A Brief Introduction To Essential Substation Components
A Brief Introduction To Essential Substation Components
This article presents brief introduction to substation. The substation components are discussed. Also the
position, working and purpose of each component of substation is presented briefly.
Contents [hide]
1.0.1 Definition
1.2 Transformers
1.7 Isolators
1.8 Earthing Switch
1.10 Relays
generation, transmission, and distribution system. Substations transform voltage from high to low, or the
reverse, or perform any of several other important functions”.
Substation components
Transformer (main component)
Rest of components are Auxiliary like CB, CT, PT, lightning Arrester etc.
Figure below shows the typical grid station arrangement with minimum number of substation
components. There can be more components in the sophisticated substation however the components
described in this article are essential and needs to be in every substation.
Transformers
Among substation components , Transformer is the main and most expensive one. It is used to change the
voltage level for transmission or distribution purpose. It consists of two coils which are electrically isolated
but magnetically coupled. One is called primary winding and second is called secondary winding. Between
two windings there is iron block called core (in large transformers).
Alternating current in primary winding setup flux, which travels through the core and induce voltage in
secondary winding. To vary the voltage on secondary side, the important factor is turn ratio which is the
ratio of number of coils in primary winding to the secondary winding. By varying the turn ratio, the voltage
level can be varied.
V1/V2 = n1/n2
The function of transformer is to step up and step down the voltage level. Normally based on voltage level,
substations are named. For example 132kV Rawat substation, 220kV Ghatti substation etc.
If the voltage on the secondary side needs to be varied manually; a movable connection from secondary
or primary winding is taken which is called transformer tapping. For further details refer to all about
transformer tapings.
Types of transformer
On the basis of cooling arrangement, transformer are divided into following
Shell-Type Transformer
Auto transformer
Circuit Breakers
Among safety substation components, Circuit breaker is the main component. It is the back bone of
electrical safety system. Its basic function is to interrupt the continuity of electrical power in faulty
condition. It isolates the faulty part of the network from the healthy part by opening its contacts.
Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either
manually or automatically) to resume normal operation.
Circuit breakers are connected with the relays. Relays senses different abnormal condition and gives trip
command to the breaker. One of the important properties of circuit breaker is that they have the ability to
break very high currents and quench arcs that are produced as a result. Different quenching media are
used for this purpose.
At least one breaker is installed for the protection of each line on both sides of transformers. However the
number vary with the complexity and bus bar scheme.
In a substation, there is a copper strip that runs from one end of switch yard to another and having a
specific voltage and frequency is called bus bar.
Increases the reliability of substation that is if one incoming is out of service, the whole substation can
be energized by energizing the bus using any other incoming line.
Position in substation
In each substation, there are two bus bars. One is on the HT (high tension or high voltage) side and other
is on LT (low tension, low voltage) side.
Incoming lines are terminated on HT busbar. Also transformer incoming is connected to HT bus bar.
Outgoing lines are connected on LT bus bars. For example in 132kV/11kV substation, there will be 132kV
bus bar and 11kV bus bar. The voltage transformers are connected on Bus bars.
Components are arranged in definite manner in a substation such that they provide power with maximum
reliability with the provision that power can be switched off manually in normal condition and
automatically in faulty condition is called bus bar scheme.
There are a number of bus bar schemes. Most prominent are as follows
CURRENT TRANSFORMER
A current transformer is an instrument transformer which steps down the current. The current in the
secondary winding of CT is proportional to the current in the line. Since very high current flows in the
lines, which can neither be measured directly nor used with any protection devices. Therefore the current
is step down, which is then used for protection as well as metering purpose
Purpose in substation
In metering, they are used in ammeters, power meters, energy meters etc.
In protection, their output is given to the protective relays. Most common are over current, short circuit,
earth fault, reverse power etc.
Position in Substaion:
CTs are connected in series in substation. Most commonly they are connected on incoming line, both side
of transformer and outgoing feeders.
It must be noted that protection CTs are different from measuring CTs. Main
difference lies between the saturation level of their core. Measuring CTs are saturated earlier than
Protection CTs.
Potential Transformer
Another type of instrument transformer which reduces the voltage level in substation is called potential
transformer or voltage transformer. It is uneconomical to design measuring as well as protective
equipment to work on very high voltages. Therefore using instrument transformers, voltage is brought to
low and safe level which is then given to protective relays and measuring instrument.
The purpose of Potential transformer is
Reducing line voltage for measuring purpose. Meters for very voltage level become uneconomical due to
sophisticated insulation requirement.
Position in Substaion: These substation components is usually connected to the bus bars and it is always
connected in parallel.For further click voltage transformers
Isolators
Isolator is a mechanical switch which is used to isolate a portion of network. Unlike circuit breaker, it is off
load switch and it is manually operated. It is a visual switch that is it is clearly visibly that Isolator is on or
off. It is also named as Disconnector switch by some engineers. They are normally connected on incoming
lines, bus bars and both sides of transformers.
Position in Substaion: It is located on each bus bar, incoming lines and both sides of transformer.
In some cases, an earthling arrangement is coupled with isolator switch. That assembly is called
disconnector earthling switch.
Earthing Switch
Earthing switches are safety devices used to open or to close a circuit when there is no current through
them. Grounding must be conducted at both the upstream and downstream sections of the device under
maintenance. This is accomplished by earthing switches.
The purpose of earthing switch in substation is
Provide protection along with isolator. Isolator cannot remove static charges. So for complete
protection, system or component is isolated as well as earthed on both ends.
It is mechanically coupled with isolator. Earthing switch cannot be closed if isolator is closed
(connected). Similarly isolator cannot be on (closed) if earth switch is intact (closed).
Position in Substaion: It usually accompanies isolator. It is connected at each incoming line, at HT bus
bar and both sides of T/F.
Lightening Arresters
A lightning arrester / surge arrester is a protection device which provides protection against lighting
and voltage surges. It consists of high voltage terminal and ground terminal. In normal condition, it offers
very impedance (infinity) for current. However during fault, the medium between high terminal and
ground is either ionized or offers less impedance path towards ground. As a result high voltage surges are
gounded saving electrical equipment.
Arching horns are also joined with surge arresters which serve as second line defence against lighting.