GTC Materials List
GTC Materials List
GE-CIC-ES-0064
GTC Appendix A for ENA ENGINEERING RECOMMENDATION
G81-PART 2: MATERIAL SPECIFICATION
CONTENTS
FOREWORD ..................................................................................................................... 3
1. SCOPE .................................................................................................................... 3
2. GENERAL ................................................................................................................ 3
Appendix 1 .............................................................................................................. 4
Appendix 2 .............................................................................................................. 10
Appendix 3 .............................................................................................................. 12
FOREWORD
This document forms Appendix A to Energy Networks Association (ENA) Engineering
Recommendation (ER) G81 ‐ Part 2: Materials Specification, “Framework for new low
voltage housing development " and should be read in conjunction with that document
This document contains a summary of the information contained in GTC product
specifications.
Please note that GTC is unable to provide copies of external documentation, standards and
specifications referenced in this document, but copies may be obtained from the relevant
issuing body (such as the British Standards Institution (BSI) or Energy Networks
Association)
Appendix A of this document details assessed products by reference, description and
supplier.
1. SCOPE
This appendix to ENA ER G81 Part 2 covers the materials specification for new low
voltage services and mains, and associated high voltage to low voltage substations for
the purpose of connecting housing developments to the electricity distribution network of
GTC comprised of licenses Energy Network Company (ENC) and Independent Power
Network Company (IPNL).
2. GENERAL
2.1 This document provides details of GTC's approved range of cables, plant, equipment
and auxiliary items used to construct distribution assets for connection to GTC’S
distribution network. Only equipment approved by GTC and listed in this document
shall be used to construct electricity networks, substations and services for adoption
by GTC in its distribution networks.
2.2 For all new connections work, the approved installer (ICP) shall provide the Engineer
with a full list of equipment to be used. The Engineer will then aim to formally accept
or reject the proposal within 10 working days.
2.3 Where GTC's requirements are not specified in this document, the approved installer
shall liaise with the Engineer, to gain approval from GTC's Electricity Networks
Director for its suggested equipment, prior to purchasing the equipment.
2.4 This document will be updated on a regular basis when new equipment is approved
by GTC’s Electricity Networks Director. Further details will also be added as
requirements for further information on the range of equipment used is identified.
Appendix 1
LOW VOLTAGE EQUIPMENT INCLUDING UNDERGROUND CABLES, JOINTS, LINK
BOXES, TERMINATIONS AND FUSES
Material
S.No. Part Number Description
Supplier
1 BMJ185W/GTC BRANCH JOINT- 185mm² (NO RESIN)
2 BMJ300W/GTC BRANCH JOINT - 300mm² (NO RESIN)
3 BMJ95W/EME/C MAINS BRANCH JOINT 95mm²
4 BMJ95W/GTC BRANCH JOINT, inc RESIN - 95mm² - NO RESIN
5 EAC1J15WLH 15 WAY MSDB ST LH INCOMING MECH CONNECTOR
6 EAC1J15WRH 15 WAY MSDB ST RH INCOMING MECH CONNECTOR
7 EAC1J24WRH 24 WAY MSDB ST RH INCOMING MECH CONNECTOR
8 EAC1J30WLH 30 WAY MSDB ST LH INCOMING MECH CONNECTOR
9 EAC1J30WRH 30 WAY MSDB ST RH INCOMING MECH CONNECTOR
10 EAC1J45WDD MSDB 1J 45 WAY DBL DOOR C/W 100A HSCO
11 EAC1J45WLH 45 WAY MSDB ST LH INCOMING MECH CONNECTOR
12 EAC2J24WRH MSDB 2J 24 WAY RH
2 WAY J TYPE 30 WAY MSDB LH INCOMING MECH
13 EAC2J30WLH
CONN
14 EAC374LSF01 374LSF01 2 BOLT LSOH CABLE CLEAT
Material
S.No
Part Number Description Supplier
35 EL6ASLKIT STREET LIGHTING CUT OUT KIT
36 ELBET120-12 BRASS S/O NEUTRAL LUG 185/300WF 12mm HOLE
37 ELBET120-16 BRASS S/O NEUTRAL LUG 185/300WF 16mm HOLE
38 ELBET60-12 BRASS S/O NEUTRAL LUG 95WF 12mm HOLE
39 ELBET60-16 BRASS S/O NEUTRAL LUG 95WF 16mm HOLE
40 ELC35ACPC-100M 35mm CNE Service Cable - 100m drum
1 PHASE 35mm SNE LSOH SERVICE CABLE - 100m
41 ELC35ACSCLS-100
DRUM
35mm² SPILT CONCENTRIC CABLE LSOH - IDNO
42 ELC35ACSCLSIDNO
ONLY
43 ELC3X185ACWC 3 x 185mm² WAVEFORM
44 ELC3X25ACPC 3X25mm² AL/CU PLAIN CONCENTRIC LV CABLE
45 ELC3X300ACWC 3 x 300mm² WAVEFORM
46 ELC3X35ACPC 3 x 35mm² Al/Cu PLAIN CONCENTRIC LV CABLE
47 ELC3X35ACSC 3 x 35mm² AL/CU SPILT CONCENTRIC LV CABLE
CABLE 3 CORE CONCENTRIC SPILT LV 3x35mm²
48 ELC3X35ACSCLS
LSOH
49 ELC3X95ACWC 3 x 95mm²WAVEFORM
Material
S.No. Part Number Description
Supplier
1PH SERVICE TO SERVICE BRANCH JOINT,INC RESIN
74 NSEJ1PBR35
(2P)-35 mm²
1PH SERVICE TO SERVICE STRAIGHT JOINT,INC
75 NSEJ1PST35
RESIN (2P)-35 mm²
76 NSEJ3PBR35 BRANCH JOINT, inc RESIN(2p) - 35mm²
77 NSEJ3PSJ35 SERVICE STRAIGHT JOINT, INC RESIN (2P)-35 mm²
78 NSEJBR185 BRANCH JOINT, inc RESIN(2p) - 185mm²
79 NSEJBR300 BRANCH JOINT, inc RESIN(2p)
80 NSEJBR95 BRANCH JOINT, inc RESIN(2p) - 95mm²
81 NSEJPK30IDNO 95mm² MAINS STRAIGHT JOINT (2P, OLD SHELL)
82 NSEJPK51SPJ 300mm² 3-CORE WAVEFORM BRANCH JOINT
3x35mm² MAINS BRANCH JOINT (WITH 2
83 NSEJPKSBJ5IDNO2
ADDITIONAL CONNECTORS)
84 NSEJPKSE1SPJ 4-35mm² SINGLE PHASE CNE SERVICE POT END
85 NSEJSE95185 STOP END KIT, INC RESIN (2P) - 95/185mm²
86 NSEJSER300 SERVICE JOINT, INC RESIN (2P) - 300mm²
87 NSEJSER95185 SERVICE JOINT, INC RESIN (2P) - 95/185mm²
88 NSEJST185 STRAIGHT JOINT, INC RESIN (2P) - 185mm²
Material
S.No. Part Number Description
Supplier
110 EF25AHOUSE22 HOUSE SERVICE FUSE 25 AMP SMALL DIAMETER
111 EF315MJ30-7 FEEDER PILLAR FUSE 315 AMPS 82mm FIXINGS
112 EF315MJ31-7 FEEDER PILLAR FUSE 315 AMPS 92mm FIXINGS
113 EF355PJ31-7 FEEDER PILLAR FUSE 355 AMPS 92mm FIXINGS
114 EF400AJP FEEDER PILLAR FUSE 400 AMPS 82mm FIXINGS
115 EF400PJ31-7 FEEDER PILLAR FUSE 400 AMPS 92mm FIXINGS
116 EF500SL92 92mm SOLID LINKS (set of 3)
117 EF60AHOUSE 60A HOUSE SERVICE FUSE BS1361 - 60LR85
118 ES500RJ31-7 J(Type) 500A FUSESs 92mm CENTRES
119 ELC120CEWCOV 120mm² GREEN/YELLOW EARTH CABLE
Material
S.No. Part Number Description
Supplier
151 ERH02W CONCRETE INSPECTION PIT
152 JG253 SQUARE TAPE CLAMP 4 WAY/CROSS
153 NM253B DC CLIP PLASTIC 25mm²X3mm² TAPE
154 DCB253 COPPER DC CLIP 25mm²X3mm² TAPE
155 EBC100 SINGLE WAY EARTH BAR, DISCONNECTING LINK
156 EBC006 6 WAY EARTH BAR
6 WAY EARTH BAR WITH SINGLE DISCONNECTING
157 EBC106
LINK
158 EBC008 8 WAY EARTH BAR
159 BBO200 BRAID BONDS (200MM HOLE CENTRE)
JOINTING TECHNOLOGY
160 BBO400 BRAID BONDS (400MM HOLE CENTRE)
161 EBI002 INSULATOR M10 C/W STUDS AND NUTS
162 EBG25P BENTONITE 25KG SACK
163 DT510 DENSO TAPE 50MMX10M
164 CL406 SELF LOCKING CLEAT 40MMX6MM TAPE
165 CL404 SELF LOCKING CLEAT 40MMX4MM TAPE
40MMX6MM ALUMINIUM TAPE (50M COIL) PER
166 TA406
METRE
167 BCT256 25x6MM BARE COPPER TAPE (40M)
168 BCT404 40X4MM BARE COPPER TAPE (30M)
169 16BSTR 16MM BARE STRANDED COPPER CABLE (50M)
170 70BSTR 70MM BARE STRANDED COPPER CABLE (50M)
171 70GYSTR 70MM G/Y STRANDED COPPER CABLE (50M)
172 120BSTR 120MM BARE STRANDED COPPER CABLE (50M)
173 120GYSTR 120MM G/Y STRANDED COPPER CABLE (50M)
174 TC254 25x4MM BARE COPPER TAPE (50M)
175 EA-16CU6491X-GY 16MM G/Y STRANDED COPPER CABLE (50M)
176 VDA3J95BCOBRE 95mm² 3 CORE LSOH ORANGE CABLE
PRYSMIAN
Material
S.No. Part Number Description
Supplier
185-300mm²MAINS/SERVICE BRANCH THREE PHASE
189 GTC-MSB300/4S
(10ltr)
95 mm²WAVEFORM MAINS POT END - RESIN FILLED
190 GTC-MSE-3W95R
(4ltr)
185-300 mm²WAVEFORM MAINS POT END - RESIN
191 GTC-MSE-3W300R
FILLED
192 GTC-MSE-3W95HS 95 mm²WAVEFORM MAINS POT END - HEATSHRINK
GTC-MSE- 185-300 mm²WAVEFORM MAINS POT END -
193
3W300HS HEATSHRINK
CABLE SERVICE
194 GTC-SSJ-1P 4-35 mm² CNE STRAIGHT JOINT SINGLE PHASE
195 GTC-SBJ-1P 4-35 mm²CNE BRANCH JOINT SINGLE PHASE
196 GTC-SSJ-3P 4-35 mm²CNE STRAIGHT JOINT THREE PHASE
197 GTC-SBJ-3P 4-35 mm²CNE BRANCH JOINT THREE PHASE
198 GTC-SE-1P 4-35 mm²CNE HEATSHRINK SINGLE PHASE STOP END
199 GTC-SE-3P 4-35 mm²CNE HEATSHRINK THREE PHASE STOP END
200 TNLK-MMS-95-FR 95 mm²WAVEFORM MAINS STRAIGHT JOINT
201 TNLK-MMS-185-FR 185 mm² WAVEFORM MAINS STRAIGHT JOINT
15-2J-LH-DD-3C- LUCY MSDB 15 WAY 2J LEFT HAND DOUBLE DOOR 3
202
BN CORE BOTTOM NEUTRAL
TYCO/CE (56168) 4 WAY CNE LV UNDERGROUND
203 BAH038110101
LINK BOX
Appendix 2
HIGH VOLTAGE EQUIPMENT INCLUDING UNDERGROUND CABLES, JOINTS &
TERMINATIONS
PRYSMIAN
214 VKBDTJ95ZFOCRD
11KV
215 VKBDTJ95ZQOCRD 3X1X95SAC XLPE WST CU/W (35) WST MDPE 11KV
216 VKBDTL18ZCOCRD 3X1X185 SAC XLPE CU/W (25) MDPE 11KV
3X1X185SAC XLPE WST EW CU/W (35) WST MDPE
217 VKBDTL18ZFOCRD
11KV
218 VKBDTL18ZQOCRD 3X1X185SAC XLPE WST CU/W (35) WST MDPE 11KV
219 VKBDTL30ZCOCRD 3X1X300 SAC XLPE CU/W (25) MDPE 11KV
3X1X300SAC XLPE WST EW CU/W (35) WST MDPE
220 VKBDTL30ZFOCRD
11KV
221 VKBDTL30ZQOCRD 3X1X300SAC XLPE WST CU/W (35) WST MDPE 11KV
222 VKCD3K95JDOCRD 3 x 95SAC XLPE CU/W (70) + EQ RED MDPE 11KV
223 VKCD3L18JPOCRD 3 x 185SAC XLPE CU/W (95) + EQ RED MDPE 11KV
224 VKCD3L30JPOCRD 3 x 300SAC XLPE CU/W (95) + EQ RED MDPE 11KV
225 VKEDTJ95ZCWCRD 3X1X95 SAC EPR CU/W (35) MDPE 11KV
226 VKEDTL18ZCWCRD 3X1X185 SAC EPR CU/W (35) MDPE 11KV
227 VKEDTL30ZCWCRD 3X1X300 SAC EPR CU/W (35) MDPE 11KV
228 IXSU-F3121-GB03 70-95MM² AL TRIPLEX TERMINATION KIT
229 IXSU-F3131-GB08 185-300MM² AL TRIPLEX TERMINATION KIT
230 IXSU-F3141-GB03 300MM² CU TRIPLEX TERMINATION KIT
CABLE SERVICE
SERVICE
CABLE
EPKB12C1XU2XU- 185-30MM² H/S TRIPLEX BRANCH JOINT ONE PER
237
GB04 PHASE
EPKB12C1XU2XU- 300MM² MAIN 95MM BRANCH H/S TRIPLEX BRANCH
238
GB05 JOINT ONE PER PHASE
Appendix 3
DISTRIBUTION SUBSTATIONS - PLANT, EQUIPMENT & HOUSING
Material
S.No Part Number Description Supplier
239 GTC/POWER ON TRANSFORMER 315KVA ONAN /OIL FILLED
240 GTC/POWER ON TRANSFORMER 500KVA ONAN /OIL FILLED
241 GTC/POWER ON TRANSFORMER 800KVA ONAN /OIL FILLED
242 GTC/POWER ON TRANSFORMER 1000KVA ONAN /OIL FILLED
243 GTC/POWER ON TRANSFORMER M315KVA MIDEL
244 GTC/POWER ON TRANSFORMER M500KVA MIDEL
245 GTC/POWER ON TRANSFORMER M800KVA MIDEL
246 GTC/POWER ON TRANSFORMER M1000KVA MIDEL
247 GTC/POWER ON STANDARD RN2C-T1/21 (TLF PROTECTION)
248 GTC/POWER ON STANDARD RN2C-T2/21 (VIP300 PROTECTION)
249 GTC/POWER ON STANDARD CN2-T6 (TLF PROTECTION)
250 GTC/POWER ON STANDARD CN2-T1 (VIP300 PROTECTION)
251 GTC/POWER ON SN6-S1 (SWITCH DISCONNECTOR)
252 GTC/POWER ON GTC RN2C T1/21 TM (TLF PROTECTION)
253 GTC/POWER ON GTC RN2C T2/21 (VIP PROTECTION)
254 GTC/POWER ON GTC - 1600A 4WAY
255 GTC/POWER ON GTC - 1600A 5WAY
SCHNEIDER
256 GTC/POWER ON GTC - 1600A 6WAY
257 GTC/POWER ON GTC - 1600A 7WAY
258 GTC/POWER ON GTC - 800A 800A ACB + 1W
259 GTC/POWER ON GTC - 1600A 1250A ACB + 1W
260 GTC/POWER ON GTC - 1600A 1600A ACB + 1W
800A ACB CABINET WITH 3-POLE NW08 H1
261 GTC/POWER ON
MICROLOGIC 5.0
1200A ACB CABINET WITH 3-POLE NW12 H1 MICRO
262 GTC/POWER ON
LOGIC 5.0
1600A ACB CABINET WITH 3-POLE NW16 H1 MICRO
263 GTC/POWER ON
LOGIC 5.0
2000A ACB CABINET WITH 3-POLE NW20 H1 MICRO
264 GTC/POWER ON
LOGIC 5.0
2500A ACB CABINET WITH 3-POLE NW25 H1 MICRO
265 GTC/POWER ON
LOGIC 5.0
3200A ACB CABINET WITH 3-POLE NW32 H1 MICRO
266 GTC/POWER ON
LOGIC 5.0
800A ACB CAB WITH 3-POLE NW08 H1 MICRO LOGIC
267 GTC/POWER ON
6.0 (EARTH FAULT PROTECTION)
1200A ACB CAB WITH 3-POLE NW12 H1 MICRO LOGIC
268 GTC/POWER ON
6.0 (EARTH FAULT PROTECTION)
1600A ACB CAB WITH 3-POLE NW16 H1 MICRO LOGIC
269 GTC/POWER ON
6.0 (EARTH FAULT PROTECTION)
Material
S.No Part Number Description Supplier
2000A ACB CAB WITH 3-POLE NW20 H1 MICRO LOGIC
270 GTC/POWER ON
6.0 (EARTH FAULT PROTECTION)
2500A ACB CAB WITH 3-POLE NW25 H1 MICRO LOGIC
271 GTC/POWER ON
6.0 (EARTH FAULT PROTECTION)
3200A ACB CAB WITH 3-POLE NW32 H1 MICRO LOGIC
272 GTC/POWER ON
6.0 (EARTH FAULT PROTECTION)
800A INC DISCONNECTOR & 4X630A SHIELDED
273 GTC/POWER ON
OUTGOING FUSEWAYS, EATS 37-2 ISSUE 4
1600A INC DISCONNECTOR & 4X630A SHIELDED
274 GTC/POWER ON
OUTGOING FUSEWAYS, EATS 37-2 ISSUE 4
800A INC DISCONNECTOR & 4X630A SAIF OUTGOING
275 GTC/POWER ON
FUSEWAYS, EATS 37-2 ISSUE 4
1600A INC DISCONNECTOR AND 4X630A SAIF
276 GTC/POWER ON
OUTGOING FUSEWAYS, EATS 37-2 ISSUE 4
SHIELDED CAB WITH 1001T I/C DISCONNECTOR,
277 GTC/POWER ON 1XNS800N MICRO LOGIC 2.0 MCCB & 2X630A
SHIELDED
SHIELDED CAB WITH 2001T I/C DISCONNECTOR,
278 GTC/POWER ON 1XNS1250N MICRO LOGIC 2.0 MCCB & 2X630A
SHIELDED
SAIF CAB WITH 1001T I/C DISCONNECTOR,
279 GTC/POWER ON
1XNS800N MICRO LOGIC 2.0 MCCB & 1X630A SAIF
SAIF CAB WITH 2001T I/C DISCONNECTOR,
280 GTC/POWER ON 1XNS1250N MICRO LOGIC 2.0 MCCB AND 1X630A
SCHNEIDER
SAIF
281 GTC/POWER ON NS400N 3-P MCCB CABINET (UP TO 315KVA)
282 GTC/POWER ON NS400N 4-P MCCB CABINET (UP TO 315KVA)
283 GTC/POWER ON NS630N 3-P MCCB CABINET (315 - 500KVA)
284 GTC/POWER ON NS630N 4-P MCCB CABINET (315 - 500KVA)
285 GTC/POWER ON NS800N 3-P MCCB CABINET (315 - 500KVA)
286 GTC/POWER ON NS800N 4-P MCCB CABINET (315 - 500KVA)
287 GTC/POWER ON NS1250N 3-P MCCB CABINET (500 - 800KVA)
288 GTC/POWER ON NS1250N 4-P MCCB CABINET (500 - 800KVA)
289 GTC/POWER ON NS1600N 3-P MCCB CABINET (500 - 1000KVA
290 GTC/POWER ON NS1600N 4-P MCCB CABINET (500 - 1000KVA)
291 GTC/POWER ON NW08 H1 3-P ACB CABINET (315 - 500KVA)
292 GTC/POWER ON NW08 H1 4-P ACB CABINET (315 - 500KVA)
293 GTC/POWER ON NW12 H1 3-P ACB CABINET (500 - 800KVA)
294 GTC/POWER ON NW12 H1 4-P ACB CABINET (500 - 800KVA)
295 GTC/POWER ON NW16 H1 3-P ACB CABINET (800 - 1000KVA)
296 GTC/POWER ON NW16 H1 4-P ACB CABINET (800 - 1000KVA)
297 GTC/POWER ON NW20 H1 3-P ACB CABINET (800 - 1250KVA)
298 GTC/POWER ON NW20 H1 4-P ACB CABINET (800 - 1250KVA)
299 GTC/POWER ON NW25 H1 3-P ACB CABINET (800 - 1600KVA)
300 GTC/POWER ON NW25 H1 4-P ACB CABINET (800 - 1600KVA)
301 GTC/POWER ON NW32 H1 3-P ACB CABINET (10000 - 2000KVA)
302 GTC/POWER ON NW32 H1 4-P ACB CABINET (10000 - 2000KVA)
Material
S.No Part Number Description Supplier
GRP HOUSING WITH LOCKING SHROUD GTC Envico
303 GTC/POWER ON
SPEC Engineering
GRP HOUSING WITH LOCKING SHROUD Morgan
304 GTC/POWER ON
SCOTISH POWER SPEC Marine
GRP HOUSING WITH LOCKING SHROUD SSE Morgan
GTC/POWER ON
305 SPEC Marine
GTC/POWER ON SUBSTATION FLOODGATE
306 JT Atkinson
307 GTC/POWER ON ROXTEC DUCT SEALS Roxtec