City of San Diego - Retaining Wall Detail
City of San Diego - Retaining Wall Detail
INFORMATION
Retaining Wall/Level Backfill BULLETIN
DS-5221 (08-09)
Page of 6 City of San Diego • Information Bulletin 221 August 2009
construction shall conform to ASTM C 270 and VII. SOIL DESIGN CRITERIA
shall conform to the proportion specifications This information bulletin is to be used only when
of Table 2103.8(1) or the property specifica- the soils to be retained are not expansive (i.e.
tions of Table 2103.8(2) of the CBC. sandy soils). The design of this information bul-
letin is based on the following criteria:
C. GROUT 1. Soil type: granular, non-cohesive soil backfill.
Grout must have a compressive strength equal 2. Active earth pressure with an equivalent fluid
to 2,000 psi minimum. Grout shall conform to weight of 30 pounds per cubic foot.
Table 2103.12 or to ASTM C 476. When grout 3. Passive earth pressure with an equivalent
conforms to ASTM C 476, the grout shall be fluid weight of 150 pounds per cubic.
specified by proportion requirements or prop- 4. Allowable bearing value of 1,500 psf.
erty requirements (CBC 2103.12) 5. Soil friction factor 0.25.
FOOTNOTES:
1
Tables A makes the following assumptions:
f ’y= 600000psi
Fs= 24000
Solid grouting
Using half f ’m stress
2
Walls not shown in Table A must be designed specifically for the actual conditions.
3
All construction must comply with the specifications shown in this information bulletin.
4
When Wall Type III is required, the first 32 inches of block must be 12-inch wide masonry units.
I=6” Block
II=8” Block
III=12” Block
5
Footing depth shall be 24 inches below finish grade and 12 inches of compacted soil is required on top of foot-
ing to stabilize the wall.
6
For the purpose of the structural design, wall height shall be measured from the top of the footing to the top
of the wall.
7
For zoning requirements fence height shall be measured from finish grade.
Page of 6 City of San Diego • Information Bulletin 221 August 2009