1769-HSC - Module Error Code, Reading With A MicroLogix 1500 Controller
1769-HSC - Module Error Code, Reading With A MicroLogix 1500 Controller
Rockwell Automation
Rockwell logo
Automation
Listen
Think
Solve
Support Center Get Support Training & Webinars Online Forumsabarinatha…
logo
My TechConnect
ADD TO FAVORITES
Document ID QA8034
Summary
1769-HSC: Module Error Code, reading with a MicroLogix 1500 Controller
Question
1769HSC, where can I read the Module Error Code using a MicroLogix 1500 controller?
Answer
You are using a 1769HSC module with a MicroLogix 1500 controller and you have an error on the S:6 bit (i.e. x89h
"Expansion I/O module x generated an error"); you know only that the module in Slot 1 is in fault but you don’t
know which fault is occured. To get this information you have to open the Function Files folder: in IOS tab you
can read the fault Value and Description for the module.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/52510 1/3
3/22/2021 1769-HSC: Module Error Code, reading with a MicroLogix 1500 Controller
You can read the right error code of the 1769-HSC module going on IOS:1 Function Files
RATE CONTENT
Recently Viewed
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects
and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not intended to
constitute application, design, software or other professional engineering advice or services. Before making any
decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/52510 2/3
3/22/2021 1769-HSC: Module Error Code, reading with a MicroLogix 1500 Controller
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE
DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION
WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT
SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL,
CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE
POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE
INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR
A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not
countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.
www.rockwellautomation.com
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/52510 3/3