Catalog Solahd Buck Boost Transformers en Us 164082
Catalog Solahd Buck Boost Transformers en Us 164082
Use dimmers on the output of the transformer that are 5. Number of Phases
designed and rated for use with magnetic loads. We strongly Single or three phase line and load must match
recommend contacting the dimmer manufacturer for advice (a transformer cannot convert single to three phase.)
on your specific lighting application. A common application is to make a single phase
connection from a three phase supply by using one
Certifications and Compliances phase of the three phase supply circuit. Be careful not
to overload that phase of the three phase supply. For
• Listed buck-boost applications the supply must provide load
- UL 506 kVA – not just the nameplate rating of the buck-boost.
- CSA C22.2 No. 66 Refer to the Selection Tables on the following pages.
236 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Three phase, buck-boost applications require two or three Using the Selection Tables
transformers. Check the “Quantity Required” column of the
1. Determine if you are trying to Boost (raise) or Buck
Three Phase Selection Tables for the exact quantity.
(lower) your voltage. Select an input/output voltage
combination that comes closest to matching your
Fusing Buck-Boost Transformers application from the appropriate single or three phase
For determining the correct size of breaker or fuse for a given charts on the following pages.
range of input or output ampere ratings, refer to Section
450.4, of the National Electric Code (NEC). 2. Move across your selected input/output voltage row to
the amperage or kVA rating closest to, but greater than
Where an overcurrent protection device is required, the the rating required by your load.
electrical connections and selection tables will reference
appropriately. 3. Reading the top of the column will give you the
catalog number of the exact buck-boost transformer
you need. See the Specification Tables on the
next page.
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 237
© December 2018
Buck–Boost Transformers
Specification Tables
Note: Weights and dimensions may change and should not be used for construction purposes.
238 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Specification Tables – continued
Note: Weights and dimensions may change and should not be used for construction purposes.
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 239
© December 2018
Buck–Boost Transformers
Electrical Connections for Low Voltage Applications = Earth Ground
120 X 240 Volt Primary, 120 X 240 Volt Primary, 240 X 480 Volt Primary,
12/24 Volt Secondary
Taps: None
1 16/32 Volt Secondary
Taps: None
2 24/48 Volt Secondary
Taps: None
3
H1 H3 H2 H4 H1 H3 H2 H4 H1 H3 H2 H4
X1 X3 X2 X4 X1 X3 X2 X4 X1 X3 X2 X4
X2 to X3 X2 to X3 X2 to X3
12-0-12 X1-X2-X4 16-0-16 X1-X2-X4 24-0-24 X1-X2-X4
X2 to X2 to X2 to
X1 to X3 X1 to X3 X1 to X3
12 X1 & X4 16 X1 & X4 24 X1 & X4
X2 to X4 X2 to X4 X2 to X4
HS19 and S19 Series HS20 and S20 Series HS22 and S22 Series
240 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Design Styles
Style 4 - Encapsulated
Style 5 - Encapsulated
Available for all encapsulated kVA sizes (For Type 4, 12 and 4X)
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 241
© December 2018
Buck–Boost Transformers
Selection Tables: Single Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
242 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Selection Tables: Single Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 243
© December 2018
Buck–Boost Transformers
Selection Tables: Single Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
244 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Selection Tables: Single Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 245
© December 2018
Buck–Boost Transformers
Selection Tables: Single Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
246 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Selection Tables: Single Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 247
© December 2018
Buck–Boost Transformers
Selection Tables: Three Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
248 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Selection Tables: Three Phase
BOOSTING
kVA 22.5 30.0 45.0 75.1 112.5
188 208 2 F1 Load amps 62.5 83.3 125.0 208.3 312.5
Fuse Size 90.0 125.0 175.0 300.0 450.0
kVA 45.0 60.0 90.1 150.1 225.2
198 208 2 E1 Load amps 125.0 166.6 250.0 416.6 625.0
Fuse Size 175.0 225.0 350.0 600.0 1000.0
kVA 24.8 33.1 49.6 82.6 123.9
208 229 2 F1 Load amps 62.5 83.3 125.0 208.3 312.5
Fuse Size 90.0 125.0 175.0 300.0 450.0
kVA 49.6 66.1 99.2 165.3 247.9
208 229 3 J1 Load amps 125.0 166.6 250.0 416.6 625.0
Fuse Size 175.0 250.0 350.0 600.0 1000.0
kVA 52.0 69.3 103.9 173.2 259.8
228 ** 240 2 E1 Load amps 125.0 166.6 250.0 416.6 625.0
Fuse Size 175.0 250.0 350.0 600.0 1000.0
kVA 94.4 125.8 188.79 314.6 472.0
416 436 3 L1 Load amps 125.0 166.6 250.0 416.6 625.0
Fuse Size 175.0 250.0 350.0 600.0 1000.0
kVA 49.6 66.1 99.2 165.3 247.9
416 458 3 M1 Load amps 62.5 83.3 125.0 208.3 312.5
Fuse Size 90.0 125.0 175.0 300.0 450.0
BUCKING
kVA 47.2 62.7 94.4 157.3 236.0
218 208 2 E2 Load amps 131.0 174.0 262.0 436.6 655.0
Fuse Size 175.0 225.0 350.0 600.0 800.0
kVA 24.8 33.0 49.6 82.5 123.9
229 208 2 F2 Load amps 68.8 91.6 137.6 229.0 344.1
Fuse Size 80.0 110.0 175.0 300.0 400.0
kVA 54.6 72.5 109.1 181.8 272.8
252 ** 240 2 E2 Load amps 131.3 174.3 262.5 437.4 656.3
Fuse Size 175.0 225.0 350.0 600.0 800.0
kVA 28.6 38.0 57.2 95.1 142.9
264 ** 240 2 F2 Load amps 68.8 91.5 137.5 228.8 343.8
Fuse Size 80.0 110.0 175.0 300.0 400.0
kVA 45.0 59.9 90.1 149.9 225.2
418 378 3 M2 Load amps 68.8 91.6 137.6 228.9 343.9
Fuse Size 80.0 110.0 175.0 300.0 400.0
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 249
© December 2018
Buck–Boost Transformers
Selection Tables: Three Phase
BOOSTING
kVA 1.69 2.81 5.63 8.44 11.3
184 208 2 F1 Load amps 4.69 7.8 15.6 23.4 31.2
Fuse Size 10.0 15.0 25.0 35.0 45.0
kVA 3.38 5.63 11.3 16.9 22.5
195 208 2 E1 Load amps 9.38 15.6 31.2 46.9 62.5
Fuse Size 15.0 25.0 45.0 70.0 90.0
kVA 1.92 3.19 6.39 9.58 12.8
208 236 2 F1 Load amps 4.69 7.8 15.6 23.4 31.2
Fuse Size 10.0 15.0 25.0 35.0 45.0
kVA 3.83 6.38 12.8 19.2 25.6
208 236 3 J1 Load amps 9.38 15.6 31.2 46.9 62.5
Fuse Size 15.0 25.0 45.0 70.0 90.0
kVA 3.9 6.5 13.0 19.5 26.0
225 240 2 E1 Load amps 9.38 15.6 31.2 46.9 62.5
Fuse Size 15.0 25.0 45.0 70.0 90.0
kVA 7.2 12.0 24.0 36.0 48.0
416 443 3 L1 Load amps 9.38 15.6 31.2 46.9 62.5
Fuse Size 15.0 25.0 45.0 70.0 90.0
kVA 3.83 6.37 12.8 19.1 25.5
416 471 3 M1 Load amps 4.69 7.8 15.6 23.4 31.2
Fuse Size 10.0 15.0 25.0 35.0 45.0
BUCKING
kVA 3.61 6.0 12.0 18.0 24.0
222 208 2 E2 Load amps 10.0 16.6 33.3 50.1 66.7
Fuse Size 15.0 20.0 40.0 60.0 80.0
kVA 1.92 3.19 6.38 9.56 12.8
236 208 2 F2 Load amps 5.32 8.85 17.7 26.5 35.4
Fuse Size 10.0 10.0 20.0 30.0 40.0
kVA 4.16 6.92 13.8 20.8 27.7
256 ** 240 2 E2 Load amps 10.1 16.6 33.3 50.0 66.7
Fuse Size 15.0 20.0 40.0 60.0 80.0
kVA 2.21 3.67 7.35 11.0 14.7
272 ** 240 2 F2 Load amps 5.32 8.84 17.7 26.5 35.4
Fuse Size 10.0 15.0 20.0 30.0 40.0
kVA 3.51 5.84 11.7 17.5 23.3
432 380 3 M2 Load amps 5.33 8.87 17.7 26.6 35.5
Fuse Size 10.0 10.0 20.0 30.0 40.0
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
250 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Selection Tables: Three Phase
BOOSTING
kVA 16.9 22.5 33.8 56.3 84.4
184 208 2 F1 Load amps 46.9 62.5 93.8 156.0 234.0
Fuse Size 60.0 90.0 150.0 225.0 350.0
kVA 33.8 45.0 67.6 112.6 168.9
195 208 2 E1 Load amps 93.7 125.0 187.5 312.0 468.0
Fuse Size 125.0 175.0 250.0 450.0 700.0
kVA 19.2 25.6 38.2 63.9 95.8
208 236 2 F1 Load amps 46.9 62.5 93.7 156.0 234.0
Fuse Size 70.0 90.0 150.0 225.0 350.0
kVA 38.2 51.1 76.6 127.7 191.6
208 236 3 J1 Load amps 93.7 125.0 187.5 312.0 468.0
Fuse Size 150.0 200.0 300.0 450.0 700.0
kVA 71.9 52.0 77.9 129.9 194.0
225 240 2 E1 Load amps 93.7 125.0 187.5 312.0 468.0
Fuse Size 125.0 175.0 250.0 450.0 700.0
kVA 71.9 95.9 143.9 239.8 359.7
416 443 3 L1 Load amps 93.7 125 187.5 312.0 468.0
Fuse Size 125.0 175.0 250.0 450.0 700.0
kVA 38.2 51.0 76.5 127.5 191.2
416 471 3 M1 Load amps 46.9 62.5 93.8 156.0 234.0
Fuse Size 70.0 90.0 150.0 225.0 350.0
BUCKING
kVA 36.0 48.1 72.1 120.0 179.9
222 208 2 E2 Load amps 100.0 133.4 200.1 333.0 499.5
Fuse Size 125.0 175.0 250.0 400.0 600.0
kVA 19.2 25.5 38.8 63.8 95.6
236 208 2 F2 Load amps 53.2 70.9 106.4 177.0 265.5
Fuse Size 60.0 80.0 125.0 200.0 300.0
kVA 41.5 55.4 83.1 138.3 207.5
256 **
240 2 E2 Load amps 99.9 133.3 200.0 332.8 499.2
Fuse Size 125.0 175.0 250.0 400.0 600.0
kVA 22.1 29.4 44.2 73.5 110.2
272 ** 240 2 F2 Load amps 53.2 70.8 106.3 176.8 265.2
Fuse Size 60.0 80.0 125.0 200.0 300.0
kVA 35.1 46.8 70.2 116.7 175.1
432 380 3 M2 Load amps 53.3 71.1 106.6 177.3 266.0
Fuse Size 60.0 80.0 125.0 200.0 300.0
*F or alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 251
© December 2018
Buck–Boost Transformers
Selection Tables: Three Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
252 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Selection Tables: Three Phase
* For alternate electrical connection diagrams, refer to the section immediately following the selection tables.
** Shaded items are 60 Hz only (All other ratings shown are 50/60 Hz).
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 253
© December 2018
Buck–Boost Transformers
Alternate Electrical Connections for Buck-Boost Applications
X4 X2 X4
X2 X4
X3 X1 X3
X2 H4
X1 X3
H2 H4 X1
Output
Output
H2 H4 H3
Input Output Input
H2
Input
H1 H3 H1
H1 H3
X4 X2 X4
X2 X4
X3 X1 X3
Input
X2 H4
X1 X3
Input X1
H2 H4
Output
Output
H2 H4 H3
Input
H2
Output
H1 H3 H1
H1 H3
The O symbol shown on these connection diagrams indicates where fuses or breakers should be field installed for line to
neutral applications. For line to line applications, fuses or breakers should be installed on both lines.
Application Note: On all auto-wye connections, the source neutral must be present and connected to the transformer bank.
If source neutral is not present, do not use an auto-wye connection.
254 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Alternate Electrical Connections for Buck-Boost Applications
H1 H1
H1
H2
X H3
Diagram D2 – Bucking H2 F
X
R F
H4 R
H3 M
R X1 M
R
H4 B X2
B
X3
X1 X3
X4
X2 X4
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 255
© December 2018
Buck–Boost Transformers
Alternate Electrical Connections for Buck-Boost Applications
X2 X4 X2 X4
X4 X
X1 X3 F
X X
X3 F R
F X1 X3
X2 R R H2 H4 M
M M R
X1 R R
H2 H4 H1 H3 A
H2 H4 A
A X2 X4
H1 H3 X1 X3 X
H1 H3 F
R
H1 H3 H2 H4 M
H1 H3
R
H1 H3
H2 H4 X B
X H2 H4 F X2 X4
F
X1 R
R M X1 X3
M X
X2 X1 X3 R F
R
X3 H2 H4 R
B M
B
X4 R
X2 X4 H1 H3
C
X2 X4 X2 X4
X4
X
X1 X3 F
X X R
X3 F
F X1 X3 H2 H4 M
X2 R R
R
M M
X1 R R H1 H3
H2 H4 A
H2 H4 A X2 X4
A
X1 X3 X
H1 H3
H1 H3 F
R
H2 H4 M
H1 H3 H1 H3 R
H1 H3 B
H2 H4 X X
H2 H4 F X2 X4
F
X1 R R X1 X3
M X
M F
X2 R X1 X3 R
H2 H4 R
X3
B M
B
X4 R
X2 X4 H1 H3
C
256 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
Buck–Boost Transformers
Alternate Electrical Connections for Buck-Boost Applications
AUTO-WYE AUTO-WYE
AUTO-WYE
CONNECTION CONNECTION
CONNECTION
INPUT OUTPUT INPUT OUTPUT
INPUT OUTPUT
1 2 3 N 1 2 3 N 1 2 3 N 1 2 3 N
1 2 3 N 1 2 3 N
X4 X
X X2 X4 X X3
X4 F
F F X2
X3 X1 X3 R
X2 R R X1
M H4 M
M H4 R
X1 R
R H3 H3
H2 H4 H2
H2 A
A A
H1 H3 H1 H1
X4 X
X4 X X X3
X2 X4 X2 F
X3 F F
X2 R X1 X3 R X1 R
M M H4 M
X1 H4 R
R R H3
H2 H4 H3 H2
B H2 B B
H1 H3 H1
H1 X4
X X X3 X
X4 X2 X4 X2
X3 F F F
X2 R X1 X3 R X1 R
M H4 M
X1 M
R H4 H3 R
H2 H4 R
H3 H2
C H2 C C
H1 H3 H1
H1
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions. 257
© December 2018
Buck–Boost Transformers
Application Note
Application limitations with buck-boost transformers What is a buck-boost transformer and why is it used?
1. A Buck-boost transformer cannot be used to develop a three Isolation transformers have separate primary and secondary
phase, four wire wye circuit from a three phase, three wire windings, electrically insulated and isolated from one another.
delta circuit. With a relatively high voltage primary (typically 120, 240 or
480 Volts) and a relatively low voltage secondary (typically
A delta to wye connection does not supply enough 12, 16, 24, 32 or 48 Volts), buck-boost transformers are
current carrying capability to provide for unbalanced designed to be field connected as autotransformers. These
currents flowing in the neutral wire of the four wire are transformers with one continuous winding, a portion of
circuit. The neutral created is not stable and under which is jointly shared between the input and the output. No
load will not deliver desired line to neutral voltages. electrical isolation is present in an autotransformer.
This connection would also be in violation of the
National Electric Code, Article 210.9. Buck-boost transformers have two major uses:
2. Buck-boost transformers cannot be used in a closed delta 1. When field connected as an autotransformer, they
connection. can be used to Buck (lower) or Boost (raise)
A closed delta requires more kVA capacity than a wye or available line voltage in the range of 5 to 27% and
an open delta connection, plus phase shifting comes into at a kVA rating many times that listed on the
play on the output side. transformer nameplate.
3. Buck-boost transformers should not be used to correct for 2. When left as an isolation transformer, they can be
voltage drop on a long circuit run where the load fluctuates. used to supply power to low voltage circuits at the
nameplate rating listed.
Voltage drop varies with the load and buck-boost
transformers are connected for a specific voltage change. The importance of altering available line voltage.
If a buck-boost transformer was used to correct voltage Electrical equipment is designed to operate at maximum
drop during peak loading conditions, high voltages may efficiency at a specific standard supply voltage. Your voltage
result under light load conditions. This could be equally may not be at the standard supply voltage level. Causes can
detrimental to the load and possibly pose safety hazards. be proximity to a large utility transformer, losses in the line
voltage due to loads on that circuit, or a difference between
4. Buck-boost transformers cannot be used to create a the standard supply voltage available and the standard
240/120 Volt, single phase service from a 208Y/120 Volt supply voltage needed to run the equipment.
three phase supply.
Two problems that would occur: Normally the problem is having low voltage available. Low
voltage on a circuit, even as little as 5% lower can cause a
A. Two neutrals would exist on the same circuit. Since decrease in incandescent light output, and a decrease in
neutrals must be grounded according to the National resistive heat output. With motors low voltage can cause a
Electric Code, a short circuit would be created. decrease in motor torque, an increase in motor amperage
requirements, an increase in motor temperature and
B. Unbalanced line to output neutral voltages would be decrease in motor life expectancy.
created; one line would read 120 Volts, the other
130+ Volts.
258 Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018