Design Criterion For Civil, Structural & Architechtural Works - Pe-Dc-435-600-C001-R1
Design Criterion For Civil, Structural & Architechtural Works - Pe-Dc-435-600-C001-R1
Rev Section
2X660 MW I
Udangudi TPP Stage-I DESIGN CRITERION FOR PE-DC-435-600-C001 1 01/10/2018
CIVIL, STRUCTURAL &
ARCHITECTURAL WORKS
UDANGUDI,TAMIL NADU Page 1 of 63
1
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 2 of 64
Contents
1.1 SCOPE ........................................................................................................................... 6
1.2 SITE INFORMATION .......................................................................................................... 8
1.2.1 Site location .................................................................................................................... 8
1.2.2 Grade level ...................................................................................................................... 8
1.2.3 Soil condition and Ground Water Level & HFL .......................................................... 8
1.2.4 Seismic location ............................................................................................................. 8
1.2.5 Wind pressure ................................................................................................................ 9
1.2.6 Reference Level .............................................................................................................. 9
1 REFERENCES, CODES AND STANDARDS ........................................................................ 9
2.1 BIS CODES AND REFERENCES ...................................................................................... 9
2.1.1 EARTHWORK.................................................................................................................. 9
2.1.2 CONCRETE ................................................................................................................... 10
2.1.3 FOUNDATIONS ............................................................................................................. 13
2.1.4 Precast Concrete Works ............................................................................................. 14
2.1.5 Loading.......................................................................................................................... 14
2.1.6 Masonry ......................................................................................................................... 14
2.1.7 Doors, Windows and Ventilators ................................................................................ 15
2.1.8 Roof and Flooring ........................................................................................................ 17
2.1.9 Waterproofing ............................................................................................................... 18
2.1.10 Floor Finishes and Allied Works ................................................................................ 18
2.1.11 Soil Engineering ........................................................................................................... 19
2.1.12 Water Supply, Drainage and Sewerage ..................................................................... 19
2.1.13 Paving and Road Works .............................................................................................. 22
2.1.14 Earthquake Resistant Design ..................................................................................... 22
2.1.15 Chimney ........................................................................................................................ 22
2.1.16 Structural Steelwork .................................................................................................... 23
2.1.17 Painting ......................................................................................................................... 26
2.1.18 Sheeting Works ............................................................................................................ 27
2.1.19 Acid and Alkali Resistant Lining ................................................................................ 28
2.1.20 Safety ............................................................................................................................. 28
2.1.21 Miscellaneous .............................................................................................................. 29
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 4 of 64
Rev -01
NOTE: The overall scope of this Design criterion includes all the items covered in this Design
criterion but is not limited to the same. In case of any mismatch with specification and for all
items required for the Civil/Structural & Architectural works, which are not included in this
Design criterion, Technical specifications and relevant IS codes shall guide the overall scope.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 6 of 64
The criteria furnished in this document shall govern the design of Civil, Structural and
Architectural works of buildings, structures and yard facilities related to the proposed project,
indicated in Section 1.1 only.
This document covers the general description of structural framing system, applicable design
codes and standards, specific design criteria, design loads and combinations, design
methodology and characteristics of construction materials to be adopted for the structures
indicated above.
1.1 SCOPE
The scope includes civil, structural and architectural works of the following
areas/structures/buildings.
Topographical Survey
Site development/clearance works
Site grading & leveling
Geo-technical Investigation
Fencing and Gates
Approach road to the main entry of the plant from State Highway
Plant road network including patrol roads, approach roads to all the buildings
/structures / services.
Watch Towers
ESP foundations
ESP Control Room
ID duct foundations
Boiler area Paving
Fan Foundations (ID, FD & PA)
Chimney
Compressor House including Compressor Foundations
DG Building including DG foundations
Condensate Storage Tank Foundation & Pump house
HFO & LDO Day Tank foundations & Dyke Area including tanker unloading ramp
HFO & LDO Pressurizing Pump House
Transformer yard civil works including Transformer oil test lab & Oil Filter Plant Shed.
CPU Regeneration Building & Neutralization Pit, CPU Service Vessel Area
Service Building
Administration Building
Fire Station
Dispensary
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 8 of 64
Parking
Time office & Security Office including Guard house, parking facilities
Security Office for Stores
Weigh Bridge & Control Room
Security Building for fencing in main Power Plant Area
2x660 MW coal based STPP at Udangudi plant site is about 12 KM from Tiruchendur railway
station in Thoothukudi District, Tamil Nadu, India. The proposed site is located about 60 KM
from Vaagaikulam Airport and about 650 KM south of Chennai city. The nearest sea port is
Tuticorin which is about 45 KM away from the proposed site. Next big cities to site:
Thoothukudi (approx.45 kms from site). Road access: East Coast Road–State high way (176)
Finished Graded Level (FGL) & Finished Floor level (F.F.L) for the plant shall be as follows
respectively:
Type of foundation, depth, safe bearing capacity etc., shall be as per the approved
Geotechnical report. HFL of the site is RL 2.45 m above MSL
The project site lies in zone II as defined in IS: 1893 (Part 1)-2002. All the structures shall be
designed complying with the requirements specified in IS: 1893 (Part-1) -2002 and (Part-4) -
2005.
Wind force on structures has been considered as per the provisions of IS: 875 (Part-3) -1987.
The basic wind speed of 39 m/sec at a height of 10m above the ground level and wind
assumed to blow in any direction and the most unfavorable condition shall be considered for
design.
In the Boiler, ESP and Chimney Area, paving top shall be at EL (-)0.20m and main road levels
in Boiler Area shall be EL (-)0.20 m.
Structural design shall be developed on the basis of the standard codes and documents listed
below.
All designs shall generally be prepared in accordance with Bureau of Indian Standards (BIS)
codes of practice unless specified elsewhere.
The analysis, design and construction for structural and civil works shall be in accordance
with the BIS codes/standards or equivalent International codes, applicable at the time of issue
of LOI.
All the Bureau of Indian Standards codes referred to shall be the latest revision (including all
amendments issued thereto) at the time of issue of LOI Where British / American / DIN or
other codes and standards are referred to in this document, equivalent Indian Standards will
be substituted if available.
2.1.1 EARTHWORK
2.1.2 CONCRETE
(b) IS-383 : Coarse and fine aggregate from natural sources for
Concrete
(c) IS-432 : Mild Steel and medium tensile steel bars and hard drawn
steel wire for concrete reinforcement
(j) IS-1786 : High strength deformed steel bars and wires for
concrete reinforcement (Corrosion resistant Steel/CRS)
(l) IS-2386 : Methods of test for aggregates for concrete (all parts).
(m) IS-2502 : Code of practice for bending and fixing of bars for
concrete reinforcement.
(s) IS-7861 : Code of practice for extreme weather concreting (all parts).
(ddd) SP-16 : Design codes for reinforced concrete to IS: 456 1978.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 13 of 64
2.1.3 FOUNDATIONS
(n) DIN:2096 : Helical compression spring out of round wire and rod:
Quality requirements for hot formed compression spring.
(b) IS:10297 : Code of practice for design and construction of floors and
roofs using precast reinforced Pre stressed concrete ribbed
or cored slab units.
(c) IS:10505 : Code of practice for construction of floors and roofs using
pre- cast reinforced concrete
2.1.5 Loading
(c) IS: 4091 : Code of practice for design and construction of foundation
for transmission line towers and poles.
(e) IS: 6922 : Criteria for safety and design of structure subjected to
underground blasting.
(f) IS: 1893 : Criteria for earthquake resistant design of structure (All
parts)
(g) IRC Code : Bridge Rules of Government of India, Ministry of Railways
(Railway Board)
2.1.6 Masonry
(h) IS-2185 : Concrete masonry units. (All parts - Hollow and Solid
concrete blocks).
(n) IS-4441 : Code of practice for use of Silicate type chemical resistant
mortars.
(e) IS-1081 : Code of practice for fixing and glazing of metal (steel and
aluminium) doors, windows and ventilators.
(g) IS-2835 : Transparent sheet glass for glazing and framing purposes.
(j) IS-2191 : Wooden flush door shutters (Cellular and hollow core type).
(t) IS-281 : Mild steel sliding door bolts for use with padlocks.
(ii) IS-7452 : Hot rolled steel sections for doors, windows and ventilators.
(b) IS-3201 : Criteria for the design and construction of precast concrete
trusses.
(c) IS-2210 : Criteria for Design of R.C. shell structures and folded plates.
(i) IS-1443 : Code of practice for laying and finishing of cement concrete
flooring tiles.
(j) IS-2114 : Code of practice for laying in situ terrazzo floor finish.
(k) IS-2571 : Code of practice for laying in situ cement concrete flooring.
(l) IS-5491 : Code of practice for laying in situ granolithic concrete floor
topping.
(m) IS-5766 : Code of practice for laying burnt clay brick flooring.
2.1.9 Waterproofing
(b) IS-3067 : Code of practice for general design, details and preparatory
work for damp proofing and water proofing of buildings.
(c) IS-3384 : Bitumen primer for use in water proofing and damp proofing.
(e) ASTM : Standard specification for high solid content cold liquid
C836-89a applied electrometric water proofing membrane for use with
separate wearing course.
(g) C898-89 : Liquid applied elastomeric water proofing membrane for use
with separate wearing course.
(e) C898-89 : Liquid applied elastomeric water proofing membrane for use
with separate wearing course.
(e) IS-774 : Flushing cisterns for water closets and urinals other than
plastic cisterns.
(g) IS-1172 : Code of basic requirements for water supply, drainage and
sanitation.
(h) IS-1626 : Asbestos cement building pipes, gutters and fittings (all
parts).
(l) IS-2470 : Code of practice for installation of septic tanks (all parts).
(q) IS-1536 : Centrifugally cast (spun) iron pressure pipes for water, gas
and sewage.
(r) IS-1537 : Vertically cast iron pressure pipe for water, gas and sewage.
(t) IS-5329 : Code of practice for sanitary pipe work above ground for
buildings.
(u) IS-3076 : Low density polyethylene pipes for potable water supplies.
(v) IS-1538 : Cast iron fittings for pressure pipes for water, gas and
sewage.
(x) IS-1729 : Sand cast iron spigot and socket soil, waste and ventilating
pipes, fittings and accessories
(dd) IS-775 : Cast iron brackets and supports for wash basins and sinks.
(ff) IS-2548 : Plastic water closet seats and covers (all parts).
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 21 of 64
(gg) IS-2527 : Code of practice for fixing rainwater gutters and down pipes
for roof drainage.
(hh) IS-554 : Dimensions for pipe threads, where pressure tight joints are
required on the thread
(ii) IS-:778 : Copper alloy gate, globe and check valves for water works
purposes.
(jj) IS-781 : Cast copper alloy screw down bib taps & stop valves for
water services
(ll) IS-1703 : Copper alloy float valve for water supply fitting (mm) IS-2326
: Automatic flushing cisterns for urinals.
(oo) IS-3311 : Waste plug and its accessories for sinks and wash basins.
(qq) IS-3989 : Centrifugally cast (Spun) iron spigot and socket soil, waste
and ventilating pipes, fittings and accessories.
(ss) IS-5382 : Rubber sealing rings for gas mains, water mains and
sewers.
(tt) IS-5822 : Code of practice for laying of electrically welded steel pipes
for water supply.
(vv) IS-8931 : Copper alloy fancy single taps combination tap assembly
and stop valves for water services.
(xx) IS-10592 : Industrial emergency showers eye and face fountains and
combination units.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 22 of 64
(bbb) SP-35 : Hand book on water supply and drainage with special
emphasis on plumbing.
(c) IS-1201 : Method of testing tar and bituminous materials thru' 1220
(d) IRC:58 -2002 : Guidelines for the design of pain jointed rigid pavements for
highways (second revision).
(f) IRC:37 - 2001: Guidelines for the design of flexible pavements (Second
revision)
2.1.15 Chimney
(e) CICIND : Model Code for concrete chimneys Model code for steel
chimneys.
(f) ASCE Code : Design and construction of steel chimney liners prepared by
Task committee on steel chimney liners.Fossil power
committee, Power division published by ASCE – 1975.
(b) IS-806 : Code of practice for use of steel tubes in general building
construction.
(f) IS-816 : Code of practice for use of metal arc welding for general
construction in mild steel.
(g) IS-817 : Code of practice for training and testing of metal arc
welders.
(i) IS-819 : Code of practice for Resistance spot welding for light
assemblies in Mild Steel.
(o) IS-1239 : Mild steel tubes, tubulars and other wrought steel fittings (all
parts).
(p) IS-1363 : Black hexagonal bolts, nuts and locknuts (dia. 6 to 39 mm)
and black hexagon screws (dia.6 to 24mm). [all parts]
(r) IS-1365 : Slotted counter sunk head screws (dia range 1.6 to 20 mm).
(t) IS-1443 : Code of practice for laying and finishing of cement concrete
flooring tiles.
(v) IS-1730 : Dimensions for steel plate, sheet and strip for structural and
general engineering purpose.
(w) IS-1731 : Dimensions for steel flats for structural and general
engineering purposes.
(x) IS-1852 : Rolling and cutting tolerances for hot rolled steel products.
(bb) IS-2074 : Ready mixed paint, air-drying, red oxide zinc chrome, and
priming.
(ee) IS-3664 : Code of practice for Ultrasonic Pulse echo testing by contact
and immersions methods.
(hh) IS-4759 : Hot dip zinc coatings on structural steel and other allied
products.
(ll) IS-7318 : Approval test for welders when welding procedure approval
is not
[Part-I] required (mm) IS-8500 : Structural steel - micro alloyed
(medium and high strength qualities).
(uu) IS-4353 : Sub merged arc welding of mild steel and low alloy steel
Recommendation
(vv) IS-5369 : General requirements for plain washers and lock washer
(ccc) IS-9178 : Criteria for design of steel bins for storage of bulk material.
(Part-1to 3)
2.1.17 Painting
(e) IS-2338 : Code of practice for finishing of wood and wood based
materials.
[I & II]
(g) IS-2395 : Code of practice for painting concrete, masonry and plaster
surface.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 27 of 64
(n) IS-6278 : Code of practice for white washing and Colour washing.
(u) BS-5493 : Code of practice for protective coating of iron and steel
structures against corrosion
(c) IS-801 : Code of practice for use of cold formed light gauge steel
structural member’s in general building construction.
(f) IS-12093 : Code of practice for laying and fixing of sloped roof covering
using plain and corrugated galvanised steel sheets
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 28 of 64
(j) BS-5950 : Code of practice for design of light gauge profiled steel
(Part-6) sheeting
(b) IS-443 : Code of practice for use of resin type chemical resistant
mortars.
2.1.20 Safety
(c) IS-4081 : Safety code for blasting and related drilling operations.
(e) IS-5121 : Safety code for piling and other deep foundations
(f) IS-5916 : Safety code for construction involving use of hot bituminous
materials
(g) IS-7969 : Safety code for handling and storage of building materials.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 29 of 64
2.1.21 Miscellaneous
(a) IS-7969 : Safety code for handling and storage of building materials.
(b) IS:10430 : Criteria for design of lined canals and for selection of type of
lining
All structures will be designed for the most critical combinations of dead loads, imposed
loads, equipment loads, crane loads, steam piping (static and dynamic) and other piping
loads, wind loads, seismic loads, temperature loads and any other loading condition which
can occur during the design life of the facility.
Foundation system will be decided based as per the Geotechnical Investigation report.
Dead load shall include the weight of all structural components and architectural
appurtenances incorporated in the structures plus hung loads and any other permanent,
externally applied load. This should also include equipment dead load. The content of
tanks, silo, bins and hoppers shall be measured at full capacity for this purpose. Hung
loads and the contents of tanks, silo, bins, and hoppers shall be listed separately so that
they can be excluded from dead load when dead loads are acting as stabilizing loads for
uplift. For Chimney, all permanent loads due to the weight of chimney shell internal
platform & lining supported on them. flue duct, staircase other accessories etc.
The following unit weight of material shall be considered for computation of loads. Loads
given in IS:875 (Part-I) shall be made use of for material not listed below:
Live loads in different areas shall include dust loads, minor equipment loads, cable trays,
small pipe racks/hangers, operation/maintenance loads etc. The loads considered shall
not be less than those specified in IS: 875 (Part II).
The loads listed hereunder are minimum loads for the areas involved. Special use areas
shall be investigated and loading revised upward as necessary.
Hung loads shall be based on minimum loading equivalents of 1.0 kN/Sqm for piping and
0.5 kN/Sqm for electrical, ventilation and air conditioning. Loadings resulting from
concentrations of facilities in specific areas shall be substituted where listed base loading
is excluded.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 31 of 64
Generally, loads of major equipments such as deaerator, heaters, etc., shall be based on
the manufacturer's data of the specified equipments. Static and dynamic loads of major
equipments shall be based on the manufacturer's data of the specified equipments.
Equipment loads shall be considered as given by equipment supplier. Equipment loads
which are of permanent nature shall be treated as dead loads. Loads of all equipments
like Deaerator, Heater, Feed water Tank, Cooling Equipment, Motors, fan drive pulleys,
Pumps, Monorails, Ventilation duct, air inlet & exhaust duct, Electrical control and relay
panels, Cable load, Pipe load (static and dynamic), Tanks, AHU, Batteries, Air Washer,
etc. shall be considered over and above the imposed loads. Static and dynamic loading
of major equipments including Turbine generator, boiler feed pumps, PA, ID, FD fans,
shall be obtained from manufacturer certified drawings of specific equipments
(a) Roofs:
Trenches/pits inside building shall be designed for a surcharge equal to Live Load intensity
of Ground Floor or 20 kN/Sq.m whichever is greater. In Boiler area and other outdoor
areas within Power Block, the minimum surcharge shall be 20 kN/ Sqm.
Self-weight of top slab and a uniformly distributed load of 4.0 kN/Sqm on each panel or
one 0.75 kN central point load, whichever is critical, shall be considered. At road
crossings, the covers shall be designed for vehicular movements as per IRC standards.
Culverts and allied structures including buried RCC Pipes shall be designed for Class "AA"
loading (wheeled and tracked) and checked for Class” A” loading as per IRC standards.
3.2.9 Roads
Design of roads shall be in accordance with Indian Road Congress standard, IRC 58.
Road Culverts and its allied structures including R.C.C. Pipe Crossings & Road Crossing
of Trenches shall be designed for Class `AA’ loading (wheeled and tracked both) and to
be checked for Class `A’ loading as per IRC standards.
(a) Railway supporting structures and rail culverts shall be designed as per Railway
Bridge Rules.
Reduction in Live load as per provision of IS: 875 shall not be permitted.
(b) The areas covered with equipment shall be designed on the basis of weight of
equipment (flooded/operating) in addition to a uniform live load of 5.0 kN/Sqm or
specifically defined live load whichever is greater.
For loads caused by moving equipment over the floor for installation, consideration
shall be given to the shoring of beams and floor, from floors below.
b) All equipment, tank and piping design loadings shall include Hydraulic Testing loads.
c) Air and gas duct loadings shall include weight of insulation, duct attachments, dust
accumulation loads, seismic, wind and other loads as applicable.
d) Crane girders and supporting columns shall be designed for vertical and horizontal
forces (including impact forces) as developed from the crane weights and wheel
loads. Unless otherwise specified, the vertical and horizontal loadings shall
conform to the applicable sections of the IS specifications.
e) Weight of equipments, ducts, tanks, pipes, conduits etc. supported by structure shall
include maximum possible loading conditions i.e. flooded material contents and
associated impacts, test loadings, anchorage and constraint effects.
g) Jet forces resulting from guillotine type pipe ruptures shall be considered in the
design, if it is of high magnitude. Jet force to be considered shall be equal to the
product of the pipe cross section and the internal design pressure applied on an
area equal to the pipe cross section.
h) Lay down areas in the Turbine Hall shall be investigated for concentrated loads
resulting from equipment components to be stored during erection and maintenance
operation. Where live load allowance is inadequate to permit storing of such
equipment components, the design live load shall be increased to permit such
use or the area shall be restricted by identifying lay down areas for specific
components, each area to be identified by permanent marking.
Wind loading shall be in accordance with Indian Standard Code IS: 875 (Part3) for a basic
wind speed of 39m/sec. Terrain Category-2 shall be considered for all structures.
The lateral forces shall be established in accordance with the recommendations of IS-
1893.The site falls in Zone-II as identified in the map of IS 1893:2002. The importance
factor for each structure shall be as per Table 2 of IS: 1893 (Part 4). Under earthquake
condition, the whole frame except roof shall be assumed loaded with 50% design live
load. No further reduction in column live loads shall be considered. In view of the
asymmetrical nature of main powerhouse, response spectrum method will be used for
analysis.
The damping factors shall be as per Table 4 of IS: 1893 (Part 4).
RCC Structures - 5%; Steel Structures - 2%
The structures shall be designed to withstand stresses due to fifty (50) percent of the total
temperature variation. The total temperature variation for temperature loading should be
taken as two-thirds (2/3) of the average annual variation in temperature. The average
maximum annual variation for this purpose shall be taken as the difference between the
mean daily minimum temperature during the coldest month of the year and mean daily
maximum temperature during the hottest month of the year.
Earth pressure for all underground structures shall be calculated using coefficients of earth
pressure at rest, coefficient of active or passive earth pressure (whichever is applicable).
However, for design of substructure of pump house, cold-water basin of cooling water and
underground liquid storage tanks, earth pressure at rest shall be considered.
In addition to earth pressure and ground water pressure, surcharge load shall also be
considered for the design of all underground structures including channels, sumps, cable
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 37 of 64
& pipe trenches, etc., to take into account the vehicular traffic in the vicinity of the structure.
Intensity of Surcharge Load shall be as described elsewhere in this specification.
When a portion or whole of the adjacent soil is below free water surface, computations
shall be based on submerged weight of soil plus full hydrostatic pressure.
When pressure relief valves are allowed for the underground structures only 50% relief
shall be considered on lateral pressure due to ground water and the buoyancy check.
Dynamic effect of earth pressure due to seismic conditions shall be considered along with
hydrodynamic effect water / liquid storage structures.
Crane girders and supporting columns shall be designed for vertical and horizontal forces
(including impact forces) as per crane vender’s data. All lifting beams and monorails shall
have their design loads increased for impact factor as mentioned hereinafter.
Loads for cranes, hoists and elevators shall be taken as per IS: 875.
a. Impact factor of 10% of lifted load of hoist for monorail and support
design
b. Impact factor of 25% of the lifted load for electrical pulley and
support design
(iii) Elevator:
A 100% of the lifted load including elevator live load plus the cab
weight for the elevator support beams.
All Power House columns adjacent to first row of Boiler columns shall be designed for an
additional load of 500 kN to account for piping/cable rack loads. For the design of pipe /
cable supporting structure, the soil weight shall be considered as backfilled upto grade level
for the condition of pipe running full / cables in position.
The following basic load cases shall be considered for the analysis :
a) Dead load : DL
(Comprising of only dead
weight of Structural members)
b) Live Load : LL
(Including imposed plant loads)
c) Equipment load : EQ
k) Temperature load : TL
DL + LL+EQ ± TL
0.9DL ±WLX
0.9DL±WLZ
0.9DL±SLX
0.9DL±SLZ
Appropriate allowable increase in permissible stresses as per IS codes, may be taken only
under normal loads along with wind and seismic conditions. However, members which are
designed primarily to resist wind, no increase in permissible stresses will be permitted.
Applicable load factors to be used for design of RCC structures by Limit State Method as
per IS: 456.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 40 of 64
Following loading conditions shall be considered in addition to the loading from super
structure for the design of sub-structure of pump house, channels, sumps, tanks, reservoirs,
trenches and other underground structures.
Only liquid pressure from inside and no earth pressure and ground water pressure, and
surcharge pressure from outside (applicable only to the structures which are liable to be
filled with water or any other liquid).
Earth pressure, surcharge pressure and ground water pressure from outside and no water
pressure from inside.
Base slab of the pump house shall be designed for the condition of different combination of
pump sumps being empty during maintenance stages with maximum ground water table.
Intermediate dividing piers of pump sumps and partition walls in channel shall be designed
considering water on one side only and the other side being empty for maintenance.
Design shall also be checked against buoyancy due to ground water during construction
and operation stage. Minimum factor of safety as per IS: 3370 against buoyancy shall be
ensured considering empty condition ignoring superimposed loads.
Water in one compartment and other compartments empty (where more than one
compartment is provided).
Walls of reservoir with top slab shall be designed as propped cantilever slab between top
and bottom slabs (where L/h > 2.5) or as a two-way slab with three sides fixed and top side
propped (where L/h <2.5). Factor of safety against uplift shall be at least 1.2 as per IS 3370
(Part-1). Special care shall also be taken to prevent floatation during construction period.
3 DESIGN CONCEPTS
If R.C.C. floors and roofs except those cast over metal decking are assumed to act as
diaphragm transmitting lateral loads to braced bays then main beams/ girders shall be
provided with shear connectors.
Shear connectors shall also be provided over beams having R.C.C. slab on one side and
opening/ Chequered plate/grating on other side.
For calculation of seismic load, equipment load shall be considered as Dead Load.
grating shall be bolted or clipped to supports. Sizes of grating shall be such as to allow easy
handling. Grating units at all penetrations shall be made up in split section All gratings shall
be arranged such that bars in either direction are in line. All gratings and accessories shall
be hot dip galvanised.
It may be of rectangular pattern of parallel bearing bars of 40 mm depth and 5 mm thickness
and cross bars of 25 mm depth and 3 mm thickness. Bearing bars shall be at 30 / 40 mm
c/c with cross bars at 100 mm c/c.
In Boiler area, all gratings fabricated from MS flats shall meet minimum requirements as
bearing bars of 32x5 thick spaced at 30 mm c/c and cross bar of twisted square bar (6 mm
diagonal) at 100 mm c/c. Removable chequered plates shall be provided with two lifting
holes and the size of plates shall be such as to allow easy handling. All edges of plates shall
be smooth and straight with 3 mm clearance between plates. All chequered plates shall rest
flat on their supports without rocking. All chequered plates shall be hot dip galvanised.
Chequered plates shall conform to IS: 3502. Hot dip galvanised coatings on iron and steel
articles shall be carried out in accordance with IS:4759 and other relevant IS standards.
Galvanising shall be checked and tested in accordance with IS:2629. The coating shall be
smooth, continuous and free from flux stains.
Small areas of galvanised coating damaged by welding, cutting, or during transport shall be
repaired by applying at least two coats of zinc-rich paint. All structural steel works, which
are not galvanised, shall be painted.
The minimum average coating weight of galvanizing shall be 610 gm / sq.m.
The design of R.C. Structures shall be carried out by limit state or working stress method (if
specifically mentioned) as per the provisions of IS-456. For reinforcement detailing IS:5525
and SP:34 shall be followed. The walls shall be provided with reinforcement on both faces
for sections 150 mm or more, even if not required from design consideration.
The following minimum grades of concrete as per IS-456 shall generally be considered -
MATERIALS
Reinforcing Steel: All reinforcement shall be of CRS (Corrosion Resistant Steel) bars
conforming to the requirements of IS 1786 and shall be used for all RC structures.
Reinforcement bars shall be as per the following codes:
High Yield Strength Deformed bars - IS: 1786
Mild steel bars - IS: 432 Grade 1
Welded wire fabric - IS: 1566
Cement:Fly ash can be added in ordinary Portland cement (Grade 43). Batching plant shall
be deployed for producing the concrete. Fly ash shall conform to IS: 3812. Higher grade of
Portland ordinary cement namely Grade 43 and Grade 53 conforming to IS: 8112 and IS:
12269 respectively can also be used for specific application. For aggressive/saline soil
approved cement shall be used. Sulphate resistant cement shall conform to IS:
12330.However, the ordinary Portland cement (Grade43) shall necessarily be used for
following structures.
Grouting:
Non-shrink flowable grout shall be used for under pinning work below base plate of columns.
Non-shrink cum plasticizer admixture shall be added in the grout.
For grouting of base of machine foundation high strength flowable ready mixed non-shrink
grout shall be used. Ready mix grout with Shrink-comp or Conbextra GP2 or equivalent
shall be used for base plate grouting works for all major equipments. Crushing strength of
the grout shall generally be one grade higher than the base concrete. Minimum grade of
grout shall be M35 for equipment foundations and M40 for dynamic equipment foundations.
Nominal thickness of grouting shall be at least 50 mm for building columns and pedestals
of major equipments or as specified by the equipment supplier.
For pipe rack pedestals, secondary posts, stair and ladder base etc. grouting shall not be
less than 25 mm thick.
Surfaces to be grouted shall be thoroughly roughened and cleaned of all foreign matter and
laitance.
Anchor bolts, anchor bolt holes and the bottom of equipment and column base plates shall
be cleaned of all oil, grease, dirt and loose material. The use of hot, strong caustic solution
for this purpose will be permitted. Prior to grouting, the hardened concrete surfaces to be
grouted shall be saturated with water. Water in anchor bolt holes shall be removed before
grouting is started.
Forms around base plates shall be reasonably tight to prevent leakage of the grout.
Adequate clearance shall be provided between forms and base plate to permit grout to be
worked properly into place.
Grouting, once started, shall be done quickly and continuously to prevent segregation,
bleeding and breakdown of initial set. Grout shall be worked from one side of one end to
the other to prevent entrapment of air. To distribute the grout and to ensure more complete
contact between base plate and foundation and to help release entrapped air link chains
can be used to work the grout into place.
Grouting through holes in base plates shall be by pressure grouting.
MINIMUM COVER TO FOUNDATION BOLTS:
Minimum distance from the centre line of foundation / anchor bolt to edge of pedestal shall
be the maximum of the following:
a. Clear distance from the edge of the base plate / base frame to the outer edge of the
pedestal shall be minimum 50 mm.
b. Clear distance from the face of pocket to the outer edge of the pedestal shall be 75 mm.
c. Clear distance from the edge of the sleeve or anchor plate to the edge of pedestal shall
be 75 mm.
MINIMUM COVER TO REINFORCEMENT
The clear cover to reinforcement shall be for 2 hours’ fire rating as per table 16A of IS: 456
and also meet the requirement of durability requirements based on exposure conditions as
per table 16, whichever is stringent.
The design of foundation shall be carried out by Limit State or working stress method as
per the provisions of IS-456: 2000.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 44 of 64
Structural concrete for foundation work shall be M-30, unless a higher grade is specified
elsewhere.
Foundations for the main plant structures are those for Power House building columns,
Boiler House columns, Mill and Bunker bay columns, ESP columns, etc. Top of RCC
foundation for the steel columns shall generally be kept at a lower level so that the column
base plates together with gussets and stiffeners remain below the finished floor level.
Foundation levels of some columns shall have to be suitably lowered to accommodate
underground services, pits, trenches, etc.
Foundations for Buildings and structures shall be designed to resist forces and moments,
caused by vertical loads and by wind or seismic loads, based on static and dynamic analysis
done for those structures. The foundation sections shall be sized and reinforced adequately
for moments and shear stresses.
For all underground structures such as basement, sump etc., and water retaining structures
special care shall be taken to water proof them. Approved integral water proofing compound
shall be added to concrete mix to ensure water tightness. PVC water stop shall be provided
at all construction joints as required. Water retaining structures shall be hydro-tested as per
IS:3370 for leakage and in case leakage is noticed pressure grouting or any other approved
procedure shall be adopted to rectify it. Sumps with pumping arrangements shall be
provided at suitable location in underground structures to collect and pump out any
incidental water collection to nearest storm water drainage outlet.
Generally, foundation for buildings & equipment shall not be structurally connected to
ground floor slab. The top level of the stem for building structural column foundations shall
be so provided that no part of the steel column base assembly protrudes over finished floor
level. The column base assemblies shall be encased with M-15 grade concrete up to floor
level.
Supporting structures and foundations for equipment that may cause vibration shall be
designed for the dynamic effect of equipment together with the direct loads. The dynamic
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 45 of 64
loads and other relevant data required for analyzing the dynamic effect shall be taken as
per manufacturers’ data and recommendations.
Foundations of equipment subjected to dynamic loading shall be isolated from adjoining
floors/foundations to prevent propagation of vibration to adjoining structures. Structures and
foundations supporting vibrating, equipment shall be proportioned to avoid resonant
frequencies. The dynamic analysis shall be done as per the stipulations as recommended
by respective IS codes as well as the stipulations recommended by equipment
manufacturer.
75mm thick lean concrete 1:4:8 shall be provided below footings, pile caps, base slab etc.
as blinding concrete layer.
For the foundations of Fans (ID, FD, PA& Seal Air etc.), Boiler feed pump, Bowl Mill, detailed
static and dynamic analysis will be performed. The static analysis will include operating
conditions load cases and abnormal loads like, maximum unbalance and seismic forces.
Unbalanced loads for normal operating condition as given by machine manufacturers or as
specified in IS: 2974 whichever is more conservative shall be used.
The dynamic analysis will consist of free vibration analysis and forced vibration analysis.
Frequency separation criteria and amplitude criteria as laid down in IS: 2974 and/or DIN
4024 and/or VDI 2056 or as required by the machine manufacturer will be satisfied. RCC
design will be done by working stress method for all machine foundations as per IS: 2974.
Minimum reinforcement will be governed by the requirements specified in IS: 2974 as well
as IS: 456
All block foundation supporting rotating equipments and resting on soil will be designed
using the elastic half space theory and/or Barkan’s method. The mass of the RCC block will
not be less than three time the mass of the machine. Dynamic analysis will be carried out
to calculate natural frequencies in all the modes including coupled modes and to calculate
vibration amplitudes. Frequency and amplitude criteria as laid down in the relevant codes
and/or by machine manufacturer will be satisfied. Minimum reinforcement will be governed
by the requirements specified in IS: 2974 and IS: 456.
The analysis and design of machine foundations will be carried out to ensure the following.
Bowl mills shall be supported on conventional block type R.C.C foundations. All machine
foundation shall be separated from adjoining building / foundations. Isolation joints shall be
given all round to isolate the machine foundation from the grade slab. All appendages to
such foundation shall be reinforced suitably to ensure integrated action.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 46 of 64
Analysis and design of the Steam Turbine-Generator (STG) foundation shall be carried out
in accordance with relevant codes IS: 2974 Part-3 and IS: 456 and/or manufacturer’s
requirements. The loads to be considered for static analysis and design shall consist of
dead weight of the machine and foundation, machine power torque, condenser loads under
normal operating condition, equivalent static load due to machine unbalance, thermal
elongation forces, forces due to one sided operation of the condenser, forces due to
condensate pump failure, vacuum loads, forces due to piping, frictional forces at machine
sole plate level for turbine, generator and condenser, temperature distribution under
operating condition, failure loads of turbine (blade unbalance/loss of blade/bowed rotor),
failure loads of generator (short circuit loads), seismic loads due to generator, turbine and
condenser and erection loads.
(b) RCC sub structure of Raw water pump house/CW pump house, CW channel and
forebay, NDCT basin and outlet channel, Clarifloculators, CW pit, CEP pit,
underground sub structure of wagon tippler, underground coal conveyor tunnel,
underground structures of ETP/STP/WTP.
All water retaining/storage structures and all underground structure requiring dry working
condition shall be designed assuming liquid up to the height of wall irrespective of provision
of any over flow arrangement.
In all liquid retaining structures leak-tightness shall be ensured and guaranteed. To achieve
the same, methodology in design and construction in the way of providing PVC water bars
at construction/expansion joints and/or injection grouting, usage of admixture in concrete or
any such method should be adopted.
All underground water retaining/conveying system structures shall have plasticizer cum
waterproofing cement additives conforming to IS: 9103. In addition, limits on permeability
as given in contact with soil shall be provided with minimum two coats of bituminous painting
of grade 85/25 conforming to IS:702 @ 1.7 kg/sqm (minimum) for water/damp proofing.
Storm water drains shall not be provided with bituminous paint and weep holes also shall
not be provided in storm water drains.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 47 of 64
Foundations for vertical steel tanks shall be resting on hydraulically compacted clear river
sand, in layers of 500 mm thickness topped with 150 thk PCC. PCC layer shall be topped
with 50 thk. Anti-corrosive asphalt layer, which in turn is topped with 50 thk. Premix carpet.
The entire sand fill along with toppings shall be confined within a RCC ring beam of
appropriate design.
4.1.3 Roads
Geometric design of road shall be done in accordance with Indian Road Congress Standard
IRC-37. The ruling gradient for roads in longitudinal direction shall be 1 in 30. Normally
roads shall have much flatter gradient. Finished top (crest) of roads shall be 250 mm above
the surrounding grade level.
All roads shall have minimum shoulder width on either side of carriageway. Shoulders shall
have sufficient load bearing capacity to support loaded trucks. A flatter slope of 1 in 80 shall
be provided on shoulders. All double lane roads shall have a minimum turning radius of 25
meters and all single lane roads shall have a minimum turning radius of 10 meter.
Pipe, slab culverts, or RCC box culverts, as suitable, shall be provided at road crossings for
drainage, LP pipes, Ash pipes, cable trenches etc. Level crossings shall be provided where
a Railway siding line crosses the road. All culverts shall be designed for IRC class "AA"
loading and checked for class A loading.
Design of concrete road shall be made as per IRC 58-2002, considering single axle load of
10.2 ton with a load safety factor of 1.1. As surface soils show low to moderate swelling
potential, so provision of clause no.- 6.2.3 of IRC – 15 - 2002 to be adhered to or as per
recommendations of detailed soil investigation report.
Construction of road shall be in accordance with IRC 15-2002 and other relevant IS/IRC/
MORT&H Codes of practice. The ruling gradient for roads longitudinal shall not exceed 1 in
20. Main roads and roads around the main plant shall be designed for movement of heaviest
equipment of the plant.
The minimum thickness, minimum grade of concrete, minimum reinforcement for the RCC
roads and Pavements shall be as follows:
a) 250 mm thick with M30 Grade mix, with double mat reinforcement of 8 tor @ 250 c/c both
ways- For all roads except patrol road along the boundary wall.
b) 150mmmm thick with M30 Grade mix with single mat reinforcement of 8 tor @ 250mm
c/c both ways for the patrol road along the boundary wall.
Shoulder provided on either side shall be in murrum construction of 150 mm compacted
thickness.
The geometric design of roads shall be done in accordance with IRC-73. Road widths,
curves and parking areas shall have adequate space for maneuvering of vehicles. The
ruling gradient for roads in longitudinal direction shall not exceed 1 in 30. Normally the roads
shall have much flatter gradient. Finished top (crest) of roads shall be 250 mm above the
surrounding grade level.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 48 of 64
All double lane roads shall have a minimum turning radius of 25 meters and all single lane
roads shall have a minimum turning radius of 10 meter. However, for minor roads this shall
be reduced suitably as per layout requirements and site conditions. Road width and turning
radii shall also to be checked for to take largest vehicles and equipment which can
reasonably be expected.
California Bearing Ratio (CBR) method shall be followed for the design of roads as per
IS:2720 (Part XVI). CBR test shall be carried out in remoulded soil samples under soak
condition.
The shoulder shall be laid with slope of 1 in 30. Foot path shall be provided at both sides of
the road as per requirement for the main road connecting security main gate to the main
plant and administrative building.
RCC pipes of 150 mm diameter shall be provided below each road at every 50 m and 600
mm diameter at every 300 m and also at all turnings for maintenance purpose. RCC pipes
shall be of Grade ‘NP3’.
All the culverts shall be designed for IRC Class' AA' loading and shall be checked for class'
A' loading. The Equipment moving load shall also be properly considered.
Minimum width of RCC culverts shall be 1000 mm.
All buildings and facilities/components shall be approached by access road, which shall
either be single or double lane road depending upon the functional requirement and as
directed by the Owner.
4.1.4 Drainage
Open RCC rectangular drains shall be provided for storm water. The thickness of sides &
bottom shall be minimum 100 mm or as per design considerations whichever is higher. RCC
culverts shall be provided for road and rail crossing. Drains shall be provided on both sides
of the roads.
Inside surface of the drain will have smooth neat cement finish over with screed concrete.
Invert of the drain shall be decided in such a way that the water can easily be discharged
to the recommended nearest outfall outside the plant boundary. The minimum slope of the
drain shall be 1:1000 longitudinally to take care of the silting problems. It is recommended
to maintain the maximum velocity within 1.2 m/sec.
The plant storm water drainage system shall take in to account the topography of the plant
area, area drainage patterns and intensity of rainfall etc. All storm water drains shall be
designed for the maximum hourly rainfall intensity.
All storm water drainage shall preferably be through open storm water drains on both sides
of the roads and shall be designed to drain the appropriate catchment area including road
surface, open and covered area etc. In case of road along boundary wall, storm water drain
may be provided on one side.
Surface drains shall be open drains of RCC rectangular cross section. All drains in the
power block area and around buildings shall be covered drains.
All the paved and unpaved areas shall be adequately drained. The surface drainage system
shall be designed for surface washings and / or rain / fire water as the case may be.
Unpaved open areas shall be drained through RCC drains and connected to main storm
drains. Minimum slope for paved areas towards drains -1 in 100
Maximum drainage travel extent -10 meters
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 49 of 64
Uncontaminated area surface drainage shall be connected to nearest open storm water
drains through rectangular drains.
Contaminated area surface drainage shall be collected through separate network.
Interconnecting pipes and rectangular drains shall be sized for carrying the design
discharge when running full. Minimum width of RCC rectangular drains -450 mm Drainage
pipe material -RCC class NP2 conforming to IS: 458 except road and rail crossing areas -
RCC class NP3 for road crossings -Pipes conforming to railway loading standards for rail
crossings Minimum velocity for self-cleansing -0.6 m/sec Maximum velocity for pipe drains
-2.4 m/sec Maximum velocity for open drains -1.8 m/sec
Minimum slope of drains -1 in 2000 Minimum earth cover over drain pipes in -450 mm paved
areas. Minimum width of garland drains all round -300 mm the building
Minimum thickness of side walls and bottom -125 mm or as per design requirements slab
whichever is greater
Diameter of pipes used for drainage / culverts shall be between 300 mm to 600 mm. Beyond
600 mm, box drains / culverts shall be provided.
Run-off co-efficient for paved and unpaved areas shall be 0.9 and 0.6 respectively.
Surface drains shall normally have a bed slope not milder than 1 in 2000 along longitudinal
direction and RCC pipes shall have such slopes so as to have effective discharge.
Manholes shall be provided to piped drainage lines at every 50 m intervals, at junctions and
at change of gradient, alignment and diameter of pipe and shall be of masonry or RCC
construction. Minimum size of manholes shall be of 1.0 m x 1.0 m. All manholes shall be
designed considering maintenance, inspection and cleaning of pipes. Easy accessibility and
safety shall also be given due consideration.
The cushion over the pipes for storm water culverts shall be minimum 600 mm. Where less
cushion is available, pipe shall be encased in RCC M-15. Suitable RCC or masonry
structures shall be provided at drops / falls to prevent scouring or damage to surface.
Invert of drainage pipe / drain shall be decided in such a way that the water can easily be
discharged above the high water level in water course outside the plant boundary to which
the storm water to be let.
The Contractor shall furnish a comprehensive layout of drainage system, taking
consideration of different construction phase for the approval of the Owner.
Drainage shall be provided for all roads, pavements, sidewalks, buildings, structures and
wet areas including cable/pipe trenches, tunnels, basement of buildings, coal stockyard and
pits etc. Where gravity flow is not possible. pumps shall be installed for lifting and/or
diverting pressurized water to location of discharge points. Pump sumps and pumps shall
be provided at all necessary locations.
Proper drainage of floors, basements, cable / pipe trenches tunnels and pits shall be
provided for fire water, operation and leakage water.
The outdoor storm water may be drained through concrete lined open ditches ultimately
connecting to nearest drainage channel. All building roof and non-contaminated floor
drainage, drainage of cable / pipe trenches, tunnels, pits, basements etc., shall be provided
with suitable buried piping system (gravity flow) for discharging ultimately into the common
outdoor drainage system. The oily / process waste shall be drained / collected through a
separate sewer system consisting of underground (overground if required) concrete / cast
iron pipes. Catch pits shall be provided at the source location and they shall be
interconnected by buried pipes. No bends and branches shall be provided in the pipe line.
Manholes shall be provided at all junctions of pipes. Catch pits shall have a minimum
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 50 of 64
internal dimension of 600mm x 600mm. They shall be of RCC construction and provided
with CI grills.
In case the top of pedestal is kept at a lower level so that the column base plate together
with gussets and stiffeners remain below finished floor level (FFL) the column bases as well
as the column sections shall be encased in concrete above FFL as per following:
Stair and ladder pedestal shall be kept 200 mm above the finished floor level.
Ground floor slab-on-grade shall be minimum M-25 grade RCC construction laid over
minimum 100mm thick lean concrete. Minimum 250 mm thick graded stone (63mm down
size) soling with interstices filled with sand and compacted mechanically, shall be provided
as sub-base below lean concrete.
All internal stairs, platforms and walkways shall either be of RCC or minimum 6mm thick
chequered plate construction. All outdoor stairs, platforms and walkways shall either be of
RCC or minimum 40mm thick grating.
All handrails and posts shall be of 32NB medium duty Galvanised M.S. pipes as per IS:
1239 (Part I).
Structural steel design will be carried out as per IS-800:1984 unless noted otherwise.
All steel framed structures shall be either “rigid frame” or “simple space frames” or a
combination of two.
Lateral forces shall be resisted by stiff jointed moment connections in rigid frame. The
column bases shall generally be fixed to concrete foundation pedestal by providing moment
resistant base detail.
Simple space frame design utilizes single-span beam systems, vertical diagonal bracing at
main column lines and horizontal bracing at the roof and major floor levels. Most of the
plants’ steel buildings shall be designed as simple space frame structures.
The turbine building design shall be a combination of rigid frame in transverse direction and
simple frame in longitudinal direction.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 52 of 64
Pipe rack shall consist of rigid main frame in transverse direction spaced longitudinally as
required. In longitudinal direction, pipe rack shall be divided into sections of suitable length
with an anchor bay. The main transverse frames shall be connected with longitudinal beams
which will transmit horizontal forces to braced anchor bays. The pipe and cable rack bridge
structure shall be adequately rigid to carry the forces from pipelines at anchor points without
undue deflection so that pipelines are really anchored at the anchor points.
Concrete floors shall be considered to provide continuous lateral support to the top
(compression) flange of the support beams. Suitable shear connectors shall be welded to
the top of the top flange of all secondary beams to ensure the lateral support. However
wherever large cut outs are provided in the floor slabs horizontal floor bracing shall be
provided. Grating/chequered plate floor shall neither be considered to provide lateral
support to the top flange of supporting beams nor to provide a shear diaphragm. Adequate
lateral support and horizontal bracing shall be provided as required.
Structural steel shall conform to Grade A of IS:2062 for rolled steel members or plates up
to 20 mm thickness. For plates above 20 mm thickness and welded construction, steel
conforming to Grade B (Killed and normalized) of IS: 2062 shall be used except for crane
girders where Grade C (Killed and normalized) (IS: 2062) steel shall be used.
Connections
Connection of vertical bracings with connecting members and diagonal truss members shall
be designed for full tensile capacity of the bracings.
Size of fillet weld for flange to web connection for built up column section will be as follows:
80% of full shear capacity or actual shear (if indicated in drawings) or 0.5 times of the web
thickness whichever is more for I section.
All welds will be continuous. The minimum size of fillet weld will be as per relevant IS code.
Shear connections shall be designed for 75% of section strength for rolled sections and
80% of section strength for built up section or rolled section with cover plates.
Moment connections between beam and column will be designed for 100% of moment
capacity of the beam section.
Connection of base plate & gusset members with the columns will be done considering that
total load gets transferred through weld.
All splicing work shall be of full strength. Shop splicing for all sections other than rolled
sections shall be carried out by full penetration butt welds. Shop splicing of all rolled sections
shall be carried out using web and flange cover plate.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 53 of 64
Welded Connection
The permissible deflections of various steel members under normal loading conditions shall
be as specified below. For calculation of deflections in structures and individual members,
dynamic effects shall not be considered, unless specified otherwise. Also, no increase in
deflection limits shall be allowed when wind or seismic load are acting concurrent with
normal loading conditions.
Vertical Deflection
For crane gantries or any member subjected to working loads, the maximum deflection
under dead load and live load excluding impact shall not exceed the following values:
Horizontal Deflections
The permissible horizontal deflections shall be as per following unless specified otherwise:
Provisions of IS: 800 and relevant IS Code shall be followed for limiting deflections of
structural elements not listed above.
5.1 General
a) Minimum 1200 mm high (from floor/ roof level) hand railing shall be provided
around all floor/roof openings, projections/balconies, walkways, platforms, steel
stairs, etc., Hand railings at higher elevations (more than 6.0m from ground level
or nearest floor level) shall be 1200mm high. All handrails and ladder pipes (except
at operating floors) shall be 32 mm nominal bore MS pipes (medium class)
conforming to IS: 1161 and shall be galvanized as per IS: 4736 treated with etch
primer and finished with suitable paint. All rungs and ladders shall also be
galvanized. Minimum weight of galvanizing shall be 610 g/sqm.
For stairs and around all floor openings at operating floors, 1000 mm high hand
railing with 32 NB (polished) stainless steel pipe shall be provided.
b) All stairs shall have a riser height of 150 mm subject to max. 180mm and a
minimum tread width of 250 mm subject to a max of 300mm. Minimum clear width
of steel staircase shall be 1200 & 1500mm for RCC staircase resp. unless specified
otherwise. -Rev 01
c) All buildings having metal cladding shall be provided with a 150 mm high RCC toe
curb at the edge of the floor along the metal cladding. 1000 mm high hand railing
shall be provided on this RCC curb, wherever required from the safety point of
view.
d) In all buildings, structures, suitable arrangement for draining out water collected
from equipment blow downs, leakages, floor washings, firefighting, etc., shall be
provided for each floor. All the drains shall be suitably covered with grating or pre-
cast RCC panels.
e) RCC staircase shall be provided for all RCC construction buildings and structural
steel staircase for all structural steel buildings.
f) Parapet, Chajjas over window and door heads, architectural facia, projections, etc.,
shall be provided with drip course in cement sand mortar 1:3.
g) All fire exits shall be painted with P.O red/signal red colour shade which shall not
be used anywhere except to indicate emergency or safety measure. Fire safety
norms shall be followed as per National Building Codes and fire safety
requirements for providing fire exits, escape stairs and firefighting equipment. In
detailing of all buildings, fire safety requirements conforming to IS: 1641 and IS:
1642 shall be followed.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 56 of 64
Fine aggregate source shall be manufactured crushed stone or rock sand, excluding fines
which are by products/rejects of coarse aggregate production. The crushed stone sand shall
be graded from fine to coarse with the coarse sizes predominating to give maximum density.
The amount of fine particles as ascertained by the laboratory sedimentation method shall not
exceed 10% for crushed stone nor 4% for natural sand.
Fine Aggregates Coarse aggregate shall be crushed rock and shall be free from
decomposed stone, clay, earth or other deleterious substances. The specific gravity of the
coarse aggregate shall not be less than 2.5 t/m3. Aggregate of crushed natural stone is
deemed adequate if the stone reveals a crushing strength of 1000 kg/cm2 when tested.
Friable, flaky and laminated pieces, mica and shale shall only be present in such quantities
as not to affect the strength and durability of the concrete.
The grading of coarse aggregate for concrete shall comply with the requirements of IS:383.
a) Complete Transformer Yard, covering area between A-row of the turbine building up to
the fencing of the Transformer yard.
PCC paving of M15, 100 mm thick shall be provided as paving inside the following areas. The
paving shall be laid over well compacted ground and laid to slope towards peripheral drain.
a) Fuel oil tank farm
Stone Aggregate Paving
For auxiliary transformer yards, paving of stone aggregate of 100 mm thick using 20 mm size
aggregate shall be provided after compacting the under bed and treating with anti-weed
chemicals.
Grade Slab with equipment (Indoor / Outdoor)
Minimum 200 mm thick of grade M20 with minimum reinforcement of 8 dia (HYSD) @ 200 c/c
both ways top & bottom.
The under bed shall consist of well compacted ground supporting dry rubble soling of compacted
thickness 225 mm with interstices properly filled with grits, followed by a layer of PCC 1:4:8, 50
mm thick.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 58 of 64
All steel structures shall receive two primer coats and two finish coats of painting.
First coat of primer shall be given in shop after fabrication, before dispatch to erection site
after surface preparation as described below. The second coat of primer shall be applied
after erection and final alignment of the erected structures. Two finish coats shall also be
applied after erection.
Steel surface which is to painted shall be cleaned of dust and grease and the heavier layers
of rust shall be removed by chipping prior to actual surface preparation. The surface shall be
abrasive blasted to Sa-2½ finish as per SIS05-5900. Primer paint shall be zinc silicate of
approved make.
Finish paint shall be 2 coats of High built epoxy finish of approved brand. Dry film thickness
of each finish coat shall be 90 microns. The undercoat and finish coat shall be of different tint
to distinguish the same from finish paint. The total dry film thickness shall be 300 microns. All
paints shall be of approved brand and shade as per the OWNER’s requirement.
Joints to be site welded shall have no paint applied within 100 mm of welding zone. Similarly
where Friction grip fasteners are to be used no painting shall be provided. On completion of
the joint the surfaces shall receive the paint as specified.
Bipolar Concrete Penetrating Corrosion Inhibiting Admixture (CPCIA) shall be used. CPCIA
shall be free from nitrites, chromates and non-migrating types and having 7-8 years of usage
history in Indian conditions conforming to ASTM-G-109 with an efficiency factor of minimum
25 times. Dosage as per manufacturer specifications shall be compatible with the type of
cement used.
Two coats of tar extended moisture compatible coating with a DFT of 300-350 microns. The
system shall have minimum 7 years successful usage history in Indian conditions with the
following properties
-Salt spray test ASTM-B-117 : Pass 1000 hours min -Adhesion ASTM-D-4541 : 3.8 N/mm2
min -Resistance (Impedance) : 108 Ohms
Suitable manholes shall be provided to piped sewage lines at every 30 m intervals, at junctions
and at change of gradient, alignment & diameter of pipe and shall be of masonry or RCC
construction. Details of manholes shall be as per IS:4111 (Part-I ). Minimum size of manholes
shall be 1.0m x 1.0 m. All manholes shall be designed considering maintenance, inspection and
cleaning of pipes. Easy accessibility and safety shall also be given due consideration.
Sewage from the buildings shall be let into septic tanks. Overflow from soak pits of septic tanks
shall be sent to a central sewage treatment plant through a sewerage network. The treated
effluent shall be utilized for the irrigation of the landscaped areas and horticulture.
The sanitary sewer system shall be independent of plant and storm drainage system. The
treatment of sanitary sewage shall be through septic tanks and soak pits/leaching fields. The
number of septic tank shall be kept minimum and their location shall be away from plants,
buildings and facilities. The size of septic tanks shall be designed based on fixture units and for a
minimum storage of 5 years but not less than 2.0 CU.M.
All underground piping below concrete slab shall be HPDE minimum 100mm dia and for outdoors
it shall be HDPE pipe of minimum 200mm diameter. In buried piping system manholes shall be
placed at every change in direction and at every SOM (max.) interval in straight run. Suitable
clean outs shall be provided for buried piping under floor slab
Following minimum drainage slope shall be provided:
• Pipes of diameter less than 200mm : 1 (vertical) : 100 (horizontal)
• Pipes of diameter 200 mm & more : 1 (vertical) : 200 (horizontal)
For the treatment of sanitary sewage, a septic tank having a minimum of 3 chambers shall be
constructed. Septic tank shall consist of the RCC tank with inlet and outlets therefrom, complete
with all necessary earthwork and backfilling. The details of septic tank shall be as per IS:2470.
The chambers shall be separated by walls with slits. Each chamber shall have one manhole cover
for cleaning with mobile pump. Before the outlet in the last chambers, a screen board shall be
provided to prevent the passage of floating matter into the discharge pipe.
Project Subject Doc. No. Rev Section
2X660 MW Design Memorandum for
Udangudi TPP STAGE-I Civil, Structural and PE-DC-435-600-C001 1 Sheet No.
Architectural Works 60 of 64
Septic tank shall also include ventilating pipe of at least 100 mm dia whose top shall be provided
with a suitable mosquito proof wire meshes and cowl.
Ventilating pipe shall extend to a height of about 2 meter when the septic tank is at least 15 meter
away from the nearest building and to a height of 2 meter above the top of building when it is
located closer than 15 meter. Ventilating pipes can be connected to the normal soil ventilating
system of the building where allowed. After the Septic Tank has been tested to be watertight and
the sewage system is checked, the tank shall be filled with water to its outlet before the sewage
is let into the tank. It shall be seeded with well-digested sludge obtained from septic tank or sludge
digestion tank. In the absence of digested sludge, small quantity of decaying organic matter such
as digested cow dung may be introduced.
A soak pit shall be arranged at the location shown on drawings for the disposal of sanitary sewage
from the outlet of the septic tank. The soak pit shall be constructed in-situ. It shall consist of a
minimum 900 mm dia pit 1.0m in depth below the invert level of the inlet pipe. The pit shall be
lined with stone, brick or concrete blocks set in cement mortar (1:6). The lower part shall be
perforated and filled with brickbats.
Inspection opening of 700 mm x 700 mm shall be provided. The cover of the inspection opening
shall be of cast-iron. Inlet pipe shall be taken down to a depth of 900 mm from the top as an anti-
mosquito measure.
All cable and pipe trenches shall be of RCC. Trenches located outside buildings shall be
projecting at least 150 mm above finished formation level to avoid entry of storm water into
the trenches. The bottom of trench shall be provided with suitable slope for draining out
collected water into a sump pit.
(s) DG building & Stack, Diesel tank single storied steel Ground -
pedestals paving etc framed structure with floor
electric hoist.
(t) Chemical/hazardous storage RCC framed structure Ground
Building with RCC roof floor
(u) CST Pump shed/building Structural steel Ground --
including condensate storage framework/RCC framed floor
tanks
(v) FO Area including RCC framed structure Ground As per
FOPH,unloading ramp,dyke/tank with RCC roof floor specs
farm area,HFO/LDO/DAY
tanks,associated
piping/pedestals,OWS pit,flash
tank,paving,fencing with gates &
staircase
(w) Dispensary RCC framed structure Ground 200
with RCC roof floor sqm*(20m
x 10m)
(x) Bank extension counter & post RCC framed structure Ground 200
office with RCC roof floor sqm*(20m
x 10m)
(y) Sea Water Intake PH RCC framed structure Ground+ As per
with RCC roof 1 specs
(z) Seawater Outfall Pumphouse Ground+ As per
including CW blowdown RCC TANK 1 specs
collection sump
Glazed Aluminium
Granolithic with Two Coats of Expoxy Water Proof Cement
D Switch Gear Room Acrylic Washable Distemper Acrylic Distemper Steel Sliding Type Door Windows with
Painting. Based Paint
Wire Glass
Office, Electronic Cubicle Room, Computer Room, Common Water Proof Cement Powder Coated Aluminium
E Heavy Duty Ceramic Tiles Acrylic Emulsion Paint Acrylic Distemper
Areas & Corridor Based Paint Framework with Glazing
Granolithic with Non-Metallic Floor Water Proof Cement Pressed Steel Door Frame with
F Cable Room Acrylic Distemper Acrylic Distemper
Hardener Based Paint Elastomeric Water Double Plate Flush Shutters
Proofing Treatment
Water Proof Cement
G Laboratory Room Heavy Duty Ceramic Tiles Acrylic Washable Distemper Acrylic Distemper Aluminium Glazed Doors Aluminium Glazed
Based Paint
Sliding Windows
H Records Room, Lockers Room Glazed Vitrified Ceramic Tiles Acrylic Washable Distemper - Acrylic Distemper Pressed Steel Door Frame with
I Swas Room Glazed Vitrified Ceramic Tiles Acrylic Washable Distemper - Acrylic Distemper Double Plate Flush Shutters
Dadoing for 2100 mm High + Water Proof Cement
J Toilet Heavy Duty Ceramic Tiles Acrylic Distemper PVC Frame with PVC Door
Acrylic Distemper Based Paint
Dadoing for 2100 mm High +
K Pantry Heavy Duty Ceramic Tiles - Acrylic Distemper PVC Frame with PVC Door
Acrylic Distemper
Page 1 of 3
2
Page 2 of 3
3
Glazed Aluminium
Water Proof Cement Elastomeric Water
A Office Areas Heavy Duty Ceramic Tiles Acrylic Emulsion Paint Acrylic Distemper Aluminium Glazed Doors Sliding / Fixed
Based Paint Proofing Treatment
Type Windows
Glazed Aluminium
Dadoing for 2100 mm High + Water Proof Cement Elastomeric Water
B Toilets Heavy Duty Ceramic Tiles Acrylic Distemper PVC frame with PVC Door Sliding / Fixed
Acrylic Distemper Based Paint Proofing Treatment
Type Windows
Glazed Aluminium
Dadoing for 2100 mm High + Elastomeric Water
C Pantry Heavy Duty Ceramic Tiles - Acrylic Distemper Aluminium Glazed Doors Sliding / Fixed
Acrylic Distemper Proofing Treatment
Type Windows
2100mm High, Acid & Alkali
Glazed Aluminium
Resistant Tiles Dado and Chlorinated Rubber Elastomeric Water
D Battery Room Acid / Alkali Resistant Tiles Granular Finish PVC frame with PVC Door Sliding / Fixed
Chlorinated Rubber Based Paint Based Paint Proofing Treatment
Type Windows
Over Dadoing
Page 3 of 3