Digital Thermostats & Digital Humidistat: Type Ule & Fle

This document provides specifications for ULE and FLE series digital thermostats and humidistats. It describes the key features such as large LED displays, backup memory, and easy operation via setting knobs and buttons. It also lists the various models, their temperature or humidity set range, differential, sensor part numbers, and weights. Finally, it explains the standard and hi/lo limit operation modes and setting procedures for the thermostats and humidistats.

Uploaded by

argodumilah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
246 views

Digital Thermostats & Digital Humidistat: Type Ule & Fle

This document provides specifications for ULE and FLE series digital thermostats and humidistats. It describes the key features such as large LED displays, backup memory, and easy operation via setting knobs and buttons. It also lists the various models, their temperature or humidity set range, differential, sensor part numbers, and weights. Finally, it explains the standard and hi/lo limit operation modes and setting procedures for the thermostats and humidistats.

Uploaded by

argodumilah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

DIGITAL THERMOSTATS & DIGITAL HUMIDISTAT

Type ULE & FLE

GENERAL DESCRIPTION
• Large LED, easy to see
• Back up memory on power failure
• Easy operation with a combination of setting knob and
△▽ keypads
• Either for wall or panel mounting.
• Power source voltage: 85 to 264V. AC 50/60Hz
• Relay output: 250V. AC, 6A (cosφ=0.7)
• Ambient temperature: Controller...−10 to 50°C
Humidity sensor...0 to 50°C

Type ULE Type FLE

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type ULE Digital Thermostats Unit: °C
Sensor Part No. Wt.
Catalog No. Temp. Set Range Differential Temp. Indication Function
(Standard) (kg)

ULE–SD11–011 Standard
ULE–SD12–011 −50 to 30 −55 to 40 2 Step TEK–83H609 with 2m lead
ULE–SD13–011 Hi/Lo Limit with time delay
Min. 0.5 0.2
ULE–SD21–011 Standard
ULE–SD22–011 0 to 100 0 to 110 2 Step TEK–83H601 with 2m lead
ULE–SD23–011 Hi/Lo Limit with time delay
・Temperature sensor type TEK–83H609 or TEK–83H601, sensor holder and panel mounting brackets are supplied as standard accessory.

Type FLE Digital Humidistat Unit: %RH


Wt.
Catalog No. Humidity Set Range Differential Humidity Indication Calibration Sensor Part No.
(kg)

FLE–SD11–011 30 to 90 Min. 3 20 to 99 ±10 HEK–I1R001 0.3

MODE & SETTING


STANDARD MODEL HI/LO LIMIT WITH TIME DELAY
Set LED Position Indication Key Operation Indication
NO OPERATION 7Seg LED: Temp.(Humi.) No OPERATION 7Seg LED:Temp.
COOL/HEAT LED: On Confirm of
"SEL" Key (DEHUMI/HUMI LED: ON) COOLING/HEATING "SEL" Key COOL/HEAT LED:On Confirm of
7Seg LED: "–C–" or "–H–" (DEHUMI/HUMI) 7Seg LED: "–C–" or "–H–" COOLING/HEATING
"SEL" Key 2sec. COOL/HEAT LED: Blink "SEL" Key 2sec. COOL/HEAT LED: Blink
(DEHUMI/HUMI LED: Blink)
Mode Set of Mode Set of
7Seg LED: "–C–" or "–H–" COOLING/HEATING "▲" or "▼" Key
"▲" or "▼" Key 7Seg LED: "–C–" or "–H–" COOLING/HEATING
(7Seg LED: "dHU" or "HU" (DEHUMI/HUMI)
7Seg.LED: "oFF" Blink "SEL" Key 7Seg.LED: "oFF" Blink
"SEL" Key
OFF SET LED: Blink OFF SET LED: Blink
OFF Set Point of OFF Set Point of
"▲" or "▼" Key Thermostat "▲" or "▼" Key Thermostat
(Humidistat)
"SEL" Key 7Seg.LED: "on" and "ON SET "SEL" Key 7Seg.LED: "on" and "ON Confirm of ON Set
Point": Alternate Blink Set Point"Alternate Blink Point
ON SET LED: On ON SET LED: On
"SEL" Key 2sec. "SEL" Key 2sec.
ON SET LED: Blink 7Seg.LED: "on" Blink
ON SET LED: Blink ON Set Point of
"▲" or "▼" Key ON Set Point of "▲" or "▼" Key
Thermostat Thermostat
"ENT" Key (Humidistat) "SEL" Key 7Seg.LED: "H" and "HIGH ALRM
TEMP."Alternate Blink
2 STEP MODEL TEMP. HIGH ALARM LED: Blink ON Set Point of
"▲" or "▼" Key High Alarm Temp.
Set LED Position Indication
"SEL" Key 7Seg.LED: "Ht" and "HIGH ALRM
No Blink Temp. DELAY"Alternate Blink
DELAY HIGH ALARM LED: Blink High Alarm Delay
OF1: OFF Set Point "▲" or "▼" Key Time Set
SET1 OFF of Thermostat No.1
"SEL" Key 7Seg.LED: "L" and "LOW ALRM
ON1: ON Set Point TEMP."Alternate Blink
SET1 ON of Thermostat No.1 TEMP. LOW ALARM LED: Blink ON Set Point of
"▲" or "▼" Key Low Alarm Temp.
OF2: OFF Set Point
SET2 OFF of Thermostat No.2 "SEL" Key 7Seg.LED: "Lt" and "LOW ALRM
DELAY"Alternate Blink
DELAY LOW ALARM LED: Blink Low Alarm Delay
SET2 ON ON2: ON Set Point "▲" or "▼" Key
of Thermostat No.2 Time Set
"ENT" Key

37
OPERATION
ULE–DIGITAL THERMOSTAT
STANDARD MODEL
(Cooling Mode) (Heating Mode)

Operation Min. 0.5℃ Operation Min. 0.5℃


6 −7 On 6 −7 On
Terminal Off Terminal Off

Off On Temp. On Off Temp.


(Set Point) (Set Point)

・Free to set On/Off set point independently within the range.


・When Off set point is changed, On set point automatically shifts. (Diff. remains same)
・When On set point is changed, Off set point remains unchanged. (Diff. changes)

2 STEP MODEL
Operation (Cooling Mode) Operation (Heating Mode) Operation (Floating Mode)
6 −7 6 −7 6 −7
or On or On or On
8 − 9 Off 8 − 9 Off 8 − 9 Off
Terminal Terminal Terminal
8 − 9 On 8 − 9 On 8 − 9 On
or or or
6 − 7 Off 6 − 7 Off 6 − 7 Off
Terminal Off On Off On Temp. Terminal On Off On Off Temp. Terminal On Off Off On Temp.
(Set Point) (Set Point) (Set Point)

Hi/Lo LIMIT W/TIMER MODEL


Lo Limit Time Set Hi Limit Time Set Lo Limit Time Set Hi Limit Time Set
(Lo limit Func starts after (Hi limit Func starts after (Lo limit Func starts after (Hi limit Func starts after
Operation 0 to 120 min. ) 0 to 120 min. ) Operation 0 to 120 min. ) 0 to 120 min. )
8 −9 On 8 −9 On
Terminal Terminal
Off Lo limit Hi limit Off Lo limit Hi limit
setting range Min. 0.5℃ setting range setting range Min. 0.5℃ setting range
On On
6−7 6−7
Terminal Off Terminal Off

Temp. Temp.
Lo Limit Off On Hi Limit (Set Point) Lo Limit On Off Hi Limit (Set Point)

・Hi/Lo limit output is reset manualy (Push reset: Push ENT Key in 2 sec or power off)
・Delay Timer can be set in the time range from 0 to 120 min respectively.

FLE–DIGITAL HUMIDISTAT
(Dehumidity Mode) (Humidity Mode)

6−7 Min. 3% RH 6−7 Min. 3% RH


Terminal Terminal
On On

Off Off
Off On On Off

・Free to set On/Off set point independently within the range.


・When Off set point is changed, On set point automatically shifts. (Diff. remains same)
・When On set point is changed, Off set point remains unchanged. (Diff. changes)

WIRING DIAGRAM
Type ULE Type FLE

Sensor Sensor
1 Load
1 Load
6 1
2 Relay Power Supply Relay 6 Power Supply
Contact for Load (Type HEK) 2 2 Contact for Load
7 7
3 Load
3 3
8 Power Supply 8
4 Relay
Power Supply Contact for Load Power Supply 4
85 to 264V.AC 9 9
5 85 to 264V.AC 5

6 − 7 : STANDARD, 2 STEP & Hi/Lo Model Control Output

8 − 9 : 2 STEP Control Output Hi/Lo Limit Alarm Output

38
SENSORS
STANDARD
Sensor Applicable
Dimension Remarks
Part No. Model

• Ambient temp. on usage: −40 to 110°C


• When the sensor is in use under the condition
TEK–83H601 ULE–SD21–011 of dew, water dripping or outdoor, the sensor

φ6
(Temperature) ULE–SD22–011 should be vertically installed with lead wire
ULE–SD23–011 30 2000 outlet downward.
• Sensor holder is supplied as standard.
Sensor Holder
Lead Wire:Black
18 52
13 27 • Ambient temp. on usage: −55 to 80°C
• When the sensor is in use under the condition

15
TEK–83H609 ULE–SD11–011 of dew, water dripping or outdoor, the sensor
(Temperature) ULE–SD12–011 should be vertically installed with lead wire
2-φ4.2
ULE–SD13–011 outlet downward.
• Sensor holder is supplied as standard.
Lead Wire:Blue

• Designed to accord room interior.


• Designed to be installed where certain air flow
Sensor Mouting Bracket runs and the room humidity is represented.
• Depending on load or other conditions,
humidity control may become difficult.
• Especially when the FLE is used under 10°C
102

or above 40°C, contact manufacturer.

105
HEK–I1R001

83.5
FLE–SD11–011
(Humidity)

71 33 3 Elliptic Holes φ4.5

Following sensors are available as option. (Ambient temperature sensors are available upon request.)
Direct immersion sensor with nipple.............................TEK–83N
Wall mounting sensor ...................................................TEK–83R
Surface temp. sensor ...................................................TEK–83E
Direct immersion sensor with terminal cover................TEK–83B
Bulb well .......................................................................TEK–00N

DIMENSIONS
Type ULE, FLE
Wall Mounting Dimension

SEL

Panel Cutting Dimension

ENT
116

71 Unit: mm

PANEL MOUNTING BRACKET


In case of In case of
Panel Thickness Panel Thickness
: 1 to 1.6mm : 1.6 to 3.2mm

ULE/FLE body ULE/FLE body

39