ControlNet Scanner Module
ControlNet Scanner Module
Scanner Module
1747-SCNR
Reference Manual
Important User Information Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
!
Attention statements help you to:
• identify a hazard
• avoid a hazard
• recognize the consequences
EMC Directive
Introduction Use this manual to install, configure, and apply the features of the
1747-SCNR Scanner.
Audience This manual is intended for engineers and technicians who are
installing, programming, and maintaining a control system that
includes an SLC 500 communicating on a ControlNet network with a
1747-SCNR Scanner.
Terminology The following list contains ControlNet network terms used in this
manual.
Term Definition
Actual Packet Interval The measure of how frequently a specific connection
(API) produces its data.
Big-endian A computer architecture in which, within a given
multi-byte numeric representation, the most significant
byte has the lowest address (the word is stored
“big-end-first” - typically Motorola architecture).
Bit A unit of information consisting of a 1 or a 0. This is the
smallest data unit that can be transmitted.
Class A set of objects all of which represent a similar system
component. A class is a generalization of the object, a
template for defining variables and methods. All objects
in a class are identical in form and behavior, but they
may contain different attribute values.
Client 1. An object that uses the services of another
(server) object to perform a task.
2. An initiator of a message to which a server
reacts.
Connection A logical binding between two application objects.
These application objects may be in the same or
different devices.
Connection Path The attribute is made up of a byte stream that defines
the application object to which a connection instance
applies.
Consume The act of receiving data from a producer.
Consumer A node that is receiving data from a producer.
Device A physical hardware connection to the link. A device may
contain more than one node.
Error A discrepancy between a computed, observed, or
measured value or condition and the specified or
theoretically correct value or condition.
Frame Single data transfer on a link.
Instance The actual physical presentation of an object within a
class. Identifies one of many objects within the same
object class.
Link A collection of nodes with unique MAC IDs. Segments
connected by repeaters make up a link; links connected
by routers make up a network.
Little-endian A computer architecture in which, within a given
multi-byte numeric representation, the least significant
byte has the lowest address (the word is stored
“little-end first” - typically Intel architecture).
Multicast Connection A connection where one node produces data and
multiple nodes consume that exact same data.
Connections can be either point-to-point or multicast.
Network A series of nodes connected by some type of
communication medium. The connection paths between
any pair of nodes can include repeaters, routers, and
gateways.
Term Definition
Network Access Port Physical Layer variant that allows a temporary node to
(NAP) be connected to the link by connection to the NAP of a
permanent node.
Network Address or A node’s address on the link (also called MAC ID).
Node Address
Network Status Indicators on a node displaying the status of the Physical
Indicators and Data Link Layers.
Network Update Interval A single occurrence of the ControlNet Network Update
(NUI) Time (NUT).
Network Update Time Repetitive time interval in which data can be sent on the
(NUT) link.
Node A connection to a link that requires a single MAC ID.
Object 1. An abstract representation of a computer’s
capabilities. Objects can be composed of any or
all of the following components: data
(information which changes with time)
configuration (parameters for behavior) methods
(things that can be done using data and
configuration)
2. A collection of related data (in the form of
variables) and methods (procedures) for
operating on that data that have clearly defined
interface and behavior.
Originator The client responsible for establishing a connection path
to the target.
Point-To-Point A connection that exists between two nodes only.
Connection Connections can be either point-to-point or multicast.
Produce Act of sending data to a consumer.
Producer A node that is responsible for transmitting data.
Redundant Media A system using more than one medium to help prevent
communication failures.
Requested Packet The measure of how frequently the originating
Interval (RPI) application requires the transmission of data from the
target application.
Scanner Configuration Software tool that allows you to configure scheduled
Tool (SCT) connections, map data for these connections, and
monitor the status for the configured connections.
Scheduled Data transfers that occur in a deterministic and
repeatable manner on predefined NUTs.
Server An object which provides services to another (client)
object.
Service Operation or function that an object performs upon
request from another object.
Target The end-node to which a connection is established.
Unscheduled Data transfers that use the remaining time in the NUT
after the scheduled transfers have been completed.
Acronyms
Acronym Meaning
API Actual Packet Interval.
BNC A connector for coaxial cable having a bayonet-type shell
with two small knobs on the female connector which
lock into spiral slots in the male connector when it is
twisted (refer to the illustration on page 1-1).
CIP The control and information protocol defined by part 4 of
the ControlNet standard. CIP includes both connected
and unconnected messaging.
LED Light Emitting Diode.
MAC ID The address of a node.
NAP Network Access Port.
NUI Network Update Interval.
NUT Network Update Time.
RPI Requested Packet Interval.
SCT Scanner Configuration Tool
Common Techniques Used The following conventions are used throughout this manual:
in This Manual • Bulleted lists provide information, not procedural steps.
• Numbered lists provide sequential steps.
• Pictures of keys and/or screens represent the actual keys you
press or the screens you use.
• “What’s Happening” boxes appear in the appendices. These
boxes give a step by step explanation of the process illustrated
in the figure(s) that follow the What’s Happening box. The
figures have numbers in them that correspond to the What’s
Happening steps.
TIP
Rockwell Automation Rockwell Automation offers support services worldwide, with over 75
sales/support offices, 512 authorized distributors, and 260 authorized
Support systems integrators located throughout the United States alone, plus
Rockwell Automation representatives in every major country in the
world.
If you have any suggestions about how we can make this manual
more useful to you, please contact us at the following address:
Notes:
Chapter 1
Install and Connect the What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . 1-1
ControlNet Scanner Module Identify Scanner Module Features . . . . . . . . . . . . . . . . . . . 1-1
Prepare for Module Installation . . . . . . . . . . . . . . . . . . . . . 1-2
Select the ControlNet Node Address. . . . . . . . . . . . . . . . . . 1-3
Insert the 1747-SCNR Scanner Into the Chassis . . . . . . . . . . 1-3
Connect to a ControlNet Network . . . . . . . . . . . . . . . . . . . 1-5
Connect Programming Terminal to ControlNet Network 1-6
SLC 500 I/O Configuration for the 1747-SCNR Module . . . . 1-8
Chapter 2
Prepare to Use the ControlNet What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . 2-1
Scanner Module What Your Scanner Does . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Communicating with Your SLC Processor. . . . . . . . . . . . . . 2-1
Communicating with Your SLC processor Using M1 and M0
Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Understand ControlNet Data transfer . . . . . . . . . . . . . . . . . 2-3
Scheduled Data Transfer Operations on a ControlNet
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Unscheduled Data Transfer Operations on a ControlNet
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Link Layer Services . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Understand 1747-SCNR Mapping . . . . . . . . . . . . . . . . . . . . 2-5
Discrete Input File . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
1747-SCNR M1 File. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Discrete Output File. . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
1747-SCNR M0 File. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Communicating with Your Devices . . . . . . . . . . . . . . . . . . 2-9
I/O Scheduled Data Transfer . . . . . . . . . . . . . . . . . . . . 2-9
Unscheduled Data Server . . . . . . . . . . . . . . . . . . . . . . . 2-10
CIP Client Request Transfer . . . . . . . . . . . . . . . . . . . . . 2-10
Chapter 3
Configure/Map Scheduled Data What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Exchange with RSNetWorx for Begin the Configuration Process . . . . . . . . . . . . . . . . . . . . 3-1
ControlNet Questions to Ask. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Data Transfer Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Chapter 4
Troubleshooting What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . 4-1
Troubleshooting with the Status Indicators and Status Display 4-1
Apply Chassis Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Alphanumeric Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
OK Indicator and Display Mnemonics . . . . . . . . . . . . . . . . 4-3
Appendix A
Local Database Access Using What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . A-1
PLC-5 MSG Instructions What We Assume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Read and Write Access To
1747-SCNR Local Database Using PLC-5 MSG Instruction . . A-1
Appendix B
Local Database and ControlNet What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . B-1
Data Files Access Using CIP What We Assume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Messaging Read and Write Access to
1747-SCNR Data Files Using Assembly Object Services . . . . B-1
Assembly Object Instance Numbers Supported for Get and Set
Member on Data Attribute . . . . . . . . . . . . . . . . . . . . . . B-2
1747-SCNR Memory Layout . . . . . . . . . . . . . . . . . . . . . . . . B-3
Appendix C
CIP Client Management What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . C-1
What We Assume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
CIP Client Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Send a Get Attribute All Request to Node 14 Identity Object C-3
SLC 500 Processor: N7 Data File (hex) . . . . . . . . . . . . C-4
SLC 500 Ladder Program . . . . . . . . . . . . . . . . . . . . . . . C-5
SLC 500 Processor: Data Files (hex) . . . . . . . . . . . . . . . C-6
Send a Set Attribute Single Request . . . . . . . . . . . . . . . . . . C-7
SLC 500 Processor: N7 Data File (hex) . . . . . . . . . . . . . C-8
Example: SLC 500 Ladder Program . . . . . . . . . . . . . . . C-9
SLC 500 Processor: Target Input Data File (hex) . . . . . C-10
Send a Set Member Request. . . . . . . . . . . . . . . . . . . . . . . C-11
SLC 500 Processor: N7 Data File (hex) . . . . . . . . . . . . C-12
Example: SLC 500 Ladder Program . . . . . . . . . . . . . . C-13
SLC 500 Processor: Target Input Data File (hex) . . . . . C-14
Appendix D
Example of Reset Bit Management What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . D-1
What We Assume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Appendix E
Application Examples What This Appendix Contains . . . . . . . . . . . . . . . . . . . . . . E-1
What We Assume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Example 1: Configure the 1747-SCNR with the 1746-IV16 Input
Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Configure the ControlNet Network with RSNetWorx
for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Example 2: Configure the 1747-SCNR with the 1746-NIO4V
Analog Input/Output Module . . . . . . . . . . . . . . . . . . . . . . E-9
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-9
Configure the ControlNet Network with RSNetWorx
for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-9
Configure a Module Connection . . . . . . . . . . . . . . . . . E-16
Example 3: Configure the 1747-SCNR with the 1746-NI8 Analog
Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-19
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-19
Configure the ControlNet Network with RSNetWorx
for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-19
Configure a Module Connection . . . . . . . . . . . . . . . . . E-25
Example 4: Configure the 1747-SCNR with the 1746-BAS Series B
Interface Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-28
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-28
Configure the ControlNet Network with RSNetWorx
for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-28
Configure a Module Connection . . . . . . . . . . . . . . . . . E-34
Example 5: Configure the 1747-SCNR with the 1794-IE4XOE2
Analog Combo Module . . . . . . . . . . . . . . . . . . . . . . . . . . E-41
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-42
Configure the ControlNet Network with RSNetWorx
for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-42
Configure a Module Connection . . . . . . . . . . . . . . . . . E-48
Example 6: Creating Peer-to-Peer Scheduled Connections
Between 1747-SCNR ControlNet Scanners . . . . . . . . . . . . E-51
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-51
Configure the ControlNet Network with RSNetWorx
for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-52
Configure a Scheduled Connection Between
ControlNet Scanners. . . . . . . . . . . . . . . . . . . . . . . . . . E-54
What This Chapter Contains This chapter describes how to install and connect your ControlNet
1747-SCNR Scanner module. The following table describes what this
chapter contains and where to find specific information.
Identify Scanner The following drawing identifies the features of the 1747-SCNR
Scanner module.
Module Features
Node Address and Status Display
Displays scanner node address and
Channel B status
Status Indicator
Channel A Module Status Indicator
Status Indicator Indicates whether the device is
powered and is functioning properly
ControlNet Network
Access Port
(NAP)-RJ45 connector
Prepare for Module Before you install your module, you need the following items:
Installation
RSNetWorx for
ControlNet,
Personal Computer with catalog number 1747-SCNR Scanner Module
Microsoft Windows 9357-CNETL3 Reference Manual, publication
1747-6.23 (this manual)
Before you install the module, you must know how to:
The 1747-SCNR Scanner module fits in any slot of the chassis except
for the left-most slot of the first chassis, which is reserved for the SLC
500 processor.
Select the ControlNet Select the ControlNet node address of the 1747-SCNR by setting the
two 10-digit rotary switches on the top of the scanner.
Node Address
Insert the 1747-SCNR To insert the 1747-SCNR Scanner into the SLC chassis:
Scanner Into the Chassis 1. Turn off the SLC chassis power supply.
2. Select a slot for the module in the chassis. Choose any slot
except the left-most slot of the first chassis, which is reserved for
the SLC 500 processor.
30801-M
4. Apply firm, even pressure to seat the module in the I/O chassis
backplane connectors.
Connect to a ControlNet Connect the 1747-SCNR Scanner module to a ControlNet network via
a tap with a 1m (39.4 in.) drop cable.
Network
Four taps are available from Rockwell Automation.
Straight T-tap Straight Y-tap Right-angle-Tap Right-angle Y-tap
TIP
We recommend that you use a tap with a straight
connector—1786-TPS or 1786-TPYS—when you attach a
ControlNet 1747-SCNR Scanner to a ControlNet network.
ATTENTION
Do not connect the same communication card
to both the NAP and a tap on the ControlNet
! network.
Using 1784-KTCx15 communication card on coax media 1 Using 1784-PCC or -KTCx15 communication card and NAP 1
ControlNet 1747-SCNR Scanner Programming Terminal ControlNet 1747-SCNR Scanner Programming Terminal
3
1784-PCC
1784-KTCx15 or -KTCx15
1786-CP 2
A A ControlNet Network
B B
ControlNet Network
Using 1770-KFC15 communication interface on coax media 1 Using 1770-KFC15 communication interface and NAP 1
Serial Connection
1786-CP 2
1770-KFC15
A A ControlNet Network
B B
ControlNet Network 41521
SLC 500 I/O Configuration Select the I/O card. Or, if you do not have an I/O card, follow the
procedure below.
for the 1747-SCNR Module
Open RSLogix 500 and follow the procedure below to configure the
1747-SCNR module.
What This Chapter Contains Read this chapter to understand how to use your ControlNet
1747-SCNR Scanner module. The following table describes what this
chapter contains and where to find specific information.
What Your Scanner Does In a typical configuration, the scanner acts as an interface between
ControlNet devices and an SLC processor. The scanner communicates
with ControlNet devices over the network to:
Communicating with Your The scanner communicates with the processor in the form of M1/M0
File Transfers and/or Discrete I/O (DIO). Information exchanged
SLC Processor includes:
Your processor can communicate with the scanner via M1 file transfer
reads and M0 file transfer writes.
The scanner does not send data to your processor. Data transfer
between your scanner and the processor must be initiated by the
processor. For example, data is sent, or "written", to the scanner by
your processor by placing the data in the M0 file. This data is
organized in the scanner and then, based on the area you updated,
the appropriate action is initiated to send it on the ControlNet
network.
An M0 file transfer is the transfer of data from the SLC 500 processor
to the scanner. The processor “writes” data to the scanner’s memory.
ControlNet
network
Discrete Output Image
X
Discrete Output
Y Internal Output
Transfer
M0 Data File Data Storage
Z I/O Map X
Y
Z
M0 file
transfer
(write)
41553
Housekeeping
Scheduled
Data
Scheduled Data Transfers
Data
Logic Scan
Table Private
Files Data Update Memory
Buffers
41554
SLC 500 Program Scan Data Tables Files Housekeeping 1747-SCNR Scheduled Data
Housekeeping
M0
Local
Data Database
Table area
Files M0 file transfer
(SLC processor M0
Data read and write) CIP client
Table message
Files M0 file transfer area
(write request -
read response)
41555
SLC 500 Program Scan 1747-SCNR Unscheduled Data
Data Tables Files
Housekeeping
Time
41556
The ControlNet system places your scheduled transfers in the first part
of each Network Update Interval (NUI). Time is automatically
reserved for network maintenance, and unscheduled transfers are
performed during the remainder of the interval.
Understand 1747-SCNR The 1747-SCNR Scanner and the SLC processor exchange the
following information through the backplane:
Mapping
• Input data
• Output data
• Status data
• Command data
• CIP messages
1747-SCNR M1 File
Word Word ControlNet Contents Description
Offsets Size Transfer Mode
0 1 N/A Reserved Reserved for future use.
1 1 N/A Module Value indicating the current operational
Status (See status of the module. See the
the next page “Troubleshooting” section, chapter 4, for
“Module probable causes and recommended
Status”) actions.
2 1 N/A ControlNet Value indicating the current channel
Status (See LEDs.
the next page
“ControlNet
Status”)
3-255 253 Scheduled ControlNet You can map scheduled input data in this
Input Data area using RSNetWorx for ControlNet.
256-599 344 N/A Reserved Reserved.
600-607 8 N/A Connection Bit field reporting scheduled connections
Status status.
Two consecutive bits per scheduled
connection:
Connection State
(Even bit numbers)
1:connection opened
0:connection closed
Remote Device Mode
(Odd bit numbers)
1:remote device is in run mode
0:remote device is in idle mode
1747-SCNR M0 File
Only Input and Output data (from Input file, Output file, M0
ControlNet Output data area, and M1 ControlNet Input data area) are
exchanged during scheduled time.
The SLC processor that has read and write access to this area is then
able to receive or modify data into the database.
What this chapter contains This chapter provides information about the mapping of scheduled
connections between 1747-SCNR remote devices. This chapter also
contains questions you should ask before configuring your 1747-SCNR
scanner. The following table describes what this chapter contains and
its location.
Begin the Configuration Planning before configuring your scanner helps make sure you can:
Process • use your memory bandwidth efficiently
• give attention to device-specific needs and requirements
• give priority to critical I/O transfers
• leave room for expansion
Questions to Ask Some questions you should ask yourself before you begin configuring
the 1747-SCNR scanner are:
• communication requirements
• I/O importance and size
• frequency of message delivery
Data Transfer Mapping You can use the configuration software (RSNetWorx for ControlNet)
to select either Input or M1 files for input data and either Output or
M0 files for output data. However, it is more appropriate to use Input
and Output files for critical I/O data transfer and M1 and M0 for
non-critical I/O data transfer.
Input and Output files contain 31 words each. These files are
appropriate for discrete data. If you have more than 31 words to
transfer, you have to map the remaining connections in M1 and M0
ControlNet data areas.
For input data, you can map your connections anywhere in Input and
M1 ControlNet data areas. It is not possible to overlap the mapping of
two independent input connections.
For output data, you can map your connections anywhere in Output
and M1 ControlNet data areas (refer to chapter 2 for exact memory
mapping.) The overlapping of two output connections is authorized.
You access ControlNet data located in M1 and M0 files using the COP
(copy) instruction in your ladder program. Since the maximum data
length you can transfer with the COP instruction is 128 words, you
need two instructions to copy the whole ControlNet area and control
and status word in processor memory. If you have less than 128
words of data mapped in an M file, we recommend that you pack
them together so that you can use a single copy instruction.
When you are building your mapping, we recommend that you save
free space between device connections if the size of these
connections may increase in the future.
Troubleshooting
What This Chapter Contains The following table describes what this chapter contains and its
location.
Troubleshooting with the The 1747-SCNR has indicators on the front plate, as shown below.
Status Indicators and
Status Display
OK indicator
ControlNet
Status Indicators
30750-M
Apply Chassis Power When you apply chassis power, the module address and status display
cycles through the following mnemonics:
Alphanumeric Display The four character alphanumeric display provides you with additional
visual information about the current operational status of the module.
The tables in the next section describes problems that may occur
while using your 1747-SCNR, the probable causes, and the
recommended action.
OK Indicator and Display The OK indicator is handled consistently with the ControlNet
specifications for the Identity object.
Mnemonics
Sequence OK Alpanumeric Module Status Description Probable Cause Recommended Action
Indicator Display Word (M1 file)
Startup Alternating POST N/A The 1747-SCNR module Power was applied to No action required.
red/green is running Power On Self the module.
Test.
REV# N/A 1747-SCNR firmware Power was applied to No action required.
S/R revision: S=series, the module.
QXXX R=revision, XXX=build
number. This is a
temporary display after
start up.
Run time Green A#XX N/A ControlNet node None No action required.
address
I/O 0x26 All configured None No action required.
connections are
established.
IDLE N/A The scanner is in idle The SLC processor in If you want to put the
mode. slot 0 is in program scanner into run mode,
mode or the Scanner put the SLC processor in
Mode Command bit of slot 0 into run mode and
the Module Command set the Scanner Mode
word is clear (O:e.0/ Command bit of the
10 where e is the Module Command word
scanner slot number). (O:e.0/10) using an
unconditional OTE
instruction.
RUN N/A The scanner is in run The SLC processor in If you want to put the
mode. slot 0 is in run mode scanner into program
and the Scanner mode, either put the SLC
Mode Command bit of processor in slot 0 into
the Module Command program mode or clear
word is set (O:e.0/10). the Scanner Mode
Command bit of the
Module Command word
(O:e.0/10).
EDIT N/A The scanlist in the Edits have been Finish modifying the
1747-SCNR is being enabled with scanlist with RSNetWorx
modified. RSNetWorx for for ControlNet and then
ControlNet. accept edits.
Cancel edits with
Note: Previously RSNetWorx for
configured ControlNet.
connections will be
reestablished if lost.
Newly configured or
changed connections
will not be
established until edits
are accepted.
The following table describes how the status indicator is behaving, the
cause of the behavior and the action you should take.
What This Appendix Contains This appendix describes how a PLC-5 reads or writes data in the
1747-SCNR module Local Database using the message (MSG)
instruction.
What We Assume We assume that you know how to use the PLC-5 Message ladder
instruction.
Read and Write Access To The Local Database is used for direct read or write access from
the network. A remote PLC-5 can access this database with MSG
1747-SCNR Local Database instruction as described below.
Using PLC-5 MSG Instruction
The PLC-5 can read or write data in the 1747-SCNR Local
Database with the Message instruction. This instruction creates
unscheduled message connections that are initiated by the PLC-5
processor and sent to the 1747-SCNR processor.
What’s happening
3. The PLC-5 is put into RUN mode. Then the PLC-5 opens an
unscheduled connection to the 1747-SCNR and messages are
exchanged.
5. Elements from the PLC-5 N7 file are available in the SLC 500
N11 file, starting at address N11:10.
1
PLC-5 ladder program
MSG
Read/Write Message
Control MG9:1
Setup Screen
2
RSLogix 5 window
ControlNet
Response packet
4
SLC 500 ladder program
COP
Copy File
Source #M0:1.700
Dest #N11.0
Length 20
What This Appendix Contains This appendix provides a description of how a remote device
can read or write the Local Database and ControlNet data areas
of the 1747-SCNR by using Get Member and Set Member
services. These data files are located in Input, Output, M0 and
M1 memory files.
What We Assume We assume that you are familiar with Object modeling and CIP
protocol as described in the ControlNet Specification available
from ControlNet International. You can contact ControlNet
International at its website www.controlnet.org.
Read and Write Access to The 1747-SCNR supports the following aspects of Assembly
Object Services:
1747-SCNR Data Files Using
Assembly Object Services • The 1747-SCNR assembly object supports Get Member and
Set Member services. The IOI of these requests must
contain four logical segments: Class number, instance
number, attribute number and member number.
• The member number is interpreted as the one-based
word offset of the data transfer.
• The number of members (first word of the request field) is
interpreted as size in words of the data transfer.
1747-SCNR Memory Layout The following illustration is an example of 1747-SCNR memory layout.
I:31 32 32
O:31
one-based
word offsets
M1 file M0 file
M1:0 1 1 MO:0
M1:1 2 2 MO:1
M1:2 3 3 MO:2
M1:3 4 4 MO:3
M1:4 5 5 MO:4
ControlNet ControlNet
input data output data
M1:254 255 255 MO:254
M1:255 256 256 MO:255
1001 M0:1000
CIP
messaging
1651 M0:1650
41540
Notes
What This Appendix Contains This appendix contains an example of how you can manage the
CIP Client area to issue a CIP client request to a remote node on
the ControlNet network.
• ladder programming
• object modeling as described in ControlNet specifications.
You can contact ControlNet International at its website
www.controlnet.org.
CIP Client Area The 1747-SCNR M0 file contains a CIP client area that can be
used to allow limited unconnected data exchange with a remote
node on the local ControlNet link. These messages are
initiated by the SLC processor.
Send a Get Attribute All In this example, a 1747-SCNR module with MAC ID 11 is located in
slot 1 of the SLC rack. It sends a Get Attribute All request to the
Request to Node 14 Identity Identity object of a remote 1794-ACNR15 Flex I/O device at MAC ID
Object 14 on the ControlNet network. This request is triggered by the ladder
program using the CIP Client feature provided by the 1747-SCNR
module.
What’s happening
2. The message and its data are prepared in the SLC N7 file
to be copied in M0 using a single COP (copy) instruction.
To send the message, first clear the CIP message control
image area in the SLC 500 N7 data file. No command data
is needed for a Get Attribute Single request. Initialize the
local CIP control words and data size. Set the EN bit and
then copy the control data.
Detail:
Source 0
Dest #M0:1.1009
Be sure the EN bit is set
N7:0
L
15
Copy the control data with EN bit set!
COP
Source #N7:0
Dest #M0:1.1000
Length 10
Detail:
N7:0 = 0xA000:Control word with bits EN and DN set - Response
received
N7:23 = 0x18:Response length - 24 words
N10:Response data
RSLogix 500 window
Detail:
N10:0 to N10:23:Response data
Important: The data format on the wire is Little Endian. RSLogix 500
displays words so byte order is inverted on the screen.
Send a Set Attribute This process is illustrated in the following example. The steps in the
What’s Happening box correspond to the steps in the illustrations
Single Request following the What’s Happening box.
What’s happening
See the following list for assembly object instance numbers supported by the
Get and Set Attribute Single services on Data attribute.
Detail:
If the bit Done is set without timeout or error ... 4 The message is completed
N7:0 N7:0 N7:0 B3:0
U
0
13 8 12 41559
RSLogix 500
The 1747-SCNR at MAC ID 11 wrote 32 words into the input data file
of 1747-SCNR at MAC ID 8.
Send a Set This process is illustrated in the following example. The steps in the
What’s Happening box correspond to the steps in the illustrations
Member Request following the What’s Happening box.
What’s happening
See the following list for assembly object instance numbers supported by the
Get and Set Attribute Single services on Data attribute.
RSLogix 500
Detail:
If the bit Done is set without timeout or error ... 4 The message is completed
N7:0 N7:0 N7:0 B3:0
U
0
13 8 12 41559
RSLogix 500
What This Appendix Contains This appendix contains an example of how you can use the
ladder program to reset a 1747-SCNR module located in the SLC
500 rack.
What We Assume We assume that you are familiar with ladder programming.
What’s happening
2
If the module in slot 3 is not enabled, no access to Use a timer to re-enable the module after a 4
the module is allowed seconds delay.
S2:11 TON
Timer On Delay
Timer T4:0 EN
3 Timer Base 1.0
Preset 4
Accum 0 DN
Example: If the module in slot 3 is faulted, reset it. Set the Reset bit in Output Command Word
1 XOR
I:3 Your Precondition2 Bitwise Exclusive OR
Source A O:3.0
Source B 256
0
Length O:3.0
41558
Application Examples
What This Appendix Contains This appendix provides examples of five applications and their
use with the 1747-SCNR controlling discrete and analog data on
ControlNet via a 1747-ACNR15 and a 1794-ACNR15 ControlNet
adapter. Also included in this appendix is an example of how to
create peer-to-peer scheduled connections between 1747-SCNR
ControlNet scanners.
What We Assume We assume that you are familiar with setting up a network and
working with RSLogix500, RSLinx, and RSNetWorx for
ControlNet software and the 1784-KTCX15 interface card.
Example 1: Configure the The following example discusses how to configure the
1747-SCNR scanner with the 1746-IV16 input module.
1747-SCNR with the 1746-IV16
Input Module
Hardware Setup
4. Click OK.
1. Click with the right mouse button on the 1747-SCNR and choose
Scanlist Configuration.
2. Click YES.
Words I:3.0 and O:3.0 are reserved. Note that the input data
from the 1746-IA16 will be found in the processor’s input image
word I:3.3, the output data written to the 1746-OB16 module
will be from the processor’s output image word O:3.2, and the
input data from the 1746-IV16 will be in the processor’s input
image word I:3.5.
Important: There is a two word offset for input data for rack
connections. Therefore, for this example, the input
data for the input module in slot 1 of the remote
1747-ACNR15 chassis will be written to I:3.3 in the SLC
processor’s input image and the input module in slot 3
will be written to I:3.5.
The starting input address configured in RSNetWorx
for ControlNet for this rack connection was I:3.1, but
I:3.1 and I:3.2 are used for status information. Hence
the Input Size of 5 is shown in the “Connection
Properties” screen.
The actual input data begins after the two words of
status information. I:3.4 is not used in this example
because an output module resides in slot 2. Also, note
that there is no offset for the outputs in a rack
connection. O:3.2 is the output image word written to
the output module located in slot 2 of the
1747-ACNR15 chassis. O:3.1 is also not used in this
example because an input card is in slot 1.
You must also enter a value in the Status Address field. This field
supplies Connection Status information to the processor. The
starting bit address for this field must be an even number,
because two consecutive bits are used as status for each
connection. The even numbered bit indicates whether the
connection is open or closed and the odd numbered bit
indicates whether the connection is in normal operation or Idle
mode. In this example, the address chosen is the first available
bit pair, M1:3.600/00.
• Hold Last State - all outputs will remain in their last state if one
of the two conditions occur
• Safe State - allows you to choose exactly the state of each output
b. Click APPLY.
c. Click OK.
1. Click on the Save icon or click on the File menu and then Save.
2. Click OK.
3. Click YES.
The final step is to write a ladder program for the SLC processor,
including configuring the 1747-SCNR for slot 3 of the processor’s
chassis.
Example 2: Configure the The following example discusses how to configure the 1747-SCNR
scanner with the 1746-NIO4V combination analog input/output
1747-SCNR with the module.
1746-NIO4V Analog Input/
Output Module
Hardware Setup
You see the “Browse for Network” window. In this window, you
must select the communication path previously configured in
RSLinx for communicating with your ControlNet network. For
this example, a 1784-KTCX15 ControlNet PC card is used.
4. Click OK.
1. Click with the right mouse button on the 1747-SCNR and choose
Scanlist Configuration.
2. Click YES.
Words I:3.0 and O:3.0 are reserved. Note that the input data
from the 1746-IA16 will be found in the processor’s input image
word I:3.3, the output data written to the 1746-OB16 module
will be from the processor’s output image word O:3.2.
Important: There is a two word offset for input data for rack
connections. Therefore, for this example, the input
data for the input module in slot 1 of the remote
1747-ACNR15 chassis will be written to I:3.3 in the SLC
processor’s input image.
The starting input address configured in RSNetWorx
for ControlNet for this rack connection was I:3.1, but
I:3.1 and I:3.2 are used for status information.
Therefore, the actual input data begins after the two
words of status information. I:3.4 is not used in this
example because an output module resides in slot 2.
Also, note that there is no offset for the outputs in a
rack connection. O:3.2 is the output image word
written to the output module located in slot 2 or the
1747-ACNR15 chassis. In addition, no offset applies to
module connections at all. For this example, the input
and output data for the 1746-NIO4V is located in
M1:3.3, M1:3.4, M0:3.3, and MO:3.4. M1:3.3 and
MO:3.3 are the starting addresses entered in
RSNetWorx for ControlNet for the module connection.
You must also enter a value in the Status Address field. This field
supplies Connection Status information to the processor for each
unique connection. The bit address for this field must be an
even number, because two consecutive bits are used as status
for each connection. The even numbered bit indicates whether
the connection is open or closed and the odd numbered bit
indicates whether the connection is in normal operation or Idle
mode. In this example, the starting address chosen is the first
available bit, M1:3.600/00.
• Hold Last State - all outputs will remain in their last state if one
of the two conditions occur
• Safe State - allows you to choose the state of each output
b. Click APPLY.
c. Click OK to return to the “Scanlist Configuration” screen.
4. Click APPLY.
5. Click OK.
1. Click on the Save icon or click the File menu and choose Save.
2. Click OK.
3. Click YES.
The final step is to write a ladder program for the SLC processor,
including configuring the 1747-SCNR for slot 3 of the processor’s
chassis.
Example 3: Configure the The following example discusses how to configure the 1747-SCNR
scanner with the 1746-NI8 analog input module.
1747-SCNR with the
1746-NI8 Analog
Input Module Hardware Setup
You see the “Browse for Network” window. In this window, you
must select the communication path previously configured in
RSLinx for communicating with your ControlNet network. For
this example, a 1784-KTCX15 ControlNet PC card is used.
4. Click OK.
1. Click with the right mouse button on the 1747-SCNR and choose
Scanlist Configuration.
2. Click YES.
Words I:3.0 and O:3.0 are reserved. Note that the input data
from the 1746-IA16 will be found in the processor’s input image
word I:3.3. The output data written to the 1746-OB16 module
will be from the processor’s output image word O:3.2.
Important: There is a two word offset for input data for rack
connections. Therefore, for this example, the input
data for the input module in slot 1 of the remote
1747-ACNR15 chassis will be written to I:3.3 in the SLC
processor’s input image.
The starting input address configured in RSNetWorx
for ControlNet for this rack connection was I:3.1, but
I:3.1 and I:3.2 are used for status information.
Therefore, the actual input data begins after the two
words of status information. I:3.4 and I:3.5 are not
used in this example because an output module
resides in slot 2 and an analog module resides in slot
3.
Also, note that there is no offset for the outputs in a
rack connection. O:3.2 is the output image word
written to the output module located in slot 2 of the
1747-ACNR15 chassis. In addition, no offset applies to
module connections at all.
You must also enter a value in the Status Address field. This field
supplies Connection Status information to the processor for each
unique connection. The bit address for this field must be an
even number, because two consecutive bits are used as status
for each connection. The even numbered bit indicates whether
the connection is open or closed and the odd numbered bit
indicates whether the connection is in normal operation or Idle
mode. In this example, the starting address chosen is the first
available bit pair, M1:3.600/00.
• Hold Last State - all outputs will remain in their last state if one
of the two conditions occur
• Safe State - allows you to choose exactly the state of each output
2. Click APPLY.
1. Click with the right mouse button on the 1746-NI8 module in the
“Scanlist Configuration” window.
4. Click APPLY.
5. Click OK.
1. Click on the Save icon or choose the File menu and then Save.
2. Click OK.
The final step is to write a ladder program for the SLC processor,
including configuring the 1747-SCNR for slot 3 of the processor’s
chassis.
Example 4: Configure the The following example discusses how to configure the 1747-SCNR
scanner with the 1746-BAS Series B interface module.
1747-SCNR with the
1746-BAS Series B
Interface Module Hardware Setup
You see the “Browse for Network” window. In this window, you
must select the communication path previously configured in
RSLinx for communicating with your ControlNet network. For
this example, a 1784-KTCX15 ControlNet PC card is used.
4. Click OK.
To do this:
1. Click with the right mouse button on the 1747-SCNR and choose
Scanlist Configuration.
2. Click YES.
Words I:3.0 and O:3.0 are reserved. Note that the input data
from the 1746-IA16 will be found in the processor’s input image
word I:3.3, the output data written to the 1746-OB16 module
will be from the processor’s output image word O:3.2.
Important: There is a two word offset for input data for rack
connections. Therefore, for this example, the input
data for the input module in slot 1 of the remote
1747-ACNR15 chassis will be written to I:3.3 in the SLC
processor’s input image.
The starting input address configured in RSNetWorx
for ControlNet for this rack connection was I:3.1, but
I:3.1 and I:3.2 are used for status information.
Therefore, the actual input data begins after the two
words of status information. I:3.4 is not used in this
example because an output module resides in slot 2.
Also, note that there is no offset for the outputs in a
rack connection. O:3.2 is the output image word
written to the output module located in slot 2 of the
1747-ACNR15 chassis. In addition, no offset applies to
module connections at all.
You must also enter a value in the Status Address field. This field
supplies Connection Status information to the processor for each
unique connection. The bit addresses for this field must be even
numbers, because two consecutive bits are used as status for
each connection. The even numbered bit indicates whether the
connection is open or closed and the odd numbered bit
indicates whether the connection is in normal operation or Idle
mode. In this example, the starting address chosen is the first
available bit pair, M1:3.600/00.
• Hold Last State - all outputs will remain in their last state if one
of the two conditions occur
• Safe State - allows you to choose exactly the state of each output
If Safe State is selected, you must click on the Configuration Settings tab
and enter your Safe State data for each output word in decimal. Then,
whenever the SLC processor is placed into the Program Mode or if
communications is lost to the 1747-ACNR15 adapter, the outputs will
revert to the Safe State data you entered for each output word.
2. Click APPLY.
For this example, we must choose M-file addresses for this type
of connection. The series B module communicates via eight I/O
words and 64 M1 and 64 M0 file words. These Basic module
M-file words are independent of the 72 M-file words transferred
to and from the Basic module. These 72 M0 and 72 M1 file
words reside in the 1747-SCNR and are used to store the data
sent to the 1747-ACNR15 from the SLC-5/04 processor and to
store the data received from the 1747-ACNR15 for the SLC-5/04
processor.
By default, the Chunk 1 Output File is the output image file for
the Basic module and the Chunk 1 Input File is the input image
file for the Basic module. We must then assign the Chunk 2
Output File as the Basic module’s M0 file and the Chunk 2 Input
File as the Basic module’s M1 file. The size for each of these files
is 64 words. The total number of words transferred bi-directional
between the SLC processor and the Basic module will be 72.
The first eight will be the Basic module’s I/O image and the last
64 words will be the Basic module’s M-file words. This order is
determined by the Chunk numbers. This “Advanced” screen
should then look as follows:
5. Click APPLY.
6. Click OK.
1. Click on the Save icon or click on the File menu and then Save.
2. Click OK.
The final step is to write a ladder program for the SLC processor and a
Basic program for the Basic module. After downloading the program
to your processor and to your basic module, place the processor into
the Run mode and run your Basic program as well. Your programs
should now be able to read data from the 1746-IA16 in word I:3.3 and
write to the 1746-OB16 in word O:3.2.
The handshaking required between the SLC processor and the Basic
module to transfer data, is shown in the ladder logic program to
follow. Refer to the 1746-BAS Module Floating Point Conversion
Document Update, publication 1746-6.3 for a complete description of
CALL 22 and 23, as well as the required handshaking. The only
difference in the handshake logic when using these Basic module
CALLs is that the I/O image words used for the handshaking are
stored in the 1747-SCNR’s M-files, so they appear as M-file addresses
in the ladder logic instead of I/O addresses.
A sample Basic module program using CALL 23 for PT1 and CALL 22
for PRT2 follows, along with the necessary ladder logic to handshake
with the module for these CALLs. When the SLC processor is placed
into the Run mode, it will in turn place the 1747-SCNR into the Run
mode as well by virtue of the unconditional OTE rung described
above. When the Basic module is also placed into the Run mode, any
data placed into the SLC processor’s data table beginning with N12:0
will be sent to the 1747-SCNR, which will send it to the 1747-ACNR15
via ControlNet and then to the Basic module. The Basic module will
send the data out PRT1 and this data will be looped right back in the
Basic module’s PRT2. The module will send the data to the
1747-ACNR15, which will send it to the 1747-SCNR via ControlNet.
The SLC processor will then retrieve this data and place it into its data
table beginning at N13:0.
The next page contains ladder logic to handshake with the module for
CALLs 23 and 22.
This rung simply gives the following rung a false-to-true transition every 1 second.
T4:1 TON
0000 Timer On Delay EN
Timer T4:1
DN Timer Base 0.01 DN
Preset 100<
Accum 86<
This rung copies up to 64 words beginning with N12:0 to the SCNR for transfer to the Basic module on ControlNet.
T4:1
COP
0001 Copy File
Source #N12.0
DN
Dest #M0:3.11
Length 64
CALL 23 output
handshake bit
M0:3.3
L
6
This rung completes the handshaking between the SLC processor and ultimately the Basic module to accomplish the CALL 23.
CALL 23 input CALL 23 output
handshake bit handshake bit
M1:3.3 M0:3.3
0002 U
6 6
This rung copies up to 64 words of data received from the Basic module, when the handshake bit M1:3.3/9 becomes set. When data is
received by the Basic module in PRT2, the CALL 22 transfers it to the SCNR and ultimately to the SLC Processor.
CALL 23 input
handshake bit
M1:3.3 COP
0003 Copy File
Source #M1:3.11
9 Dest #N13.0
Length 64
CALL 23 output
handshake bit
M0:3.3
9
1747-SCNR RUN/IDLE
Bit
O:3
0004
10
1747-SCNR
0005 END
42272
Example 5: Configure the The following example discusses how to configure the 1747-SCNR
scanner with the 1794-IE4XOE2 analog combo module.
1747-SCNR with the
1794-IE4XOE2 Analog
Combo Module Hardware Setup
You see the “Browse for Network” window. In this window, you
must select the communication path previously configured in
RSLinx for communicating with your ControlNet network. For
this example, a 1784-KTCX15 ControlNet PC card is used.
4. Click OK.
1. Click with the right mouse button on the 1747-SCNR and choose
Scanlist Configuration.
2. Click YES.
Words I:3.0 and O:3.0 are reserved. Note that the input data
from the 1794-IB16 will be found in the processor’s input image
word I:3.3, the output data written to the 1794-OB16 module
will be from the processor’s output image word O:3.2.
Important: There is a two word offset for input data for rack
connections and module connections when working
with a 1794 Flex ControlNet adapter. Therefore, for this
example, the input data for the input module in slot 0
of the remote 1794-ACNR15 system will be written to
I:3.3 in the SLC processor’s input image.
The starting input address configured in RSNetWorx
for ControlNet for this rack connection was I:3.1, but
I:3.1 and I:3.2 are used for status information.
Therefore, the actual input data begins after the two
words of status information. I:3.4 is not used in this
example because an output module resides in slot 2.
Also, note that there is no offset for the outputs in a
rack connection. O:3.2 is the output image word
written to the output module located in slot 1 of the
1794-ACNR15 chassis. In addition, this same offset
scheme applies to module connections for Flex I/O on
ControlNet. For this example, the input and output
data for the 1794-IE4XOE2 is located in M1:3.5 through
M1:3.8 and M0:3.3 and M0:3.4.
You must also enter a value in the Status Address field. This field
supplies Connection Status information to the processor for each
unique connection. The bit addresses for this field must be an
even number, because two consecutive bits are used as status
for each connection. The even numbered bit indicates whether
the connection is open or closed and the odd numbered bit
indicates whether the connection is in normal operation or Idle
mode. In this example, the starting address chosen is the first
available bit pair, M1:3.600/00.
2. Click APPLY.
4. Click APPLY.
1. Click on the Save icon or click on the File menu and then Save.
2. Click OK.
The final step is to write a ladder program for the SLC processor,
including the 1747-SCNR for slot 3 of the processor’s chassis. After
downloading the program to your processor, place the processor into
the Run mode. Your programs should now be able to read data from
the 1794-IB16 in word I:3.3 and write to the 1794-OB16 in word O:3.2.
The analog input data will reside in words M1:3.5 through M1:3.8,
while the analog output data must be placed in words M0:3.3 and
M0:3.4. M1:3.9 is the seventh word received from the analog module.
It contains status bits for the analog I/O channels. Please refer to your
1794-IE4XOE2 analog combo module documentation for additional
details.
You see the “Browse for Network” window. In this window, you
must select the communication path previously configured in
RSLinx for communicating with your ControlNet network. For
this example, a 1784-KTCX15 ControlNet PC card is used.
4. Click OK.
3. Click YES.
6. Click APPLY.
7. Click OK.
You must also enter a value in the Status Address field. This field
supplies Connection Status information to the processor. The
starting bit addresses for this field must be an even number,
because two consecutive bits are used as status for each
connection. The even numbered bit indicates whether the
connection is open or closed and the odd numbered bit
indicates whether the connection is in normal operation or Idle
mode. In this example, the address chosen for the first
connection is the first available bit pair, M1:3.600/00. The next
connection automatically created by RSNetWorx for ControlNet
will use M1:3.600/02.
You must now save your Scanlist for node 1 to the network
keeper.
8. Click on the Save icon or click on the File menu and then Save.
9. Click OK.
You must now save your Scanlist for node 2 to the network
keeper.
11. Click on the Save icon or click on the File menu and then Save.
A D
alphanumeric display discrete output file 2-8
troubleshooting 4-2 display mnemonics
application examples troublshooting 4-3
configure the 1747-SCNR with the 1746-BAS interface
module E-28 E
configure the 1747-SCNR with the 1746-IV16 input examples
module E-1 application E-1
configure the 1747-SCNR with the 1746-N18 analog reset bit management D-1
input module E-19
configure the 1747-SCNR with the 1746-NIO4V input/
output module E-9 G
configure the 1747-SCNR with the 1794-IE4XOE2 I/O get attribute
analog combo module E-42 send an all request to node 14 identity object C-3
creating peer-to-peer scheduled connections between
1747-SCNR ControlNet scanners E-51 I
apply chassis power
I/O scheduled data transfer 2-9
troubleshooting 4-2
installing
connecting to network 1-5
C inserting into SLC chassis 1-3
CIP client module features 1-1
management C-1 selecting node address 1-3
send a get attribute all request to node 14 identity SLC 500 I/O configuration 1-8
object C-3
send a set attribute single request C-7 L
SLC 500 ladder program example C-9, C-13
link layer services 2-4
SLC 500 processor target data file (hex) C-10,
local database
C-14
access using PLC-5 MSG instructions A-1
SLC 500 ladder program C-5
read and write access to 1747-SCNR A-1
SLC 500 processor data files (hex) C-6
ControlNet data files access using CIP messaging B-1
request transfer 2-10
read and write access to 1747-SCNR B-1
communicating with your devices 2-9
CIP client request transfer 2-10
M S
M0 file mapping 2-9 scheduled data transfer operations on a ControlNet
M1 file mapping 2-6 network 2-3
mapping set attribute
understanding 2-5 send a single request C-7
MSG instructions SLC 500 ladder program C-5
read and write access to 1747-SCNR local database A-1 SLC 500 processor data files (hex) C-6
status indicators and status display
troubleshooting 4-1
O
OK indicator
troubleshooting 4-3 T
troubleshooting 4-1
alphanumeric display 4-2
P
apply chassis power 4-2
purpose of 1747-SCNR scanner 2-1 OK indicator and display mnemonics 4-3
with status indicators and status display 4-1
R
reset bit management example D-1 U
unscheduled data transfer operations on a ControlNet
network 2-4
Cat. No. 1747-SCNR Pub. No. 1747-RM623B-EN-P Pub. Date November 2000 Part No. 957445.90
Clarity
What is unclear?
Sequence
What is not in the right order?
Other Comments
Use back for more comments.
Return to: Marketing Communications, Allen-Bradley., 1 Allen-Bradley Drive, Mayfield Hts., OH 44124-6118Phone:(440) 646-3176
FAX:(440) 646-4320
Other Comments
PLEASE REMOVE
PLEASE FOLD HERE
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
1 ALLEN-BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
Publication 1747-RM623B-EN-P - November 2000 65 PN 957445.90
© 2000 Rockwell International Corporation. Printed in the U.S.A.