Liebert CW: System Design Manual - 26-181kW, 50 & 60Hz
Liebert CW: System Design Manual - 26-181kW, 50 & 60Hz
Liebert® CW™
System Design Manual - 26-181kW, 50 & 60Hz
FIGURES
Figure 1 Dimensions, CW026 - CW084. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 2 Dimensional Data—50 & 60 Hz Systems CW106—CW114, downflow models . . . . . . . . . . . . . . . . 7
Figure 3 Cabinet and Floor Planning Dimensional Data, Downflow Model CW181 with EC Fans . . . . . . . 8
Figure 4 Cabinet and floor planning dimensions, upflow models—CW026-CW084 . . . . . . . . . . . . . . . . . . . 9
Figure 5 Cabinet and floor planning dimensions, CW 106 and CW114 upflow models. . . . . . . . . . . . . . . . 10
TABLES
Table 1 Electrical data—60Hz-3 phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 Electrical data—50Hz-3 phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 3 CW181 electrical data—60Hz-3 phase. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 4 CW181 electrical data—50Hz-3 phase. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 5 Electrical data—50 Hz systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 6 Indoor evaporator fan motor electrical requirements—50Hz systems . . . . . . . . . . . . . . . . . . . . . 13
Table 7 Electrical data—60 Hz Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 8 Indoor evaporator fan motor electrical requirements—60Hz systems . . . . . . . . . . . . . . . . . . . . . 15
CW 114 D C S A 2 1234 A
Air Volume CFM (CMH) 5250 6050 5900 9300 9100 12,500 12,100 17,100 16,500
(8920) (10,280) (10,020) (15,800) (15,460) (21,240) (20,560) (29,070) (28,050)
Fan Motor HP (kW) 3.0 (2.2) 5.0 (3.7) 5.0 (3.7) 7.5 (5.6) 7.5 (5.6) 10 (7.5) 10 (7.5) 15 (11.2) 15 (11.2)
Ext. Static Press. in. of water (Pa) 0.2 (50) 0.2 (50) 0.2 (50) 0.2 (50) 0.2 (50) 0.2 (50) 0.2 (50) 0.2 (50) 0.2 (50)
Number of Fans 1 1 1 2 2 2 2 3 3
Chilled Water Coil
Face Area sq. ft. (m2) 11.7 (1.08) 11.7 (1.08) 11.7 (1.08) 18.5 (1.72) 18.5 (1.72) 25.0 (2.32) 25.0 (2.32) 36.28 (3.37) 36.28 (3.37)
Number of Rows 3 4 6 4 6 4 6 4 6
Face Velocity FPM (m/s) 431 (2.2) 499 (2.5) 486 (2.4) 482 (2.4) 471 (2.4) 484 (2.5) 480 (2.4) 471 (2.3) 460 (2.3)
Chilled Water Controls (Maximum design water pressure 150 PSI [1034.3 KPa]. Higher pressure available as an option. Consult factory.)
Valve Actuator Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Sensors Proportional Proportional Proportional Proportional Proportional Proportional Proportional Proportional Proportional
Valve Body 3-Way 3-Way 3-Way 3-Way 3-Way 3-Way 3-Way 3-Way 3-Way
Valve Cv 11.6 11.6 28.9 28.9 46.2 46.2 46.2 46.2 46.2
Valve Size - inches 1 1-1/4 1-1/2 1-1/2 2 2 2 2 2
2-Way Valve (0ptional)
Close Off Pressures-PSI (kPa) 86 (593) 86 (593) 70 (483) 70 (483) 45 (310) 45 (310) 45 (310) 45 (310) 45 (310)
REHEAT SECTION
Electric Reheat: Three-Stage, Fin Tube
Capacity BTU/HR (kW)* 39,200 (10) 58,800 (15) 58,800 (15) 81,000 (20) 98,100 (25) 121,500 (30) 121,500 (30) 127,900 (30) 127,900 (30)
Steam Reheat: 218°F (103.3°C) Steam, 75°F (23.9°C) E.A.T., STD MTR-Modulating Control Valve 2-way****†
84,100 85,800 85,800 93,400 144,500 163,200 163,200 171,700 171,700
Capacity BTU/HR (kW)*
(24.6) (25.1) (25.1) (27.4) (42.4) (47.8) (47.8) (50.3) (50.3)
Hot Water Reheat: Capacity @ 180°F (82.2°C) E.W.T., STD MTR 75°F (23.8°C) E.A.T. - Modulating Control Valve 2-way****†
47,000 49,500 49,500 89,900 89,900 125,200 125,200 133,700 133,700
Capacity BTU/HR (kW)*
(13.7) (14.5) (14.5) (26.3) (26.3) (36.7) (36.7) (39.2) (39.2)
Flow Rate-GPM (l/s) 5 (.31) 5 (.31) 5 (.31) 8 (.50) 8 (.50) 8 (.50) 8 (.50) 8 (.50) 8 (.50)
Pressure Drop-PSI (kPa) 3.5 (24.1) 3.5 (24.1) 3.5 (24.1) 1.6 (11.0) 1.6 (11.0) 1.6 (11.0) 1.6 (11.0) 1.6 (11.0) 1.6 (11.0)
* Includes Fan Motor ** Optional 3-Way valve available-consult factory *** 25 PSI (172.4 kPa) Max operating pressure-consult factory for higher pressures.
† Unit CFM reduced by 300 with std. motor (142 l/s) **** 150 PSI (1034.3 kPA) Max operating pressure-consult factory for higher pressures.
HUMIDIFIER SECTION
Infrared Humidifier (Note: 50Hz Models are 22.1 lb/hr. (10.0 kg/h); 9.6 kW)
Capacity-lb/hr. (kg/h) 11.0 (5.0) 11 (5.0) 11.0 (5.0) 17.4 (7.9)„ 17.4 (7.9)„ 22.1 (10.0) 22.1 (10.0) 22.1 (10.0) 22.1 (10.0)
kW 4.8 4.8 4.8 6.4„ 6.4„ 9.6 9.6 9.6 9.6
Pan Stainless Stainless Stainless Stainless Stainless Stainless Stainless Stainless Stainless
Steam Generating Humidifier (Water conductivity between 200-500 micromhos is required for ideal operation)
Capacity-lb/hr. (kg/h) 11 (5.0) 11 (5.0) 11.0 (5.0) 22 (10.0) 22 (10.0) 22 (10.0) 22 (10.0) 22 (10.0) 22 (10.0)
Capacity-kW 3.6 3.6 3.6 7.2 7.2 7.2 7.2 7.2 7.2
Steam Grid Humidifier - All Models (Standard Selection, 5 PSIG. (34.5 kPa) Steam 14 lb./hr. (6.4 kg/h)
Supply Steam Pressure,
— 2 (13.8) 4 (27.6) 5 (34.5) 6 (41.4) 8 (55.2) 10 (68.9) — —
PSIG (kPa)
Capacity-lb/hr. (kg/h),
— 8 (3.6) 12 (5.4) 14 (6.4) 16 (7.3) 19 (8.6) 21 (9.5) — —
w/ 5/32* orifice
Filter Section - Disposable Type - Nominal Sizes and Quantities, Downflow Models
Nominal Size, in 18x24 18x24 18x24 18x24 18x24 18x24 18x24 24x31 24x31
Quantity 4 4 4 6 6 8 8 5 5
Upflow Models (Front Return)
Nominal Size, in 24x24 24x24 24x24 24x24 24x24 24x24 24x24 18x24 18x24
Quantity 2 2 2 3 3 4 4 10 10
Upflow Models (Bottom & Rear Return) Bottom Return not available on CW106/CW114
Nominal Size, in 18x24 18x24 18x24 18x24 18x24 18x24 18x24 18x24 18x24
Quantity 4 4 4 6 6 8 8 10 10
CONNECTION SIZES
Chilled Water-OD Copper 1-1/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8
Infrared Humidifier-OD Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Condensate Drain-FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 1-1/4 1-1/4
Steam Reheat-MPT 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Hot Water Reheat-OD Copper 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8
Steam Humidifier-MPT 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Weight-lb (kg)- Installed 810 (367) 845 (383) 895 (406) 1140 (517) 1210 (549) 1390 (630) 1490 (676) 1950 (885) 2090 (949)
(25.4mm
) Opening turn O 2"
penin
g (50.8mm)
Pre-Filter
9"
Plenum
(228mm)
1"
Un E )
it B (25.4mm
Shaded areas
as
indicate a recommended e
F as e
clearance of 36" (914mm) B
it 72"
for component access Un
(1829mm)
and filter removal. Unit Dimensional Data
1"
F Reheat or Humidifier
(25.4mm)
3" Piping Opening
(76.2mm) G (Optional Steam and
9" (228mm) Hot Water Only)
1" (25.4mm) Air Discharge Models With Pre-Filters
Opening
) H
08mm
20" (5
1"
Standard Piping DPN001659
E (25.4mm)
and Electrical Opening Rev. 0
Fl 18"
oo
rL (457mm)
ev
el
G
Overall Dimension
Projection of A
Overall
Display Bezel C Dimen
sion
3/4" (19mm)
D
turn Air R B
2" (50.8mm) Air Re g eturn G
Openin Open 2"
ing Overall
(50.8mm) Dimens
ion
A
Overall
Projection of Dimen
C Unit an sio
Display Bezel
binet d Plenu n
76" 3/4" (19mm) Unit Ca m
Ple n u m
(1930mm) ll
1" Overa
(25.4mm) H
2" (51mm)
turn
Air Re g Air Re B
Op e n
in turn O
pening
2"
Pre-Filter (50.8mm)
Plenum 9"
(228mm)
Un E 1"
Shaded area it B
indicates a recommended as (25.4mm)
e
clearance of 36" (914mm) F se
a 76"
for component access nit B
U (1930mm)
and filter removal
F UNIT DIMENSIONAL DATA
20"
Air Discharge
(508mm)
Opening
m)
(25.4m 77" (1955.8mm) MODELS WITH PRE-FILTERS
1" 28" ) 26"
mm (660.4mm)
(711 Note: Electrical opening is also
1" used for drain connection of optional
Standard Piping E (25.4mm) steam generating canister humidifie r.
10"
Opening (254mm)
"
24 m m
) *This drawing pertains to CW106 and CW 114
6" 16-1/4"
*Electrical 0 9 .6 (152.4mm) with forward-curve blowers onl y.
( 6 1" (412.75mm)
Opening
(25.4mm)
Figure 3 Cabinet and Floor Planning Dimensional Data, Downflow Model CW181 with EC Fans
47"
39-1/2" (1194mm)
(1003mm)
Opening
122"
(3099mm)
36"
(914mm)
24"
76"
(610mm)
(1930mm)
Striated area indicates the
recommended minimum
clearance for component
access. Shaded area indicates the
required minimum clearance
120"
below the unit to lower the
(3048mm)
1-1/2" fans. Fans may also remain in
(38mm) FRONT VIEW unit if desired.
Note: Dimensions do not include filter plenum
shipped separate and field-Ainstalled. DPN001694
REV 0
35-5/8"
)
(905mm
Overall A
Projection Of on
Dimensi Overall L
Display Bezel 35" Dimen Duct Flanges on 2 Blowers
sion
3/4" (19mm) m)
(8 9m
8
H
1" K
(25.4mm) J J
M
Front of Unit
72" Duct Flanges on One Blower
(1829mm)
H
K
J
Front of Unit
33" m) 5-1/2"
8m (139.7mm)
(83 2"
2 m) ng
9m ni
/8" ( 5
5 D pe
1-1 m) Air Return O
m n
(28
.6 Opening ur
Ret
G r
Ai
Air Return A return air grille
C Opening may be ordered in
B place of the duct
F E flange. See specification
Fl Models With Rear Return sheet for option supplied.
oo
Floor Cutout Dimensions rL
ev DPN001661
Models With Bottom Return el Rev. 0
Figure 5 Cabinet and floor planning dimensions, CW 106 and CW114 upflow models
35" Overall
(889mm) 122" Overall
Projection of Display (3099mm)
32"
Bezel 3/4" (19mm)
(813mm)
Plenum 118"
2" (51mm) Flange (2997mm)
Plenum Flange
2"
76" (51mm)
(1930mm)
Filter Access
(Both Ends) 24-1/4" (616mm)
2-1/4"
(57mm)
Shaded area indicates
4" (102mm) 22" (546mm)
a recommended clearance
of 25" (635mm) for rear
return filter removal Duct Connection Data DPN001662
on one end of the unit. Models With Rear Return REV 0
10
FRONT OF UNIT
BLOWER DUCT FLANGE LOCATION - One Fan
A
G Air Return
H
B B Opening
E
4" (102mm)
FRONT OF UNIT DUCT CONNECTION DATA
BLOWER DUCT FLANGE LOCATION - Two Fans Models with Rear Return
11
6.0 BLOWER DUCT & DECK DIMENSIONS, CW106 AND CW114, UPFLOW MODELS
Dimensional Data, inches (mm)
Motor, Net Weight
Model Blower Supply hp A B C D E F lb. (Kg)
27-1/2 3 1/2 18-11/16 16-3/16 10 4 1/2
Top Front 10-15
(699) (89) (475) (411) (254) (114) 1785
CW106 15 x 15
27-1/2 12 5/16 18 11/16 16 3/16 10 4 1/2 (810)
Top Rear 10-15
(699) (313) (475) (411) (254) (114)
30 3 1/2 14 3/4 16 3/16 10 4 1/2
Top Front 10-15
(762) (89) (375) (411) (254) (114)
30 3 1/2 14 3/4 16 3/16 10 4 1/2 1925
CW114 15 x 11 20
(762) (89) (375) (411) (254) (114) (873)
30 12 5/16 14 3/4 16 3/16 10 4 1/2
Top Rear 10-20
(762) (313) (375) (411) (254) (114)
TOP-FRONT
SUPPLY SHOWN
76"
Ref
Air
117-1/2" Return
(2985mm) Opening
2
4"
(102mm) NOTE: Only 120"
2-1/4" Upflow has rear
(57mm) return filter box.
22"
(546mm) 1
122" Ref
Duct Flanges on Three Blowers
A B
Front of Unit
Blower Duct Flange Location
12
13
14
CW106 FLA 165.1 154.8 77.7 63.7 86.0 76.2 38.6 33.6 138.5 132.6 66.1 52.1 59.4 54.0 27.0 22.0
20.0 HP WSA 206.4 193.5 97.1 79.6 107.5 95.3 48.3 42.0 173.1 165.8 82.6 65.1 74.3 67.5 33.8 27.5
(Upflow only) MFCB 225 200 110 90 150 125 70 60 200 200 90 70 125 110 60 45
FLA 136.5 128.8 64.7 52.7 57.4 50.2 25.6 22.6 109.9 106.6 53.1 41.1 30.8 28.0 14.0 11.0
CW114
10.0 HP WSA 170.6 161.0 80.9 65.9 71.8 62.8 32.0 28.3 137.4 133.3 66.4 51.4 38.5 35.0 17.5 13.8
MFCB 175 150 80 60 90 80 40 35 125 125 70 50 60 60 30 20
FLA 151.9 142.8 71.7 58.7 72.8 64.2 32.6 28.6 125.3 120.6 60.1 47.1 46.2 42.0 21.0 17.0
CW114
WSA 189.9 178.5 89.6 73.4 91.0 80.3 40.8 35.8 156.6 150.8 75.1 58.9 57.8 52.5 26.3 21.3
15.0 HP
MFCB 200 175 90 70 125 110 50 45 175 150 80 60 100 90 45 35
CW114 FLA 165.1 154.8 77.7 63.7 86.0 76.2 38.6 33.6 138.5 132.6 66.1 52.1 59.4 54.0 27.0 22.0
20.0 HP WSA 206.4 193.5 97.1 79.6 107.5 95.3 48.3 42.0 173.1 165.8 82.6 65.1 74.3 67.5 33.8 27.5
(Upflow only) MFCB 225 200 110 90 150 125 70 60 200 200 90 70 125 110 60 45
15
GUIDE SPECIFICATIONS
1.0 GENERAL
1.1 Summary
These specifications describe requirements for a precision environmental control system. The system
shall be designed to maintain temperature conditions in the rooms containing electronic equipment.
The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation
requirements of the room.
1.2 Design Requirements
The precision environmental control system shall be a Liebert self-contained factory assembled unit
with (upflow) (down-flow) air delivery. The system shall have a total cooling capacity of ____ BTU/
HR, (kW) with a sensible cooling capacity of ____ BTU/ HR (kW) based on an entering air temperature
of ____ °F (°C) dry bulb and ____ °F (°C) wet bulb. The unit is to be supplied with ____ volt ____ ph
____ Hz electrical service.
1.3 Submittals
Submittals shall be provided with the proposal and shall include: Single-Line Diagrams; Dimen-
sional, Electrical, and Capacity Data; Piping and Electrical Connection Drawings.
2.0 PRODUCT
2.1 Cabinet and Frame Construction
The frame shall be constructed of heliarc welded tubular steel. It shall be painted using the auto-
phoretic coating process for maximum corrosion protection. The exterior panels shall be insulated
with a minimum 1 in. (25.4mm), 1.5 lb. (0.68 kg) density fiber insulation. The main front panel shall
have captive 1/4 turn fasteners. The main unit color shall be _________. The accent color shall be
_________. The exterior panels shall be powder coated.
2.2 Filter Chamber
The filter chambers shall be an integral part of the system, located within the cabinet serviceable
from either end of the unit. The filters shall be rated not less than ____% efficiency (based on
ASHRAE 52.1).
For models CW106 and CW114, the filters shall be serviceable from the front of the unit.
2.3 Fan Section
The fan shall be the centrifugal type, double width double inlet, and shall be factory-balanced as a
completed assembly. The shaft shall be heavy duty steel with self-aligning ball bearings with a mini-
mum life span of 100,000 hours. The fan motor shall be ____ hp at 1750 RPM at 60 Hz (1450 RPM at
50 Hz) and mounted on an adjustable slide base. The drive package shall be two-belt, variable speed,
sized for 200% of the fan motor horsepower. The fans shall be located to draw air over the A-frame coil
to ensure even air distribution and maximum coil performance.
2.3 Electronically Commutated (EC) Fan
The fan shall be the plug/plenum type, single inlet and shall be dynamically balanced. The fan motor
shall be 4.2 hp, 1520 rpm maximum operating speed. The drive package shall be direct drive Electron-
ically Commutated, variable speed. The fans shall be located to draw air over the A-frame coil to
ensure even air distribution and maximum coil performance.
2.4 Liebert iCOM™ Microprocessor Control With Small Graphic Display
The Liebert iCOM unit control shall be factory-set for Intelligent Control which uses “fuzzy logic” and
“expert systems” methods. Proportional and Tunable PID shall also be user selectable options. Inter-
nal unit component control shall include the following:
16
System Auto Restart - The auto restart feature will automatically restart the system after a power
failure. Time delay is programmable.
Sequential Load Activation - On initial startup or restart after power failure, each operational
load is sequenced with a minimum of one second delay to minimize total inrush current.
Hot Water Flush Cycles - Hot water reheat coils and Econ-O-Coils are periodically flushed to pre-
vent a buildup of contaminants.
Predictive Humidity Control - calculates the moisture content in the room and prevents unneces-
sary humidification and dehumidification cycles by responding to changes in dew point temperature.
The Liebert iCOM control shall be compatible with Liebert remote monitoring and control devices.
Options are available for BMS interface via MODbus, Jbus, BACNet, Profibus and SNMP.
The Liebert iCOM control processor shall be microprocessor based with a 128x64 dot matrix graphic
front monitor display and control keys for user inputs mounted in an ergonomic, aesthetically pleas-
ing housing. The display & housing shall be viewable while the unit panels are open or closed. The
controls shall be menu driven. The display shall be organized into three main sections: User Menus,
Service Menus and Advanced Menus. The system shall display user menus for: active alarms, event
log, graphic data, unit view/status overview (including the monitoring of room conditions, operational
status in % of each function, date and time), total run hours, various sensors, display setup and ser-
vice contacts. A password shall be required to make system changes within the service menus. Service
menus shall include: setpoints, standby settings (lead/lag), timers/sleep mode, alarm setup, sensor
calibration, maintenance/wellness settings, options setup, system/network setup, auxiliary boards
and diagnostics/service mode. A password shall be required to access the advanced menus which
include the factory settings and password menus.
17
18
Advanced Menus
Factory Settings: Configuration settings shall be factory-set based on the pre-defined component
operation.
Change Passwords: Menu shall allow new passwords to be set or changed.
2.4.1 Liebert iCOM Microprocessor Control With Large Graphic Display (Optional)
The Liebert iCOM unit control with large graphic display shall include all of the features as the Lie-
bert iCOM with small graphic display, except that it includes a larger graphical display and shall
include the additional features of:
“System View”, Spare Parts List, Unit Diary.
The Liebert iCOM control processor shall be microprocessor based with a 320x240 dot matrix graphic
front monitor display panel and control keys for user inputs mounted in an ergonomic, aesthetically
pleasing housing.
System View - Status Overview: “System View” shall display a summary of operation for the total
number of operating units within a Unit-to-Unit (U2U) configuration.
Spare Parts List: Menu shall include a list of critical spare parts, their quantity and part numbers.
Unit Diary: Menu shall include a free field area within the unit memory where unit history may be
stored for reference.
2.5 Liebert iCOM Wall-Mount Large Graphic Display (Optional)
The Liebert iCOM Large Graphic Display Kit shall include an ergonomic, aesthetically pleasing hous-
ing, a 320x240 dot matrix graphic display and a 120V power supply. The Wall-Mount Large Graphic
Display shall be used to allow remote location of a “System View” display and all features of the Large
Graphic User, Service and Advanced menus for use with Liebert iCOM controlled products connected
for Unit-to-Unit (U2U) communications.
2.5.1 Control
The control system shall allow programming of the following room conditions:
• Temperature Setpoint: 65-85°F (18-29°C)
• Temperature Sensitivity: ±1° to 9.9°F (0.6 to 5.6°C) in 0.1°F (0.1°C) increments
All setpoints shall be adjustable from the individual unit front monitor panel. Temperature and
humidity sensors shall be capable of being calibrated using the front monitor panel controls to coordi-
nate with other temperature and humidity sensors in the room.
In addition, the system shall provide the following internal controls:
19
2.5.1.4 Alarms
The Liebert iCOM control shall activate an audible and visual alarm in event of any of the following
conditions:
• High Temperature
• Low Temperature
• High Humidity
• Low Humidity
• Main Fan Overload (opt)
• Change Filters
• Loss of Air Flow
• Loss of Power
• Custom Alarm (#1 to #4)
Custom alarms are four customer accessible alarm inputs to be indicated on the front panel. Custom
alarms can be identified with prepared (programmed) labels for the following frequently used inputs:
• Leak Under Floor
• Smoke Detected
• Loss of Water Flow
• Standby Unit On
User customized text can be entered for two of the four custom alarms.
Each alarm (unit and custom) can be separately enabled or disabled, selected to activate the common
alarm, and programmed for a time delay of 0 to 255 seconds.
2.5.1.8 Diagnostics
The control system and electronic circuitry shall be provided with self-diagnostics to aid in trouble-
shooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs
shall be indicated as on or off at the front monitor panel. Control outputs shall be able to be turned On
or Off from the front monitor panel without using jumpers or a service terminal.
2.5.1.10 Communication
The Liebert iCOM control shall be compatible with Liebert remote monitoring and control devices.
2.6 Chilled Water Control Valve
The water circuit shall include a 3-way (2-way) modulating valve. The Liebert iCOM positions the
valve in response to room conditions. Cooling capacity will be controlled by bypassing chilled water
around the coil.
20
21
3.0 EXECUTION
3.1 Installation of Precision Cooling Units
3.1.1 General
Install precision cooling units in accordance with manufacturer’s installation instructions. Install
units plumb and level, firmly anchored in locations indicated, and maintain manufacturer’s recom-
mended clearances.
22
Emerson Network Power, the global leader in enabling business-critical Technical Support / Service
continuity, ensures network resiliency and adaptability through Web Site
a family of technologies—including Liebert power and cooling www.liebert.com
technologies—that protect and support business-critical systems. Monitoring
800-222-5877
Liebert solutions employ an adaptive architecture that responds
[email protected]
to changes in criticality, density and capacity. Enterprises benefit Outside the US: 614-841-6755
from greater IT system availability, operational flexibility and Single-Phase UPS
reduced capital equipment and operating costs. 800-222-5877
[email protected]
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
[email protected]
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
Fax: +39 049 5841 257
responsibility and disclaims all liability for damages resulting from use of Asia
this information or for any errors or omissions. 7/F, Dah Sing Financial Centre
© 2008 Liebert Corporation 108 Gloucester Road, Wanchai
All rights reserved throughout the world. Specifications subject to change
without notice. Hong Kong
® Liebert is a registered trademark of Liebert Corporation. 852 2572220
All names referred to are trademarks Fax: 852 28029250
or registered trademarks of their respective owners.
SL-18056_REV0_11-08
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.