4TTA3060D-SUB-106.

01

TAG: _________________________________ S U BM IT TA L
5 Ton Split System
NOTE: All dimensions are in mm/inches.
Cooling — 3 Phase
4TTA3060D
Product Specifications
OUTDOOR UNIT 12 4TTA3060D3000A
POWER CONNS. — V/PH/HZ 3 208/230/3/60
MIN. BRCH. CIR. AMPACITY 21
BR. CIR. PROT. RTG. - MAX. (AMPS) 35
COMPRESSOR CLIMATUFF® - SCROLL
NO. USED - NO. SPEEDS 1-1
VOLTS/PH/HZ 200/230/3/60
R.L. AMPS 7 - L.R. AMPS 15.6 - 110
FACTORY INSTALLED
START COMPONENTS 8 NO
INSULATION/SOUND BLANKET NO
COMPRESSOR HEAT YES
OUTDOOR FAN PROPELLER
DIA. (IN.) - NO. USED 27.5 - 1
TYPE DRIVE - NO. SPEEDS DIRECT - 1
CFM @ 0.0 IN. W.G. 4 4342
NO. MOTORS - HP 1 - 1/5
MOTOR SPEED R.P.M. 835
VOLTS/PH/HZ 200/230/1/60
F.L. AMPS 0.93
OUTDOOR COIL — TYPE SPINE FIN™
ROWS - F.P.I. 1 - 24
FACE AREA (SQ. FT.) 24.93
TUBE SIZE (IN.) 3/8
REFRIGERANT
LBS. — R-410A (O.D. UNIT) 5 8 LBS., 0 OZ.
FACTORY SUPPLIED YES
LINE SIZE - IN. O.D. GAS 6 7/8
LINE SIZE - IN. O.D. LIQ. 6 3/8
CHARGING SPECIFICATION
SUBCOOLING 10°F
DIMENSIONS H X W X D
CRATED (IN.) 42.4 x 35.1 x 38.7
WEIGHT
SHIPPING (LBS.) 261
NET (LBS.) 226
1 Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program, which
is based on AHRI standard 210/240.
2 Rated in accordance with AHRI standard 270.
3 Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses.
4 Standard Air — Dry Coil — Outdoor
5 This value approximate. For more precise value see unit nameplate.
6 Max. linear length 60 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft.
For greater length consult refrigerant piping software Pub. No. 32-3312-0*
From Dwg. D152898 (* denotes latest revision).
7 This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to
compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selec-
tion current.
8 No means no start components. Yes means quick start kit components. PTC means positive temperature
coefficient starter.

MODELS BASE FIG. A B C D E F G H J K


4TTA3060D 4 1 943 (37-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

A-WEIGHTED SOUND POWER LOVEL [dB(A)]


MODELS SOUND POWER A-WEIGHTED FULL OCTOAVE SOUND POWER LEVEL Db - [dB(A)]
LEVEL [dB(A)]
63 125 250 500 1000 2000 4000 8000
4TTA3060D 75 80 73 70 72 71 65 63 59
Note: Rated in accordance with AHRI Standard 270-2008

© 2010 Trane All Rights Reserved


Mechanical
­Specification Options

General Condenser Coil


The 4TTA3 - D model is fully charged The outdoor coil provides low airflow
from the factory for up to 15 feet of resistance and efficient heat transfer.
piping. This unit is designed to oper- The coil is protected on all four sides by
ate at outdoor ambient temperatures louvered panels.
as high as 115°F. Cooling capacities Low Ambient Cooling
are matched with a wide selection of As manufactured, this unit has a cool-
air handlers and furnace coils that are ing capability to 55°F. The addition of
AHRI certified. The unit is certified to UL an evaporator defrost control permits
1995. Exterior is designed for outdoor operation to 40° F. The addition of an
application. evaporator defrost control with TXV per-
Casing mits low ambient cooling to 30° F.
Unit casing is constructed of heavy Accessories
gauge, G90 galvanized steel and Thermostats — Cooling only and heat/
painted with a weather-resistant powder cooling (manual and automatic change-
paint on all louvers, panels, prepaint on over). Sub-base to match thermostat
all other panels. Corrosion and weather- and locking thermostat cover.
proof CMBP-G30 DuraTuff™ base.
Evaporator Defrost Control — See
Refrigerant Controls Low Ambient Cooling.
Refrigeration system controls include
condenser fan, compressor contactor
and high pressure switch. High and low
pressure controls are inherent to the
compressor. A factory installed liquid line
drier is standard.
Compressor
The Climatuff® compressor features
internal over temperature and pressure
protection and total dipped hermetic
motor. Other features include: roto lock
suction and discharge refrigerant con-
nections, centrifugal oil pump and low
vibration and noise.

Literature Order Number SS-PRC007-EN 11/10


File Number —
Supersedes SS-PRC007-EN  2/02
Stocking Location PI Louisville & Webb/Mason Houston

Trane
6200 Troup Highway
Trane has a policy of continuous product and product data improvement and it reserves the right to change
Tyler, TX 75707
design and specifications without notice.
www.trane.com