Directly Buried Cable (600 - 22 KV) : General Notes
Directly Buried Cable (600 - 22 KV) : General Notes
DIRECTLY BURIED CABLE (600 -22 KV) Table 300.50: Embedment depth requirements:
- Directly buried cable (600 - 22,000 volts): 75cm.
- Cable in conduit (600 -22,000 volts): 45cm.
300.5 (d) (3): Protection from Damage. Direct-buried conductors and cables
shall be protected from damage in accordance with 300.5(D)(1) through
(D)(4).(3) Service Conductors. Underground service conductors that are not
700 encased in concrete and that are buried 450 mm (18 in.) or more below grade
1100 1100
shall have their location identified by a warning ribbon that is placed in the trench
BACKFILLING WITH 90 ºC cm/W THERMAL RESISTIVITY BACKFILLING WITH 90 ºC cm/W THERMAL RESISTIVITY at least 300 mm (12 in.) above the underground installation.
BACKFILLING WITH 90 ºC cm/W THERMAL RESISTIVITY
750
750
800
810
300.5 (f) Backfill: Backfill that contains large rocks, paving materials, cinders,
large or sharply angular substances, or corrosive material shall not be placed in
1190
300
300
300
3 WIRE FOR POSITIVE 10AWG/6mm2 1 WIRE FOR POSITIVE 600 kCmil/300mm2 3 WIRE FOR POSITIVE 10AWG/6mm2 an excavation where materials may damage raceways, cables, or other
1 WIRE FOR NEGATIVE 4 AWG/25mm2 1 WIRE FOR NEGATIVE 600 kCmil/300mm2 1 WIRE FOR NEGATIVE 4 AWG/25mm2 substructures or prevent adequate compaction of fill or contribute to corrosion of
90 190 90 raceways, cables, or other substructures.Where necessary to prevent physical
damage to the raceway or cable, protection shall be provided in the form of
granular or selected material, suitable running boards, suitable sleeves, or other
190
approved means.
190
EARTH CONDUCTOR. BARE COPPER 2 AWG/35 mm2 1 WIRE FOR NEGATIVE 600 kCmil/300mm2
EARTH CONDUCTOR. BARE COPPER 2 AWG/35 mm2
190 The distance between circuits is not standardized for circuits smaller than 22KV,
so the circuit details in Figure 310-60 of NOM-001-SEDE-2012, "Installation
dimensions of cables for use, are taken as reference, with the tables 310-60c
(77) to 310-60c (68) ".
450
450
500
600
300
300
1 WIRE FOR NEGATIVE 4 AWG/25mm2
90 1 WIRE FOR POSITIVE 600 kCmil/300mm2 90
3 WIRE FOR POSITIVE 10AWG/6mm2 190
1 WIRE FOR NEGATIVE 600 kCmil/300mm2
1 WIRE FOR NEGATIVE 4 AWG/25mm2
950
HDPE Ø 3"/ 78mm
190
190
190
EARTH CONDUCTOR. BARE COPPER 2 AWG/35 mm2 1 WIRE FOR NEGATIVE 600 kCmil/300mm2
300
300
1050
600