0% found this document useful (0 votes)
143 views

Image For Illustrative Purposes Only..: Generating Set Model (Pm165)

Deals in All types of Engines, Generators (2kva 2500kva), Solar Panels etc call us Now 03212010005 , 03032010005 visit our website : www.powermax.pk

Uploaded by

Anamta Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
143 views

Image For Illustrative Purposes Only..: Generating Set Model (Pm165)

Deals in All types of Engines, Generators (2kva 2500kva), Solar Panels etc call us Now 03212010005 , 03032010005 visit our website : www.powermax.pk

Uploaded by

Anamta Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TM PZ165

PM 165
3 PHASE/1500RPM

Image for illustrative purposes only..


GENERATING SET MODEL (PM165) ALTERNATOR DATA
Output Ratings Prime Standby Make Stamford
380-415 V, 3 ph, 50 Hz, 1500 rpm 150 KVA 165 KVA Model UC1274F
120 KW 132 KW No. of bearings 1
Insulation class H
Total Harmonic Content <2%
Wires 12
ENGINE / TECHNICAL DATA Ingress Protection IP23
Excitation System SHUNT
Ratings at 0.8 Power Factor
Winding Pitch 2/3 (n° 6)
AVR Model R250
Engine Make Perkins
Overspeed 2250 mn-1
Engine Model 1106A-70TAG2
Voltage Regulation (steady) ± 0.5%
Governing Type Electronic
Short Circuit Capacity -
Number of Cylinders 6
Cylinder Arrangement Vertical in line CONTROL PANEL
Bore and Stroke mm 105 x 135 Make Deep Sea
Displacement / Cubic Capacity litres 7.01 Model 7120
Induction System Turbocharged, air to air aftercooled
The DSE7120 is an Auto Start Control Module for
Cycle 4 stroke
single genset applications. It includes a backlit LCD
Combustion System Direct Injection display which clearly shows the status of the
Compression Ratio 16:1 engine all the times. This module can either be
Rotation Anti-clockwise, viewed on flywheel programmed using the front panel or by using the
Cooling System Water - cooled DSE configuration suite PC software.

Frequency and Engine Speed 50Hz & 1500rpm Metering and Alarm indications:
Prime Standby • Generator frequency
• Underspeed, Overspeed
Gross Engine Power kW (hp) 136.8 (183.4) 150.5 (201.7) • Generator volts (L-L, L-N)
Fuel Consumption @ 50% load L/hr 16.7 - • Generator current
@ 75% load L/hr 25 - • Engine oil pressure
• Engine coolant temperature
@ 100% load L/hr 32.4 45
• Fuel level (Warning or shutdown) - Optional
Total Lubrication System Capacity litres 16.5 16.5 • Hours run counter
Total Coolant Capacity (inc. radiator) litres 21 21 • Battery volts
• Fail to start/stop
• Emergency stop
Exhaust Temperature: °C 580 595
• Failed to reach loading voltage/frequency
Radiator Cooling Air Flow (Min): m3/sec 2.57 2.57 • Charge fail
Combustion Air Flow: m3/min 10.1 10.7 • Loss of magnetic pick-up signal - Optional
Exhaust Gas Flow: m3/min 29.1 31.3 • Low DC voltage
Fuel Tank Capacity: litres 259 259 • CAN diagnostics and CAN fail/error
STANDARD SPECIFICATIONS PM165

1. ENGINE 7. ALTERNATOR 913..FACTORYWARRANTYTEST

Perkins four stroke heavy duty high 7.1 INSULATION SYSTEM • The Generating set is load tested before dispatch
performance industrial type diesel engine. • The insulation system is Class H. • All protective devices control functions and site
• All windings are impregnated in either a load conditions are simulated. The generator and
triple dip thermosetting liquid, oil and acid it’s systems are checked before dispatch.
2. ENGINE FILTRATION SYSTEM resisting polyester varnish or vacuum pressure
impregnated with a special polyester resin. 10.13. EQUIPMENTWARRANTY FINISHING
• Cartridge type dry air filter.
• Heavy coat of antitracking varnishadditional
• Two Cartridge type fuel filters.
protection against moisture or condensation.
• Full flow lube oil filter. All mild steel components are fully degreased and
All filters have replaceable elements. 7.2 AUTOMATIC VOLTAGE REGULATOR (AVR) painted with powder coated paint to ensure
The fully sealed Automatic Voltage maximum scuff resistance and durability.
3 . Regulator maintains the Voltage Regulation
3 . COOLINGRADIATOR at ±0.5%. Nominal adjustment by means of 1113.. DOCUMENTATIONWARRANTY
Radiator and cooling fan, complete with safety guards, a trim pot incorporated on the AVR.
designed to cool the engine at high ambient temperatures
Operation & Maintenance manual, Circuit wiring diagrams
(consult your dealer for de-ration factors) 7.3 MOTOR STARTING
and Commissioning / Fault Finding instruction leaflets are
An overload capacity equivalent to 300% of
accompanied with the Generator.
the Full Load impedance at zero Power
4. EXHAUST SYSTEM Factor can be sustained for 10 seconds,
when AREP or PMG option is fitted. 123.2..QUALITYWARRANTYSTANDARDS
Heavy duty Industrial Exhaust Silencer
813..MOUNTINGWARRANTYARRANGEMENT
The equipment meets the following standards:
Silencer noise reduction level 12 (dB)
8.1 BASE FRAME BS4999, BS5000, BS5514 IEC 60034,
Maximum allowable back pressure 6 (kPa) The complete Generating Set is mounted as a whole VDE0530, NEMA MG 1.22 and ISO 8528.
on a heavy duty fabricated steel Baseframe.

55..CIRCUTBREAKER TYPE 8.2 COUPLING 1313.. WARRANTY


The Engine and Alternator are directly coupled by
ABB 3 pole MCCB. (4 pole is optional) means of an SAE flange. The Engine flywheel is All of the Generating Sets
flexibly coupled to the Alternator rotor. arecovered under a
warranty policy for a period of 24 months.
6.6.FUEL SYSTEM 8.3 ANTI-VIBRATION MOUNTING PADS Warranty of the equipment is in line with
Anti-Vibration pads are affixed between the Engine / manufacturers warranty terms & conditions.
The baseframe design is incorporated with an Alternator feet and the Baseframe thus ensuring (check warranty statement for more details, as it may vary for different countries)
integral fuel tank with a capacity of approx. 8 hours complete vibration isolation of the rotating assembly.
running at Full Load. The tank is supplied complete In line with continuous product development, we reserve

with fill cap breather, fuel feed and return lines to 8.4 SAFETY GUARDS the right to change specifications without notice.
the Engine and drain plug. The Fan & Fan Drive along with the Battery
Charging Alternator are Safety Guard
protected for personnel protection.

STANDARD REFERENCE CONDITIONS

H
Prime Power
These ratings are applicable for supplying continuous electrical power (at variable load)
in lieu of commercially purchased power. 10% overload power is available for 1 hour in 12
hours continuous operation.
Standby Power L
These ratings are applicable for supplying continuous electrical power (at variable load)
in the event of a utility power failure. No overload is permitted on these ratings.
DIMENSIONS AND WEIGHT

Length cm Width cm Height cm Weight* kg (wet)


211 69 130 1360