Exp 6
Exp 6
----------------------------------------------------------------------------------------------------------
1
The force applied to the armature depends on the current I in the winding
C. When this force exceeds the spring force F the armature is pulled towards the
electromagnet. One or more contacts can be operated (opened or closed) when
the armature moves. Relay RXIC 1 is graduated for overcurrent operation and is
available for both d.c. and a.c. at 16 2/3, 50 and 60-Hz..
On the front panel there is a relay symbol with terminal markings, and
setting knob which adjusts the tension of the armature spring. The scale is
graduated for operation (pick-up) with slowly increasing current. This particular
relay operates so rapidly that the operating values depend on the rate of change
of the actuating quantity. For example, in the event of a short circuit, when the
current increases very rapidly, the relay operates at a value approximately 10%
below the set value. If the short-circuit current has a fully-developed d.c.
component, the relay picks up at a value of the a.c. component which is
approximately 50% of the relay setting.
Equipment:
1. Relay unit,
2. Power supply unit.
3- Digital Voltmeter.
4. Main switch L.
5. Resistor: 5 A, R > 5 Ohm.
6. Digital Ammeter.
2
3
METHOD
Figure 2
4
TABLE 1 RXIG 2
TABLE 2 RXIC 1
ANALYSIS
Calculate the resetting ratio for the two types of relay, and compare the results.
2. POWER CONSUMPTION
METHOD
5
2.5 Check (hat the current (operating values) has not changed after pick-up
(adjust if necessary) and note the voltage.
2.6 Move the voltmeter to RXIG 2.
2.7 Increase the current further and enter the values obtained in Table 4.
2.8 Repeat steps 2.3 - 2.6 twice.
TABLE 3 RXIC 1
Measur- Set Operating Voltage Voltage
ment value Value before after before after
no. (A) (A) operation operation operation operation
(mV) (mV) (VA) (VA)
A
B 1.0 X 2.0
C
TABLE 4 RXIG 2
Measur- Set Operating Voltage Voltage
ment value Value before after before after
no. (A) (A) operation operation operation operation
(mV) (mV) (VA) (VA)
A
B 1.0 X 2.5
C
ANALYSIS:
Calculate the VA, i.e. the product of operating current and relay
voltage before and after operation. Compare the relays and check
whether the readings obtained agree with the listed data. What is
the effect of contact resistance on the readings?.
6
3. EFFECT OF THE D.C. COMPONENT
Equipment:
1- Relay unit.
2- Power supply unit.
3- Digital Voltmeter.
4- Main switch L.
5- Switch B.
6- Diode.
7- Resistor.
8- Digital Ammeter A1.
9- Digital Ammeter A2.
With reference to Fig. 3, when switch B is "ON" the relays can be supplied
with alternating current from the rotary transformer. When the switch is set to
"OFF' the relays are supplied with half-wave-rectified current.
Set ammeter A1 to measure a.c, A2 for d.c, and A3 for true r.m.s. Check
that the ammeters can measure the a.c, and d.c. components of the current when set
in this way. The resistor must be capable of handling 5 A and must have R > 5 ohm.
Ensure that the full resistance of R is in circuit before L is closed.
METHOD
7
Fig. 3
8
TABLE 5 RXIC 1
Measurement Set value Operating Value Resetting Value
(A) (A) (A)
-
A
B 1.0 X 2.0
C
TABLE 6 RXIG 2
Measurement Set value Operating Value Resetting Value
(A) (A) (A)
A
B 1.0 X 2.5
C
TABLE 7 RXIG 1
Measur- Set Operating value (A) Reseting value (A)
ment- value(A) A1 A2 A3 A1 A2 A3
A
B 1.0 X 2.0
c
* Calculated as described in the equation below:
TABLE 8 RXIG 2
Measur- Set Operating value (A) Reseting value (A)
ment- value(A) A1 A2 A3 A1 A2 A3
A
B 1.0 X 2.5
c
Note:
True rms I d2 I a2
-9-