Manual de Huawei
Manual de Huawei
Quick Guide
Issue: 07
Part Number: 31500AQK
Date: 2019-08-30
1 Product Overview
Front View
(1) PV connection indicator
(2) Grid-tied indicator
(3) Communication indicator
(4) Alarm/Maintenance
indicator
(5) Host panel cover
(6) Maintenance
compartment
Port Description
2 Installation Requirements
2.1 Installation Angle
2
2.2 Installation Space
3
2. Unpack the inverter and move it to the specified position.
Handles are packed in a fitting bag and are not delivered with the SUN2000
3. Adjust the installation positions of the handles, and install the SUN2000 on the mounting
bracket.
4
4 Installing Cables
4.1 Installation Preparations
If outdoor copper-core cables are used, select copper wiring terminals. For details about the
requirements for cables and terminals of other materials, see the user manual.
5
No. Item Type Specifications Description
Note a: The value is valid only if the conductors of the PE cable and AC power cable use the same
material. If the materials are different, ensure that the conductor cross-sectional area of the PE
cable produces a conductance equivalent to that of the area S/2.
Note b: You are advised to use a soft cable to prevent poor terminal contact due to the bending
stress of the cable.
6
4.3 Opening the Maintenance Compartment Door
1. Loosen the screws on the maintenance 2. Open the maintenance compartment door
compartment door. and adjust the support bar.
7
3. Remove the crimping modules and three-hole rubber plug that are bound in the maintenance
compartment for future use.
Crimping
module
Three-hole
rubber plug
If the AC output power cable has a single core, replace the crimping module.
8
4.5 Removing the Rubber Rings from the Crimping Module
Use scissors to cut off the joints of the rubber rings to remove them. All rubber rings are removed in
the same way.
9
4.7 Installing AC Output Power Cables
Remove the corresponding rubber rings in strict accordance with the cable diameter, and ensure
that the crimping module is not damaged. Otherwise the protection level of the solar inverter will
be affected.
Ensure that AC terminations provide firm and solid electrical connections. Failing to do so may
cause SUN2000 malfunction and damage to its terminal block, even starting thermal events.
If the AC output power cables are subject to a pulling force because the inverter is not installed
stably, ensure that the last cable that bears the stress is the PE cable.
Multi-core Cable (Four-Core Cable Is Used as an Example)
(six rings)
(five rings)
(four rings)
(three rings)
(two rings)
(one ring)
10
Single-core Cable
(four rings)
(three rings)
(two rings)
(one ring)
11
4.8 Closing the Maintenance Compartment Door
When connecting cables using Y-branch connectors, ensure that all connectors are of the
same model provided by the same vendor.
If connectors of different vendors are connected to each other or different types of connectors
of the same vendor are connected to each other without permission, the contact resistance of
the connectors will exceed the allowed value. As a result, the connectors will be heated and
oxidized continuously, which is prone to faults.
Wiring rules:
1. A maximum of one set of Y-branch connectors can be used for each MPPT.
2. The PV+ on the inverter side must be connected to the PV+ on the PV string side, and the PV
on the inverter side must be connected to the PV on the string side.
12
a. Wiring diagram (with Y-branch connectors connected to the inverter)
Y-branch connectors
Y-branch connectors
13
Selecting DC Input Terminals
The SUN2000 has three DC switches (DC SWITCH 1, DC SWITCH 2, and DC SWITCH3).
DC SWITCH 1 controls routes 1 6 of DC input terminals, DC SWITCH 2 routes 7 12, and DC
SWITCH 3 routes 13 18.
1. Use the MC4 EVO2 PV connectors delivered with the SUN2000. If the PV connectors are lost or
damaged, purchase the connectors of the same model. The device damage caused by
incompatible PV connectors is beyond the warranty scope.
2. Before connecting DC input power cables, label the cable polarities to ensure correct cable
connections. If the cables are connected incorrectly, the SUN2000 may be damaged.
3. Measure the voltage at the DC input end using a multimeter. If the voltage is a negative value,
the DC input polarity is incorrect. Correct the polarity. If the voltage is greater than 1500 V, too
many PV modules are configured to the same string. Remove some PV modules.
4. If polarity of the DC input power cable is reversed and the DC switch is ON, do not turn off the
DC switch immediately or unplug positive and negative connectors. The device may be
damaged if you do not follow the instruction. The caused equipment damage is beyond the
warranty scope. Wait until the solar irradiance declines and the PV string current reduces to
below 0.5 A, and then turn off the three DC switches and remove the positive and negative
connectors. Correct the string polarity before reconnecting the string to the SUN2000.
14
Installing a DC input power cable
Positive metal contact Positive connector
32.6020-22100-HZ
Negative metal contact (STAUBLI) Negative Click
Ensure that the cable connector
cannot be removed after
crimped.
13001462
(STAUBLI)
15
Connecting Communications Cables
If three communications cables are to be connected, use the three-hole rubber plug that is bound
in the maintenance compartment.
3. All ground cables are connected securely, without open circuits or short circuits.
4. AC output power cables are connected correctly and securely, without open circuits or short
circuits.
5. DC input power cables are connected correctly and securely, without open circuits or short
circuits.
7. The maintenance compartment door is closed and the door screws are tightened.
16
6 Powering On the System
Before turning on the AC switch between the SUN2000 and the power grid, use a multimeter to
check that the AC voltage is within the specified range.
1. Turn on the AC switch between the SUN2000 and the power grid.
2. Set DC SWITCH 1 (MAIN SWITCH) at the bottom of the SUN2000 chassis to ON.
3. Check the status of LED 1. If it is steady green, set DC SWITCH 2 and DC SWITCH 3 to
ON.
4. Observe the LED indicators to check the SUN2000 operating status.
Blinking at short intervals (on for 0.2s and then off for 0.2s).
Blinking at long intervals (on for 1s and then off for 1s).
Blinking
green at Steady
An environmental fault occurs at DC side.
short red
intervals
Blinking
green at Steady
An environmental fault occurs at AC side.
short red
intervals
Communications LED3 -
indication
Blinking green at short The SUN2000 receives data over RS485 or MBUS
intervals communication.
17
Display Category Indicator Status Description
Alarm/O&M LED4 -
indication
Steady red A warning alarm is generated.
7 SUN2000 APP
1. The SUN2000 app is mobile phone app that communicates with the SUN2000 monitoring system
over a USB data cable, Bluetooth module, or WLAN module. As a convenient local monitoring
and maintenance platform, it supports alarm query, parameter configuration, and routine
maintenance. The app name is SUN2000.
2. Access the Huawei app store (http://appstore.huawei.com) or Google Play
(https://play.google.com), search for SUN2000, and download the SUN2000 app software
package.
3. Connect a USB data cable, a Bluetooth module, or a WLAN module to the USB port of the
SUN2000 to implement the communication between the SUN2000 and the app.
18
Selecting a Switching Quick
Login screen between users
connection mode settings
Main menu
screen
The screenshots in this document correspond to app version 3.2.00.001.
When the WLAN connection is used, the initial name of the WLAN
hotspot is Adapter-WLAN module SN, and the initial password is
Changeme.
The initial password for Common User, Advanced User, and Special
User is 00000a.
Use the initial password upon first power-on and change it immediately
after login. To ensure account security, change the password periodically
and keep the new password in mind. Not changing the initial password
may cause password disclosure. A password left unchanged for a long
period of time may be stolen or cracked. If a password is lost, devices
cannot be accessed. In these cases, the user is liable for any loss
caused to the PV plant.
Set the correct grid code based on the application area and scenario of
the solar inverter.
19
8 Grid Code Mapping Table
SUN2000- SUN2000- SUN2000-
No. Grid Code Description
175KTL-H0 185KTL-INH0 185KTL-H1
China medium-voltage power -
1 CHINA_MV800 Supported -
grid
G59 medium-voltage power
2 G59-England-MV800 - - Supported
grid
Australia medium-voltage
3 AS4777-MV800 - - Supported
power grid
India medium-voltage power
4 INDIA-MV800 - Supported -
grid
IEC61727 medium-voltage
5 IEC61727-MV800 - Supported Supported
power grid (50 Hz)
Germany medium-voltage
6 BDEW-MV800 - - Supported
power grid
ABNT NBR 16149- Brazil medium-voltage power
7 - - Supported
MV800 grid
UTE C 15-712-1- France medium-voltage
8 - - Supported
MV800 power grid
Chile medium-voltage power
9 Chile-MV800 - - Supported
grid
Turkey medium-voltage power
10 EN50438-TR-MV800 - - Supported
grid
Thailand PEA medium-
11 TAI-PEA-MV800 - - Supported
voltage power grid
Philippines medium-voltage
12 Philippines-MV800 - - Supported
power grid
Malaysia medium-voltage
13 Malaysian-MV800 - - Supported
power grid
South Africa medium-voltage
14 NRS-097-2-1-MV800 - - Supported
power grid
South Africa RPPs medium-
15 SA_RPPs-MV800 - - Supported
voltage power grid
Jordan power transmission
Jordan-Transmission-
16 network medium-voltage - - Supported
MV800
power grid
Jordan power distribution
Jordan-Distribution-
17 network medium-voltage - - Supported
MV800
power grid
Egypt medium-voltage power
18 Egypt ETEC-MV800 - - Supported
grid
20
SUN2000- SUN2000- SUN2000-
No. Grid Code Description
175KTL-H0 185KTL-INH0 185KTL-H1
Dubai medium-voltage
19 DUBAI-MV800 - - Supported
power grid
Saudi Arabia medium-
20 SAUDI-MV800 - - Supported
voltage power grid
Ireland medium-voltage
21 EN50438_IE-MV800 - - Supported
power grid
CLC/TS50549_IE- Ireland medium-voltage
22 - - Supported
MV800 power grid (CLC/TS50549)
Northern Ireland- Northern Ireland medium-
23 - - Supported
MV800 voltage power grid
Italy medium-voltage power
24 CEI0-21-MV800 - - Supported
grid (CEI0-21)
IEC 61727-MV800- General medium-voltage
25 - Supported Supported
60HZ power grid
Pakistan medium-voltage
26 Pakistan-MV800 - - Supported
power grid
BRASIL-ANEEL- Brazil medium-voltage
27 - - Supported
MV800 power grid
Israel medium-voltage
28 Israel-MV800 - - Supported
power grid
Italy medium-voltage power
29 CEI0-16-MV800 - - Supported
grid
Zambia medium-voltage
30 ZAMBIA-MV800 - - Supported
power grid
Kenya low-voltage and
KENYA_ETHIOPIA_
31 Ethiopia medium-voltage - - Supported
MV800
power grid
Namibia medium-voltage
32 NAMIBIA_MV800 - - Supported
power grid
Cameroon medium-voltage
33 Cameroon-MV800 - - Supported
power grid
Nigeria medium-voltage
34 NIGERIA-MV800 - - Supported
power grid
Abu Dhabi medium-voltage
35 ABUDHABI-MV800 - - Supported
power grid
Lebanon medium-voltage
36 LEBANON-MV800 - - Supported
power grid
Argentina medium-voltage
37 ARGENTINA-MV800 - - Supported
power grid
Jordan-Transmission- Jordan high-voltage and
38 - - Supported
HV800 medium-voltage power grid
21
SUN2000- SUN2000- SUN2000-
No. Grid Code Description
175KTL-H0 185KTL-INH0 185KTL-H1
Tunisia medium-voltage
39 TUNISIA-MV800 - - Supported
power grid
AUSTRALIA-NER- Australia NER standard
40 - - Supported
MV800 medium-voltage power grid
VDE-AR- VDE4120 standard
41 - - Supported
N4120_HV800 medium-voltage power grid
Nicaragua medium-voltage
42 Nicaragua-MV800 - - Supported
power grid
43 Custom-MV800-50Hz Reserved - - Supported
Spain medium-voltage
44 RD1699/661-MV800 - - Supported
power grid
Spain medium-voltage
45 PO12.3-MV800 - - Supported
power grid
Vietnam medium-voltage
46 Vietnam-MV800 - - Supported
power grid
Chile PMGD medium-
47 CHILE-PMGD-MV800 - - Supported
voltage power grid (800 V)
Ghana medium-voltage
48 GHANA-MV800 - - Supported
power grid (800 V)
Taiwan power medium-
49 TAIPOWER-MV800 - - Supported
voltage power grid (800 V)
Oman medium-voltage
50 OMAN-MV800 - - Supported
power grid
Kuwait medium-voltage
51 KUWAIT-MV800 - - Supported
power grid
Bangladesh medium-
52 BANGLADESH-MV800 - - Supported
voltage power grid
Bahrain medium-voltage
53 BAHRAIN-MV800 - - Supported
power grid
Kazakhstan medium-
54 KAZAKHSTAN-MV800 - - Supported
voltage power grid
Oman PDO medium-
55 Oman-PDO-MV800 - - Supported
voltage power grid
Thailand medium-voltage
56 TAI-MEA-MV800 - - Supported
power grid
NOTE
The grid codes are subject to change. The listed codes are for your reference only.
22
Huawei Technologies Co., Ltd.
Huawei Industrial Base, Bantian, Longgang,
Shenzhen 518129, People's Republic of China
solar.huawei.com