0% found this document useful (0 votes)
1K views

TLS485 Manual en

This document provides instructions for installing and using the TLS485 weighing instrument. It contains information about safety symbols, warranty, guidelines for proper disposal, technical specifications, electrical connections, menu navigation, programming system parameters such as calibration, filters, outputs/inputs configuration, setpoints, alarms, and serial communication settings. The document also includes declarations of conformity and instructions reserved for installers regarding menu locking, program selection, and keypad locking.

Uploaded by

phat nguyen minh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views

TLS485 Manual en

This document provides instructions for installing and using the TLS485 weighing instrument. It contains information about safety symbols, warranty, guidelines for proper disposal, technical specifications, electrical connections, menu navigation, programming system parameters such as calibration, filters, outputs/inputs configuration, setpoints, alarms, and serial communication settings. The document also includes declarations of conformity and instructions reserved for installers regarding menu locking, program selection, and keypad locking.

Uploaded by

phat nguyen minh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 52

ENGLISH ENGLISH ENGLISH ENGLISH

Installation and User Manual


version 1.15

TLS485

2014/30/UE

EN55022:2010 EN61000-6-2:2005 EN61000-6-4:2007


SYMBOLS

Here are the symbols used in the manual to draw the reader's attention:

Caution! Risk of electric shock.

Caution! This operation must be performed by skilled personnel.

Pay particular attention to the following instructions.

Further information.

WARRANTY
24 months from the date of the delivery note. Warranty covers only failures of defective components (due to construction
defects or defects in materials) and includes replacement or repair of the components and related labor costs.
Warranty is automatically forfeited in the event of:
- tampering, deletion, removal of the identification label and/or serial number of the product
- misuse, transformation, alteration, repair of products not carried out by Laumas personnel
Laumas provides a 1-year warranty from the date of the delivery note on defects in material or manufacture of the battery.

GUIDELINES FOR PROPER DISPOSAL

This symbol on the product or packaging indicates that:


- This is electrical/electronic equipment and cannot be disposed of as municipal solid waste, but must be delivered
to a recycling center
- Improper use or disposal can pollute the environment or damage human health
- Non-compliance with these guidelines will be penalized in accordance with the regulations in force in the country
of destination
- It is recommended to dispose of the packing and packaging as required by local regulations
TABLE OF CONTENTS

USER WARNINGS ................................................................................................................... 1


RECOMMENDATIONS FOR CORRECT INSTALLATION OF WEIGHING INSTRUMENTS ... 1
RECOMMENDATIONS FOR CORRECT INSTALLATION OF THE LOAD CELLS ................ 2
LOAD CELL INPUT TEST (QUICK ACCESS) .......................................................................... 4
LOAD CELL TESTING ............................................................................................................... 4
MAIN SPECIFICATIONS OF THE INSTRUMENT ................................................................... 5
TECHNICAL SPECIFICATIONS .............................................................................................. 6
ELECTRICAL CONNECTIONS ................................................................................................ 7
BASIC INFORMATION............................................................................................................... 7
WIRING DIAGRAM..................................................................................................................... 7
LED AND KEY FUNCTIONS .................................................................................................... 8
MENU MAP .............................................................................................................................. 9
SETPOINTS ................................................................................................................................ 9
SYSTEM PEREMETERS ........................................................................................................... 9
INSTRUMENT COMMISSIONING.......................................................................................... 10
PROGRAMMING OF SYSTEM PARAMETERS .................................................................... 11
THEORETICAL CALIBRATION ............................................................................................... 11
MAXIMUM CAPACITY ...................................................................................................................... 12
TARE WEIGHT ZERO SETTING ...................................................................................................... 12
ZERO VALUE MANUAL ENTRY ...................................................................................................... 12
REAL CALIBRATION (WITH SAMPLE WEIGHTS) ................................................................ 13
FILTER ON THE WEIGHT ....................................................................................................... 14
ANTI PEAK ........................................................................................................................................ 14
ZERO PARAMETERS .............................................................................................................. 15
RESETTABLE WEIGHT SETTING FOR SMALL WEIGHT CHANGES .......................................... 15
AUTOMATIC ZERO SETTING AT POWER ON ............................................................................... 15
ZERO TRACKING ............................................................................................................................. 15
SETTING UNITS OF MEASURE .............................................................................................. 15
DISPLAY COEFFICIENT .................................................................................................................. 16
OUTPUTS AND INPUTS CONFIGURATION .......................................................................... 17
SEMI-AUTOMATIC TARE (NET/GROSS) ............................................................................... 19
PRESET TARE (SUBTRACTIVE TARE DEVICE) ................................................................... 19
SEMI-AUTOMATIC ZERO (WEIGHT ZERO-SETTING FOR SMALL VARIATIONS) ............ 20
PEAK ........................................................................................................................................ 20
SERIAL COMMUNICATION SETTING .................................................................................... 21
RS485 SERIAL CONNECTION ........................................................................................................ 22
DIRECT CONNECTION BETWEEN RS485 AND RS232 WITHOUT CONVERTER ...................... 23
TEST ......................................................................................................................................... 23
SETPOINTS PROGRAMMING............................................................................................... 24
ALARMS ................................................................................................................................. 24
FAST CONTINUOUS TRANSMISSION PROTOCOL............................................................ 26
CONTINUOUS TRANSMISSION PROTOCOL TO REMOTE DISPLAYS............................. 27
ASCII BIDIRECTIONAL PROTOCOL .................................................................................... 28
MODBUS-RTU PROTOCOL .................................................................................................. 33
MODBUS SUPPORTED FUNCTIONS ................................................................................... 34
EXCEPTIONAL RESPONSE.................................................................................................. 35
RESERVED FOR THE INSTALLER ...................................................................................... 43
MENU LOCKING ...................................................................................................................... 43
MENU UNLOCKING ................................................................................................................. 43
TEMPORARY MENU UNLOCKING ......................................................................................... 43
PROGRAM SELECTION AND DATA DELETION ................................................................... 43
KEYPAD OR DISPLAY LOCKING .......................................................................................... 44
DECLARATION OF CONFORMITY - EU............................................................................... 45
USER WARNINGS

RECOMMENDATIONS FOR THE PROPER USE OF WEIGHING INSTRUMENT


- Keep away from heat sources and direct sunlight
- Repair the instrument from rain (except special IP versions)
- Do not wash with water jets (except special IP versions)
- Do not dip in water
- Do not spill liquid on the instrument
- Do not use solvents to clean the instrument
- Do not install in areas subject to explosion hazard (except special Atex versions)

RECOMMENDATIONS FOR CORRECT INSTALLATION OF WEIGHING INSTRUMENTS

The terminals indicated on the instrument’s wiring diagram to be connected to earth must have
the same potential as the weighed structure (same earthing pit or earthing system). If you are
unable to ensure this condition, connect with an earthing wire the terminals of the instrument
(including the terminal 0 VDC) to the weighed structure.
The cell cable must be individually led to its panel input and not share a conduit with other cables;
connect it directly to the instrument terminal strip without breaking its route with support terminal strips.
Use “RC” filters on the instrument-driven solenoid valve and remote control switch coils.
Avoid inverters in the instrument panel; if inevitable, use special filters for the inverters and separate
them with sheet metal partitions.
The panel installer must provide electric protections for the instruments (fuses, door lock switch etc.).
It is advisable to leave the equipment always switched on to prevent the formation of condensation.

MAXIMUM CABLE LENGTHS


- RS485: 1000 metres with AWG24, shielded and twisted cables
- RS232: 15 metres for baud rates up to 19200

-1-
RECOMMENDATIONS FOR CORRECT INSTALLATION OF THE LOAD CELLS

SIZING OF LOAD CELLS CAPACITY


For safety reasons, in case of static weighing, it is advisable to use the load cells at a maximum of 70-
80% of its nominal capacity (assuming that the load is uniformly distributed over the entire weighed
structure); depending on the handling mode of the load to weigh, consider to further reduce the % of
load with respect to the nominal capacity (ex.: forklifts handling, bridge cranes, etc.).

In case of weighing with dynamic loads, the installer has to estimate the thrust speed, the acceleration,
the frequency, etc.

INSTALLING LOAD CELLS


The load cells must be placed on rigid, stable in-line structures; it is important to use the mounting
modules for load cells to compensate for misalignment of the support surfaces.

PROTECTION OF THE CELL CABLE


Use water-proof sheaths and joints in order to protect the cables of the cells.

MECHANICAL RESTRAINTS (pipes, etc.)


When pipes are present, we recommend the use of hoses and flexible couplings with open mouthpieces
with rubber protection; in case of hard pipes, place the pipe support or anchor bracket as far as possible
from the weighed structure (at a distance at least 40 times the diameter of the pipe).

CONNECTING SEVERAL CELLS IN PARALLEL


Connect several cells in parallel by using - if necessary - a watertight junction box with terminal box.
The cell connection extension cables must be shielded, led individually into their piping or conduit and
laid as far as possible from the power cables (in case of 4-wire connections, use cables with 4x1 mm2
minimum cross-section).

WELDING
Avoid welding with the load cells already installed. If this cannot be avoided, place the welder ground
clamp close to the required welding point to prevent sending current through the load cell body.

WINDY CONDITIONS - KNOCKS – VIBRATIONS


The use of weigh modules is strongly recommended for all load cells to compensate for misalignment
of the support surfaces. The system designer must ensure that the plant is protected against lateral
shifting and tipping relating to: shocks and vibration; windy conditions; seismic conditions in the
installation setting; stability of the support structure.

-2-
EARTHING THE WEIGHED STRUCTURE
By means of a copper wire with suitable cross-section, connect the cell upper support plate with the
lower support plate, then connect all the lower plates to a single earthing system. Electrostatic charges
accumulated because of the product rubbing against the pipes and the weighed container walls are
discharged to the ground without going through or damaging the load cells. Failure to implement a
proper earthing system might not affect the operation of the weighing system; this, however, does not
rule out the possibility that the cells and connected instrument may become damaged in the future. It
is forbidden to ensure earthing system continuity by using metal parts contained in the weighed
structure.

FAILURE TO FOLLOW THE INSTALLATION RECOMMENDATIONS WILL BE CONSIDERED


A MISUSE OF THE EQUIPMENT

-3-
LOAD CELL INPUT TEST (QUICK ACCESS)

From the weight display, press for 3 seconds; the response signal of the load cells is
displayed, expressed in mV with four decimals.

LOAD CELL TESTING

Load cell resistance measurement (use a digital multimeter):

- Disconnect the load cells from the instrument and check that there is no moisture in the cell junction
box caused by condensation or water infiltration. If so, drain the system or replace it if necessary.
- The value between the positive signal wire and the negative signal wire must be equal or similar
to the one indicated in the load cell data sheet (output resistance).
- The value between the positive excitation wire and the negative excitation wire must be equal or
similar to the one indicated in the load cell data sheet (input resistance).
- The insulation value between the shield and any other cell wire and between any other cell wire
and the body of the load cell must be higher than 20 Mohm (mega ohms).

Load cell voltage measurement (use a digital multimeter):

- Take out the load cell to be tested from underneath the container, or alternatively, lift the container
support.
- Make sure that the excitation of two wires of the load cell connected to the instrument (or amplifier)
is 5 Vdc ±3%.
- Measure the response signal between the positive and the negative signal wires by directly
connecting them to the tester, and make sure that it is comprised between 0 and ±0.5 mV
(thousandths of a Volt).
- Apply load to the cell and make sure that there is a signal increment.

IF ONE OF THE ABOVE CONDITIONS IS NOT MET, PLEASE CONTACT THE TECHNICAL
ASSISTANCE SERVICE.

-4-
MAIN SPECIFICATIONS OF THE INSTRUMENT

PLC

DC power supplier
(12-24 Volt )

MAX 8 LOAD CELLS IN


PARALLEL RS485 SERIAL PORT

2 DIGITAL
OUTPUTS 2 DIGITAL INPUTS
(Opto relay) (Optoisolated,
Externally supplied)

TRANSMISSION BY RADIO MODULES, RS232


CONVERTER, PROFIBUS CONVERTER ETHERNET
PLC or FIELD SIGNALS
CONVERTER, MODEM GSM

- Weight indicator and transmitter for Omega/DIN rail mounting suitable for back panel or junction
box. Six-digit semi-alphanumeric display (8mm h), 7 segment. Four-key keyboard. Dimensions:
25x115x120 mm.
- IP67 box version (170x140x95mm). Four fixing holes diameter 4 mm (centre distance 122x152 mm).
- Displays the gross weight; from external contact allows to zero set or display the net weight (both
values will be lost when the instrument is turned off).
- Peak weight function.
- Transmits the gross or net weight via RS485 serial port, by means of protocols:
▫ Modbus RTU
▫ ASCII bidirectional protocol
▫ Continuous transmission

-5-
TECHNICAL SPECIFICATIONS

POWER SUPPLY and CONSUMPTION (VDC) 12 - 24 VDC +/- 10% ; 5 W


NO. OF LOAD CELLS IN PARALLEL and SUPPLY max 8 ( 350 ohm ) ; 5VDC/120mA
LINEARITY < 0.01% F.S.
THERMAL DRIFT < 0.0005 % F.S. /°C
A/D CONVERTER 24 bit (16.000.000 points)
MAX DIVISIONS (with measurement range: +/-10mV =
+/- 999999
sens. 2mV/V)
MEASUREMENT RANGE +/- 19.5 mV
MAX SENSITIVITY OF USABLE LOAD CELLS +/-3 mV/V
MAX CONVERSIONS PER SECOND 80 conversions/second
DISPLAY RANGE - 999999 ; + 999999
NO. OF DECIMALS / DISPLAY INCREMENTS 0 - 4 / x 1 x 2 x 5 x 10 x 20 x 50 x 100
DIGITAL FILTER / READINGS PER SECOND 10 levels / 5 – 80 Hz
OPTO RELAY OUTPUTS N.2 - max 24 VDC ; 60mA
DIGITAL INPUTS N.2 - optoisolated 5 - 24 VDC PNP
SERIAL PORTS RS485
BAUD RATE 2400, 4800, 9600, 19200, 38400, 115200
HUMIDITY (non condensing) 85 %
STORAGE TEMPERATURE - 30°C + 80°C
WORKING TEMPERATURE - 20°C + 60°C

OPTO RELAY OUTPUTS N.2 - max 24 VDC ; 60mA


Equipment to be powered by 12-24 Vdc LPS or Class 2 power source.

IP67 BOX VERSIONS

CASTL IP67 box with transparent cover


CASTLPG9 IP67 box with transparent cover and six M16x1.5 cable glands
CASTLGUA (1) IP67 box with transparent cover and six PVC fittings
CASTLTAST IP67 box with external keypad
CASTLTASTPG9 (2) IP67 box with external keypad and six M16x1.5 cable glands
CASTLTASTATEX (3) IP67 box with external keypad. ATEX version II3GD (zone 2, 22)
CASTLTASTGUA IP67 box with external keypad and six PVC fittings

(1) (2) (3)

-6-
ELECTRICAL CONNECTIONS

BASIC INFORMATION

- It is recommended that the power supply negative pole be grounded.


- It is possible to supply up to eight 350 ohm load cells or sixteen 700 ohm load cells.
- Connect terminal “0 VDC” to the RS485 common of the connected instruments in the event that
these receive alternating current input or that they have an optoisolated RS485.
- In case of an RS485 network with several devices it is recommended to activate the 120 ohm
termination resistance on the two devices located at the ends of the network, as described in the
paragraph RS485 SERIAL CONNECTION.

WIRING DIAGRAM

RS485 12-24Vdc

OUTPUTS
INPUTS 24Vdc
5-24Vdc 60mA

22 2324 25 26 27 28 29 30 31 32 33 34
RS485 termination
NET 0 kg g L
+ 12-24
0 VDC
IN1
IN2

OUT1
OUT2

- RS485
+ RS485
IN COM

0 TARE PRINT MENU


ESC Enter
J1 J2
POWER

6-WIRE LOAD CELL


TLS485
LOAD CELLS IN PARALLEL
+ SIG
+ SIG

+ SIG

+ SIG

SIG
SIG

SIG

SIG

+ EX
+ EX

+ EX

+ EX

EX
EX

EX

EX
+ SIG
SIG
+ EX
EX

SH

SH

SH

SH
SH

-
-
-
-

-
-

-
-
-
-

1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 1112 13 14 1516 1718 19 20 21


- EXCITATION
+ EXCITATION

+ REF
- REF
+ SIGNAL
- SIGNAL

2 outputs: settable setpoints or remote output management via protocol.


2 inputs (Default: SEMI-AUTOMATIC ZERO input 1; NET/GROSS input 2): settable to have the
following functions: SEMI-AUTOMATIC ZERO, NET/GROSS, PEAK or REMOTE CONTROL (see
paragraph OUTPUTS AND INPUTS CONFIGURATION)

-7-
LED AND KEY FUNCTIONS

LED Main function Secondary function *


net weight LED: net weight display (semi-
NET LED lit: input 1 closed
automatic tare or preset tare)
zero LED (deviation from zero not more than +/-
0 LED lit: input 2 closed
0.25 divisions)
stability LED LED lit: output 1 closed
kg unit of measure: kg LED lit: output 2 closed
g unit of measure: g no meaning
L other unit of measure no meaning

*) To activate the secondary LED function, during weight display press and hold down the keys
and at the same time (press immediately followed by ).

Long press
KEY Short press Into menus
(3 sec)
Cancel or return to
Tare resetting
previous menu
Select figure to be
Gross  Net Net  Gross modified or return to
previous menu item
Gross weight:
mV load cell test
Modify selected figure or
Net weight: go to next menu item
temporarily display
the gross weight
Setting setpoints and Confirm or enter in
hysteresis submenu
Setting general parameters

+ (press immediately
followed by )
Setting preset tare (press

+ immediately followed by

The LEDs light up in sequence to indicate that a setting and not a weight is being viewed.

-8-
MENU MAP

Within the menu, the changes are applied immediately after pressing the button (no further
confirmation).

SETPOINTS

SYSTEM PEREMETERS

-9-
INSTRUMENT COMMISSIONING

Upon switch-on, the display shows in sequence:


- instrument model (e.g.: “”);
- “” followed by the software code (e.g.: );
- program type:  (base);
- “” followed by the software version (e.g.: );
- “” followed by the hardware code (e.g.: );
- the serial number (e.g.: );

Check that the display shows the weight and that when loading the load cells there is an increase in
weight. If there is not check and verify the connections and correct positioning of the load cells.

- If the instrument has already been theoretical CALIBRATED (plant system identification tag
present on the instrument and on the cover: load cell’s rated data already entered):
o Reset to zero (follow the procedure in paragraph TARE WEIGHT ZERO SETTING)
o Check the calibration with sample weights and correct the indicated weight if necessary (follow
the procedure in paragraph REAL CALIBRATION (WITH SAMPLE WEIGHTS)).

- If the instrument HAS NOT BEEN CALIBRATED (missing plant system identification tag)
proceed with calibration:
o If load cells data are unknown, follow the procedure in paragraph REAL CALIBRATION (WITH
SAMPLE WEIGHTS)
o Enter the rated data of load cells following the procedure given in paragraph THEORETICAL
CALIBRATION
o Reset to zero (follow the procedure in paragraph TARE WEIGHT ZERO SETTING)
o Check the calibration with sample weights and correct the indicated weight if necessary (follow
the procedure in paragraph REAL CALIBRATION (WITH SAMPLE WEIGHTS)).

- If you use serial communication, set the related parameters (see paragraph SERIAL
COMMUNICATION SETTING).
- If setpoints are used, set the required weight values and the relevant parameters (see
paragraphs SETPOINTS PROGRAMMING and OUTPUTS AND INPUTS
CONFIGURATION).

- 10 -
PROGRAMMING OF SYSTEM PARAMETERS

From the weight display, press simultaneously keys and to access the parameter setting.
: to enter a menu/confirm the data entry.
: to modify the displayed value or menu item.
: to select a new value or modify the displayed menu item.
: to cancel and return to the previous menu.

THEORETICAL CALIBRATION

This function allows the load cell rated values to be set.

To perform the theoretical calibration set the following parameters in sequence:


- (Default: ): The system full scale is given by one cell capacity multiplied by the
number of cells used. Example of system full scale value calculation: 4 cells of 1000kg  FULL
SCALE = 1000 X 4 = 4000. The instrument is supplied with a theoretical full scale value 
corresponding to 10000. To restore factory values, set 0 as full scale.
- (Default: 2.00000 mV/V): Sensitivity is a load cell rated parameter expressed in mV/V. Set
the average sensitivity value indicated on the load cells. It’s possible to set a value between 0.50000
and 7.00000 mV/V. Example of 4-cell system with sensitivity: 2.00100, 2.00150, 2.00200, 2.00250;
enter 2.00175, calculated as (2.00100 + 2.00150 + 2.00200 + 2.00250) / 4.
- : The division (resolution) is the minimum weight increment value which can be displayed.
It is automatically calculated by the system according to the performed calibration, so that it is
equal to 1/10000 of full scale. It can be changed and be variable between 0.0001 and 100 with x1
x2 x5 x10 increments.

- By modifying the theoretical full scale or the sensitivity, the real calibration is cancelled
and the theoretical calibration only is considered valid.
- If the theoretical full scale and the recalculated full scale in real calibration (see section
REAL CALIBRATION (WITH SAMPLE WEIGHTS)) are equal, this means that the
calibration currently in use is theoretical; if they are different, the calibration in use is the
real calibration based on sample weights.
- By modifying the theoretical full scale or the sensitivity, the system’s parameters
containing a weight value will be set to default values (setpoint, hysteresis, etc.).

- 11 -
MAXIMUM CAPACITY

: Maximum displayable weight (from 0 to full scale; default: 0). When the weight exceeds this
value by 9 divisions the following is displayed ‘’. To disable this function, set 0.

TARE WEIGHT ZERO SETTING

This menu may also be accessed directly from the weight display, holding down the key
for 3 seconds.

Perform this procedure after having set the THEORETICAL CALIBRATION data.

Use this function to set to zero the weight of the empty system after commissioning and then later on
to compensate zero variations due to the presence of product residues.
Procedure:
- Confirm the message  (Zero) by pressing .
- The weight value to be set to zero is displayed. In this phase all of the LEDs are flashing.
- Confirming once again, the weight is set to zero (the value is stored to the permanent memory).
- Press to display the value of the total weight reset by the instrument, given by the sum of all
of the previous zero settings.

ZERO VALUE MANUAL ENTRY

WARNING: Perform this procedure only if it’s not possible to reset the weighed structure tare, for
example because it contains product that can not be unloaded.

Set in this parameter the estimated zero value (from 0 to 999999; default: 0).

- 12 -
REAL CALIBRATION (WITH SAMPLE WEIGHTS)

After having performed the THEORETICAL CALIBRATION and TARE WEIGHT ZERO SETTING,
this function allows correct calibration to be done using sample weights of known value, if
necessary, any deviations of the indicated value from the correct value to be corrected.

Load onto the weighing system a sample weight, which must be at least 50% of the maximum quantity
to be weighed.
By confirming the message the flashing value of the weight currently on the system is
displayed. In this phase all of the LEDs are off. Adjust the value on display by using the arrow keys if
necessary. After confirming, the new set weight will appear with all the LEDs flashing.

After an additional confirmation, the message will be restored and by repeatedly pressing
the key the weight will once again be displayed.

Example: for a system of maximum capacity 1000 kg and 1 kg division, two sample weights are
available, one of 500 kg and the other one of 300 kg. Load both weights onto the system and correct
the indicated weight to 800. Now remove the 300 kg weight, the system must show 500; remove the
500 kg weight, too; the system must read zero. If this does not happen, it means that there is a
mechanical problem affecting the system linearity.

CAUTION: identify and correct any mechanical problems before repeating the procedure.

- If theoretical full scale and recalculated full scale in real calibration are equal, it means that
the theoretical calibration is currently in use; otherwise, the real calibration based on
sample weights is in use.
- If the correction made changes the previous full scale for more than 20%, all the
parameters with settable weight values are reset to default values.

LINEARISATION OPTION ON MAX 8 POINTS:


It is possible to perform a linearisation of the weight repeating the above-described procedure
up to a maximum of eight points, using eight different sample weights. The procedure ends by
pressing the button or after entering the eighth value; at this point it will no longer be possible
to change the calibration value, but only to perform a new real calibration. To perform a new
calibration, should return to the weight display and then re-entering into the calibration menu. 
By pressing after having confirmed the sample weight that has been set, the full scale appears,
recalculated according to the value of the maximum sample weight entered and making reference to
the cell sensitivity set in the theoretical calibration ().

- 13 -
FILTER ON THE WEIGHT

Setting this parameter allows a stable weight display to be obtained.

To increase the effect (weight more stable) increase the value (from 0 to 9, default 4).
As seen in the diagram:
- By confirming the  message, the currently programmed filter value is displayed.
- By changing and confirming the value, the weight is displayed and it will be possible to experimentally
verify its stability.
- If stability is not satisfactory, confirming brings back the message and the filter may be
modified again until an optimum result is achieved.

The filter enables to stabilise a weight as long as its variations are smaller than the corresponding
“Response Time”. It is necessary to set this filter according to the type of application and to the full
scale value set.

Display and serial port refresh


FILTER VALUE Response times [ms]
frequency [Hz]
0 80 80
1 190 80
2 260 40
3 450 26
4 (default) 900 13
5 1700 13
6 2500 13
7 4200 10
8 6000 10
9 7500 5

ANTI PEAK

When the weight is stable, the anti peak filter removes any sudden disturbances with a maximum duration
of 1 second. Confirm the filter on the weight with ENTER and select one of the following options:
- : anti peak filter enabled (default);
- : anti peak filter disabled.

- 14 -
ZERO PARAMETERS

RESETTABLE WEIGHT SETTING FOR SMALL WEIGHT CHANGES

(from 0 to full scale; default: 300; considered decimals: 300 – 30.0 – 3.00 – 0.300): this
parameter indicates the maximum weight value resettable by external contact, keypad or serial
protocol.

AUTOMATIC ZERO SETTING AT POWER ON

(from 0 to 10% of full scale; default: 0): If at switch-on the weight value is lower than the
value set in this parameter, the weight is reset. To disable this function, set 0.

ZERO TRACKING

(from 1 to 5, default:): When the zero weight value is stable and, after a second, it
deviates from zero by a figure in divisions smaller or equal to the figure in divisions set in this
parameter, the weight is set to zero. To disable this function, set .
Example: if the parameter  is set to 5 and   is set to 2, the weight will be automatically
set to zero for variations smaller than or equal to 10 (x ).

SETTING UNITS OF MEASURE

Available unit of measure are:

: kilograms
: grams
: tons
: pounds*
: newton*
: litres*
: bar*
: atmospheres*
- 15 -
: pieces*
: newton metres*
: kikogram metres*
: other generic units of measure not included in the list*

If the print function is enabled, the symbol corresponding to the selected unit of measure will be printed
after the measured value.

For the units marked with * it’s possible to set also the display coefficient (parameter
, see the related paragraph). To use  is necessary to enable it, closing the
input (see paragraph OUTPUTS AND INPUTS CONFIGURATION).

DISPLAY COEFFICIENT

By setting the coefficient  the display is changed accordingly.

If one of the inputs is set to  mode (see paragraph OUTPUTS AND INPUTS
CONFIGURATION) when the input is closed the value will be displayed modified according to the
 coefficient; when the input is opened the standard weight display will be restored.

: (max settable value: 99.9999; default: 1.0000) will have different meanings according to the
value set in , i.e. the selected unit of measure. (see paragraph SETTING UNITS OF MEASURE).

If the unit of measure chosen is:


: pounds, the value set in  will be multiplied by the weight value currently displayed;
: newton, the value set in  will be multiplied by the weight value currently displayed;
: litres, in  set the specific weight in kg/l, assuming that the system is calibrated in kg;
: bar, the value set in  will be multiplied by the weight value currently displayed;
: atmosphere, the value set in  will be multiplied by the weight value currently displayed;
: pieces, in  set the weight of one piece;
: newton metres, the value set in  will be multiplied by the weight value currently
displayed;
: kilogram metres, the value set in  will be multiplied by the weight value currently
displayed;

- 16 -
: generic unit of measure not included in the list, the value set in  will be multiplied by
the weight value currently displayed.

CAUTION: All other settings (setpoints, hysteresis, calibration ...) are expressed in weight
value. If you want to convert them to the new unit of measurement, perform one of the
following procedures for changing the system calibration.
The parameter  must remain set to 1.0000.

THEORETICAL CALIBRATION’S CHANGE FOR OTHER UNITS OF MEASURE


Set in the parameter  the F.SCALE value divided by the conversion coefficient from kg to the
new unit of measure.
Example: The 4 load cells of 1000 kg are placed under a scale for olive oil, which has a specific gravity
of 0,916 kg / l. Setting the F.SCALE = (4x1000) / 0916 = 4367, the system works in liters of olive oil.
Also, if you set the parameter  =  (see paragraph SETTING UNITS OF MEASURE), the
system will display and print the symbol ‘l’ instead of ‘kg’.

REAL CALIBRATION’S CHANGE FOR OTHER UNITS OF MEASURE


Load a known quantity of product litres on the scale (equal to at least 50% of the maximum amount
that you must weigh) and enter in the parameter , the product loaded value in litres. Also, if
you set the parameter  =  (see paragraph SETTING UNITS OF MEASURE), the system
will display and print the symbol ‘l’ instead of ‘kg’.

OUTPUTS AND INPUTS CONFIGURATION

OUTPUTS
The outputs are set by default as follows:  /  /  / .

Possible operation modes:

- (normally open): the relay is de-energised and the contact is open when the weight is
lower than the programmed setpoint value; it closes when the weight is higher than or equal to the
programmed setpoint value.

- 17 -
- (normally closed): the relay is energised and the contact is closed when the weight is
lower than the programmed setpoint value; it opens when the weight is higher than or equal to the
programmed setpoint value.

- : the contact will switch on the basis of weight, according to setpoints (see paragraph SETPOINTS
PROGRAMMING).
- : the contact will not switch on the basis of weight, but is controlled by remote protocol
commands.
- : relay switching occurs when the weight is stable.

- If the operation mode  is selected, the following options are also active:
- : the contact will switch on the basis of gross weight.
- : the contact will switch on the basis of net weight (If the net function is not active, the contact
will switch on the basis of gross weight).

- : relay switching occurs for both positive and negative weight values.
- : relay switching occurs for positive weight values only.
- : relay switching occurs for negative weight values only.

By confirming with the setpoints operation can be set to the value ‘0’:
- : relay switching will not occur if the setpoint value is ‘0’.
- :
- Setpoint = ’0’ and =, relay switching occurs when the weight is ‘0’; the relay
will switch again when the weight is different from zero, taking hysteresis into account (both
for positive and for negative weights).
- Setpoint = ’0’ and =, relay switching occurs for a weight higher than or equal to
‘0’, the relay will switch again for values below ‘0’, taking hysteresis into account.
- Setpoint = ’0’ and =, relay switching occurs for a weight lower than or equal to
‘0’, the relay will switch again for values above ‘0’, taking hysteresis into account.

INPUTS
Default: input 1 =  input 2 = 

Possible operation modes:

-  (NET/GROSS): by closing this input for no more than one second, it’s making an operation
of SEMI-AUTOMATIC TARE and the display will show the net weight. To display the gross weight
again, hold the NET/GROSS input closed for 3 seconds.
- : by closing the input for no more than one second, the weight is set to zero (see paragraph
SEMI-AUTOMATIC ZERO (WEIGHT ZERO-SETTING FOR SMALL VARIATIONS)).
- : keeping the input closed the maximum weight value reached remains on display. Opening
the input the current weight is displayed.
- : closing the input no operation is performed, the input status may however be read remotely
by way of the communication protocol.

- 18 -
- : closing the input for max one second the weight is transmitted over the serial connection
according to the fast continuous transmission protocol only once (only if  is set in the
item ).
- : when the input is closed the weight is displayed based on the set coefficient (see setting
of the units of measure and coefficient), otherwise the weight is displayed.

SEMI-AUTOMATIC TARE (NET/GROSS)

THE SEMI-AUTOMATIC TARE OPERATION IS LOST UPON INSTRUMENT POWER-OFF.

To perform a net operation (SEMI-AUTOMATIC TARE), close the NET/GROSS input or press the
key for less than 3 seconds. The instrument displays the net weight (just set to zero) and the
NET LED lights up.
To display the gross weight again, keep the NET/GROSS input closed or press for 3 seconds.
This operation can be repeated many times by the operator to allow the loading of several products.

Example of weighing fruit in a box:


Put the box on the scale, the display shows the box weight, press and the display shows the
net weight to zero; by introducing the fruit in the box, the display shows the fruit weight. This
operation can be repeated several times.

During the net weight displaying, keep pressed the key to temporarily display
the gross weight. As soon as the key is released, the net weight will be displayed
again.

The semi-automatic tare operation is not allowed if the gross weight is zero.

PRESET TARE (SUBTRACTIVE TARE DEVICE)

It is possible to manually set a preset tare value to be subtracted from the display value
capacity condition is verified.

After setting the tare value, going back to the weight display, the display shows the net weight
(subtracting the preset tare value) and the NET LED lights up to show that a tare has been entered.

- 19 -
To delete a preset tare and return to gross weight display, hold down for about 3 seconds or
keep the NET/GROSS input (if any) closed for the same length of time (3 seconds). The preset tare
value is set to zero. The NET LED is turned off when the gross weight is displayed once again.

During the net weight displaying, keep pressed the key to temporarily display
the gross weight. As soon as the key is released, the net weight will be displayed
again.

- IF A SEMI-AUTOMATIC TARE (NET) IS ENTERED, IT IS NOT POSSIBLE TO ACCESS


THE ENTER PRESET TARE FUNCTION.
- IF A PRESET TARE IS ENTERED, IT’S STILL POSSIBLE TO ACCESS THE SEMI-
AUTOMATIC TARE (NET) FUNCTION. THE TWO DIFFERENT TYPES OF TARE ARE
ADDED.

ALL THE SEMI-AUTOMATIC TARE (NET) AND PRESET TARE FUNCTIONS WILL BE
LOST WHEN THE INSTRUMENT IS TURNED OFF.

SEMI-AUTOMATIC ZERO (WEIGHT ZERO-SETTING FOR SMALL VARIATIONS)

By closing the SEMI-AUTOMATIC ZERO input, the weight is set to zero. The zero setting will be lost
when the instrument is turned off.

This function is only allowed if the weight is lower than the  value (see paragraph
RESETTABLE WEIGHT SETTING FOR SMALL WEIGHT CHANGES), otherwise the alarm 
appears and the weight is not set to zero.

PEAK

Keeping the input closed the maximum weight value reached remains displayed. Opening the input
the current weight is displayed.

If you wish to use this input to view a sudden variation peak, set the FILTER ON THE
WEIGHT to 0.

- 20 -
SERIAL COMMUNICATION SETTING

According to the chosen protocol only the necessary settings will be displayed in sequence
(see diagram here above).

- : communication port.

- : it disables any type of communication (default).


- : MODBUS-RTU protocol; possible addresses: from 1 to 99 (see Communication
Protocols).
- : ASCII bidirectional protocol; possible addresses: from 1 to 99 (see Communication
Protocols).
- 
- 
- : continuous weight transmission protocol (see Communication protocols manual),
at the frequency set in  item (from 10 to 80).
-  (set: =, =).
-  (set: =, =).
- : continuous weight transmission protocol to RIP5/20/60, RIP50SHA, RIPLED series
remote displays; the remote display shows the net weight or gross weight according to its
settings (set: =, =, =).
- : continuous weight transmission protocol to RIP6100, RIP675, RIP6125C series
remote displays; the remote display shows the net weight or gross weight according to its
settings (set: =, =, =).
- : continuous weight transmission protocol to RIP6100, RIP675, RIP6125C series
remote displays (set: =, =, =).
When the remote display is set to gross weight:
- if the instrument displays the gross weight, the remote display shows the gross weight.
- if the instrument shows the net weight the remote display shows the net weight
alternated with the message ‘'.

- 21 -
- : transmission speed (2400, 4800, 9600, 19200, 38400, 115200; default:
9600).
- : instrument’s address (from 1 to 99; default: 1).
- : maximum transmission frequency (10 – 20 – 30 – 40 – 50 – 60 – 70 – 80; default:
10); to be set when the transmission protocol is selected.
Maximum setting frequency ():
- 20Hz with minimum baud rate 2400 baud.
- 40Hz with minimum baud rate 4800 baud.
- 80Hz with minimum baud rate 9600 baud.
- : delay in milliseconds which elapses before the instrument replies (from 0 to
200 msec; default: 0).
- :
- : parity none (default).
- : even parity.
- : odd parity.
- : stop bit (1 – 2; default: 1).

RS485 SERIAL CONNECTION


RS485 termination
TLS TLS TLS
28 29 34 28 29 34 28 29 34

RS485 +
RS485 +

RS485 +

RS485 -
RS485 -

RS485 -
0 VDC

0 VDC

0 VDC
J2 J1

max 500 m

24 Vcc
-
+
VIN TX+ RS485 + RS485 +
PC RS232
3 2 5

0 TX- RS485 - RS485 -


TX CONVLAU RX+
RX RX-

If the RS485 network exceeds 100 metres in length or baud-rate over 9600 are used,
close the two jumpers, called "RS-485 termination", to activate two 120 ohm
terminating resistors between the ‘+’ and ‘–’ terminals of the line, on the terminal strip
of the furthest instruments. Should there be different instruments or converters, refer
to the specific manuals to determine whether it is necessary to connect the above-
mentioned resistors.

- 22 -
DIRECT CONNECTION BETWEEN RS485 AND RS232 WITHOUT CONVERTER

Since a two-wire RS485 output may be used directly on the RS-232 input of a PC or remote display,
it is possible to implement instrument connection to an RS-232 port in the following manner:

INSTRUMENT RS232
RS 485 - → RXD
GND → GND

This type of connection allows A SINGLE instrument to be used in a ONE WAY mode.

TEST

- Input Test:
: ensure that for each open input is displayed,  is displayed when the input is closed.
- Output Test:
: setting  ensure that the corresponding output opens. Setting  ensure that the
corresponding output closes.
- Millivolt Test:
: displays the load cell response signal in mV with four decimals.

- 23 -
SETPOINTS PROGRAMMING

From the weight display, press to access the setpoints setting.

: to enter a menu/confirm the data entry.


: to modify the displayed value or menu item.
: to select a new value or modify the displayed menu item.
: to cancel and return to the previous menu.

-  (from 0 to full scale; default: 0): Setpoint; relay switching occurs when the weight exceed the
value set in this parameter. The type of switching is settable (see paragraph OUTPUTS AND
INPUTS CONFIGURATION).

- (from 0 to full scale; default: 0): Hysteresis, value to be subtracted from the setpoint to
obtain contact switching for decreasing weight. For example with a setpoint at 100 and hysteresis
at 10, the switching occurs at 90 for decreasing weight.

These values are set to zero if the calibration is changed significantly (see paragraphs
THEORETICAL CALIBRATION and REAL CALIBRATION (WITH SAMPLE WEIGHTS).

ALARMS

: the load cell is not connected or is incorrectly connected; the load cell signal exceeds 39
mV; the conversion electronics (AD converter) is malfunctioning;
: the weight display exceeds 110% of the full scale.
: internal instrument converter failure; check load cell connections, if necessary contact
Technical Assistance.
: the weight exceeds the maximum weight by 9 divisions.
: maximum displayable value exceeded (value higher than 999999 or lower than -999999).
: weight too high: zero setting not possible.
: this message appears in the sample weight setting, in real calibration, after the eighth
sample weight value has been entered.
: the value set for the parameter is beyond the permitted values; press to quit the setting
mode leaving the previous value unchanged. Examples: a number of decimals is selected
for full scale which exceeds the instrument's display potential; value above the maximum

- 24 -
setting value; the weight value set in sample weight verification does not match the detected
mV increase.
: lock active on menu item, keypad or display.
: It’s not possible to display properly the number because is greater than 999999 or less
than -999999.
: gross weight equal to zero: the semi-automatic tare operation cannot be performed.

Serial protocols alarms:

     


MODE
Bit LSB 76543210 76543210 76543210 76543210 76543210 The response to the
Status xxxxxxx1 xxxx1xxx xxxxxx1x xxxxx1xx On gross: zero command is a
Register xxx1xxxx 'value not valid' error
MODBUS RTU On net: (error code 3)
xx1xxxxx

ASCII __O-F_ __O-L_ __O-F_ __O-L_ __O-F_ &aa#CR


RIP * __O-F_ __O-L_ __O-F_ __O-L_ __O-F_ __O-F_
HDRIP-N _ERCEL _ER_OL _ER_AD ###### _ER_OF O__SET
CONTIN _ERCEL _ER_OL _ER_AD ^^^^^^ _ER_OF O__SET
* For RIP remote displays, if the message exceeds 5 digits the display reads .

If an alarm becomes active the relays open.

- 25 -
FAST CONTINUOUS TRANSMISSION PROTOCOL

This protocol allows for automatic weight reception via a serial connection at high update frequencies.
Up to 80 strings per second are transmitted (with a minimum transmission rate of 9600 baud).
Following communication modes available (see paragraph SERIAL COMMUNICATION SETTING):
 :communication compatible with TX RS485 instruments;
 :communication compatible with TD RS485 instruments.

- If   is set, the following string is transmitted to PC/PLC: xxxxxxCRLF

where: xxxxxx = 6 ASCII characters for gross weight (48  57 ASCII).


CR = 1 character of back to start (13 ASCII).
LF = 1 character of new line (10 ASCII).

In case of negative weight, the first character on the left acquires the value « - » (minus
sign - ASCII 45).
In case of error or alarm, the 6 weight characters are replaced by the messages
found in the table of the ALARMS.

- If   is set, the following string is transmitted to PC/PLC: &TzzzzzzPzzzzzz\ckckCR

where: & = 1 initial string character (38 ASCII).


T = 1 character of gross weight identification.
P = 1 character of gross weight identification
zzzzzz = 6 characters of gross weight (48  57 ASCII).
\ = 1 character of separation (92 ASCII).
ckck = 2 ASCII control characters calculated considering that the characters between &
and \ are excluded. The control value is obtained by carrying out the XOR (or exclusive)
operation for the 8 bit ASCII codes of the characters considered. A character expressed in
hexadecimal is thus obtained, with 2 digits which may acquire values from “0” to “9” and
from “A” to “F”. “ckck” is the ASCII code of the two hexadecimal digits.
CR = 1 character for string end (13 ASCII).

In case of negative weight, the first character on the left acquires the value « - » (minus
sign - ASCII 45).

In case of error or alarm, the 6 gross weight characters are replaced by the
messages found in the table of the ALARMS.

FAST TRANSMISSION VIA EXTERNAL CONTACT: it’s possible to transmit the weight, just once,
even closing an input for no more than a second (see paragraphs OUTPUTS AND INPUTS
CONFIGURATION and SERIAL COMMUNICATION SETTING).

- 26 -
CONTINUOUS TRANSMISSION PROTOCOL TO REMOTE DISPLAYS

Using this protocol, the instrument transmits, in continuous, the weight to remote displays; the
communication string is transmitted 10 times per second. Following communication modes available
(see paragraph SERIAL COMMUNICATION SETTING):
- : communication with remote displays series RIP5/20/60, RIP50SHA, RIPLED; remote
display shows the net or gross weight, depending on the remote display setting.
- : communication with remote displays series RIP6100, RIP675, RIP6125C; remote
display shows the net or gross weight, depending on the remote display setting.
- : communication with remote displays series RIP6100, RIP675, RIP6125C.

The instrument sends the following string to the remote display:

&NxxxxxxLyyyyyy\ckckCR

where: & = 1 initial string character (38 ASCII).


N = 1 character of net weight identification (78 ASCII).
xxxxxx = 6 characters of net weight or PEAK if present (48  57 ASCII).
L = 1 character of gross weight identification (76 ASCII).
yyyyyy = 6 characters of gross weight (48  57 ASCII).
\ = 1 character for separation (92 ASCII).
ckck = 2 ASCII control characters calculated considering that the characters between
“&” and “\” are excluded. The control value is obtained by carrying out the XOR (or
exclusive) operation for the 8 bit ASCII codes of the characters considered. Character
expressed in hexadecimal is thus obtained, with 2 digits which may acquire values from
“0” to “9” and from”A” to “F”. “ckck” is the ASCII code of the two hexadecimal digits.
CR = 1 character for string end (13 ASCII).

In case of negative weight, the first character on the left acquires the value « - » (minus sign - ASCII
45).

If the protocol on  has been set, the decimal point at the position shown on the instrument's
display can also be transmitted. In this case, if the value exceeds 5 digits, only the 5 most significant
digits are transmitted, while if the value is negative, no more than the 4 most significant digits are
transmitted. In both cases, however, the decimal point shifts consistently with the value to display.
If has been set, in addition to what stated in protocol, the instrument transmits the
prompt  every 4 seconds in the gross weight field, if on the instrument, it has been carried out a
net operation (see paragraph SEMI-AUTOMATIC TARE (NET/GROSS)).
In case of weight value is under -99999, the minus sign (‘-‘) is sent alternated with the most significant
figure.

In case of error or alarm, the 6 characters of the gross and net weight are replaced by the
messages found in the table of the ALARMS.

- 27 -
ASCII BIDIRECTIONAL PROTOCOL

The instrument replies to the requests sent from a PC/PLC.


It is possible to set a waiting time for the instrument before it transmits a response (see
parameter in the paragraph SERIAL COMMUNICATION SETTING).
Following communication modes available (see paragraph SERIAL COMMUNICATION SETTING):
:communication compatible with W60000, WL60 Base, WT60 Base, TLA60 Base
instruments;
 :communication compatible with TD RS485 instruments.

Captions:
$: Beginning of a request string (36 ASCII);
& o &&: Beginning of a response string (38 ASCII);
aa: 2 characters for instrument address (48  57 ASCII);
!: 1 character to indicate the correct reception(33 ASCII);
?: 1 character to indicate a reception error (63 ASCII);
#: 1 character to indicate an error in the command execution (23 ASCII);
ckck: 2 ASCII characters for Check-Sum (for furthers information, see paragraph CHECK-
SUM CALCULATION);
CR: 1 character for string end (13 ASCII);
\: 1 character for separation (92 ASCII).

1. SETPOINT VALUES SETTING:

The PC transmits: $aaxxxxxxyckckCR

where: xxxxxx = 6 characters for the setpoint value (48  57 ASCII);


y = A (set the value in the Setpoint 1)
y = B (set the value in the Setpoint 2)

Possible instrument responses:


- correct reception: &&aa!\ckckCR
- incorrect reception: &&aa?\ckckCR

2. SETPOINTS STORAGE INTO EEPROM MEMORY:

The setpoints value relevant to the two setpoints programmed via the PC are stored to the RAM
volatile memory and lost upon instrument power off. It is necessary to send a special command to
save them permanently in the EEPROM memory. Please note that the writing number allowed in the
EEPROM memory is limited (about 100000).

The PC transmits: $aaMEMckckCR

- 28 -
Possible instrument responses:
- correct reception: &&aa!\ckckCR
- incorrect reception: &&aa?\ckckCR

3. READING WEIGHT, THE SETPOINT AND THE PEAK (IF PRESENT) FROM THE PC:

The PC transmits: $aajckckCR

where: j = a to read setpoint 1


j=b to read setpoint 2
j=t to read gross weight
j=n to read net weight
j=p to read the gross weight peak if the parameter is set as ; if, instead,
the  parameter is set on  the gross weight will be read. To read the
points, set the  equal to 50000.

Possible instrument responses:


- correct reception: &aaxxxxxxj\ckckCR
- incorrect reception: &&aa?\ckckCR
- if the peak is not configured: &aa#CR

where: xxxxxx = 6 value characters of the required weight;

Notes:
In case of negative weight, the first character on the left acquires the value « - » (minus sign - ASCII
45).
In case of weight value is under -99999, the minus sign (‘-‘) is sent alternated with the most significant
figure.

Error messages:
In case of an instrument alarm for exceeding 110% of the full scale or 9 divisions above the value of
the parameter , the instrument sends the string:

&aassO-Lst\ckck

In case of faulty connection of the load cells or of another alarm, the instrument sends:

&aassO-Fst\ckck

where: s = 1 separator character (32 ASCII – space-).

Generally refer to the ALARMS paragraph in this manual.

- 29 -
4. SEMI-AUTOMATIC ZERO (WEIGHT ZERO-SETTING FOR SMALL VARIATIONS)

CAUTION: The zero-setting will not be maintained after an instrument power-off.

The PC transmits: $aaZEROckckCR

Possible instrument responses:


- correct reception: &&aa!\ckckCR
- incorrect reception: &&aa?\ckckCR
- the current weight is over the maximum value resettable: &aa#CR

5. SWITCHING FROM GROSS WEIGHT TO NET WEIGHT

The PC transmits: $aaNETckckCR

Possible instrument responses:


- correct reception: &&aa!\ckckCR
- incorrect reception: &&aa?\ckckCR

6. SWITCHING FROM NET WEIGHT TO GROSS WEIGHT

The PC transmits: $aaGROSSckckCR

Possible instrument responses:


- correct reception: &&aa!\ckckCR
- incorrect reception: &&aa?\ckckCR

7. READING OF DECIMALS AND NUMBER OF DIVISIONS

The PC transmits: $aaDckckCR

Possible instrument responses:


- correct reception: &aaxy\ckckCR
- incorrect reception: &&aa?\ckckCR

where: x = number of decimals


y = division value

The y field acquires the following values:


'3' for division value = 1;
'4' for division value = 2;
'5' for division value = 5;
'6' for division value = 10;
'7' for division value = 20;
'8' for division value = 50;
'9' for division value = 100;
- 30 -
8. TARE WEIGHT ZERO SETTING

The PC transmit the following ASCII string containing the zeroing command:: $aazckckCR

where: z = = weight zeroing command (122 ASCII)

Possible instrument responses:


- correct reception: &aaxxxxxxt\ckckCR
- incorrect reception: &&aa?\ckckCR
- If the instrument is not in gross weight displaying condition, the response is: &aa#CR

where: xxxxxx = 6 characters for the required weight value;


t = weight identification code (116 ASCII).

Example: Weight zero setting for instrument with address 2:

For the calibration, make sure that the scale is empty and the instrument measures a corresponding mV
signal.

query: $02z78(Cr) response: &02000000t\76(Cr)

In case of correct weight zero setting the read value (response) must be 0 (in the string “000000”).

The zero values are stored to the EEPROM memory, please note that the writing
number allowed is limited (about 100000). If it is necessary to reset the weight quite
often, it is recommended to perform it by PC or PLC program, keeping in mind the
weight deviation respect to the zero instrument.

9. REAL CALIBRATION (WITH SAMPLE WEIGHTS)

After having performed the TARE WEIGHT ZERO SETTING, this function allows correct
calibration to be done using sample weights of known value and, if necessary, any deviations
of the indicated value from the correct value to be corrected.

Load onto the weighing system a sample weight, which must be at least 50% of the Full Scale
otherwise make sure that the instrument measures a corresponding mV signal

The PC sends the following ASCII string containing the calibration command:
$aasxxxxxxckckCR

where: s = calibration command (115 ASCII)


xxxxxx = 6 characters for sample weight value (negative values are not allowed).

Possible instrument responses:


- correct reception: &aaxxxxxxt\ckckCR
- incorrect reception or full scale equal to zero: &&aa?\ckckCR

- 31 -
where: t = gross weight identification code (116 ASCII).
xxxxxx = 6 characters to indicate the current weight value.

In case of correct calibration, the read value must be equal to sample weight.

Example: Calibration for instrument with address 1 and sample weight of 20000 kg:

query: $01s02000070(Cr) response: &01020000t\77(Cr)

In case of correct calibration the read value has to be “020000”.

10. KEYPAD LOCK (ACCESS PROTECTION TO THE INSTRUMENT)

The PC transmits: $aaKEYckckCR

Possible instrument responses:


- correct reception: &&aa!\ckckCR
- incorrect reception: &&aa?\ckckCR

11. KEYPAD UNLOCK

The PC transmits: $aaFREckckCR

Possible instrument responses:


- correct reception: &&aa!\ckckCR
- incorrect reception: &&aa?\ckckCR

12. DISPLAY AND KEYPAD LOCK

The PC transmits: $aaKDISckckCR

Possible instrument responses:


- correct reception: &&aa!\ckckCR
- incorrect reception: &&aa?\ckckCR

- 32 -
CHECK-SUM CALCULATION

The two ASCII control characters (ckck) are the representation of a hexadecimal digit in ASCII
characters. The check digit is calculated by performing the operation XOR (exclusive or) 8-bit ASCII
codes of the only part of the underlined string.

The procedure to calculate the check- sum is the following:


- Consider only the string characters highlighted with underlining;
- Calculate the EXCLUSIVE OR (XOR) of the ASCII codes for the characters;

Example:
character decimal ASCII code hexadecimal ASCII code binary ASCII code
0 48 30 00110000
1 49 31 00110001
t 116 74 01110100
XOR = 117 75 01110101

- The result of the XOR operation expressed in hexadecimal notation is made up of 2 hexadecimal
digits (numbers from 0 to 9 or letters from A to F). In this case the hexadecimal code is 0x75.

- The check-sum inserted in the strings transmitted is made up of the 2 characters which represent
the result of the XOR operation in hexadecimal notation (in our example the character “7” and the
character “5”).

MODBUS-RTU PROTOCOL

The MODBUS-RTU protocol enables to manage the reading and writing of the registers listed here
below according to the specifications contained in the reference document for this standard Modicon
PI-MBUS-300.

To select the communication with MODBUS-RTU, refer to paragraph SERIAL COMMUNICATION


SETTING

Check if the Master MODBUS-RTU in use (or the development tool) requires the disclosure of
registers based on 40001 or 0. In the first case the registers numbering corresponds to the one in the
table; in the second case the register must be determined as the value in the table minus 40001. E.g.:
the register 40028 shall be reported as 27 (= 40028- 40001).

When specifically indicated certain data will be written directly to EEPROM type memories. This
memory has a limited number of writing operations (100.000), therefore unnecessary operations at
said locations must be avoided. The instrument, in any case, ensures that no writing occurs if the
value to be stored is equal to the stored value.

The numerical data listed below are expressed in decimal notation, or hexadecimal notation if
preceded by 0x.
- 33 -
MODBUS-RTU DATA FORMAT

The data received and transmitted via MODBUS-RTU protocol have the following characteristics:

- 1 start bit
- 8 data bits, least significant bit sent first
- Instrument settable parity bit
- Instrument settable stop bit

MODBUS SUPPORTED FUNCTIONS

Among the commands available in the MODBUS-RTU protocol, only the following are used to manage
communication with the instruments. Other commands may not be interpreted correctly and could
generate errors or system shut-downs:

FUNCTIONS DESCRIPTION
03 (0x03) READ HOLDING REGISTER (PROGRAMMABLE REGISTER READING)
16 (0x10) PRESET MULTIPLE REGISTERS (MULTIPLE REGISTER WRITING)

The interrogation frequency is linked with the preset communication rate (the instrument will stand by
for at least 3 bytes before beginning to calculate a possible response to the query). The
parameter present in the paragraph SERIAL COMMUNICATION SETTING allows for a
further delay in the instrument response, and this directly influences the number of possible queries
in the unit of time.
For additional information on this protocol, refer to the general technical specification PI_MBUS_300. In
general, the query and response to and from a slave instrument are organised as follows:

FUNCTION 3: Read holding registers (PROGRAMMABLE REGISTER READING)

QUERY
Address Function Add. Register1 No. register 2 bytes
A 0x03 0x0000 0x0002 CRC
Tot. bytes = 8

RESPONSE
Address Function No. bytes Register1 Register 2 2 bytes
A 0x03 0x04 0x0064 0x00C8 CRC
Tot. bytes = 3+2*No. registers+2

where: No. registers= number of Modbus register to be read, starting from the Address 1° register;
No. bytes = number of data bytes to follow;

- 34 -
FUNCTION 16: Preset multiple registers (MULTIPLE REGISTER WRITING)

QUERY
Address Function Add. reg. 1 No. reg. No. bytes Val. reg.1 Val.reg.2 2 bytes
A 0x10 0x0000 0x0002 0x04 0x0000 0x0000 CRC
Tot. bytes = 7+2*No. registers+2

RESPONSE
Address Function Add. reg. 1 No. reg. 2 bytes
A 0x10 0x0000 0x0002 CRC
Tot. bytes = 8

where: No. registers = number of Modbus register to be read, starting from the Address 1° register;
No. bytes = number of data bytes to follow;
Val.reg.1 = register contents beginning from the first.

The Response contains the number of records changed starting from the Address 1° register.

COMMUNICATION ERROR MANAGEMENT

The communication strings are controlled by CRC (Cyclical Redundancy Check).


In case of a communication error the slave will not respond with any string. The master must allow for
a time-out before response reception. If no response is received it infers that a communication error
has occurred.

In the event of a string received correctly but not executable, the slave responds with an
EXCEPTIONAL RESPONSE. The "FUNCTION" field is transmitted with the msb at 1.

EXCEPTIONAL RESPONSE
Address Function Code 2 bytes
A Funct + 0x80 CRC

CODE DESCRIPTION
1 ILLEGAL FUNCTION (Function not valid or not supported)
2 ILLEGAL DATA ADDRESS (The specified data address is not available)
3 ILLEGAL DATA VALUE (The data received have no valid value)

LIST OF USABLE REGISTERS

The MODBUS-RTU protocol implemented on this instrument can manage a maximum of 32 registers
read and written in a single query or response.

R = the register can be read only


W = the register can be written only

- 35 -
R/W = the register can be both read and written
H = high half of the DOUBLE WORD forming the number
L = low half of the DOUBLE WORD forming the number

REGISTER DESCRIPTION Saving to EEPROM ACCESS

40001 Firmware version - R


40002 Type of instrument - R
40003 Year of Production - R
40004 Serial Number - R
40005 Active program - R
40006 COMMAND REGISTER NO W
40007 STATUS REGISTER - R
40008 GROSS WEIGHT H - R
40009 GROSS WEIGHT L - R
40010 NET WEIGHT H - R
40011 NET WEIGHT L - R
40012 PEAK WEIGHT H - R
40013 PEAK WEIGHT L - R
40014 Divisions and Units of measure - R
40015 Coefficient H R
40016 Coefficient L R
40017 SETPOINT 1 H R/W
40018 SETPOINT 1 L R/W
40019 SETPOINT 2 H R/W
Only after command ‘99’
40020 SETPOINT 2 L R/W
of the
40021 HYSTERESIS 1 H
COMMAND REGISTER
40022 HYSTERESIS 1 L
40023 HYSTERESIS 2 H R/W
40024 HYSTERESIS 2 L R/W
40025 INPUTS - R
40026 OUTPUTS NO R/W
40037 Sample weight for calibration H Use with command ‘101’ R/W
of the COMMAND
40038 Sample weight for calibration L REGISTER R/W

CAUTION: At the time of writing, the setpoints and hysteresis values are saved to the RAM and will
be lost upon the next power-off; to store them permanently to the EEPROM so that they are
maintained at power-on, the 99 command of the Command Register must be sent.

- 36 -
REAL CALIBRATION COMMANDS (WITH SAMPLE WEIGHTS)

- Unload the system and reset to zero the displayed weight value with the command 100 “TARE
WEIGHT ZERO SETTING for calibration” of the Command Register.
- Load a sample weight on the system and send its value to the registers 40037-40038.
- To save the first sample weight value and remove the previously saved values, send the command
101 “Save first sample weight for calibration” to the Command Register;
- To store a sample weight value and keep the previously saved values, send the command 106
“Add sample weight for calibration” to the Command Register;
- Up to 8 different sample weights can be saved to perform a linearization on multiple points.
▫ The same sample weight can only be saved once for each calibration.
▫ Zero sample weight values cannot be saved.

If the operation is successfully completed, the two sample weight registers are set to zero.

To cancel the real calibration and return to the theoretical calibration, send the command 104 to the
Command Register. The tare reset is not cancelled.

In order to correctly set the sample weight, consider the value of the Division register
(40014). Example: to set the sample weight to 100 kg and the division is 0.001, then the
value to enter is 100000 (100 / 0.001 = 100000).

In order to correctly set a sample weight of negative value, it is necessary to consider the
registers “Sample weight for calibration” (40037 – 40038) as a 32-bit signed number. If the
development system does not handle signed numbers, enter the values in two’s complement.
Example: to set the sample weight to - 56 kg, enter the values indicated in the table in the
registers “Sample weight for calibration”.

VALUE
REGISTER DESCRIPTION
HEX DECIMAL
40037 Sample weight for instrument calibration H 0xFFFF -1
40038 Sample weight for instrument calibration L 0xFFC8 -56

- 37 -
STATUS REGISTER (40007)

Bit 0 Cell Error


Bit 1 AD Convertor Malfunction
Bit 2 Maximum weight exceeded by 9 divisions
Bit 3 Gross weight higher than 110% of full scale
Bit 4 Gross weight beyond 999999 or less than -999999
Bit 5 Net weight beyond 999999 or less than -999999
Bit 6
Bit 7 Gross weight negative sign
Bit 8 Net weight negative sign
Bit 9 Peak weight negative sign
Bit 10 Net display mode
Bit 11 Weight stability
Bit 12 Weight within +/-¼ of a division around ZERO
Bit 13
Bit 14
Bit 15

INPUT REGISTER (40025) OUTPUT REGISTER (40026)


(read only) (read and write)

Bit 0 INPUT 1 Status Bit 0 OUTPUT 1 Status


Bit 1 INPUT 2 Status Bit 1 OUTPUT 2 Status
Bit 2 Bit 2
Bit 3 Bit 3
Bit 4 Bit 4
Bit 5 Bit 5
Bit 6 Bit 6
Bit 7 Bit 7
Bit 8 Bit 8
Bit 9 Bit 9
Bit 10 Bit 10
Bit 11 Bit 11
Bit 12 Bit 12
Bit 13 Bit 13
Bit 14 Bit 14
Bit 15 Bit 15

The output status can be read at any time but can be set (written) only if the output has been
set as  (see paragraph OUTPUTS AND INPUTS CONFIGURATION).

- 38 -
DIVISIONS AND UNITS MEASURE REGISTRY (40014)

This register contains the current setting of the divisions (parameter ) and of the units of
measure ( parameter).

H Byte L Byte
Units of measure division

Use this register together with the Coefficient registers to calculate the value displayed by the
instrument.

Least significant byte (L Byte) Most significant byte (H Byte)

Utilisation of the
Coefficient value with the
Units of
Division Units of measure different units of
Divisor Decimals measure
value description measure settings
value
compared to the gross
weight detected
0 100 0 0 Kilograms Does not intervene
1 50 0 1 Grams Does not intervene
2 20 0 2 Tons Does not intervene
3 10 0 3 Pounds Does not intervene
4 5 0 4 Newton Multiples
5 2 0 5 Litres Divides
6 1 0 6 Bar Multiples
7 0.5 1 7 Atmspheres Multiples
8 0.2 1 8 Pieces Divides
9 0.1 1 9 Newton Meter Multiples
10 0.05 2 10 Kilogram Meter Multiples
11 0.02 2 11 Other Multiples
12 0.01 2
13 0.005 3
14 0.002 3
15 0.001 3
16 0.0005 4
17 0.0002 4
18 0.0001 4

- 39 -
POSSIBLES COMMAND TO SEND TO THE COMMAND REGISTER (40006)

0 No command 1
6 7 SEMI-AUTOMATIC TARE enabling
(net display)
8 SEMI-AUTOMATIC ZERO 9 SEMI-AUTOMATIC TARE disabling
(gross display)
20 21 Keypad lock
22 Keypad and display unlock 23 Keypad and display lock
98 99 Save data in EEPROM
100 TARE WEIGHT ZERO SETTING for 101 Save first sample weight for calibration
calibration
104 Real calibration cancellation 106 Add sample weight for calibration
130 Preset Tare enabling 131

- 40 -
COMMUNICATION EXAMPLES

The numerical data below are expressed in hexadecimal notation with prefix h.
EXAMPLE 1
Command for multiple writing of registers (hexadecimal command 16, h10):

Assuming that we wish to write the value 0 to the register 40017 and the value 2000 to the register
40018, the string to generate must be:

h01 h10 h00 h10 h00 h02 h04 h00 h00 h07 hD0 hF1 h0F

The instrument will respond with the string:

h01 h10 h00 h10 h00 h02 h40 h0D

Query field name hex Response field name hex

Instrument Address h01 Instrument Address h01


Function h10 Function h10
Address of the first register H h00 Address of the first register H h00
Address of the first register L h10 Address of the first register L h10
Number of registers to send H h00 Number of registers H h00
Number of registers to send L h02 Number of registers L h02
Byte Count h04 CRC16 H h40
Datum 1 H h00 CRC16 L h0D
Datum 1 L h00
Datum 2 H h07
Datum 2 L hD0
CRC16 H hF1
CRC16 L h0F

EXAMPLE 2
Command for multiple writing of registers (hexadecimal command 16, h10):
Assuming that we wish to write the two setpoint values on the instrument, at 2000 and 3000
respectively, the string must be sent:

h01 h10 h00 h10 h00 h04 h08 h00 h00 h07 hD0 h00 h00 h0B hB8
hB0 hA2

The instrument will respond with the string:

h01 h10 h00 h10 h00 h04 hC0 h0F

Query field name hex Response field name hex

Instrument Address h01 Instrument Address h01


Function h10 Function h10
Address of the first register H h00 Address of the first register H h00
- 41 -
Address of the first register L h10 Address of the first register L h10
Number of registers H h00 Number of registers H h00
Number of registers L h04 Number of registers L h04
Byte Count h08 CRC16 H hC0
Datum 1 H h00 CRC16 L h0F
Datum 1 L h00
Datum 2 H h07
Datum 2 L hD0
Datum 3 H h00
Datum 3 L h00
Datum 4 H h0B
Datum 4 L hB8
CRC16 H hB0
CRC16 L hA2

EXAMPLE 3
Multiple commands reading for registers (hexadecimal command 3, h03):
Assuming that we wish to read the two gross weight values (in the example 4000) and net weight values
(in the example 3000), reading from address 40008 to address 40011 must be performed by sending the
following string:

h01 h03 h00 h07 h00 h04 hF5 hC8

The instrument will respond with the string:

h01 h03 h08 h00 h00 h0F hA0 h00 h00 h0B hB8 hB3 h30

Query field name hex Response field name hex


Instrument Address h01 Instrument Address h01
Function h03 Function h03
Address of the first register H h00 Byte Count h08
Address of the first register L h07 Datum 1 H h00
Number of registers H h00 Datum 1 L h00
Number of registers L h04 Datum 2 H h0F
CRC16 L hF5 Datum 2 L hA0
CRC16 H hC8 Datum 3 H h00
Datum 3 L h00
Datum 4 H h0B
Datum 4 L hB8
CRC16 H hB3
CRC16 L h30

For additional examples regarding the generation of correct control characters (CRC16) refer to the
manual Modicon PI-MBUS-300.

- 42 -
RESERVED FOR THE INSTALLER

MENU LOCKING

Through this procedure, it’s possible to block the access to any menu on the instrument.
Select the menu that you wish to lock:

press simultaneously for 3 seconds, the display shows


(the left point on the text indicates that this menu item is now locked). If the operator tries
to enter this menu, the access is denied and the display shows .

MENU UNLOCKING

press simultaneously for 3 seconds, the display shows


(the left point on the text is off to indicate that this menu item is unlocked).

TEMPORARY MENU UNLOCKING

press simultaneously for 3 seconds: it is now possible to enter


and modify all menus including those which are locked. By returning to weight display, the menu lock
is restored.

PROGRAM SELECTION AND DATA DELETION

CAUTION: operation must only be performed after contacting technical assistance


Upon instrument power-on, hold down the key until the display shows:

DATA DELETION: confirm the  prompt, use the arrow keys to select the item , enter
the code 6935 and confirm.

- 43 -
PROGRAM SELECTION:
: basic program, management of the only setpoint.

By confirming the displayed program, the system variables are set with default values.
By pressing you will quit the program without introducing any changes and without
deleting any of the set variables.

If you do not have a specific manual for the newly set program, you can request it
to technical assistance.

KEYPAD OR DISPLAY LOCKING

Press first immediately followed by hold them down for about 5 seconds (this operation is
also possible via the MODBUS and ASCII protocols):

- : no lock.
- : keypad lock: if active, when a key is pressed the message  is displayed for 3.
- : keypad and display lock: if active, the keypad is locked and the display shows the instrument
model (weight is not displayed); by pressing a key the display shows  for 3 seconds.

- 44 -
DECLARATION OF CONFORMITY - EU

SISTEMI DI PESATURA INDUSTRIALE - CELLE DI CARICO - BILANCE


LAUMAS Elettronica S.r.l. Tel. (+39) 0521 683124
Via I Maggio 6 - 43022 Montechiarugolo (PR) Italy Fax (+39) 0521 681091
C.F. - P.IVA IT01661140341

Email: [email protected] Fabbricante metrico Prot. N. 7340 Parma - R.E.A. PR N. 169833 - Reg. Imprese PR N.19393 - Registro Nazionale Pile
Web: http://www.laumas.com N. IT09060P00000982 - Registro A.E.E. N. IT08020000002494 - N. Mecc. PR 008385 - Cap. Sociale € 100.000 int. vers.
SISTEMA QUALITÀ CERTIFICATO UNI EN ISO 9001 - SISTEMA GESTIONE AMBIENTALE ISO 14001 - MODULO D: GARANZIA DELLA QUALITÀ DEL PROCESSO DI PRODUZIONE

Dichiarazione di Dichiariamo che il prodotto al quale la presente dichiarazione si riferisce è conforme alle norme di seguito
I
conformità citate.
Declaration of
GB We hereby declare that the product to which this declaration refers conforms with the following standards.
conformity
Declaración de Manifestamos en la presente que el producto al que se refiere esta declaración está de acuerdo con las
E
conformidad siguientes normas
Wir erklären hiermit, dass das Produkt, auf das sich diese Erklärung bezieht, mit den nachstehenden
D Konformitäts-erklärung
Normen übereinstimmt.
Déclaration de Nous déclarons avec cela responsabilité que le produit, auquel se rapporte la présente déclaration, est
F
conformité conforme aux normes citées ci-après.
Tímto prohlašujeme, že výrobek, kterého se toto prohlášení týká, je v souladu s níže uvedenými
CZ Prohlášení o shode
normami.
Wij verklaren hiermede dat het product, waarop deze verklaring betrekking heeft, met de hierna vermelde
NL Conformiteit-verklaring
normen overeenstemt.
Declaração de Declaramos por meio da presente que o produto no qual se refere esta declaração, corresponde às
P
conformidade normas seguintes.
Niniejszym oświadczamy, że produkt, którego niniejsze oświadczenie dotyczy, jest zgodny z poniższymi
PL Deklaracja zgodności
normami.
Заявление о Мы заявляем, что продукт, к которому относится данная декларация, соответствует
RUS
соответствии перечисленным ниже нормам.

Models: TLS485

Mark Applied EU Directive Standards


2014/35/EU
Not Applicable (N/A) for VDC type
Low Voltage Directive
EN 55022:2010
EN 61000-6-2:2005
EN 61000-6-4:2007
2014/30/EU EN 61000-4-2:2009
EMC Directive EN 61000-4-3:2006+A2:2010
EN 61000-4-4:2012
EN 61000-4-5:2014
EN 61000-4-6:2014

M 2014/31/EU
NAWI Directive
EN 45501:2015
OIML R76-1:2006
(only if “M” mark is applied)

Montechiarugolo (PR), 12/01/2021 LAUMAS Elettronica s.r.l.


M. Consonni
(Legal Representative)

- 45 -
On our website www.laumas.com there are videos on the guidelines for correct installation of
weighing systems and video tutorials on configuring our transmitters and weight indicators.

All Laumas product manuals are available online. You can download the manuals in PDF format
from www.laumas.com by consulting the Products section or the Download Area.
Registration is required.

Think about the environment before you print!


CERTIFICATION OF THE ENVIRONMENTAL MANAGEMENT SYSTEM
in accordance with UNI EN ISO 14001.
Laumas contributes to environmental protection by saving on paper consumption.

You might also like