
DI3 Digital In 3 Sample Input Interlock Interlock Remote stop Sample Input
P1 Digital Out 1
Floating DC
DO Alarm Output Alarm Output Alarm output Alarm Output Alarm Output
switch max 30 V,
100 mA
Analog input
AI2 Analog In 2 signals from
external equipment Internally pre-
4 - 20 mA wired(a) Internally
P6 Not used Not used
pre-wired(a)
AI3 Analog In 3
Not used
AI4 Analog In 4 Not used
Internally pre-
DI4 Digital In 4 Not used Sample Input
wired(a)
P7 Digital Out 2 Not used Not used
DO2 Floating DC Data ready Not used Data Ready
switch max 30 V, Channel 1
100 mA
Internally pre-
SV4 Sol. valve 4
wired(a)
P8 Not used Not used Internally pre-wired(a) Not used
SV5 Sol. valve 5 Not used
Data ready
SV1 Sol. valve 1 Channel 2
Internally pre-
P9
SV2 Sol. valve 2
Not used
wired(a) Internally pre-wired(a) Not used
Not used
SV3 Sol. valve 3
(a) For more information about internally pre-wired connections, see the installation drawing for the transmitter
(b) Average since last start. Normally only used for batch applications
ACT-2500
BLT-5500
BTT-5500
DLT-5500
TCT-25x1
Connection Block MBT-2500 DRT-5500 MEK-3000 RET-25x2
MBT-4500
MEK-2500
RT-5500
TCR-25xx
Alarm Output
DO Digital Out Alarm Output Data Ready Alarm Output or PCD-1000
control
P1
Interlock Sample Input
DI3 Digital In 3 Sample Input (1 = interlock) or Interlock Sample Input
ACT-2500
Profi- Trans MBT-2500 BT-5500 DLT-5500 DRT-5500 MBT-4500
bus mitter MEK-2500 BLT-5500
MEK-3000
Dissolved
Consistency Channel 1 lignin Freeness Viscosity
AI1 AO output output (Channel 1) output output
output
AI2 Total
Channel 2 consistency
AO2 Not used output (Channel 2) Not used Not used
output
AI3 AO3 Not used Channel 3 Not used Not used Not used
output
AI4 Channel 4
AO4 Not used output Not used Not used Not used
Channel 5
AI5 AO5 Not used Not used Not used Not used
output
AI6 AO6 Not used Channel 6 Not used Not used Not used
output
Input signal
AO1 AI Not used from external Not used Not used Temperature
or Flow Input
equipment
DI DO Alarm Out(a) Alarm Out(a) Alarm Out(a) Data Ready(a Alarm Out(a)
Total Total
Total Total
consistency consistency
AI1 AO Consistency (Channel 1) Consistency (Channel 1)
output value output value
output value output value
Ash Ash
consistency consistency
AI2 AO2 Not used (Channel 2) Not used (Channel 2)
output value output value
AI3 AO3 Not used Not used Not used Not used
AI4 AO4 Not used Not used Not used Not used
AI5 AO5 Not used Not used Not used Not used
AI6 AO6 Not used Not used Not used Not used
DO3 DI3 Sample In(a) Sample In(a) Sample In(a) Sample In(a)
DO Digital Out 1 Alarm Output Alarm Output Alarm Output Alarm Output Alarm Output
P1
DI3 Digital In 3 Interlock Sample Input Interlock Interlock Remote stop
P2 FF / PROFIBUS PA See separate table below for data between Profibus and Transmitter
Ash
Consistency White water
(Channel 2) Conductivity charge Configurable RMS
(Channel 2) (Channel 2)
AO2 Analog Out 2 output value output value (Channel 2) output value output value
4-20 mA output value 4 - 20 mA
(RET-55x3 4 - 20 mA 4 - 20 mA 4 - 20 mA
P4 only)
Start
streaming CwT
AO4 Analog Out 4 potential for output value
white water Internally pre- 4 - 20 mA
P5 Not used Not used (Channel 2)
wired(a)
Mean Kappa
AO5 Analog Out 5 Not used output value
4 - 20 mA
Analog input
signals from
AI2 Analog In 2 external Internally pre-
equipment
P6 Not used 4 - 20 mA Not used wired(a) Internally
pre-wired(a)
AI3 Analog In 3
Not used
AI4 Analog In 4 Not used
Internally pre-
DI4 Not used Not used Sample Input
Internally wired(a)
P7 Not used
pre-wired(a)
Data ready
DO2 Digital Out 2 Not used Data Ready
Channel 1
Internally pre-
SV4 Sol. valve 4
P8
Internally
Not used Not used wired(a) Internally pre-
pre-wired(a) wired(a)
SV5 Sol. valve 5 Not used
(a) For more information about internally pre-wired connections, see the installation drawing for the transmit-
ter
Profi- Trans
bus mitter RET-55xx RT-5500 SPC-5500 SPM-5500 SPK-5500
Ash
consistency White water
Conductivity Configurable
(Chanel 2) (Channel 2) charge (Channel 2) RMS
AI2 AO2 (Channel 2)
output(a) output(a)
output(a) output(a)
(RET-55x3 output(a)
only)
Start
Media temp. streaming Configurable
CwZ
AI3 AO3 Not used (Channel 3) potential for (Channel 3)
output(a)
output(a) filtrate(a) output(a)
(Channel 1)
Start
streaming Stockline
CwT
AI4 AO4 Not used Not used potential for dilution
output(a)
white water(a) actuator(a)
(Channel 2)
Sensor
dilution Mean Kappa
AI5 AO5 Not used Not used Not used
actuator(a) output(a)
AI6 AO6 Not used Not used Not used Not used Not used
Input signal
AO1 AI Not used from external Not used Not used Not used
equipment
DI DO Alarm Out(a) Alarm Out(a) Alarm Out(a) Alarm Out(a) Alarm Out(a)
Sample Remote
DO3 DI3 Interlock(a) Interlock(a) Interlock(a)
Input(a) stop(a)