AWC-DCA4-CAM For Calculating and Demonstrating Assembly Fire Resistance-2014
AWC-DCA4-CAM For Calculating and Demonstrating Assembly Fire Resistance-2014
Wood-frame walls and floors offer designers a veloped from conducting a series of fire resistance
unique opportunity to provide structures with economy tests. The Component Additive Method (CAM) pro-
as well as proven energy performance. Where these vides for calculating the fire resistance of load bearing
assemblies are required by the building codes to and non-load bearing floor, wall, ceiling and roof
achieve a minimum fire resistance rating, a wide range assemblies. The calculated fire resistance provisions
of options for design exists. within Section 722.6 of the International Building
Code® (IBC) were developed using CAM.
Building Code Requirements
History
The original methodology for calculating fire re-
sistance ratings of assemblies by CAM was devel-
oped in the early 1960’s by the Fire Test Board of the
National Research Council of Canada (NRCC). The
methodology resulted from their detailed review of
135 standard fire test reports on wood stud walls and
73 test reports on wood-joist floor assemblies, and the
Ten Rules of Fire Endurance Rating by Tibor Har-
mathy, an eminent fire researcher from NRCC. The
“Ten Rules” provided a method for combining the
individual component contributions to obtain the fire
resistance rating of the assembly. The fire tests were
used to validate this methodology, and to derive as-
signed time values for contribution to fire resistance
ratings of each separate component of an assembly.
These tests included both load bearing and non-load
bearing assemblies with wood, gypsum wallboard and
other membranes. Fire resistance ratings ranged from
20 to 90 minutes.
Rule 1. The "thermal" fire endurance of a construction consisting of a number of parallel layers is greater than the
sum of the "thermal" fire endurance characteristics of the individual layers when exposed separately to fire.
Where two layers of panel materials, such as gypsum wallboard or plywood, are fastened to studs or joists separate-
ly, their combined effect is greater than the sum of their individual contributions to the fire endurance rating of the
assembly.
Rule 2. The fire endurance of a construction does not decrease with the addition of further layers.
This is a corollary to Rule 1. The fire resistance will not decrease with the addition of layers such as wallboard or
other panel materials, regardless of how many layers are added or where they are located within the assembly.
Rule 3. The fire endurance of constructions containing continuous air gaps or cavities is greater than the fire en-
durance of similar constructions of the same weight, but containing no air gaps or cavities.
Wall and ceiling cavities formed by studs and joists protected and encased by wall coverings adds to the fire re-
sistance rating of these assemblies.
Rule 4. The farther an air gap or cavity is located from the exposed surface, the more beneficial its effect on the fire
endurance.
In cases where cavities are formed by joists or studs and protected by 2-inch-thick panel materials against fire ex-
posure, the beneficial effect of such air cavities is greater than if the protection is only 1/2 inch thick.
Rule 5. The fire endurance of an assembly cannot be increased by increasing the thickness of a completely enclosed
air layer.
An increase in the gap distance between separated layers does not change the fire resistance of an assembly.
Rule 6. Layers of materials of low thermal conductivity are better utilized on the side of the construction on which
fire is more likely to happen.
A building material having relatively low thermal conductivity, such as a wood-based material, is more beneficial to
the fire resistance of the assembly if placed on the fire-exposed side of the framing than it would be on the opposite
side.
Rule 7. The fire endurance of asymmetrical constructions depends on the direction of heat flow.
Walls which do not have the same panel materials on both faces will demonstrate different fire resistance ratings
depending upon which side is exposed to fire. This rule results as a consequence of Rules 4 and 6, which point out
the importance of location of air gaps or cavities and of the sequence of different layers of solids.
Rule 8. The presence of moisture, if it does not result in explosive spalling, increases fire resistance.
Materials having a 15 percent moisture content will have greater fire resistance than those having 4 percent mois-
ture content at the time of fire exposure.
Rule 9. Load-supporting elements, such as beams, girders and joists, yield higher fire endurance when subject to
fire endurance tests as parts of floor, roof, or ceiling assemblies than they would when tested separately.
A wood joist performs better when it is incorporated in a floor/ceiling assembly, than tested by itself under the same
load.
Rule 10. The load-supporting elements (beams, girders, joists, etc.) of a floor, roof, or ceiling assembly can be re-
placed by such other load-supporting elements which, when tested separately, yielded fire endurance not less than
that of the assembly.
A joist in a floor assembly may be replaced by another type of joist having a fire resistance rating not less than that
of the assembly.
The times assigned to wood studs and joists were Roofs and Floor/Ceiling Assemblies
determined from ASTM E119 fire resistance tests, and
represent the contribution of the framing members to In the case of a roof or floor/ceiling assembly, fire
the total fire resistance rating of the assembly. The testing is normally done with exposure from below the
times assigned to framing members are given in Table assembly. To comply with this calculation methodolo-
722.6.2(2) of the 2012 IBC. gy, floor and roof assemblies must have a protective
These time values are, in part, the result of membrane in conformance with Table 722.6.2(1) of
full-scale tests of unprotected wood studs and floor the 2012 IBC. The upper membrane must consist of a
joists where the structural elements were loaded to subfloor or roof deck and finish in conformance with
design capacity. They apply to all framing members Table 722.6.2(4) of the 2012 IBC. Alternatively, any
and do not increase if, for example, 2x6 studs are used combination of membranes listed in Table 722.6.2(1)
rather than 2x4 studs as implied by Harmathy’s rule of the 2012 IBC, with an assigned time of at least 15
#5. It should be noted that the intent of footnote b to minutes, may be used on the unexposed (upper) side.
Table 722.6.2(2) of the 2012 IBC is not to limit the
table’s applicability to 2x4 studs only, but rather, to
require 2x4s as the minimum stud size.
Walls
1 For examples of fire-resistance-rated exterior walls see “Design for Code Acceptance No. 3: One-Hour Fire Rated Wood-Frame Wall and
Floor/Ceiling Assemblies” American Wood Council, 2013.
.
2 Online Heights and Areas Calculator available free of charge on the American Wood Council website: www.awc.org.