Protection and Control
• Six-stage phase overcurrent protection (50/51P, 67P)
41
www.nrec.com/en
The zero sequence current of the No.1 group of zero This protection can support all kinds of VT connection:
sequence overcurrent protection can be derived from a three phase voltage (Ua, Ub, Uc), three phase-to-phase
dedicated zero sequence current transformer or be voltages (Uab, Ubc, Uca), two phase-to-phase voltages
self-calculated, and the zero sequence current of the No.2 (Uab, Ubc), anyone of three phase voltages or anyone of
group of zero sequence overcurrent protection only can be led three phase-to-phase voltages. This relay can support
from another dedicated zero sequence current transformer. two voltage input modes: phase-to-phase voltage or
phase voltage. And two methods are used to check the
• Sensitive earth fault protection (51SEF, 67SEF)
undervoltage condition: check all input voltages or check
This relay provides a six-stage sensitive earth fault protection any input voltage.
with independent time delay characteristics. Each stage can
• Overvoltage protection (59P)
be enabled or disabled independently by the corresponding
logic setting respectively, and can be controlled by the This relay provides a two-stage overvoltage protection with
directional element respectively. Each stage also can be set definite time delay characteristics. The two stages have same
with inverse definite minimum time (IDMT) characteristic, and protection logics. Each stage can be used for tripping or alarming,
each stage can be configured for tripping or alarming. and each stage of overcurrent protection can be set as either
definite time (DT) or inverse definite minimum time (IDMT).
• Negative sequence overcurrent protection (50/51Q)
This protection can support all kinds of VT connection: three
This relay provides a two-stage negative sequence overcurrent
phase voltage (Ua, Ub, Uc), three phase-to-phase voltages
protection with independent time delay characteristics. Each
(Uab, Ubc, Uca), two phase-to-phase voltages (Uab, Ubc),
stage can be enabled or disabled by scheme logic settings
anyone of three phase voltages or anyone of three
independently. Each stage also can be set with inverse definite
phase-to-phase voltages. This relay can support two voltage
minimum time (IDMT) characteristic.
input modes: phase-to-phase voltage or phase voltage. And
• Switch onto fault protection (SOTF) two methods are used to check the overvoltage condition:
check all input voltages or check any input voltage.
Switch onto fault overcurrent protection and zero sequence
accelerated overcurrent protection are equipped in this relay. • Zero sequence overvoltage protection (59G)
Acceleration before or after tripping can be configured.
On a healthy three-phase power system, the addition of each
Acceleration after tripping includes accelerated tripping for
of the three-phase to earth voltages is nominally zero.
manual switching-onto-fault or automatic reclosing-onto-fault.
However, when an earth fault occurs on the primary system,
The current settings and delays of these two accelerated
the balance is upset and a residual voltage is produced.
tripping protections can be configured independently.
Hence, a zero sequence overvoltage protection can be used to
• Undercurrent protection (37) offer earth fault protection on such a system.
This relay provides a one-stage undercurrent protection for This relay provides a two-stage zero sequence overvoltage
monitoring a motor or a capacitor. If the circuit breaker of the protection with definite time (DT) delay or inverse definite
protected equipment is closed and the current is less than the minimum time (IDMT) characteristics. The two stages have
predefined setting, the undercurrent protection will operate. same protection logics.
• Cold load pickup logic (CLP) • Negative sequence overvoltage protection (59Q)
The cold load pickup (CLP) logic which is included within this On a healthy three-phase power system, the negative
relay serves to either inhibit the selected protective elements sequence voltage is nominally zero. However, when an
for an appointed duration, or to raise the settings of the unbalance situation occurs on the primary system, the
selected protective elements. Therefore, it allows the negative sequence voltage is produced.
protection settings to be set closer to the load profile by
This relay provides a two-stage negative sequence
automatically increasing them following circuit energization.
overvoltage protection with definite time (DT) delay or inverse
The CLP logic thus provides stability, whilst maintaining
definite minimum time (IDMT) characteristics. The negative
protection during starting.
sequence voltage is self-calculated.
• Undervoltage protection (27P)
• Unbalance current/voltage protection (60C/V)
This relay provides a two-stage undervoltage protection with
This relay provides a two-stage unbalance current protection,
definite time delay characteristics. The two stages have same
each stage of unbalance current protection also supports for
protection logics. Each stage can be used for tripping or
tripping and alarming. The two stages have the same logics.
alarming. If the system voltage is lost, the undervoltage
protection is blocked. The circuit breaker state is taken into This relay provides a two-stage unbalance voltage protection,
account in the undervoltage protection logic. When the circuit each stage of unbalance voltage protection also supports for
breaker is opened, the undervoltage protection is not in service. tripping and alarming. The two stages have the same logics.
42
PCS S Series
• Reverse power protection (32R) Monitoring and Measurement
The aim of the reverse power protection is to detect the • CT circuit failure supervision
inverse flow of energy and to ensure that the motor does not
• VT circuit failure supervision
feed the fault which has appeared on the network.
• System frequency supervision
This relay provides a two-stage reverse power protection with
definite time delay characteristic. • Fault phase selection
This relay provides three check modes for the automatic • Full compatibility between IEC 61850 Editions 1 and 2
reclosing function: synchronism check mode (25), dead check
• Redundancy protocols PRP and HSR
mode and non-check mode.
• One front RJ-45 port for debugging
• Manual closing function