Checklist For Plinth Beam Design& Drawing

1. The document reviews the design and drawings of a control room plinth beam according to relevant standards. 2. It checks parameters like design assumptions, loads, materials, dimensions, reinforcement, and calculations against standards. 3. The drawing review checks aspects like north direction, scale, units, grid, title block information, and included plans. Deviations from the standards, if any, are noted.

Uploaded by

Rupesh Khandekar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
3K views

Checklist For Plinth Beam Design& Drawing

1. The document reviews the design and drawings of a control room plinth beam according to relevant standards. 2. It checks parameters like design assumptions, loads, materials, dimensions, reinforcement, and calculations against standards. 3. The drawing review checks aspects like north direction, scale, units, grid, title block information, and included plans. Deviations from the standards, if any, are noted.

Uploaded by

Rupesh Khandekar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

Control Room Plinth Beam Design & Drawing Review Doc. No.

Rev. : 00 Date :
Checks for Control Room Plinth Beam Design & Drawing
Reference 01 : Bureau of Indian Standards ( IS : 456_2000), & Other relavent IS Standards
Reference 02 : Suzlon Technical Specification No.: ENG:PEV:T-012 , CEA Te
Standards for Construction of Electrical Plants and Electric Lines Regulations, 2010.
Sl.No Parameters to be Checked OK NOT OK

A DESIGN UNITS
All Design units are as per Standard International (SI) Metric System
1

B DESIGN ASSUMPTIONS

1 General design Methodology is provided

2 All Design assumptions are clearly described

C DESIGN PARAMETERS

1 Allowable total settlement is provided

2 Allowable differential settlement is provided

3 Concrete & Reinforcement grades

4 Soil Unit weight is provided

5 Water Table is provided

6 Young's modulus is provided

7 Poison's ratio is provided

D DESIGN LOADS

1 Design Loads are as per Project Design Basis /IS Codes

2 Dynamic loads are as Per Vendor Data for Heavy Rotating Equipment

3 Thermal loads are as per Project Design Basis


Load combinations for Allowable Stress Design are as per Project Design Basis ,
4 IS Codes
Load combinations for Ultimate Strength Design are as per Project Design
5 Basis , IS Codes

F PLINTH BEAM DESIGN


As per IS 13920-2016, the minimum width for the Design of Plinth Beam shall
not be less than 200 mm. The width of the beam shall not be more than the
1 width of supporting beams such as columns and shear walls.

As per IS 13920-2016, The Design Depth of beams shall not be more than 1/4th
of the Clearspan. It shall not be less than 200 mm. Depth of beam not only
2 depends upon the dead load, live load, earthquake load, etc. but also depends
upon the span of the beam.

As per IS 13920-2016, the ration of width to depth shall be more than 0.3.
3
The ratio of span to overall depth shall be in the range of 12 to 15.
4
As per IS 456-2000, the Minimum Grade of concrete of Reinforced Concrete
beam shall not be less than M20. Where M stands for Mix and 20 stands for
5 Specified compressive strength of 150 mm cube after 28 days of curing and
expressed in N/mm2
As per IS 456-2000, The Grade of steel for Stirrups Shall not be less than Fe 415.
Steel Main Reinforcement used shall be of grade Fe 500 and Fe 550, that is;
6 high strength deformed bars.

A minimum of two numbers of Top reinforcement shall be provided.


7
The diameter of Top reinforcement shall not be less than 12 mm.
8
Minimum two number of Bottom reinforcement shall be provided.
9
The diameter of Bottom reinforcement shall not be less than 12 mm.
10
The maximum spacing of shear reinforcement shall not be more than 0.75 d for
vertical stirrups and d for inclined stirrups at 45 degrees, where d is the
11 effective depth of the section. In no case shall be spacing exceed 300 mm

The minimum diameter of shear reinforcement shall not be less than 8 mm and
having U link with 1350 hook with an extension of 6 times diameter (but not
12 less than 65 mm) at each end.

Spacing between the stirrups shall not be more than 150 mm


13
The First stirrups shall be at a distance not more than 50 mm from the joint face
14
Lap length shall not be provided within the junction of the Beam – column and
15 Beam – Beam junction.
It shall not be within the distance of 2d from the face of the column, where d is
16 the effective depth of the beam.
It shall not be provided within a quarter length of beam adjoining the location
17 where the flexural yielding may occur under earthquake effects.
Not more than 50% of the area of a steel bar on either Top or bottom face shall
18 be lapped at any section.
Lap length in beam shall not less than the development length of the largest
19 longitudinal reinforcement bar in tension.

G CALCULATION PRESENTATION
Calculations Cover Sheet with Document Number, Project title, Caculation
1 Subject, Date, etc. is provided
Name of calculation originator/Checker on Claculation Sheets
2
Subject of Structural Calculations
3
Reference drawing number,Table of contents , List of appilcable coded,&
4 Standards .
General description of Structure design Methodology/Design Criteria /Primary
5 Loads Definition
Drawings
H
Check North Direction, Check Scale, Check units, Check Grid Dimensions
1
The information within the Title Block of each drawing has been reviewed for
accuracy including the “Designed By”, “Drawn By”, “Checked By” and “File No.”
2 fields.

The Index Sheet has been coordinated with the current list of
3 architectural drawings with respect to drawing number and title.
A drawing has been included to identify abbreviations and symbols utilized on
the project drawings and have been coordinated with the other architectural
4 drawings for compliance.

Loading plans, vertical loads layout


5
Deviations, if any

Verification team
Reviewed & Verfied by Approved & Accepted by
Remarks
Name
Date
Sign.

Prepared by Reviewed by Accepted by


Rupesh Khandekar Jagadish Ghogare Pravinkumar Patil
Doc. No.
Rev. : 00 Date :

CEA Technical

Remarks, if any
Approved & Accepted by

Accepted by
Pravinkumar Patil