EPM307 - Protection Devices and Systems
EPM307 - Protection Devices and Systems
Part I : Switchgear
BY
CHAPTER (1)
TYPES OF CIRCUIT BREAKERS
1.1 Arc Extinction
1.1.1 Introduction
The electric arc is a type of an electric discharge between electrodes. In
circuit-breakers, the arc persists during the brief period after separation of current
carrying contacts. The circuit-breaker should be capable of extinguishing the arc
without getting damaged. The arc plays an important role in the behavior of the
circuit breaker. The interruption of d.c. arcs is relatively more difficult than a.c. arcs.
In a.c. arcs, as the current becomes zero during the regular wave, the arc vanishes
and it is prevented from re-striking. In this chapter we shall study technical aspects
regarding the arc and the techniques employed for arc extinction.
The arc extinction duty, though not frequent, produces highest stresses on the
circuit-breaker. The techniques adopted for the arc extinction can be classified into
the following two categories:
- High resistance interruption. The resistance of the current path is increased
rapidly resulting in the increased voltage drop. The arc gets extinguished
when the system voltage can no longer maintain the arc, due to high value of
the voltage drop. This principle is used in d.c. circuit-breakers and air-break
type a.c. circuit-breakers of relatively low capacities of the order of a few
hundred MVA. In this method the high value and the energy arc-length is
increased. The energy stored in system inductance is gradually dissipated in
the arc.
- Current zero interruption. The arc is interrupted at natural current zero of
the alternating current wave and the dielectric strength of the contact-gap is
increased to such an extent that it can withstand the voltage stress across it.
This principle is used in almost all the other circuit-breakers except the d.c.
circuit-breakers and air break a.c. circuit breakers.
1.1.3 Deionization
Deionization can take place by the processes of recombination or attachment
as well as by process of diffusion and drift. These have been discussed here very
briefly.
t
E arc ivdt
0
t
(iarct )(v)dt
0
t
iarc
2
r sin 2 tdt
0
The theory assumes that the re-striking voltage and buildup of dielectric
strength are comparable quantities. The assumption is not quite correct. These two
entities are not identical. Secondly this theory does not consider the energy relations
in the arc extinction. This theory does not cover the arcing phase, hence it is
incomplete. Slepian was the first to point out that the re-striking voltage plays an
important role in arc extinction.
QUESTIONS
(a)
(b)
(c)
1. Main contacts.
2. Arcing contacts.
3. Arc rising in the direction of the arrow.
4. Arc getting split.
5. Arc splitter plates.
6. Current carrying terminal.
7. Arc runners.
Fig.1.9. Arc extinction is air-break circuit-breaker
1. Isolating contacts.
2. Insulating bushing.
3. Carriage.
4. Arc runner.
5. Arc splitters.
6. Contacts.
7. Operating solenoid.
8. Operating mechanism.
9. Operating Lever.
10. Cover with vents … current path.
11. Link.
Fig.1.9. Truck-mounted air-break circuit-breaker shown in closed position
1.2.4. Some Technical Aspects
- Simple construction, indoor, panel mounted. Current limiting feature. The
short circuit current is limited by opening of circuit-breaker and the resistance
of extended arc.
- Suitable for repeated operation because the medium is air. Hence this type of
circuit-breaker is popular for industrial loads in which breaking occurs
repeatedly.
- Mounting can be on a panel or in a draw-out cubicle.
- Operating control is manual as well as automatic.
These breakers are commonly used for voltage up to 660 volts and breaking
capacity of 15 MVA. However, now breakers up to 12kV, 500 MVA have been
developed.
These breakers have only one break per pole.
1. Arc chutes having deionization plates coated with plastic paint on the top half.
2. Arc runner for extending the arc for effective and quick extinction.
3. Magneto thermal release with inverse time current characteristic on overload and instantaneous
tripping on heavy fault currents.
4. Moving contact carrier.
5. Main trip rocker arm on which the super rapid tripping device acts.
6. Main operating shaft.
7. Arcing horn.
8. Arcing contacts.
9. Main contacts.
10. Current transformer for feeding releases.
11. Line terminal.
12. Load terminal.
13. Super rapid tripping device : a built-in protection device which trips the breaker from the function
point.
Fig.1.10. Sectional view of a low voltage circuit0breaker
Fig.1.11 we observe that the prospective short circuit current, (i.e. the current
that would flow in the circuit if the circuit-breaker is replaced by conductor), would
be as indicated by thin line. But the circuit-breaker modifies the current waveform
and has a limiting effect so as to obtain the waveform shown by thick line of let
through current. The contacts open rapidly and the increased are length gives the
current limiting property.
Typical rating of d.c. circuit breaker 1500V, 10kA continuous, 80kA breaking.
1. Describe with neat sketches the principle of d.c. circuit-breakers. How does is differ from a.c.
circuit-breakers?
2. Explain the arc interruption process in air-break circuit-breakers incorporating arcing horns and
arc splitters.
3. Describe the principle of magnetic blow out.
4. Explain the features of an air-break circuit-breaker by means of simple sketches.
5. State the merits of air-break circuit-breakers for application in industrial switchgear.
6. Write short notes (any two) :
- Air-break circuit-breaker.
- Miniature circuit-breaker.
- Magnetic blow-out of arc.
- Current limiting by air c.b.
7. State whether correct or wrong. Write corrected statement where necessary.
(a) Air-break circuit-breakers are generally provided with current limiting feature.
(b) Miniature circuit-breakers are used instead of HRC fuses in LV circuits.
(c) Air-break circuit-breakers are applied for 36kV and 66kV rated voltages.
(d) Ratings of low voltage a.c. switchgear follow the same specifications as the specifications of
high voltage a.c. circuit-breakers.
(e) Hydraulic Mechanism is preferred for Air-break circuit-breakers.
1.3 Air Blast Circuit-Breaker
1.3.1 Construction of an Air Blast Circuit-Breaker
In air blast circuit-breaker (also called compressed air circuit-breaker) high
pressure air is force on the arc through a nozzle at the instant of contact separation.
The ionized medium between the contacts is blown away by the blast of the air. After
the arc extinction the chamber is filled with high pressure air, which prevents
restrike. In some low capacity circuit-breakers, the isolator is an integral part of the
circuit-breaker. The circuit-breaker opens and immediately after that the isolator
opens, to provide additional gap.
In EHV circuit of today, isolators are generally, independently mounted.
Fig.1.14. shows one pole of the EHV air blast circuit-breaker. In the complete
assembly there are three identical poles.
Description. High pressure air, at a pressure between 20 to 30kg/cm2 is stored
in the Air reservoir (Item 1 in Fig 1.14). Air is taken from compressed air system.
breaker
Fig.1.14. (b) Details of (3) Double arc extinction chamber.
S.No. Item Nos. Material
15. Port
14. Enclosure 6 Porcelain
13. Resistance switching unit 3 Assembly
12. Arcing horns Optional 4 Steel
11. Openings for air outler 6 -
10. Compression springs 6 Alloy steel
9. Connection for current - Copper or its alloy
8. Moving contact (in 3) 2 Copper, silver or its alloy
7. Fixed contact (in 3) 3 Copper, or its alloy
6. Pneumatic valve
5. Operating rod 1 Steel
4. Pneumatic operating mechanism 1
3. Double arc extinction chamber 3 (Assembly)
2. Hollow insulator assembly 3 Steatite
1. Tank air reservior (receiver) 1 Boiler plate steel
Three hollow insulator columns (Item 2) are mounted on the reservoir with
valves (6) at their base. The double arc extinguishing chambers (3) are mounted on
the top of the hollow insulator chambers. The current carrying parts (9) connect the
three arc extinction chambers to each in series and the pole to the neighboring
equipment. Since there exists a very high voltage between the conductors and the air
reservoir, the entire arc extinction chamber assembly is mounted on insulators.
The details of the double arc extinction chambers (3) are shown in
Fig.1.14.(b). Since there are three double arc extinction poles in series, there are six
breaks per pole. Each are extinction chamber (Fig.1.14.(b)) consists of one twin fixed
contact (7). There are two moving contacts (8) which are shown in the opening
process. The moving contacts can move axially so as to open or close. Its position
open or close depends on air pressure and spring (10) pressure.
The operating mechanism (3) operates the rod (5) when it gets a pneumatic or
electrical signal. The valves (6) open so as to send the high pressure air in the hollow
of the insulator. The high pressure air rapidly enters the double arc extinction
chamber (Air Intel in Fig1.14.(b)). As the air enters into the arc extinction chamber
the pressure on the moving contacts (8) becomes more than spring pressure and
contacts open.
The contacts travel through a short distance against the spring pressure. At
the end of contact travel the port for outgoing air (15) is closed by the moving contact
and the entire arc extinction chamber is filled with high pressure air, as the air is not
allowed to go out. However, during the arcing period the air goes out through the
openings (11) and takes away the ionized air of arc.
While closing the valve (6) is turned so as to close connection between the
hollow of the insulator and the reservoir. The valve lets the air from the hollow
insulator to the atmosphere. As result the pressure of air in the arc extinction
chamber (3) is dropped down to the atmospheric pressure and the moving contacts
(8) close over the fixed contacts (7) by virtue of the spring pressure.
The opening is fast because the air takes a negligible time to travel from the
reservoir to the moving contact. The arc is extinguished within a cycle. Therefore, air
blast circuit-breaker is very fast in breaking the current.
Closing is also fast because the pressure in the arc extinction chamber drops
immediately as the valve (6) operates and he contacts close by virtue of the spring
pressure.
The construction described above applied to Air Blast Circuit Breakers for
EHV applications, for voltages above 145kV. For voltages of 420kV and more, the
construction is modified by adding required number of arc-interrupting chambers in
series.
Air blast circuit-breaker requires an auxiliary compressed air system.
Air blast circuit-breakers for 12kV generally have a different type of
construction. Air blast circuit-breakers are preferred for Arc Furance Duty and
traction system, because they are suitable for repeated duty, whereas oil circuit-
breakers are not satisfactory for such duties. Typical ratings of Air Blast Circuit-
Breakers are :
- 12kV, 40kA
- 22kV, 40kA
- 145kV, 40kA, 3cycle
- 245kV, 40kA, 50kA, 21/2cycle
- 420kV, 40kA, 50kA, 63.5kA, 2cycle
The grading capacitors are connected across the interrupter unit for the equal
distribution of voltage between the units. Closing resistors are connected across the
interrupter units for limiting the over voltages during closing operation. Opening
resistors are connected across the interrupter units to make the circuit-breakers
restrike free.
1.3.2. Principle of Arc quenching in ABCBs
The air blast circuit-breaker needs an auxiliary compressed air system which
supplies air to the air receiver of the breaker. For opening operation, the air is
admitted in the arc extinction chamber. It pushes away the moving contacts. In doing
so, the contacts are separated and the air blast takes away the ionized gases along
with it and assists are extinction. After a few cycles the arc is extinguished by the air
blast and the arc extinction chamber is filled with high pressure air (30kg/cm2). The
high pressure air has higher dielectric strength than that of atmospheric pressure.
Hence a small contact gap of few centimeters is enough.
The flow of air around contacts is guided by the nozzle shaped contacts. It
may be axial, cross or a suitable combination (Fig.1.15.(a),(b)).
In the axial blast type air flow Fig.1.15(a) the flow air is longitudinal along
the arc.
In axial blast type air flow, the air flows from high pressure reservoir to the
atmosphere through a convergent divergent nozzle. The difference in pressure and the
design of nozzle is such that as the air expands into the low-pressure zone, it attains
almost supersonic velocity. The mass flow of air through the nozzle is governed by the
parameters like pressure ratio, area of throat, nozzle throat diameter and is
influenced by the diameter of the arc itself.
The air flowing at a high speed axially along the arc causes removal of heat
from the periphery of the arc and the diameter of the arc reduces to a low value at
current zero. At this instant the arc is interrupted and the contact-space is flushed
with fresh air flowing through the nozzle.
The flow of fresh air through the contact space ensures removal of hot gases
and rapid building up of the dielectric strength.
The principle of cross-blast illustrated in Fig.1.15.(b) is used only in circuit-
breakers of relatively low rating such as 12kV, 500 MVA.
The experience has shown that in the cross-blast flow, the air flows around the
arc and the diameter of arc is likely to remain stable for higher values of current.
During the period of arc extinction, the air continues to flow through the
nozzle of the atmosphere. The mass flow rate can be increased by increasing the
pressure of the high pressure system. The increase in the mass flow results in
increased breaking capacity.
After the brief duration of air flow, the interrupter is filled with high pressure
air. The dielectric strength of air increases with pressure. Hence the fresh high
pressure air in the contact space is capable of withstanding the transient recovery
voltage.
After the arc extinction the interrupter chamber is filled with high pressure
air. For closing operation, the air from this chamber is let out to the atmosphere.
Thereby the pressure on the moving contacts from one side is reduced and the moving
contacts close rapidly by the spring pressure (Fig.1.16.).
The air blast circuit-breakers come under the class external extinguishing
energy type. The energy supplied for arc extinction is obtained from high pressure air
and is independent of current to be interrupted.
Fig.1.17. Comparison between circuit-breakers with A internal source of extinguishing energy and
B external source of extinguishing energy.
The arcing time of ABCB is almost independent of arc-current (Fig.1.17.).
Whereas in oil current breaker the arcing time is more for lower currents
(Fig.1.16.(a)) and the re-striking voltages are damped out by contact space of law
dielectric strength.
In the circuit-breakers with external energy source the breaking capacity of
the unit is determined by the pressure of extinguishing medium. In circuit-breakers
with internal energy source the capacity limit is determined by the design features.
1.3.6. Design Features of Ultra High Voltage Air Blast Circuit Breaker
In 1910 the highest system voltage was about 100kV. In 1965, it was 765kV.
Todays, some projects have been commissioned for rated voltages of 1100kV. The
breakers are required for breaking short circuit currents of the order of 40kA, 50kA,
60kA. To achieve such high ratings the Air Blast Circuit-Breakers have been provided
with following features.
- Multi-unit design.
- Increasing mass flow of air arc extinction by making necessary modifications
in the design of compressed air system and passage of air in the breaker.
- Use of parallel pre-closing resistors to damp switching over-voltages.
- Intensifying the cooling of arc space by developing the nozzle of suitable
shape by enlarging nozzle shape and raising the operating pressure.
- Larger diameters of flow paths, larger components.
Fig.1.18.(a) One pole of an air blast circuit-breaker
with vertical air-receiver and two interrupters pole.
- Using new techniques of air supply to ensure almost constant pressure of air
during the opening operations. These techniques include.
1. Using vertical tanks, one for each hollow insulator (Fig.1.18).
2. Using high pressure system such 60kg/cm2, 150kg/cm2.
3. Connecting the breaker pneumatic valve directly to high pressure system
instead of connecting it to local air receiver.
In circuit breaker with air receiver, the air pressure drops to about 70per
cent of initial pressure during arc interruption. Thereby the rating of breaker for the
subsequent opening operation for auto-re-closure duty is reduced. To overcome this
difficulty, the above mentioned modifications are incorporated in UHV circuit,
breakers. Further, breakers are fitted with silencers and are made earthquake-proof.
Air storage is in bottles kept below the compressor units. Number of bottles
depends upon requirements. Such packaged compressed air equipment is either one
for each breaker or one for a group of breakers. It is installed in switchyard near the
breaker. Costly civil work conventional compressed air system is thus avoided.
1. Describe the principle of air blast circuit breaker. With the help of neat sketches, explain the
construction of a typical EHV air blast circuit breaker.
2. How does the current effect the arcing time in :
(a) Oil circuit breaker?
(b) Air blat circuit breaker?
3. Explain the principle of Resistance Switching Why is it necessary in air blast circuit breaker?
4. What are favourable technical aspects of air blast circuit breaker? Why are pre-closing resistors
necessary?
5. What are the necessary auxiliaries of ABCB? Describe compressed air system for supplying
compressed air to the air blast circuit breakers?
6. Explain the terms "breakers with external source of energy". What is the difference between such a
breaker and oil circuit breaker?
7. Explain why Air Blast Circuit-Breaker is preferred for Arc Furnace Duty and Traction Duty?
8. With the help of neat sketches, describe the principle of resistance switching units in an Air-Blast
Circuit Breakers.
9. Why is ABCB the most popular breaker for modern UHV circuits?
10. State the various ratings of a 254kV circuit breaker.
11. What is the effect of unequal capacitance in multi-break design? How is the problem solved?
1.4. Sulphur Hexafluoride (SF6) Circuit-Breaker and SF6 Insulated Metalclad
Switchgear
1.4.1. Physical Properties of SF6 gas
- Colourless.
- Odourless.
- Notoxic. Pure SF6gas is not harmful to health.
- Non-inflammable. However impure SF6gas contains toxic impurities.
- State-Gas at normal temperature, Pressure.
- Density-Heavy gas, density 5 time that of air at 20oC and Atmospheric
pressure.
Liquefaction of SF6Gas
The gas starts liquefying at certain low temperatures. The temperature of
liquefaction depends on pressure. At 15kg/cm2 the gas starts liquefying at 10oC.
Hence this gas is not suitable for pressures above 15kg/cm2.
The temperature at which the SF6gas changes to liquid state depends on
pressure. With higher pressure, this temperature increases. To avoid the liquefaction
of SF6gas, the temperature of SF6 should be maintained above certain value. For
15atm. Pressure, SF6gas starts liquefying at a temperature of about 10oC. Hence
thermostatically controlled heaters are provided, which maintain the gas temperature
above about 16oC in case of high pressure system. Fig 1.20. illustrates the
characteristics of SF6 medium. The curve shows transition condition, the left side
represents liquid state and right side represents gaseous state. The inclined lines
(1/kg) represent constant specific volume, (liters per kg).
Low arc-time constant: The time constant of the medium is defined as "the
time between current zero and the instant the conductance of contact space reaches
zero value".
Fig.1.20. Temperature-Pressure variation characteristics of SF6gas
at constant specific volumes (litre/kg).
Due to the electronegativity of SF6gas the arc time constant of SF6gas is very
low and the rate of rise of dielectric strength is high. Hence SF6 cricuit-breakers are
suitable for switching condition involving high rate-of rise of TRV.
During opening stoke, puffer-cylinder and moving contact tube start moving.
Gas gets compressed within puffer cylinder (P1P2). After a certain travel, contact
separates, arc is drawn. However, compressed gas flows from higher pressure P1 to
lower pressure P2 through the nozzle. Fig.1.24.(d) gives pressure characteristics.
Fig.1.24. (c) Three stages of puffer action – Double Flow,
A Breaker fully close
B Contact Separate, Arcing present
C Arc Quenched
1. Enclosure (Insulating tube). 7. Normal path for current flow.
2. Fixed contact holder. 8. Gas trapped between 3 and 11.
3. Puffer Cylinder. 9. Compressed Gas.
4. Insulating Nozzle (PTFE). 10. Valve for gas intel during closing.
5. Insulating Cap. 11. Fixed Piston.
6. Parallel path for normal current flow 12. Arc.
QUESTIONS
B&C
A.1. Fully closed B.2. Contact separated C.3. Full open
2. Puffer cylinder 5. Support for 4 9. Arc drawn into 6
3. Moving contact tube 6. Fixed 10. Gas flow from P2 to
4. Fixed piston 7. Conducting nozzles
8. Finger contacts on 3
(a) Appearance of a single tank three-phase bulk (b) Appearance of a three phase bulk oil circuit
oil circuit breaker breaker with three tanks
1. Tank 2. Operating mechanism
3. Bushing 4. Terminal.
Fig 1.26. Bulk oil circuit-breaker.
The contact separation takes place in steel tanks filled with oil. The gases
formed due to the heat of the arc expand and set the turbulent flow in the oil.
To assist of arc extinction process, arc control devices are fitted to the contact
assembly. These are semi-enclosed chamber of dielectric materials. The performance
of oil circuit-breaker depends on the effectiveness of arc control devices.
Fig.1.27. illustrates the tank type oil circuit-breaker, in open positions with
the arc not yet extinguished.
The tension rod (7) is raised by operating mechanism (not shown in the figure)
while, closing the circuit-breaker. As the contacts separate, and arc is drawn this arc
is extinguished by the oil and by the gases formed by the decomposition of oil.
The arc control devices (5) are normally connected to the fixed contact
assembly, such that contact separation takes place inside this semi-enclosed device.
The gas produced in the device (4) produces high pressure in it. Thereby the arc
extinction is quick. As the moving contacts leave the arc control devices, the trapped
gas gets released from the arc control device, while doing so, the arc is extinguished
by blast effect. Arc control devices are fitted to all modern circuit-breakers rated 3.6
kV and above.
The construction and venting the arc-control devices is such that the gases
flow axially or radially with respect to arc. The major disadvantages of tank type
circuit-breaker are:
1. Large quantity of oil is necessary in oil circuit-breakers though only a
small quantity is necessary for arc extinction. The large quantity is necessary to
provide insulation between the live parts and earthed steel tank. If the container is
made of ceramic material, the size of container could be made small.
Fig.1.30. (b)
1. Fixed.
2. Arc.
3. Moving contact with Tungsten-Copper Tip.
4. Fiber Reinforced Tube.
5. Gases evolved by decomposition of oil.
6. Dielectric oil
7. Outer Enclosure (Porcelain or Fiber Reinforced Epoxy)
P- Piston
P- Pressure
- Flushing the contact space by fresh dielectric oil forced into the contact
space by means of piston-action. A piston attached to the moving contact
compresses the dielectric oil in a cylinder. The oil at a high pressure in the
cylinder flows into the contact space.
- Maintaining the pressure on the oil in the interrupter. If the oil in the
interrupter is maintained at higher pressure by means of an inert gas, the
oil flow into the contact space and the hot gases travel upwards. Pressure
reduces the size of gas bubbles.
These techniques are used in minimum oil circuit-breakers to avoid restrikes
during capacitor switching.
1. Contact support.
2. Main contacts (Electrolytic copper with tungsten copper tips).
3. Coiled spring (Phosphor-bronze).
4. Moving contact.
5. Arcing tip of (4) brazed to (6) (Tungsten-copper).
6. Moving contact stem (Electrolytic copper).
Arrow indicates current path.
QUESTIONS
1. State clearly the difference between minimum oil circuit breaker and tank type oil circuit breaker.
2. With the help of a neat sketch, describe the construction of a minimum oil circuit breaker.
3. Describe the action of an arc control device used in minimum oil circuit breaker.
4. State the application of MOCBs.
5. Describe the procedure of “reconditioning of oil”. Which oil is used in minimum oil Circuit
Breakers? Can the same oil be used in Bulk oil Circuit Breaker?
6. Discuss the arc extinction process in dielectric-oil.
7. What is meant by breaker with internal sources of extinguishing energy? How does magnitude of
current affect arcing time in such circuit breaker?
8. What are the desirable properties of electrical contacts used is circuit-breakers? Which materials
are used for contacts?
9. State clearly the functional requirements of cross-jet pots in MOCB.
10. Describe the difficulty in breaking low inductive currents in minimum oil circuit-breakers. What is
critical current?
11. Describe the “Results” phenomenon occurring while opening capacitor banks. What design
features are generally provided in minimum oil circuit-breakers for restricke-free operation.
Fig.1.33. Voltage-current characteristic of a 0.5mm, high vacuum gap with steel electrodes.
1. Enclosure: Glass.
2. End Flanges: Non-magnetic metal.
3. Contacts.
4. Vapor condensing shield.
5. Metallic Bellows.
6. Seals.
7. Fixed contact stem.
8. Moving contact stem.
Fig.1.37. Breakdown characteristic of a vacuum gap. (10 mm) for different vacuum levels
One vacuum interrupter used for on pole. Refer Fig.9.8. for end elevation of a vacuum
Circuit-breaker indicating location of the Vacuum Interrupter
1. Terminal Plate.
2. Insulator (Ceramic).
3. Arc chamber (Metallic) (Condensing shield).
4. Fixed contact piece.
5. Moving contact piece.
6. Insulator (Ceramic).
7. Metal bellow.
8. Moving contact Guide.
9. Moving contact stem.
Fig1.39. Time travel characteristic of moving contact of VCB. for Opening Stoke.
Number of current zeros available.
Development Tests
These are carried out on components, sub-assemblies and complete circuit-
breakers during and after the development of the circuit-breaker. The designers and
research scientist verify the effect of various parameters on the behaviour of circuit-
breakers, by conducting development tests. Development tests are not specified in the
standards.
Type of Tests
These are conducted on first few prototype circuit-breakers of each type to
prove the capabilities and to confirm the rated characteristics of the circuit-breaker.
Type tests are conducted in specially built testing laboratories. Type tests are
performed as per recommendations of standards (IEC) or (IS).
Routine Tests
Routine tests are also performed as per the recommendations of the standards
(IEC/IS).
Routine tests are conducted on each circuit-breaker. These are performed in
the manufacturer’s premises. Routine tests confirm the proper functioning of the
circuit-breaker.
Reliability Tests
Type tests and Routine tests are conducted on new-circuits breakers under
laboratory conditions. The performance of circuit breakers installed at site is affected
by additional stresses such as variation in ambient temperature variations, dust,
humidity repeated operations, maintenance schedules etc. Reliability tests are
conducted to verify the reliability of the circuit-breakers under various stresses
occurring in actual applications. Reliability tests can be conducted in specially built
laboratories and at site.
Commissioning Tests
These are conducted on the circuit-breaker after installation at site to verify
the operational readiness and proper functioning.
The tests on low-voltage a.c. circuit-breakers are described in Sec. 157.
Table 2.1
Summary of Type Tests on High Voltage A.C.
Circuit-Breakers
Ser. Test Remarks
1. No load mechanical operation test. No loan operations to verify speed of travel, opening
time, closing time. Carried out at 85% and 110% rated
Ser. Test Remarks
voltage of shunt trip release.
2. Mechanical performance tests 1000 close-open operations.
(Endurance tests).
2.8. High Voltage Power Frequency with stand Test (Routine Test)
Power frequency voltage withstand tests are routine tests High voltage tests
(as per the recommendation of standards) are conducted on each circuit-breaker. By
such tests, the defective insulation or small clearance if any are bought to notice. Test
Voltages are applied as follows: Aa, Bb, Cc, are terminals of poles and F is the
Frame.
QUESTIONS
Table 3.1
Maintenance of Quenching Medium Contacts
Maintenance of
Replacement of contacts K
Quenching Medium
Type of C.B
Load *
Fault Load** Fault 1 n 2
Table 3.2.
Maintenance of Contacts
Life of Contacts
Type of C.B. Number of load operations Number of fault operations on rated
on rated load current short-circuit current
VCB 10.000 50-100
SF6 4.000 12-25
MOCB 1.000 3-6
Air break CB 1.000 1-6
Air Blast CB 4.000 15-25
Table 3.1 gives recommendation regarding the period of maintenance of
contacts and quenching medium in terms of number of load operations and number of
short circuit operations on rated short-circuit breaking current. The schedule should
be established for each site by checking the contacts of one pole after every three
months and observing the rate of erosion.
During every breaking operation, contact loses some material and the
quenching medium gets decomposed. The decomposed products get deposited on the
internal insulation is proportional I2n, where I is breaking current in kA and n is the
number of breaking operation. After cumulative I 2 n K , the contacts internal
insulation and the quenching medium needs inspection/servicing. The value of K
depends upon the type of circuit breakers (Refer Table 3.1.).
3.7. Maintenance of Air Break Circuit Breaker, Fusegear for Low and Medium
Voltages
The schedule of maintenance depends upon the frequency of load operations
and fault operations. For frequent load operations/fault operations, maintenance
requirement is high. For indoor, dust-free installation with infrequent load
operations, the following schedule is recommended:
- Inspect as often as possible with maximum internal of 12 months.
- Examine at 5 years interval.
- Overhaul when examination and diagnostic tests indicate need. Maximum
interval of 15 years.
Table 3.5.
Maintenance for air circuit breaker and switchgear.
Routine Maintenance
Past fault
Clause Maintenance operation Examination
Inspection maintenance
and overhaul
1. Operational checks x x
2. Visual Inspection x x x
3. Cleaning x x
4. Insulation resistance x x
5. Circuit-breaker enclosure x x
6. Main/arching contacts x x
7. Arc control devices and Interphase barriers x
8. Mechanisms x
9. Auxiliary switches, indicating devices and
x
interlocks
10. Isolating contacts x
11. Overload devices and protective relays x x x
12. Instrument and protective transformers x
13. Control relay or contractor x
14. Main connections x
15. Secondary wiring and fuses x
16. Earth connections x
17. Heaters x
18. Shutters x x
19. Switchgear spouts x
20. Busbars and busbars chamber
21. Weather shields x
22. Final verification x x x
23. Maintenance of auxiliary equipment x
24. Diagnostic testing x
3.8. Maintenance of Oil Circuit Breakers (BOCB, MOCB).
The schedule for inspection and maintenance depends upon the frequency of
load operations and fault operations. Oil circuit-breaker installed outdoor and in
damp/rainy areas need frequent inspection.
The main requirement is inspection of oil, contacts and internal insulation.
1. Under normal conditions for frequent operations. Once in 6 months
with maximum period of 9 months.
2. For frequent operations. Once in three months.
3. After fault clearance. If fault level is high; inspect as early as possible. If
fault level is low, inspect after fault opening operations.
4. Overhaul. Once in 5 years for normal and once in 3 years for
repeated/frequent fault duty.
5. During the periodic checkup the following checks should be made (Refer
Sec. 3.6).
(a) Check the level and condition of oil.
(b) Clean the insulators with fine fabric cloth that will not leave fibers.
Do not use cotton waste in any case. For removing oil, grease,
carbon deposit use trichloroethylene or other chemical
recommended by the manufacturer.
(c) Check contacts.
(d) Check operating mechanism.
(e) Check oil.
(f) Check auxiliary switches.
(g) Tighten nuts, bolts etc.
(h) Test insulation resistance by means of high voltage (1000 V.D.C.)
megger in case of high voltage circuits and by 500V megger in 220V
control circuits.
(i) Carry out tests according to the specifications.
(j) Take the steps as mentioned in the subsequent paragraphs.
6. When the breaker operates on fault, the internal and external inspection.
(a) Examine the oil. If badly deteriorated, change it.
(b) Check arcing contacts. Clean with smooth file. If badly damaged,
replace them.
(c) Inspect the insulation, carefully checks the surface.
(d) Check the arc control device. If damaged, replace the plates.
(e) Check the tripping circuit and operating mechanism.
(f) Be sure that no tools are left in the tank. Maintenance summarized
recommended is in table 3.7.
Table 3.7.
Maintenance for Oil Circuit-Breakers in Metal enclosed Switchgear.
Routine Maintenance
Past fault
Clause Maintenance operation Examination
Inspection maintenance
and overhaul
1. Operational checks C, O, CO x x x
2. General Inspection x x
3. Cleaning x
4. Insulation, Insulating oil x x x
5. Circuit-breaker enclosure x
6. Main arching contacts x
7. Arc-control devices x x
8. Isolating contacts x x
9. Venting and gas seals x x
10. Mechanism x x
Routine Maintenance
Past fault
Clause Maintenance operation Examination
Inspection maintenance
and overhaul
11. Auxiliary switches, indicating devices and
x
interlocks
12. Overload devices and protective relays x x
13. Instrument and CTs, VTs x
14. Control relay or contractor x
15. Insulating oil x x
16. Tank and tank lining x x
17. Tank lifting mechanism x
18. Main connections x
19. Secondary wiring and fuses x
20. Earth connections x
21. Heaters x
22. Shutters x
23. Switchgear spouts x
24. Bus-bars and bus-bars chamber x
25. Weather shields x
26. Final verification x x x
27. Joints and seals x
28. General mechanical inspection x
29. Maintenance of oil switches etc. x
30. High voltage fuse connection and associated
x
linkage
31. Maintenance of air-break isolating devices
x
associated with oil switchgear
32. Maintenance of auxiliary equipment x x
There are statutory obligations, to inspect, test and certify air receivers
(pressure vessels) periodically. Safety and reducing values should also be inspected
during the same time.
Guidance on the maintenance of this equipment given by the manufacturer
should be followed.
The driers should be inspected. If necessary, the drying agent should be
changed.
Table 3.9.
Maintenance for Vacuum Circuit-Breaker
Routine Maintenance
Past fault
Clause Maintenance operation Examination
Inspection maintenance
and overhaul
1. Operational checks x
2. General Inspection x
3. Cleaning x x
4. Opening device (trip) x
5. Insulation x x
6. Circuit-breaker enclosure (Interrupter) x
7. Main connection x
8. Secondary wiring and fuses
9. Mechanism x
10. Auxiliary switches, indicating devices and
x
interlocks
11. Shutters x x
12. Switchgear spouts x x x
13. Isolating contacts x x
14. Vacuum interrupter x x
15. Isolating and earthing switchgear x
16. Earth connection x x
17. Overload devices and protective transformers x x
18. Instruments and protective transformers x
19. Control relays or contractors x
20. Busbars and busbar chambers x
21. Final verification x x
Table 3.10.
Maintenance for SF6 Circuit-Breakers
Routine Maintenance
Past fault
Clause Maintenance operation Examination
Inspection maintenance
and overhaul
1. Operational checks x x
2. General Inspection x x
3. Cleaning x x
4. Opening device (trip) x x
5. Circuit-breaker enclosure x
6. Gas system x x
7. Sulphur hexafluriode gas x x x
Routine Maintenance
Past fault
Clause Maintenance operation Examination
Inspection maintenance
and overhaul
8. Insulation x x x
9. Local control kiosk x x
10. Pressure gauges x
11. Pressure switches x
12. Main connection x
13. Secondary wiring and fuses x
14. Earth connection x
15. SF6 gas heaters x
16. Interpole linkages x x
17. Main mechanism x
18. Auxiliary switches indicating devices and
x
interlocks
19. Interrupters x x
20. Local air receives and pressure vessels x
21. Filters and desiccants x
22. Overload devices and protective relays x x
23. Instruments and protective transformers x
24. Control relays or contractors x
25. Busbars and busbar chambers x
26. Final verification x x x