Elements of Power Systems (Pdfdrive)
Elements of Power Systems (Pdfdrive)
ELECTRICAL ENGINEERING
K26369
ISBN: 978-1-4987-3446-2
Pradip Kumar Sadhu • Soumya Das
90000
9 781498 734462
This book contains information obtained from authentic and highly regarded sources. Reasonable
efforts have been made to publish reliable data and information, but the author and publisher cannot
assume responsibility for the validity of all materials or the consequences of their use. The authors and
publishers have attempted to trace the copyright holders of all material reproduced in this publication
and apologize to copyright holders if permission to publish in this form has not been obtained. If any
copyright material has not been acknowledged please write and let us know so we may rectify in any
future reprint.
Except as permitted under U.S. Copyright Law, no part of this book may be reprinted, reproduced,
transmitted, or utilized in any form by any electronic, mechanical, or other means, now known or
hereafter invented, including photocopying, microfilming, and recording, or in any information stor-
age or retrieval system, without written permission from the publishers.
For permission to photocopy or use material electronically from this work, please access www.copy-
right.com (http://www.copyright.com/) or contact the Copyright Clearance Center, Inc. (CCC), 222
Rosewood Drive, Danvers, MA 01923, 978-750-8400. CCC is a not-for-profit organization that pro-
vides licenses and registration for a variety of users. For organizations that have been granted a photo-
copy license by the CCC, a separate system of payment has been arranged.
Trademark Notice: Product or corporate names may be trademarks or registered trademarks, and are
used only for identification and explanation without intent to infringe.
Visit the Taylor & Francis Web site at
http://www.taylorandfrancis.com
and the CRC Press Web site at
http://www.crcpress.com
Contents
Preface, xxiii
Acknowledgments, xxv
Authors, xxvii
Symbols of Circuit Elements, xxix
Chapter 1 ▪ Introductory 1
1.1 INTRODUCTION 1
1.2 SIGNIFICANCE OF ELECTRICAL ENERGY 1
1.3 BASIC CONCEPTS OF A POWER SYSTEM 2
1.4 SINGLE-LINE DIAGRAM OF A POWER SUPPLY
NETWORK 3
1.5 DIFFERENT TYPES OF ENERGY SOURCES 5
1.5.1 Conventional (Nonrenewable) Sources of
Electric Energy 5
1.5.1.1 Steam Power Station (Thermal Station) 5
1.5.1.2 Gas Turbine Power Plant 7
1.5.1.3 Hydroelectric Power Generation 9
1.5.1.4 Nuclear Power Plant 11
1.5.1.5 Diesel Power Plant 13
1.5.1.6 Magneto Hydrodynamic Generation 16
1.5.2 Nonconventional (Renewable) Sources of
Electric Energy 17
1.5.2.1 Solar Energy 17
1.5.2.2 Wind Power 18
v
vi ◾ Contents
Chapter 4 ▪ Tariffs 49
4.1 INTRODUCTION 49
4.2 OBJECTIVES OF A TARIFF 50
4.3 DESIRABLE CHARACTERISTICS OF A TARIFF 50
4.4 TYPES OF TARIFF 51
4.4.1 Flat-Demand Tariff 51
4.4.2 Simple Tariff 51
4.4.3 Flat-Rate Tariff 52
4.4.4 Step-Rate Tariff 52
4.4.5 Block-Rate Tariff 53
4.4.6 Two-Part Tariff 53
4.4.7 Maximum-Demand Tariff 55
4.4.8 Three-Part Tariff 55
4.4.9 Power Factor Tariff 56
4.4.9.1 kVA Maximum-Demand Tariff 56
4.4.9.2 Sliding Scale Tariff 56
4.4.9.3 kW and kVAR Tariff 56
WORKED EXAMPLES 56
5.2.1.1 Copper 62
5.2.1.2 Aluminum 63
5.2.1.3 Steel-Cored Aluminum 63
5.2.1.4 Galvanized Steel 64
5.2.1.5 Cadmium Copper 65
5.2.1.6 Phosphor Bronze 65
5.3 LINE SUPPORTS 65
5.3.1 Wooden Poles 66
5.3.2 Steel Poles 67
5.3.3 RCC Poles 67
5.3.4 Steel Towers 67
5.4 INDIAN ELECTRICITY RULES (1956) FOR
OVERHEAD LINES 69
5.5 SAG IN OVERHEAD LINES 69
5.5.1 Conductor Sag and Tension 70
5.6 CALCULATION OF SAG 70
5.6.1 When Supports Are at Equal Levels 71
5.6.2 When Supports Are at Unequal Levels 72
5.6.3 Effect of Wind and Ice Loading 74
5.7 SAG TEMPLATE 75
5.8 STRINGING CHART 76
WORKED EXAMPLES 76
IBLIOGRAPHY, 515
B
INDEX, 517
Preface
xxiii
This page intentionally left blank
Acknowledgments
xxv
This page intentionally left blank
Authors
xxvii
xxviii ◾ Authors
6. Current transformer
7. Potential transformer
(Continued)
xxix
xxx ◾ Symbols of Circuit Elements
Introductory
1.1 INTRODUCTION
Energy is the main reason to progress. The natural resources of a coun-
try may be massive but they can only be turned into assets if they are
developed, exploited, and interchanged for other goods. This cannot be
achieved without energy. Energy exists in different forms in nature but the
most important form is electrical energy. Energy is needed for heat, light,
motive power, etc. The modern development in science and technology
has made it possible to convert electrical energy into any desired form.
This has given electrical energy a place of pride in the modern world. The
survival of industrial undertakings and our social structures depend pri-
marily upon low cost and continuous supply of electrical energy. In fact,
availability of sufficient electrical energy and its proper use in any country
can result in its people rising from subsistence level to the highest stan-
dard of living.
1. Power stations may be built close to coal mines (called pit head sta-
tions), and electric energy is evacuated over transmission lines to the
load centers.
2. Power stations may be built close to the load centers, and coal is
transported to them from the mines by rail road.
G.S. 11 kV
Switchyard
11/132 kV Transformer
Primary
transmission
132/33 kV
RS Receiving
station
Large Large
consumers consumers
Secondary
transmission
33/11 kV
SS Substation
Medium Medium
consumers consumers
Primary
distribution
11 kV/400 V DS
Secondary
distribution
Small consumers
Chimney
Induced
draught fan
Switchyard
Bus bars
Electro- R
static Y
presipi- B
tator
Isolators
Hot air Air CB
pre-
heater Isolators
Forced
Flue gases draught fan
Supply
line Econo-
of coal miser Transformer
11/132 kV
Flue
gases Turbine
Coal Exciter
Coal Super
handling Boiler
storage heater
plant Valve Alternator
Ash Exhaust
Ash Flue gases steam
handling
storage
plant
Feed water
heater
Condensate
Ash
Feed water extraction
cleaning
pump pump
Condenser
Circulating
water pump
Cooling
Water
tower
treatment
chamber
River
furnace by coal handling unit. Heat produced due to burning of the coal
is utilized in converting water in the boiler drum to steam at suitable pres-
sure and temperature. The steam generated is passed through the super-
heater. Superheated steam then flows through the turbine. In the turbine,
the pressure of steam is reduced. Steam leaving the turbine passes through
the condenser, where the pressure of steam at the exhaust of turbine is
maintained. Steam pressure in the condenser depends upon flow rate and
temperature of cooling water and on effectiveness of air removal equip-
ment. Water circulating through the condenser may be taken from the
various sources such as river, lake, or sea. If sufficient quantity of water is
Introductory ◾ 7
not available, the hot water is coming out of the condenser may be cooled
in cooling tower and circulated again through the condenser. Blade sys-
tem taken from the turbine at suitable extraction point is sent to low- and
high-pressure water heaters. With the help of force draught fan, air is col-
lected from the atmosphere and is first passed through the air preheater,
where it is heated by flue gases. The hot air then passes through the fur-
nace. The flue gases after passing through the boiler and superheated tube,
flow through economizer, air preheater, and electrostatic precipitator (dust
collector), and finally they are exhausted to the atmosphere through the
chimney by induced draught fan.
Merits
5. The cost of generation is lesser than that of the diesel power station.
Demerits
Switchyard
Bus bars
R
Regenerator Y
B
Isolators
CB
Isolators
Exhaust
gases
Combustion
chamber Transformer
11/132 kV
Compressor
Gas
A M
turbine
Alternator Starting
motor
Filter
in shell. The compressed air from the compressor passes through the
tubes on its way to the combustion chamber. In this way, compressed air
is heated by the exhaust gases. The air at high pressure from the com-
pressor is led to the combustion chamber via regenerator. In this cham-
ber, heat is added to the air by burning oil. The oil is injected through
the burner into the chamber at high pressure to ensure atomization of oil
and its mixing with air. The result is that the chamber attains very high
temperature (about 3000°F). The combustion gases are suitably cooled
led to 1300–1500 °F and then delivered to the gas turbine. The product
of combustion consisting of a mixture of gases at high temperature and
pressure is passed to the gas turbine. There gases passing over the tur-
bine blade expand and thus do the mechanical work. The temperature
of the exhaust gases from the turbine is about 900°F. The gas turbine
is coupled to the alternator. The alternator converts mechanical energy
of the turbine into electrical energy. The output from the alternator is
given to the bus bars through transformer, circuit breaker, and isola-
tors. Before starting the turbine, the compressor has to be started. For
this purpose, electric motor is mounted on the same shaft as that of the
turbine. The motor is energized by the batteries. Once the unit starts, a
part of mechanical power of the turbine drives the compressor and there
is no need of motor now.
Introductory ◾ 9
Merits
Demerits
Surge tank
Reservoir Dam
Valve house
Pressure channel
Penstock
Power house
River
Demerits
Switchyard
Bus bars
R
Y
B
Isolators
CB
Isolators
Heat Transformer
exchanger 11/32 kV
Hot metal
Turbine Exciter
Nuclear Steam
reactor
Valve Alternator
Filter Exhaust
steam
Pump
Cold Condenser
metal
Feed water
pump
Circulating
water pump
Cooling
tower
River
4. It can be located near the load centers because it does not require
large quantities of water and need not be near coal mines. Therefore,
the cost of primary distribution is reduced.
5. There are large deposits of nuclear fuels available all over the world.
Therefore, such plants can ensure continued supply of electrical
energy for thousands of years.
Demerits
Intake
air filter Silencer Surge
Day tank tank
Diesel engine
Jacket
Exhaust water pump
Fuel oil Fuel injection
starting pump
Jacket
air Generator water
Filter Oil pump
Starting
air Lube
oil Lubricating oil Cooling water
comp.
Starting Oil
oil tank Lubricating
oil tank cooler
Auxiliary
oil pump Filter or
Overflow Transfer purifier
pump Strainer
Fuel tank
Heat
exchanger
Raw water
pump
by rail or road. This oil is stored in the storage tank. From the storage
tank, oil is pumped to smaller all day tank at daily or short intervals.
From this tank, fuel oil is passed through strainers to remove sus-
pended impurities. The clean oil is injected into the engine by fuel
injection pump.
Air intake system: This system supplies necessary air to the engine for
fuel combustion. It consists of tubes for the supply of fresh air to the
engine manifold. Filters are provided to remove dust specks from the
breeze which may act as abrasive in the engine cylinder.
Exhaust system: This system leads the engine exhaust gas outside the
building and discharges it into the atmosphere. A silencer is usually
incorporated in the system to reduce the noise level.
Cooling system: The heat liberated by the combustion of fuel in the
engine cylinder is partially converted into work. The remainder part
of the heat passes through the cylinder walls, piston, rings, etc. and
may cause damage to the system. In order to keep the temperature of
the engine parts within the safe operating limits, cooling is p
rovided.
The cooling system consists of a water source, pump, and cooling
Introductory ◾ 15
towers. The pump circulates water through the piston chamber and
head jacket. The water carries away heat from the locomotive and it
gets hot. The hot water is cooled by cooling towers and is recirculated
for cooling.
Lubricating system: This arrangement minimizes the wear of rubbing
surfaces of the locomotive. It contains of the lubricating oil tank,
pump, filter, and oil cooler. The lubricating oil is drawn from the
lubricating oil tank by the pump and is passed through filters to
remove impurities. The clean lubricating oil is delivered to the points
which require lubrication. The oil coolers incorporated in the system
keep the temperature of the oil low.
Engine starting system: This is an agreement to rotate the engine ini-
tially, while bugging out, until firing starts and the unit runs with
its own force. Small sets are taken off manually by handles, but for
larger units, compressed air is used for initiating. In the latter case,
air at high pressure is admitted to a few of the cylinders, making
them to act as reciprocating air motors to turn over the engine shaft.
The fuel is admitted to the remaining cylinders which makes the
locomotive to take off under its own force.
Diesel engine generator (alternator): The alternator used in diesel elec-
tric power plants are of rotating field, salient pole construction,
speed ranging from 214 to 1000 rpm (poles 28 to 6), and capacity is
ranging from 25 to 5000 kVA at 0.8 pf lagging. Their output voltages
are of 440 V in case of small machines and as high as 2200 V in case
of large machines. Voltage regulation is about 30%.
They are directly coupled to the diesel engines. They are supplied
with automatic voltage regulation and satisfactory parallel operation.
The excitation is usually provided at 115 or 230 V from a DC exciter
of rating about 2%–4% of the alternator ratings, usually coupled to
the engine shaft either directly or through a belt.
Merits
Demerits
1. The plant has high running charges as the fuel (i.e., diesel) used is
costly.
1.5.2.1 Solar Energy
The Sun is the primary and main source of energy. The average incident
solar energy received on earth’s surface is about 600 W/m2 but the actual
value varies considerably. It possesses the vantage of being complimen-
tary of cost, non-exhaustible, and completely pollution free. On the other
hand, it has several drawbacks—energy density per-unit area is very low,
it is available for only a part of the day, and cloudy and hazy atmospheric
conditions greatly reduce the energy received. So, harnessing solar energy
for electricity generation, challenging technological problems exist, the
Load
Anode
Gas flow
Flow
at 2500°C
Cathode
Strong magnetic
field
1.5.2.2 Wind Power
This method can be used where wind flows for a considerable length of
time. The wind energy is used to run the wind mill which drives a small
generator. In order to obtain the electrical energy from a wind mill con-
tinuously, the generator is arranged to charge the batteries. These batteries
Introductory ◾ 19
supply the energy when the wind stops. This method has the advantages
that maintenance and generation costs are negligible.
In our country, this source of generation of electrical energy will prove
economical at a number of places as revealed in a recent study undertaken
by National Aerospace Laboratories, Bengaluru.
However, this method is unreliable since the production of electrical
energy depends largely upon the pressure of the wind.
1.5.2.3 Wave Energy
The energy content of sea waves is very high. In India, with several hun-
dreds of kilometers of coast line, a vast source of energy is available. The
power in the wave is proportional to the square of the amplitude and to the
period of the motion. Therefore, the long period (~10 s) and large ampli-
tude (~2 m) waves are of considerable interest for power generation, with
energy fluxes commonly averaging between 50 and 70 kW/m width of
oncoming wave. Though the engineering problems associated with wave
power are formidable, the amount of energy that can be harnessed is large
and development work is in progress. Sea wave power estimated potential
is 20,000 MW.
1.5.2.5 Biofuels
The material of plants and animals is called biomass, which may be
transformed by chemical and biological processes to produce intermedi-
ate biofuels such as methane gas, ethanol liquid, or charcoal solid. Biomass
is burnt to provide heat for cooking, comfort heat (space heat), crop
drying, factory processes, and raising steam for electricity p
roduction and
transport. In India, potential for bio-energy is 17,000 MW and that for
agricultural waste is about 6000 MW.
20 ◾ Elements of Power Systems
1.5.2.6 Geothermal Energy
Geothermal energy is another energy source that can be harnessed for
power generation and thermal applications in near future. Geothermal
energy is the natural heat generated from within the earth. The steam
and hot water come naturally to the airfoil of the ground at some posi-
tions. The primary source of geothermal energy is magma. The extraction
of heat form earth’s interior needs a natural or artificial heat exchanger.
Water is injected by an injection well into hot dry rock inside the ground
to extract the hot water and steam from production wells. Water injected
into the wall acts as a heat collecting and heat transporting medium.
EXERCISES
9. Draw the flow diagram of a diesel power station and discuss its
operation.
10. Discuss the advantages and disadvantages of a diesel power station.
11. Draw the schematic diagram of a nuclear power station and discuss
its operation.
12. Explain the working of a gas turbine power plant with a schematic
diagram.
13. Give the comparison of steam power plant, hydroelectric power
plant, and nuclear power plant on the basis of operating cost, ini-
tial cost, efficiency, maintenance cost, and availability of source of
power.
This page intentionally left blank
Chapter 2
Per-Unit Systems
2.1 INTRODUCTION
In large interconnected power systems with several voltage levels and vari-
ous capacity equipments, it has been found very convenient to play with
per-unit (pu) systems of quantities for analysis rather than in absolute val-
ues of measures. The pu system leads to great simplification of three-phase
networks involving transformers. The numerical pu value of any amount
is determined as the proportion of its actual value to another arbitrarily
chosen value of the quantity of the dimensions assumed as the theme or
extension.
Ka
K pu = (2.2)
Kb
23
24 ◾ Elements of Power Systems
I amp
Per-unit current = I pu = (2.3)
Ib
Vvolt
Per-unit voltage = Vpu = (2.4)
Vb
Zohm
Per-unit impedance = Z pu = (2.5)
Zb
or
Z pu = Rpu + jX pu
Rohm
∴ Rpu = (2.6)
Zb
and
X ohm
X pu = (2.7)
Zb
Per-unit volt-ampere
Svolt-amp
Spu = (2.8)
Sb
Per-Unit Systems ◾ 25
S = P + jQ = VI *
Svolt-amp P Q
Spu = = +j
Sb Sb Sb
∴ Spu = Ppu + jQpu
Pwatt
∴ Ppu = (2.9)
Sb
Qvars
∴ Qpu = (2.10)
Sb
Vb
Zb = (2.11)
Ib
and
Sb = Vb I b (2.12)
Vb VbVb Vb2
Zb = = = ohms (2.13)
Ib Vb I b Sb
1 S
Yb = = b siemens
Z b Vb 2
Vpu = Z pu I pu (2.14)
26 ◾ Elements of Power Systems
Spu = Vpu I pu
*
(2.15)
Sb
Z pu = Z ohm (2.16)
Vb2
Sb Base kVA
Ib = =
Vb Base kV
where base kW is the numerical value of base kVA and base MW is the
numerical value of base MVA.
Let YSim be the actual admittance in siemens and Ypu the pu admittance,
then
1 Vb2 V2
Ypu = = = YSim b
Z pu Z ohm Sb Sb
2.3 CHANGE OF BASE
It is sometimes necessary to convert pu quantities from one base to
another. Let the base volt-ampere and base voltage in system 1 be repre-
sented by Sb1 and Vb1, respectively. The corresponding values in system 2
are represented by Sb2 and Vb2, respectively.
Sb1
I b1 = (2.17)
Vb1
Sb 2
I b2 = (2.18)
Vb 2
I
I1pu = (2.19)
I b1
Per-Unit Systems ◾ 27
I
I 2 pu = (2.20)
I b2
I b1 S V S V
I 2 pu = I1pu = I1pu b1 b 2 = I1pu b1 b 2 (2.21)
I b2 Vb1 Sb 2 Sb 2 Vb1
We know
Sb
Z pu = Z ohm
Vb2
Sb1
Z1pu = Z ohm (2.22)
Vb21
Sb 2
Z 2 pu = Z ohm (2.23)
Vb22
2
Sb 2 Vb1
Z 2 pu = Z1pu (2.24)
Sb1 Vb 2
Equation 2.24 is used for changing the pu impedance from one set of V
and S bases to any other set of V and S.
So the change of base for the admittance can be written as
2
Sb1 Vb 2
Y2 pu = Y1pu (2.25)
Sb 2 Vb1
28 ◾ Elements of Power Systems
I l = I ph , I lb = I phb
Vl 3Vph
(Vl )pu = = = (Vph )pu (2.26)
Vlb 3Vphb
Il I ph
(I l )pu = = = (I ph )pu (2.27)
I lb I phb
where Vl is the line voltage, Vph is the phase voltage, Il is the line current,
and Iph is the phase current in a balance 3ϕ system.
In a delta connection,
I l = 3 I ph , I lb = 3 I phb
Vl Vph
(Vl )pu = = = (Vph )pu (2.28)
Vlb Vphb
Il 3 Iph
(I l )pu = = = (Iph )pu (2.29)
I lb 3 I phb
Thus, it is seen that in both star and delta connections, a pu-phase voltage
has the same numerical value as the corresponding pu-line voltage. Also,
the pu-phase current has the same numerical value as the corresponding
pu-line current.
Sb Vb I b Vb I b × 10−6
Z pu = Z ohm = Z = Z
Vb2 ohm
Vb2 ohm
(Vb × 10−3 )2
(MVA)b
Z pu = Z ohm (2.30)
(kV)2b
2
(MVA)b 2 (kV)b1
Z 2pu = Z1pu (2.31)
(kV)2b1 (kV)b 2
[(MVA)b ]3 φ
Z pu = Z ohm (2.32)
[(kVl )b ]2
Z1 e
Z1epu = (2.33)
Z b1
The total series impedance of the two windings referred to the second-
ary is
2
N
Z 2 e = Z1 e 2 (2.34)
N1
In the secondary, base current is Ib2, base voltage is Vb2, and base imped-
ance, Zb2, is (V2/I2).
Per-unit impedance of the transformer referred to the secondary is
Z2e Z I
Z 2 e pu = = 2e 2 (2.35)
V2 /I 2 V2
Also
N1
I 2 = I1 (2.36)
N2
and
N2
V2 = V1 (2.37)
N1
2
N I N N1 I
Z 2 e pu = Z1e 2 1 1 = Z1 e 1 (2.38)
N1 N 2 V1 N 2 V1
Z 2 e pu = Z1e pu
2.7 ADVANTAGES OF PU REPRESENTATION
Per-unit system computation has the following advantages:
WORKED EXAMPLES
EXAMPLE 2.1
A 230-kV transmission line has a series impedance of (8 + j64)
ohms and a shunt admittance of j4 × 10−3 s. Using 100 MVA and
the line voltage as base values, calculate pu impedance and pu admit-
tance of the line.
Solution
100
Z pu = Z ohm = (8 + j64) ×
(230)2
= (0.015 + j0.12) pu
(230)2
Ypu = j 4 × 10−3 ×
100
= j 2.116 pu
EXAMPLE 2.2
A three-phase, star-connected system is rated at 100 MVA and
110 kV. Express 20,000 kVA of three-phase apparent power as a pu
value referred to as
Solution
1. For the three-phase base:
1
Base kVA = × 1,00,000 = 33.33 MVA = 1 pu
3
110
Base kV = = 63.5
3
1 20,000
Per-unit kVA = × = 0.20 pu
3 33.33 × 103
EXAMPLE 2.3
A 200-MVA, 11-kV, three-phase generator has a subtransient reac-
tance of 10%. The generator is connected to the motors through
transmission lines and transformers. The motors have rated inputs
of 20 MVA and 30 MVA at 20 kV with 10% subtransient reactance.
Three-phase transformers are rated at 110 MVA, 13 kV,Δ/110 kV,Y
with leakage reactance at 8%. The line has a reactance of 30 Ω. Select
the generator rating as the base quantities in other parts of the sys-
tem and evaluate the corresponding pu values.
Solution
Assuming base values as 200 MVA and 11 kV in the generator cir-
cuit, the pu reactance of generator will be 10%. The base value of
voltage in the line will be
110
11 × = 93.07
13
13
93.07 × = 11 kV
110
Per-Unit Systems ◾ 33
2
200 13
0. 8 × × = 0.203
100 11
30 × 200
Per-unit impedance of line = = 0.6926
(93.07)2
2
200 20
Per-unit reactance for motor 1 = 0.1 × × = 3.30
20 11
2
200 20
Per-unit reactance for motor 2 = 0.1 × × = 2.20
30 11
2
200 20
Per-unit reactance for motor 3 = 0.1 × × = 1.32
50 11
EXERCISES
Load Characteristics
3.1 INTRODUCTION
The primary function of a power station is to serve power to a large
number of consumers. Nevertheless, the power needs of consumers are
subjected to change depending upon their actions. As a consequence of
this variance in demand, the load on a power station is never constant,
rather it shifts with time. Due to this reason modern power plant faces
a lot of complexities. Regrettably, we cannot store electrical power and,
consequently, the power station must create power as and when required
to meet the demands of the consumers. On one hand, for maximum effi-
ciency, it is important to run the alternators in the power station at their
rated capacity and on the other hand, the requirements of the consum-
ers have wide variances. This makes the design of a power station highly
complex.
3.2 LOAD
A device that uses electrical energy is said to impose a load on the system.
The term load has number of applications such as
35
36 ◾ Elements of Power Systems
3.5 DEMAND
The demand of a system is the load that is drawn from the source of sup-
ply at a receiving terminal averaged over a suitable and specified interval
of time.
The load may be given in kW, kilovar (kvar), kilovoltampere (kVA), or
ampere (A).
1. Instantaneous demand
2. Sustained demand
The former is not very important because all the machines are designed
for overloads. The sustained intervals are generally taken as 15 min,
30 min, or even longer. But 30 min is the basic time in India.
Max. demand
DF =
Total connected load
The DF can also be found for a part of the system. For example, an
industrial or commercial consumer, instead of for the whole system.
Average load
LF =
Max. demand
If the plant is in operation for T hours,
Average load × T Units generated in T hours
LF = =
Max. demand × T Max. demand × T hours
Load Characteristics ◾ 39
The plant capacity factor is a measure of the reserve capacity of the plant.
A power station must be designed in such a way that it has some reserve
capacity for meeting the increased load demand in future. Therefore, the
installed capacity of the plant is always somewhat greater than maximum
demand on the plant.
7.35 × 106
Plant use factor = = 0.167 = 16.7%
20 × 103 × 2190
Average load
LF =
Max. demand
Average load = Max. demand × LF
Units generated/annum = Average load (in kW) × Hours in a year
= Max. demand (iin kW)
× LF × 8760
This relationship is applicable for the copper losses of the system but not
for the iron losses.
Load Characteristics ◾ 41
10
8
6
Load in MW
12 2 4 6 8 10 12 2 4 6 8 10 12
Midnight Noon
Hour
(a) (b)
25 25
20 20
Load in MW
Load in MW
15 15
10 10
5 5
0
12 4 8 12 16 20 24 0 4 8 12 16 20 24
(Midnight) Time of day Hours duration
Load curve Load duration curve
FIGURE 3.2 (a) Daily load curve and (b) daily load duration curve.
Load Characteristics ◾ 43
5. The average demand during some specified time period such as a day or
month or year can be obtained from the load duration curve as follows:
kWh(or MWh) consumed in a given time period
Average demand =
Hours in the time period
Area under the load duration curve
=
Base of the load duration curve
WORKED EXAMPLES
EXAMPLE 3.1
The peak load on a power station is 60 MW. The load having maxi-
mum demand of 30, 20, 15, and 10 MW are connected to the power
plant. The capacity of the power plant is 80 MW and the annual LF is
0.80. Estimate (a) the average load on the power plant, (b) the energy
supplied per year, (c) the DF, (d) the diversity factor, (e) the utiliza-
tion factor, (f) the plant capacity factor, and (g) the reverse factor.
Solution
(a) Average load = LF × Peak or max. load
= 0.8 × 60 = 48 MW
(b) Energy supplied per year or kWh gen = Average load
× No. of hours in year
= 48 × 103 × 8760
= 42,048 × 104 kWh
(c) Simultaneous maximum demand of the group of consum-
ers = (30 + 20 + 15 + 10) = 75 MW.
Let the connected load be equal to the maximum demand of
the group consumers, then
Max. demand 60
DF = = = 0. 8
Connected load 75
Sum of individual consumers max.
demand
(d) Diversity factor =
Simultaneous max. demand
of the group of consumers
75
= = 1.25
60
44 ◾ Elements of Power Systems
EXAMPLE 3.2
A 150 MW power station delivers 150 MW for 2 h, 75 MW for 8 h,
and is shut down for the rest of each day. It is also shut down for
maintenance for 50 days each year. Calculate its annual LF.
Solution
EXAMPLE 3.3
A power station has a maximum demand of 20,000 kW. The annual
LF is 40%, and plant capacity factor is 35%. Determine the reserve
capacity of the plant.
Solution
Units generated/annum
Plant capacity factor =
Plant capacity × Hours in a year
70.08 × 106
∴ Plant capacity =
0.35 × 8760
= 22,857.14 kW
EXAMPLE 3.4
A power plant has maximum demand of 80 MW, an LF of 0.7, plant
capacity factor of 0.5, and plant use factor of 0.9. Find (a) the daily
energy produced, (b) the reverse capacity of the plant, and (c) the
maximum energy that could be produced daily if the plant operating
schedule is fully loaded when in operation.
Solution
Average load = LF × Peak or max. load
= 0.7 × 80 = 56 MW
56
Capacity of the plant = = 112
0. 5
EXAMPLE 3.5
Estimate the generation cost per unit of electric energy production
from a power plant having the following data:
Solution
Output per charge = No. of units generated
= Average load × 8760
= 5 ×108 kWh
5 × 108
Average load = = 57,077.62 kW
8760
Let the installed capacity of the plant be equal to peak load, then
EXERCISES
1. Why is the load on a power station variable? What are the effects of
variable load on the operation of the power station?
2. What do you understand by the load curve? What information are
conveyed by a load curve?
3. Define and explain the importance of the following terms in
generation:
a. Connected load
b. Maximum demand
c. Demand factor
d. Average load
4. Explain the terms load factor and diversity factor. How do these fac-
tors influence the cost of generation?
5. Explain how load curves help in the selection of size and number of
generating units.
6. Discuss the important points to be taken into consideration while
selecting the size and number of units.
7. What do you understand about
a. Base load
b. Peak load of a power station
8. Write short notes on the following:
a. Load curves
b. Load division on hydro-steam system
c. Load factor
d. Plant capacity factor
This page intentionally left blank
Chapter 4
Tariffs
4.1 INTRODUCTION
The electrical energy that is produced in a power station is delivered to
a large number of consumers. The consumers can be convinced to use
electrical energy if it is sold at a reasonable price. Here comes the idea of
tariffs. A tariff is the schedule of rates structured by the supplier for sup-
plying electrical energy to various types of consumers. The rate at which
electric energy is supplied to a consumer is known as tariff. The following
elements are engaged into account to determine the tariff:
The way in which consumers pay for electrical energy changes accord-
ing to their demands. Industrial consumers consume more energy for rel-
atively longer period than domestic consumers. Tariffs should be framed
in such a way so that it covers the cost of production, cost of supply, and
yet yields some reasonable profit.
The price of energy supplied by a generating station depends on the
established capacity of the plant and kWh generated. Maximum demand
increases the installed capacity of the generating station.
49
50 ◾ Elements of Power Systems
Disadvantages
Disadvantages
Disadvantage
• However, by increasing the energy consumption, cost is reduced.
Thus, there is a tendency with the consumer, just approaching the
Tariffs ◾ 53
limit of the step, to anyhow cross the step and enter the next one in
order to reduce the total energy cost.
Disadvantage
• Its principal defect is that it cannot measure the consumer’s demand.
Domestic Residential load, light, fan, television, 1ϕ: supply up to a load of 5 kW Small consumers 1. Simple Meter rent and
radio, electric irons, domestic 3ϕ: supply for loads exceeding (high unity), big 2. Flat rate electricity duty
pumps, coolers, air conditioners 5 kW consumers (0.5) 3. Block rate
Commercial Shops, business houses, hotels, 1ϕ: supply up to a load of 5 kW Fairly high 1. Simple Meter rent and
cinemas, clubs, etc. 3ϕ: supply for loads exceeding 2. Flat rate electricity duty
5 kW 3. Block rate
Agricultural Tube wells 3ϕ: power up to 20 kW Unity Flat rate
Bulk Railways, educational institutes, 3ϕ: power at 415 V or 11 kV Flat rate
military establishment, hospitals depending on their requirement,
load exceeding 10 kW
Industrial Atta chakkis, small workshop, saw 3ϕ: power supply at 415 V, load Usually high Block tariff
(small) mill, etc. not exceeding 20 kW (0.8)
Industrial 3ϕ: power supply at 415 V, load Two-part tariff
(medium) exceeding 20 kW but not
exceeding 100 kW
Industrial Power supplied at 11 kV or 33 kV, 0.5 KVA maximum
(large) load exceeding 100 kW demand factor
tariff
Tariffs ◾ 55
Advantages
Disadvantages
• Fixed charges
• Semi-fixed charges
• Running charges
where a is the fixed charge made during each billing period. It includes
interest and depreciation on the cost of secondary distribution and labor
56 ◾ Elements of Power Systems
WORKED EXAMPLES
EXAMPLE 4.1
The maximum demand of a consumer is 15 A at 230 V and his/her
total energy consumption is 9000 kWh. If the energy is charged at
the rate of Rs. 5 per unit for 600 h use of the maximum demand per
Tariffs ◾ 57
annum plus Rs. 2 per unit for additional units, calculate (1) annual
bill and (2) equivalent flat rate.
Solution
Assume the load factor and power factor to be unity.
230 × 15 × 1
Maximum demand = = 3.45 kW
1000
EXAMPLE 4.2
A consumer has a maximum demand of 150 kW at 50% load factor.
If the tariff is Rs. 800 per kW of maximum demand plus Rs. 2 per
kWh, find the overall cost per kWh.
Solution
1,434,000
∴ Overall cost/kWh = Rs . = Rs. 2.18
657, 000
EXAMPLE 4.3
The monthly readings of a consumer’s meter are as follows:
Maximum demand = 75 kW
Energy consumed = 50,000 kWh
Reactive energy = 277,500 kVAR
If the tariff is Rs. 600 per kW of maximum demand plus Rs. 2 per
unit plus Rs. 1 per unit for each 1% of power factor below 90%, cal-
culate the monthly bill of the consumer.
Solution
50,000
Average load = = 69.44 kW
24 × 30
27,500
Average reactive power = = 38.19 kVAR
24 × 30
kVAR 38.19
tan φ = = = 0.55
Active power 75
or
50,000 × 1
Power factor surcharge = Rs. × (90 − 87.6) = Rs. 1200
100
EXAMPLE 4.4
The daily load of an industrial concern is as follows: 150 kW for 10 h,
175 kW for 5 h, 60 kW for 6 h, 50 kW for 3 h, the tariff is Rs. 700 per
kW of maximum demand per year plus Rs. 1.20 per kWh. Determine
the energy consumption per year and the yearly bill.
Solution
Annual maximum demand charges = Rs. 175 × 700 = Rs. 122, 500
Total annual charges = Rs. (1, 263, 630 + 122, 500) = Rs. 1, 386,130.
EXAMPLE 4.5
The following tariffs are offered to a consumer:
Find the energy consumed per month for which the charges due
to both tariffs become equal.
Solution
Let x be the number of units consumed, where x > 200.
Monthly charges due to second tariff c2 = Rs. (1.5 × 100) + (1.7 × 100)
+ (11.9)(x − 200)
= Rs. (1.9 x − 60)
If c1 = c2, then
600 x + 1x = 1.9 x − 60
(1.9 − 1)x = 540
540
x= = 600 kWh
0. 9
EXERCISES
Mechanical Design
of Overhead Line
5.1 INTRODUCTION
For proper operation of overhead line, protective measures must be consid-
ered in the invention of electrical parameters as well as for the mechanical
portion. The line should have sufficient current-carrying capacity so that the
necessary power transfer can take place without violating allowable voltage
drop criterion or overheating. Line losses should be as low as possible and
spacing between the line conductors and with the earth should be adequate
to cope up with the system voltage. On the other hand, for the mechanical
aspects, the line conductors, supports, and the cross arm should have suf-
ficient mechanical strength to cope with the probable weather problems. The
mechanical design should estimate the “sag” of the conductor at its mid-span
length, as sag is to be allowed to cater the load of the conductor. Adequate dis-
tance between the lowest point of the line and the earth must be maintained.
5.2 CONDUCTOR MATERIAL
The conductor is one of the important objects, as most of the capital outlay
is invested for it. Therefore, choice of material and size of conductor are
of utmost importance. The conductor material used for transmission and
distribution of electric power should possess the following properties:
61
62 ◾ Elements of Power Systems
5.2.1.1 Copper
Copper is an ideal material for overhead lines due to its high electrical
conductivity and greater tensile strength. It is always used in the hard
drawn form as stranded conductor. Although hard drawing decreases the
electrical conductivity slightly, yet it increases the tensile strength reason-
ably. Copper has high current density, that is, the current carrying capac-
ity of copper per unit of cross-sectional area is quite large. This leads to
two advantages:
Moreover, this metal is quite homogeneous, durable, and has high scrap
value. There is no doubt that copper is an ideal material for transmis-
sion and distribution of electric power. However, due to its high cost and
nonavailability, it is rarely used for these purpose. Nowadays the trend is
to use aluminum in place of copper.
Mechanical Design of Overhead Line ◾ 63
5.2.1.2 Aluminum
Aluminum is cheap and light as compared to copper but it has much
smaller conductivity and tensile strength. The relative comparison of the
two materials is given below:
5.2.1.3 Steel-Cored Aluminum
Due to low tensile strength, aluminum conductors produce greater sag.
This prohibits their use for larger spans and makes them unsuitable for
long distance transmission. In order to increase the tensile strength, the
aluminum conductor is reinforced with a core of galvanized steel wires.
The composite conductor thus obtained is known as steel-cored alumi-
num and is abbreviated as ACSR (aluminum conductor steel reinforced).
64 ◾ Elements of Power Systems
5.2.1.4 Galvanized Steel
Steel has very high tensile strength. Therefore, galvanized steel conductors
can be used for extremely long spans or for short-line sections exposed to
abnormally high stresses due to climatic conditions. They are found very
suitable in rural areas where cost is the main consideration. Due to poor
(a)
(b)
Aluminum
Steel
FIGURE 5.1 (a) Conventional ACSR conductor and (b) cross-sectional view of
ACSR conductor.
Mechanical Design of Overhead Line ◾ 65
conductivity and high resistance of steel, such conductors are not suitable
for transmitting large power over a long distance. However, they can be
used to transmit a small power over a small distance where the size of the
desired copper conductor would be too small and thus unsuitable for use
because of poor mechanical strength.
Nowadays, use of galvanized steel wires is limited to telecommunica-
tion lines, stray wires, earth wires, and guard wires.
5.2.1.5 Cadmium Copper
The conductor material now being employed in certain cases is copper
alloyed with cadmium. An addition of 1% or 2% cadmium to copper
increases the tensile strength by 50%, and the conductivity is only reduced
by 15% below that of pure copper. Therefore, cadmium copper conduc-
tor can be useful for exceptionally long spans. However, due to high cost
of cadmium, such conductors will be economical only for lines of small
cross-sections, that is, where the cost of conductor material is compara-
tively small compared with the cost of supports.
5.2.1.6 Phosphor Bronze
When harmful gases such as ammonia are present in atmosphere and the
spans are extremely long, phosphor bronze is most suitable material for
an overhead line conductor. In this conductor, some strands of phosphor
bronze are added to the cadmium copper.
5.3 LINE SUPPORTS
The supporting structures for overhead line conductors are various types
of poles and towers called line supports. In general, the line supports
should have the following properties:
5.3.1 Wooden Poles
These are made of seasoned wood (sal or chir) and are suitable for lines
of moderate cross-sectional area and of relatively shorter spans, say up to
50 m. Such supports are cheap, easily available, provide insulating proper-
ties, and therefore are widely used for distribution purposes in rural areas
as an economical proposition. The wooden poles generally tend to rotten
below the ground level, causing foundation failure. In order to prevent
this, the portion of the pole below the ground level is impregnated with
preservative compound like creosote oil. Double pole structures of the
“A” or “H” type are often used (Figure 5.2) to obtain a higher transverse
strength than could be economically provided by means of a single pole.
(a) (b)
Insulator
Crossarm
Steel
bracing
Poles
FIGURE 5.2 (a) “A” type wooden poles and (b) “H” type wooden poles.
Mechanical Design of Overhead Line ◾ 67
5.3.2 Steel Poles
The steel poles are often used as a substitute wooden pole. They posses
greater mechanical strength, longer life, and permit longer span to be
used. Such poles are generally used for distribution purposes in the cities.
These types of supports need to be galvanized or painted in order to pro-
long its life. The steel poles are of three types:
1. Rail poles
2. Tubular poles
5.3.3 RCC Poles
The reinforced concrete poles usually called the concrete poles are exten-
sively used for low- and high-voltage distribution lines up to 33 kV. They
have greater mechanical strength, longer life, and permits longer spans
than steel poles. Moreover, they give good outlook, require little mainte-
nance, and have good insulating properties. Figure 5.3 shows RCC poles
for single and double circuit. The holes in the poles facilitate the climbing
of poles and at the same time reduce the weight of line supports.
The main difficulty with the use of these poles is the high cost of trans-
port owing to their heavy weight; therefore, such poles are often manufac-
tured at the site in order to avoid heavy cost of transmission.
5.3.4 Steel Towers
For long distance transmission at higher voltage, steel towers are invari-
ably employed which have greater mechanical strength, longer life, and
68 ◾ Elements of Power Systems
(a) (b)
FIGURE 5.3 (a) RCC poles for single circuit and (b) RCC poles for double circuit.
can withstand most severe climate conditions and permit the use of longer
spans. The risk of interrupted service due to broken or punctured insula-
tion is considerably reduced owing to longer spans. Tower footings are
usually grounded by driving rods into the earth. This minimizes the light-
ening troubles as each tower acts as a lightening conductor.
Figure 5.4a and c shows a single circuit 110 kV tower and 500 kV tower,
respectively. However, at a moderate additional cost, double circuit tower
FIGURE 5.4 (a) Single circuit 110 kV steel tower, (b) double circuit steel tower,
and (c) single circuit 500 kV steel tower.
Mechanical Design of Overhead Line ◾ 69
can be provided as shown in Figure 5.4b. The double circuit has the
advantage that it ensures continuity of supply. In case, there is break-
down of one circuit, the continuity of supply can be maintained by the
other circuit.
• Rule 75—Joints
• Rule 90—Earthing
(a) (b) T
A B B
S
O
O T0
FIGURE 5.5 (a) A conductor suspended between two equilevel supports and (b)
tension at any point on the conductor.
2. The tension at any point on the conductor acts tangentially. Thus, ten-
sion T0 at the lowest point acts horizontally as shown in Figure 5.5b.
3. The horizontal component of tension is constant throughout the
length of the wire.
4. The tension at supports is approximately equal to the horizontal ten-
sion acting at any point on the wire. Thus, if T is the tension at the
support B, then T = T0.
5.6 CALCULATION OF SAG
In an overhead line, the sag should be so adjusted that tension in the
conductors is within safe limits. The tension is governed by conductor
weight, effect of wind, ice loading, and temperature variations. It is a
standard practice to keep conductor tension less than 50% of its ulti-
mate tensile strength, that is, minimum factor of safety in respect of
conductor tension should be 2. We shall now calculate sag tension of a
conductor when (i) supports are at equal level and (ii) supports are at
unequal level.
Mechanical Design of Overhead Line ◾ 71
x
Ty = wx ×
2
or
wx 2
y=
2T
w(1/2)2 wl 2
S= =
2T 8T
A l l B
2 2
P S
x
2 y
T
O wx
x
FIGURE 5.6 External forces on the sag between two equilevel supports.
72 ◾ Elements of Power Systems
wx12
Sag S1 =
2T
wx22
Sag S2 =
2T
Also
x1 + x2 = 1
(5.1)
Now
w 2 w
S2 − S1 = (x2 − x12 ) = (x + x )(x − x )
2T 2T 2 1 2 1
h
S2
A
S1 O
x1 x2
l
wl
∴ S2 − S1 = (x − x ) [∵ x1 + x2 = 1]
2T 2 1
But
S2 − S1 = h
wl
∴h = (x − x )
2T 2 1
or
2Th
x2 − x1 = (5.2)
wl
1 Th
x1 = − (5.3)
2 wl
1 Th
x2 = + (5.4)
2 wl
1 Th
If > , then x1 is positive
2 wl
1 Th
If > , then x1 is zero
2 wl
1 Th
If < , then x1 is negative
2 wl
d2
O d1
x1
x2
w t = (w + wi )2 + w w2
Ice coating
(a)
(c)
ww
θ
t d
(b) (w + wi) wt
Wind
FIGURE 5.9 (a) Ice coating on the conductor, (b) wind pressure on the conduc-
tor, and (c) total force on the conductor.
Mechanical Design of Overhead Line ◾ 75
5.7 SAG TEMPLATE
For perfect design and maintaining economic balance, location of struc-
tures of profile with a template is very essential. Sag template is a suitable
device, which is often used in designing a transmission line to determine
the location and height of the structures. Sag template can be a reliable
option which provides the following:
1. Economic layout
2. Minimum errors in design and layout
3. Proper grading of structures
4. Controls excessive insulator swing
The straight run towers are used for straight runs and normal con-
ditions. The angle towers are designed to withstand heavy loading as
76 ◾ Elements of Power Systems
Line conductor
Tower Ground
clearance
e
ing lin
Tower foot
compared to standard towers because angle towers are used at angles, ter-
minals, and other points, where a large unbalanced pull may be thrown
on the supports.
For standard towers, normal or average spans, the sag and the nature
of the curve (catenary or parabola) the line conductor occupies under
expected loading conditions are evaluated and plotted on the template.
Template will also show the required minimum ground clearance by plot-
ting a curve parallel to the conductor shape curve. For the standard tower
and same height, the tower footing line can also be plotted on the tem-
plate. Tower footing line is used for locating the position of towers, and
minimum ground clearance is maintained throughout. Figure 5.10 shows
the sag template used for locating towers.
5.8 STRINGING CHART
For use in the field work of stringing the conductors, temperature–sag and
temperature–tension charts are plotted for the given conductor and load-
ing conditions. Such curves are called stringing charts (Figure 5.11). These
charts are very helpful while stringing overhead lines.
WORKED EXAMPLES
EXAMPLE 5.1
A 132-kV transmission line has the following data: weight
of conductor = 700 kg/km, length of span = 250 m, ultimate
strength = 2800 kg, and safety factor = 2.
Calculate the height above ground at which the conductor should
be supported. Ground clearance required is 15 m.
Mechanical Design of Overhead Line ◾ 77
Sag
Tension in kg
Sag in meters
Tensi
on
Temperature
Solution
• Weight of conductor/meter run,
700
w= = 0.7 kg
1000
• Working tension,
wl 2 0.7 × 2502
Sag = = = 3.90 m
8T 8 × 1400
EXAMPLE 5.2
A transmission line has a span of 250 m between level supports.
The conductor has an effective diameter of 1.44 cm and weighs
0.900 kg/m. Its ultimate strength is 7520 kg. If the conductor has ice
coating of radial thickness 1.43 cm and is subjected to a wind pres-
sure of 3.8 g/cm2 of projected area, calculate sag for a safety factor of
2. Weight of 1 cm3 of ice is 0.91 g.
78 ◾ Elements of Power Systems
Solution
Span length, l = 250 m
Weight of conductor/meter length, w = 0.900 kg
Conductor diameter, d = 1.44 cm
Ice-coating thickness, t = 1.43 cm
Working tension is
7520
T = = 3760 kg
2
= πt (d + t ) × 100 cm3
= π × 1.43 × (1.44 + 1.43) × 100 = 1289.34 cm3
w t = (w + wi )2 + (w w )2
= (0.900 + 1.173)2 + (1.634)2
= 2.639 kg
wt l 2 2.639 × (250)2
∴ Sag = = = 5.48 m
8T 8 × 3760
EXAMPLE 5.3
A transmission line conductor at a river crossing is supported from
two towers at a height of 50 and 80 m above water level. The hori-
zontal distance between the towers is 300 m. If the tension in the
Mechanical Design of Overhead Line ◾ 79
Solution
Difference in level between the two supports: h = 80 − 50 = 30 m
Distance of lowest point of conductor from the support of low
level: x = (L/2) − (Th/wL)
300 2000 × 30
∴x = − = − 86.967 m
2 0.844 × 300
L 300
−x= − (−86.967)
2 2
= 236.967 m
L − x = 300 + 86.967 = 386.967 m
w × ((L /2) − x )2
Smid =
2T
0.844 × (236.967)2
=
2 × 2000
= 11.848 m
w × (L − x )2
S2 =
2T
0.844 × (386.967)2
=
2 × 2000
= 31.596 m
80 ◾ Elements of Power Systems
EXERCISES
Overhead Line
Insulators
6.1 INTRODUCTION
The overhead line conductors are open and do not have any insulated
coating over them. Those conductors should be supported on the poles
or towers in such a way that current from conductors do not flow to earth
through supports, that is, line conductors must be properly insulated. This
is accomplished by connecting line conductors to a support with the help
of insulators. The insulator provides necessary insulation between line
conductors and supports and thus prevents any leakage current from con-
ductors to ground. Insulators also provide support to the conductor.
In general, the insulator should have the following desirable properties:
81
82 ◾ Elements of Power Systems
• Porcelain
• Glass
• Synthetic resin
Sheds
Cementing
Galvanized
steel pin
FIGURE 6.1 (a) Pin-type insulator and (b) cross-sectional view of pin-type insulator.
Conductor
b
Pin
c
Crossarm
Puncture strength
Safety factor of the insulator =
Flash − Over voltage
Insulator
Line
conductor
3. If any disk is damaged, the whole string does not become useless
because the damaged disk can be replaced by the sound one.
4. The arrangement provides greater flexibility to the line. The con-
nection at the crossarm is such that insulator is free to swing in
any direction and can take up the position, where the mechanical
stresses are minimum.
5. The suspension type insulators are generally used with steel towers.
As the conductors run below the earthed crossarm of the tower, there-
fore, this arrangement provides partial protection from lightning.
6. In case of increased demand on the transmission line, it is found
more satisfactory to supply greater demand by raising the line volt-
age, than to provide another set of conductor. The additional insu-
lation required for the raised voltage can be easily obtained in the
suspension arrangement by adding the desired number of disks.
1. Cap-and-pin type
2. Hewlett or interlink type
Strain
insulator
Guy
insulator Conductor
Pole
Bolt
Shackle
insulator
D-strap
two metal links. Therefore, each disk forms a capacitor C known as mutual
capacitance or self-capacitance. If there were mutual capacitance alone, then
charging current would have been the same through all the disks and conse-
quently voltage across each unit would have been same, that is, V/3 as shown
in Figure 6.9b. However, in actual practice, capacitance also exists between
metal fitting of each disk and tower or earth. This is known as shunt capaci-
tance C1. Due to shunt capacitance, charging current is not same through all
the discs of the string shown in Figure 6.9c. Therefore, voltage across each
disk will be different. Obviously, the disk nearest to the line conductor will
have the maximum voltage. Therefore, V3 will be much more than V1 or V2.
The following points may be noted regarding the potential distribution
over a string of suspension insulators:
V1 C V/3 C V1
C1 I1
I i1
V
V2 C V/3 C V2
C1 I2
I
i2 I
Conductor 3
V3 C V/3 C1 C V3
I i3
Conductor
FIGURE 6.9 (a) Three discs string of suspension insulators; (b) voltage distribu-
tion shown in the presence of mutual capacitances; (c) voltage distribution shown
in the presence of both mutual and shunt capacitances.
Overhead Line Insulators ◾ 89
C V1
C1 i I1
1
A
V
C V2
C1 i I2
2
B
C V3
C1 i I3
3
C
I 2 = I1 + i1
or
or
or
V2 = V1 (1 + K ) (6.1)
I 3 = I 2 + i2
or
or
or
V3 = V2 + (V1 + V2 )K
= KV1 + (1 + K )V2
= KV1 + V1 (1 + K )2 [∵ V2 = V1 (1 + K )]
= V1[K + (1 + K )2 ]
Overhead Line Insulators ◾ 91
∴ V3 = V1[1 + 3K + K 2 ] (6.2)
V = V1 + V2 + V3
= V1 + V1 (1 + K ) + V1[1 + 3K + K 2 ]
= V1 + (3 + 4 K + K 2 )
∴ V = V1 (1 + K )(3 + K ) (6.3)
V1 V2 V3 V
= = =
1 1 + K [1 + 3K + K 2 ] (1 + K )(3 + K )
V
V1 =
(1 + K )(3 + K )
V2 = V1 (1 + K )
V3 = V1[1 + 3K + K 2 ]
1. Disk nearest to the conductor has maximum voltage across it. The
voltage across other disk decreasing progressively as the crossarm in
approached.
92 ◾ Elements of Power Systems
Tower
Crossarm
Shunt
capacitor
Line
C
C1 i i'1
1
C2
I
C
C1 i
2 i'2
C3
I
C
Guard
ring
WORKED EXAMPLES
EXAMPLE 6.1
The three bus-bar conductors in an outdoor substation are sup-
ported by units of post-type insulators. Each unit consists of a stack
of three pin-type insulators fixed one on the top of the other. The
voltage across the lowest insulator is 11.3 kV and that across the next
unit is 10.2 kV. Find the bus-bar voltage of the station.
Solution
The equivalent circuit of insulators is the same as shown in Figure
6.13. It is given that V3 = 11.3 kV and V2 = 10.2 kV. Let K be the ratio
of shunt capacitance to self-capacitance of each unit.
Applying Kirchhoff’s current law to junctions A and B, we can
easily derive the following equations.
V2 = V1 (1 + K )
C V1
C1 i I1
1
A
V
C V2
C1 i I2
2
B
C V3
C1 i I3
3
C
or
V2
V1 = (6.4)
(1 + K )
and
V3 = V2 + (V1 + V2 ) K (6.5)
V2
V3 = V2 + + V2 K
(1 + K )
or
V3 (1 + K ) = V2 (1 + K ) + [V2 + V2 (1 + K )] K
or
V3 (1 + K ) = V2[(1 + K ) + K + (K + K 2 )]
= V2[1 + 3K + K 2 ]
Therefore,
11.3 (1 + K ) = 10.2 [1 + 3K + K 2 ]
or
or
or
or
Therefore,
V2 10.2
V1 = = = 9.71
(1 + K ) 1 + 0.05
EXAMPLE 6.2
An insulator string consists of three units, each having a safe work-
ing voltage of 13 kV. The ratio of self-capacitance to shunt capaci-
tance of each unit is 10:1. Find the maximum safe working voltage of
the string. Also find the string efficiency.
Solution
The equivalent circuit of string insulators is the same as shown in
Figure 6.13. The maximum voltage will appear across the lowest unit
in the string.
1
V3 = 13 kV, K = = 0. 1
10
V2 = V1 (1 + K )
or
V2 V2
V1 = = = 0.909 V2 (6.6)
(1 + K ) 1 + 0.1
or
V3 = 1.190 V2 (6.7)
V3 13
V2 = = = 10.916 kV
1.190 1.190
33.84
String efficiency = × 100% = 86.76%
3 × 13
EXAMPLE 6.3
In a transmission line, each conductor is at 30 kV and is supported by
a string of three suspension insulators. The air capacitance between
each cap–pin junction and tower is one-eighth of the capacitance of
each insulator unit. A guard ring, effective only over the line-end
insulator unit is fitted so that the voltages on the two units nearest
the line-end are equal. (a) Calculate the voltage on the line-end unit.
(b) Calculate the value of capacitance Cx required (Figure 6.14).
Solution
Voltage between unit conductor and earth V = 30 kV.
C
I1 V1
i1 C/8
A
C V2
Cx Ix I2 i2 C/8
V
B
C
I3 V3
Mutual capacitance = C
Shunt capacitance = C/8 = 0.125C
Applying Kirchhoff’s first law to node A:
I 2 = I1 + i1
or
V2 = 1.125V1
also
V3 = V2
and
V = V1 + V2 + V3
or
30 = V1 + V2 + V3
or
30 = V1 + 1.125V1 + 1.125V1
or
30
V1 = = 9.23 kV
1 + 1.125 + 1.125
or
V3 = 1.125 × V1 = 10.38 kV
a. Voltage on the line-end unit ≥ V3 = 10.38 kV
b. Applying Kirchhoff’s first law to node B, we have:
I 3 + ix = I 2 + i2
or
C
ωCV3 + ωCxV3 = ωCV2 + ω (V + V2 )
8 1
Overhead Line Insulators ◾ 99
or
C
C × 1.125V1 + Cx × 1.125V1 = C × 1.125V1 + 2.125
8
or
2.125
Cx = C = 0.3148C farads
6 × 1.125
EXAMPLE 6.4
In a string of three identical suspension insulator units supporting
a transmission line conductor, if the self-capacitance of each unit is
denoted as C farads, the capacitance of each connector pin to ground
can be taken as 0.20 farads. Determine the voltage distribution across
the string if the maximum possible voltage par unit is given as 30 kV.
Also determine the string efficiency.
Solution
Number of units, n = 3. Ratio of shunt capacitance to mutual capaci-
tance is
0.2C
K = = 0. 2
C
V3 30
V1 = = = 18.29 kV
1 + 3K + K 2 1 + 0 . 6 + 0.04
V 70.25
String efficiency = = × 100 = 78.04%
nVn 3 × 30
100 ◾ Elements of Power Systems
EXERCISES
1. Why are insulators used with overhead lines? Discuss the desirable
properties of insulators.
2. Discuss the advantages and disadvantages of (i) pin-type insulators
and (ii) suspension-type insulators.
3. Explain how the electrical breakdown can occur in an insulator.
4. What is a strain insulator and where is it used? Give a sketch to show
its location.
5. Give reasons for unequal potential distribution over a string of sus-
pension insulators.
6. Define and explain string efficiency. Can its value be equal to 100%?
7. Show that in a string of suspension insulators, the disk nearest to the
conductor has the highest voltage across it.
8. Explain various methods of improving string efficiency.
9. Explain why the voltage across the insulators of a simple insulator
string are not equal?
Chapter 7
Corona
7.1 INTRODUCTION
The use of high-voltage supply has become necessary in order to fulfill the
rapidly increasing demand of power. With extra high-voltage transmission
lines of more than 230 kV coming into prominence, the corona character-
istics of conductors have gained great importance. Below this size of the
conductor is mainly determined by corona loss and radio noise. A series of
experiments carried out in many countries reveal that it is now possible to
predict the extent of corona performance of a line under different operat-
ing conditions with a fair degree of accuracy.
101
102 ◾ Elements of Power Systems
electrostatic stress in the air around the conductor exceeds 30 kV max/cm
or 21.21 kV rms/cm.
The phenomenon of violet glow, hissing noise, and production of ozone
gas in an overhead transmission line is known as corona.
If the conductors are polished and smooth, the corona glow will be uni-
form throughout the length of the conductor; otherwise, the rough points
will appear brighter. With DC voltage, there is difference in the appear-
ance of the two wires. The positive wire has uniform glow around it, while
the negative conductor has spotty glow.
Conductor. It has been observed that the corona very much depends
1.
upon the shape and condition of conductor. A rough and irregu-
lar surfaced conductor gives more corona, that is, near rough and
dirty surface, corona glow is intensified because unevenness of the
surface decreases the value of breakdown voltage. For example,
stranded conductor gives more corona than a single solid conduc-
tor (without strand).
Corona ◾ 103
7.5 ADVANTAGES OF CORONA
1. Due to corona formation, the air surrounding the conductor become
conducting and hence virtual diameter of the conductor is increased.
The increased diameter reduces the electromagnetic stresses between
the conductors.
2. Corona reduces the effects of transients produced by surges.
7.6 DISADVANTAGES OF CORONA
1. Corona is accompanied by a loss of energy. This affects the transmis-
sion efficiency of the line.
2. Ozone is produced by corona and may cause corrosion of the con-
ductor due to chemical action.
3. The current drawn by the line due to corona is non-sinusoidal, and
hence non-sinusoidal voltage drop occurs in the line. This may cause
inductive interference with neighboring communication line.
104 ◾ Elements of Power Systems
V
g= V/cm
r log e (d /r )
In order that corona is formed, the value of g must be made equal to the
breakdown strength of air. The breakdown strength of air at 76 cm pres-
sures and temperature of 25°C is 30 kV/cm (max) or 21.21 kV/cm (rms)
and is denoted by g0. If Vc is the phase-neutral potential required under
these conditions, then
Phase wire
r cm
L
d cm V rms
Neutral wire
Vc
g0 =
r log e (d / r )
d
Vc = g 0r log e
r
3.92b
δ = Air density factor =
273 + t
d
Vc = g 0δr log e
r
d
Vc = m0 g 0δr log e kV/phase
r
0. 3
g v = g 0δ 1 + kV/cm
rδ
d
Vv = g v r ln
r
or
Vv 0.3
gv = = g 0δ 1 +
r log e (d / r ) rδ
or
0. 3 d
Vv = rg 0δ 1 + log e kV
rδ r
0 .3 d
Vv = g 0mv δr 1 + log e r
rδ
0.3 d
= 21.21 mv δr 1 + log e r kVrms
rδ
The irregularity factor value mv is 1 for polished wires, 0.98 to 0.93 for
rough conductor exposed to atmospheric severities, and 0.72 for local
corona on stranded conductors.
f + 25 r
P = 242.2 (V − Vc )2 × 10−5 kW/km/phase
δ d
7.11 RADIO INTERFERENCE
Radio interference is one of the adverse effects caused by corona on wire-
less broadcasting. The corona discharges radiation which may introduce
noise signal in the communication lines, radio, and television receivers.
It is primarily because of the brush discharges on the surface irregulari-
ties of the conductor during positive half cycles. This causes corona to
occur at voltages below the critical voltages. The negative discharges are
less troublesome for radio reception. Radio interference is considered as a
field measured in microvolts per meter at any distance from the transmis-
sion line and is significant only at voltages greater than 200 kV. There is
gradual increase in radio interference (RI) level until the voltage reaches a
value which causes corona to take place. Above this voltage, there is rapid
increase in RI level. The rate of increase is more for smooth and large diam-
eter conductors. The amplitude of RI level varies inversely as the frequency
at which the interference is measured. Thus, the services in the higher fre-
quency band, for example, television, frequency-modulated broadcasting,
microwave relay, radar, etc., are less affected. Radio interference is one of
the very important factors while designing a transmission line.
108 ◾ Elements of Power Systems
7.12.1 Electromagnetic Effects
Figure 7.2A–C shows the power conductors of a three-phase single
circuit line on a transmission tower, and D and E, the conductors of
a neighboring communication line running on the same transmission
towers as the power conductors or a neighboring separate line. Let the
distances between power conductors and communication conductors be
dAD, dAE , dBD, dBE , dCD, and dCE , and the currents through power conduc-
tors be IA, IB, and IC , such that IA + IB + IC = 0. The flux linkage to con-
ductor D due to current IA in conductor A will be ψAD = 2 × 10 −7IA loge(∞/
dAD). Similarly, the flux linkage to conductor E due to current IA in a
conductor A.
∞
ψ AE = 2 × 10−7 I A log e
dAE
dAE
ψ AD − ψ AE = 2 × 10−7 I A log e
dAD
Corona ◾ 109
B C
D E
D' E'
B' C'
A'
or mutual inductance
ψ AD − ψ AE d
MA = = 2 × 10−7 log e AE H/m
IA dAD
dBE
M B = 2 × 10−7 log e H/m
dBD
dCE
MC = 2 × 10−7 log e H/m
dCD
M = M A + M B + MC
where M is the net mutual inductance which is the phasor sum of the three
inductances.
If I is the current in the power conductors and f is the supply frequency,
the voltage induced in the communication conductors D and E will be
V = 2πfMI V/m.
110 ◾ Elements of Power Systems
7.12.2 Electrostatic Effects
Consider again Figure 7.2. Let Q be the charge per-unit length of the
power line. The voltage of conductor D due to charge on conductor can be
obtained by considering the charge on conductor A and its image on the
ground. Let conductor A be at a height hA from the ground. Therefore, the
voltage of conductor D will approximately be
dAD
Q 1 1
VAD =
2π0 ∫ x + (2h
hA
dx
A − x)
h
Q 2hA − x
A
Q 2hA − dAD
= ln = log e
2π0 x dAD 2π0 dAD
Q 2h
VA = ln A
2π0 r
2π0VA 1 2h − dAD
VAD = ln A
log e (2hA /r ) 2π0 dAD
log e[(2hA − dAD )/dAD ]
= VA
log e (2hA/r )
Corona ◾ 111
WORKED EXAMPLES
EXAMPLE 7.1
A three-phase transmission line consists of 1 cm radius conduc-
tors spaced symmetrically 3 m apart. Dielectric strength of air is
30 kV/cm. Determine the unit voltage for commencing of corona
(Irregularity factor = 0.9, temperature 20°C, barometric pressure
72.2 cm of mercury).
Solution
d = 3 m = 300 m
r = 1 cm
30
Dielectric strength of air: v0 = kV/cm = 21.21 kV/cm
2
d
Line voltage for commencing corona = 3Vc = 3 g 0· m0r log e
r
300
= 3 × 21.21 × 0.966 × 0.96 × 1 × log e = 194.31 kV
1
EXAMPLE 7.2
A three-phase, 220-kV, 50-Hz transmission line consists of 1.15 radius
conductor spaced 3 m apart in equilateral triangular formation, if
112 ◾ Elements of Power Systems
Solution
The corona loss is given by
242.2 r
P= ( f + 25) (V − Vc )2 × 10−5 kW/km/phase
δ d
Now
d
Vc = m0 g 0δ r log e kV
r
300
= 0.966 × 21.21 × 0.96 × 1.15 × log e
1.15
= 125.885 kV
242.2 1.15
P= (50 + 25) (127 − 125.8)2 × 10−5
0.966 300
= 0.015 kW/km/phaase
EXERCISES
1. What is corona? What are the factors which affect corona?
2. Discuss the advantages and disadvantages of corona.
3. Explain the following terms with reference to corona:
a. Critical disruptive voltage
b. Visual critical voltage
c. Power loss due to corona
4. Describe the various methods for reducing corona effect in an over-
head transmission line.
This page intentionally left blank
Chapter 8
Transmission Line
Parameters
8.1 INTRODUCTION
An electric transmission line consists of four parameters, namely resis-
tance, inductance, capacitance, and shunt conductance. Shunt conduc-
tance, which is mostly due to leakage over line insulators, is almost always
neglected in overhead transmission lines. The electrical design and opera-
tion of a line are dependent on these parameters. These four parameters
are uniformly distributed on the whole distance of the cable. The commu-
nication channel parameters are functions of the communication channel
geometry, building material, and operational frequency. The line resis-
tance and inductance form the series impedance. The capacitance and
conductance form the shunt admittance.
d dφ
| e |= (φN ) = N Volts
dt dt (8.1)
115
116 ◾ Elements of Power Systems
di
|e|= L Volts (8.2)
dt
dφ di dφ
N =L , L=N (8.3)
dt dt di
dφ φ
=
di i
and
φN
L= H (8.4)
i
φ
L= H (8.5)
i
I Ix 2
Ix = πx 2 = 2
πr 2
r
Current
Hx =
2π × Distance
Ix 2 1 Ix
∴ Hx = × = AT/m
r2 2πx 2πr 2
(a) (b)
Flux
r
I
x
r
dx
FIGURE 8.1 (a) Single current carrying conductor and (b) flux linkage due to
internal flux (cross-sectional view).
118 ◾ Elements of Power Systems
µ o Ix
∴ Bx = µ o H x Wb/m2 = Wb/m2
2πr 2
µ o xI
dφ = B x × 1 × dx = dx Wb
2πr 2
πx 2 µ Ix 3
dΨ = dφ = o 4 dx Wb
πr 2
2πr
r
µo x 3 I µ I
Ψint =
∫
0
2πr 4
dx = o Wb/m
8π
4 π × 10−7 × I (8.6)
= Wb/m
8π
1
= I × 10−7 Wb/m
2
2
d2
r
x
d1
1 dx
the conductor, whole of the flux between points 1 and 2 lies within the
concentric cylindrical surface passing through these points 1 and 2.
The field strength at any distance x from the center of the conductor
(x > r),
I
Hx = AT/m
2πx
Flux density,
µo I
Bx = µ o H x Wb/m2 = Wb/m2
2πx
So, the flux through a cylindrical shell of radial thickness dx and axial
length 1 m.
µo I
dφ = B x × 1 × dx = dx Wb/m
2πx
Now flux linkages per meter is equal to dϕ, since flux external to con-
ductor links all the current in the conductor only once
µo I
dΨ = dx Wb/m
2πx
d2
µo I 4 π × 10−7
∫
d2
Ψext = dx = I log e x Wb/m
2πx 2π d1
d1 (8.7)
d
= 2 × 10−7 I log e 2 Wb/m
d1
+Q –Q
r1 r2
A B
directions, as one forms the return path for the other. The inductance of
each conductor is due to internal flux linkages and external flux linkages,
and the following points are to be noted regarding external flux linkages:
d
ΨA ext = 2 × 10−7 I log e Wb/m
r1
1
ΨAint = × I × 10−7 Wb/m
2
Transmission Line Parameters ◾ 121
d 1
ΨA = ΨA ext + ΨAint 2 × 10−7 I log e + × I × 10−7 Wb/m
r1 2
d
= 0.5 + 2 × log e I × 10−7 Wb/m
r1
LA =
ΨA
=
( )
0.5 + 2 log e (d / r1 )
× I × 10−7 H/m
I I
d
= 2 × 10−7 0.25 + log e H/m
r1
d
= 2 × 10−7 log e e1/ 4 + log e H/m
r1
d
= 2 × 10−7 log e −1/ 4 H/m
r1e
r1′ = 0.7788r1
d
∴ LA = 2 × 10−7 log e H/m
r1′
Similarly, inductance of conductor B is
d
LB = 2 × 10−7 log e H/m
r2′
L = LA + LB
d d
= 2 × 10−7 log e + log e
r1′ r2′
d
L = 4 × 10−7 × log e H/m
r′
d
= 0.4 × log e mH/km
r1e −1/ 4
d1p
2
d2p
P
d3p
3
dnp
The flux linkage of conductor 1 due to its own current I1 (internal and
external), up to point P is
d1p
Ψ1p1 = 2 × 10−7 I1 log e Wb/m
r1′
d2 p
Ψ1p2 = 2 × 10−7 I 2 log e
d12
d1p d2 p d3 p dnp
Ψ1p = 2 × 10−7 I1 log e + I 2 log e + I 3 log e + + In log e
r1′ d12 d13 d1n
Wb/m
1 1 1 1
Ψ1p = 2 × 10−7 I1 log e + I 2 log e + I 3 ln + + In log e
r1′ d12 d13 d1n
+ 2 × 10−7 [ I1 log e d1p + I 2 log e d2 p + I 3 log e d3 p + + In log e dnp ]
(8.8)
To account for the total flux linkage to conductor 1, the point P must be
approach infinity and in this condition
Then,
lim[I1 + I 2 + I 3 + + In ] log e d = 0, ∵ I1 + I 2 + I 3 + + In = 0
d →∞
124 ◾ Elements of Power Systems
This simplifies the Equation 8.8 and the equation for the flux linkages
to conductor 1 becomes
1 1 1 1
Ψ1 = 2 × 10−7 I1 log e + I 2 log e + I 3 log e + + In log e Wb/m
r1′ d12 d13 d1n
(8.9)
I 1 1 1 1
Ψ1 = 2 × 10−7 log e + log e + log e + + In log e
x r1′ d12 d13 d1x
I 1 1 1 1
− 2 × 10−7 I1 log e + I 2 log e + I 3 log e + + In log e
y d11′ d12′ d13′ d1 y
y
(d11′ d12′ d13′ …d1 y )
Ψ1 = 2 × 10 I log e
−7
Wb/m
x r1′d12 d13d14 …d1x
3 3′
2 2′
4 4′
1 6 6′
5 1′
x y′ 5′
A B
Ψ1
y
(d11′ d12′ d13′ …d1 y )
L1 = = 2 × 10−7 x log e (8.10)
I /x x r ′ d d d …d
12 13 14 1x
Ψ1
y
(d11′ d12′ d13′ …d1 y )
L1 = = 2 × 10−7 x log e H/m (8.11)
I /x x d d d d …d
11 12 13 14 1x
Similarly, the expression for inductance for strand 2 can be written as
Ψ2
y
(d21′ d22′ d23′ …d2 y )
L2 = = 2 × 10−7 x log e H/m (8.12)
I /x x d d d d …d
21 22 23 24 2x
L1 + L2 + L3 + + Lx
Lav =
x
Lav L + L + L + + Lx
LA = = 1 2 32
x x
(d11′ d12′ d13′ …d1 y )(d21′ d22′ d23′ …d2 y )…(dx1′ , dx 2′ , dx 3′ …dxy )
xy
= 2 × 10−7 log e
x2 (d11d12 d13 …d1x )(d21d22 d23 …d2 x )…(dx1 dx2 dx3 …dxx )
(8.13)
126 ◾ Elements of Power Systems
Dm
LA = 2 × 10−7 log e H/m
DsA
Similarly
Dm
LB = 2 × 10−7 log e H/m
DsB
Loop inductance,
Dm D
L = LA + LB = 2 × 10−7 log e + 2 × 10−7 log e m
Ds Ds
(8.14)
D D
= 4 × 10−7 log e m H/m or 0.4 log e m mH/km
Ds Ds
d1 d3
B d2 C
The flux linkages of conductor A due to its own current IA and other
conductor current IB and IC.
1 1 1
ΨA = 2 × 10−7 I A log e + I B log e + I C log e Wb/m
r ′ d d 3
1
Similarly
1 1 1
ΨB = 2 × 10−7 I B log e + I A log e + I C log e Wb/m
r ′ d d 2
1
and
1 1 1
ΨC = 2 × 10−7 I C log e + I A log e + I B log e Wb/m
r′ d3 d2
1 1 1
ΨA = 2 × 10−7 I log e + I (−0.5 − j0.866) log e + I (−0.5 + j0.866)log e
r′ d1 d3
1 d
= 2 × 10−7 I log e + log e d1d3 + j 3 log e 1
r′ d3
and
ΨA 1 d
LA = = 2 × 10−7 log e + log e d1d3 + j 3 log e 1 H/m
IA r′ d3
(8.15)
Similarly
1 d
LB = 2 × 10−7 log e + log e d1d2 + j 3 log e 2 H/m (8.16)
r′ d1
128 ◾ Elements of Power Systems
1 d
LC = 2 × 10−7 log e + log e d2d3 + j 3 log e 3 H/m (8.17)
r′ d2
When three-phase line conductors are not equidistant from each other,
the conductor spacing is said to be unsymmetrical. Under such condi-
tions, the flux linkages and inductance of each phase are not same. A dif-
ferent inductance in each phase results in unequal voltage drop in three
phases even if the current in the conductors are balanced. Therefore, the
voltage at the receiving end will not be same for all phases. In order that
voltage drops are equal in all conductors, we generally interchange the
positions of the conductor at regular intervals along the line, so that each
conductor occupies the original position of every other conductor over an
equal distance. Such an exchange of position is known as transposition,
as shown in Figure 8.7. In practice, the conductors are so transposed that
each of the three possible arrangement of conductors exist for one-third of
the total length of the line.
1. The effect of transposition is that each conductor has the same aver-
age inductance, which is given as
1
L = [LA + LB + LC ]
3
1 1
(
= 2 × 10−7 log e + log e d1d3 + log e d1d2 + log e d2d3
r′ 3 )
j 3 d d d
+ log e 1 + log e 2 + log e 3 H/m (8.18)
3 d3 d1 d2
1
= 2 × 10−7 log e + log e 3 d1d2d3 + 0
r ′
d1d2 d3
= 2 × 10−7 log e 3 H/m
r′
A C B
Position 1
d1 d3
B A C
2
d2
3 C B A
d d
d
B C
d1d2d3
L = 2 × 10−7 log e 3 H/m
r′
d
= 2 × 10−7 log e H/m
r′
1 d
LA = 2 × 10−7 log e + log e 2d × d + j 3 log e H/m
r′ 2d
d 1
= 2 × 10−7 log e + log e 2 + j0.866 log e 2 H/m
r ′ 2
A B C
2d
1 d
LB = 2 × 10−7 log e + log e d × d + j 3 log e H/m
r′ d
d
= 2 × 10−7 log e H/m
r′
1 2d
LC = 2 × 10−7 log e + log e 2d × d + j 3 log e H/m
r′ d
d 1
= 2 × 10−7 log e + log e 2 + j0.866 log e 2 H/m
r′ 2
4. When the conductors are at the corners of right-angled triangle, as
shown in Figure 8.10. In this position,
d1 = d2 = d and d3 = 2d
Substituting this values in Equations 8.15 through 8.17 for LA, LB, and
LC, respectively, we get
1 d
LA = 2 × 10−7 log e + log e 2d × d + j 3 log e H/m
r′ 2d
1 1
= 2 × 10−7 log e + log e 2 − j0.866 log e 2 H/m
r ′ 2
1 d
LB = 2 × 10−7 log e + log e d × d + j 3 log e H/m
r′ d
d
= 2 × 10−7 log e H/m
r′
2d d
A
d B
1 2d
LC = 2 × 10−7 log e + log e 2d × d + j 3 log e H/m
r′ d
d 1
= 2 × 10−7 log e + log e 2 + j0.866 log e 2 H/m
r′ 2
(a) (b)
A C′ A A′
B B′ B B′
C A′ C C′
1 1 1 1
ΨA = 2 × 10−7 I A log e + log e + I B log e + log e
r ′ 2d d 3d
1 1
+ I C log e + log e
3d d
1 1
= 2 × 10 −7 I A log e + (I B + I C )log e
2 dr ′ 3d 2
1 1
= 2 × 10−7 I A log e − I A log e ∵ I A + I B + IC = 0
2 dr ′ 3d 2
3d
= 2 × 10−7 I A log e Wb/m
2r ′
ΨA 3d
Inductance of conductor A is, LA = = 2 × 10−7 log e H/m (8.19)
IA 2r ′
Similarly, inductance of remaining conductors can be worked out,
which will be the same as LA. This is due to the fact that the conductors of
different phases are symmetrically placed.
Since conductors are electrically in parallel, inductance of each phase is
1 3d (8.20)
= L = 1 × 10−7 log e H/m
2 A 2r ′
A d C′
d d
3d
B 2d B′
3d
d d
C d A′
1 1 1 1
ΨA1 = 2 × 10−7 I A log e + log e + I B log e + log e
r′ 4d12 + d22 d1 d12 + d22
1 1
+ I C log e + log e
2d1 d2
Similarly flux linkages with conductor A in positions (b) and (c) are
1 1 1 1
ΨA 2 = 2 × 10−7 I A log e + log e + I B log e + log e
r′ d2 d1 d12 + d22
1 1
+ I C log e + log e
d1
d12 + d22
1 1 1 1
ΨA 3 = 2 × 10−7 I A log e + log e + I B log e 2d + log e d
r ′ 4d1 + d2
2 2
1 2
1 1
+ I C log e + log e
d1
d12 + d22
ΨA1 + ΨA 2 + ΨA 3
ΨA =
3
−7
2 × 10 1 1 1
=
3 I A 3 log e r ′ + log e d + log e 4d 2 + d 2
2 1 2
1 1 1 1
+ I B 2 log e + log e + log e 2 + log e
d1 2d1 d1 + d2
2 d2
1 1 1 1
+ I C log e + log e 2 + log e + 2 log e
2d1 d1 + d2
2 d2 d1
2 × 10−7 1 1 1
=
3 I A 3log e r ′ + log e d + log e 4d 2 + d 2
2 1 2
1 1 1 1
+ ( I B + I C ) log e + log e 2 + log e + 2 log e
2 d 1 d1 + d22 d 2 d1
2 × 10−7 1 1 1
=
3 I A 3 log e r ′ + log e d + log e 4d 2 + d 2
2 1 2
1 1 1 1
− I A log e + log e 2 + log e + 2 log e
2 d 1 d1 + d22 d2 d 1
∵ I A + I B + IC = 0
ΨA
And inductance, LA =
IA
1/3 (8.21)
d1 d12 + d22
= 2 × 10 log e 2
−7 1/3
H/m
r ′ 4d12 + d22
Transmission Line Parameters ◾ 135
1 1
Inductance of each phase L = × Inductance per conductor = LA
2 2
1/2 1/6
1/6 d1 d1 + d2
2 2
= 2 × 10 log e 2 2
−7
H/m
r ′ 4d1 + d22
(8.22)
If the distance d2 is too large as compared to d1, (d12 + d22 )/(4d12 + d22 )
would tend to be unity and inductance per phase,
1/2 1/2
d d
L = 2 × 10−7 log e 21/6 1 H/m or L = 2 × 10−7 log e 21/6 1 mH/km
r′ r′
(8.23)
8.8 CAPACITANCE
We know that any two conductors separate by an insulating material con-
stitute a capacitor. As any two conductors of an overhead transmission line
are separated by air which acts as insulation. Therefore, capacitance exists
between any two overhead line conductors. The capacitance between the
conductors is the charge per-unit potential difference.
Q
Capacitance C = Farad
V
where Q is the charge on the line in coulomb, and V is the potential differ-
ence between the conductors in volts.
spaced. The points which are equally placed from the conductor will be
at the same potential and have the same flux density. All the cylinders
concentric with the conductor will be equipotential surfaces. The electric
flux density Dx at a point x meters from the axis of the conductor is the
quotient of flux leaving the conductor per meter length and the curved
surface of a cylinder 1 m long and having a radius x meters.
Q
Dx = C/m2
2πx × 1
Q
Ex = V/m
2πε 0 ε r x
d2 d2
Q
∫
VAB = Ex dx =
∫ 2πε 0 x
dx
d1 d1
Q d
VAB = log e 2 (8.24)
2πε 0 d1
B
d2
r
d1
A
+Q
QA d QB r QC d
VAB = log e AB + log e B + log e CB +
2πx ε 0 rA 2πx ε 0 dBA 2πx ε 0 dCA
QN d
+ log e NB
2πx ε 0 dNA
B D
dAB
A
dAN N
dAC
If rA, r B, rC,… are replaced by dAA, dBB, dCC,… , respectively, for the sake
of symmetrical result
dNB
+ QN log e Volts (8.25)
dNA
dNC
+ + QN log e Volts (8.26)
dNA
1 d
x =N
VAN =
2πε 0 ∑
Qx log e xN Volts
x =A
dxA
(8.28)
QA + QB + QC + + QN = 0 (8.29)
1 dAB dBB
VAB = QA log e d + QB log e d
2πε 0 BA
AA
Transmission Line Parameters ◾ 139
+Q –Q
r
A B
Here, QA + QB = 0
QA = −QB
dAB = dBA = d
dAA = dBB = r
2
1 d r 1 d 1 d
VAB = QA log e r − QA log e d = 2πε QA log e r = πε QA log e r
2πε 0 0 0
QA QA
CAB = = F/m
VAB (2Q /2πε 0 )log e (d /r )
πε 0
CAB = F/m (8.30)
log e (d /r )
A B
CAB
Q 2πε 0
CN = = F/m (8.31)
(1/2)VAB log e (d /r )
CN = 2CAB
1 d r d
VAB = QA log e r + QB log e d + QC log e d Volts (8.32)
2πε 0
A B
N
d d
d
B C
1 d d r
VAC = QA log e r + QB log e d + QC log e d Volts (8.33)
2πε 0
1 d r
VAB + VAC = 2QA log e r + (QB + QC ) log e d Volts (8.34)
2πε 0
∴ QB + QC = −QA (8.36)
1 d r 3QA d
VAB + VAC = 2QA log e r − QA log e d = 2πε log e r (8.37)
2πε 0
0
VAB + VAC
30
VAC
=2 3 cos 30° VAN
= 3 VAN
VAB
VCA 30°
VAN
N
VCN VBN
C B
VBC
QA d
VAN = log e (8.39)
2πε 0 r
QA 2πε 0
CN = = (8.40)
VAN log e (d /r )
d1 d3
B d2 C
1 d1 r d2
VAB = QA1 log e r + QB1 log e d + QC1 log e d (8.41)
2πε 0 3
1
1 d2 r d3
VAB = QA 2 log e r + QB2 log e d + QC 2 log e d (8.42)
2πε 0 1
2
1 d3 r d1
VAB = QA 3 log e r + QB3 log e d + QC 3 log e d (8.43)
2πε 0 2
3
If the voltage drop along the line is neglected, VAB is the same in each
transposition cycle. On similar lines, three such equations can be written
for VBC = VAB ∠ −120°. Three more equations can be written equating to
zero the summation of all line charges in each section of the transposition
cycle. From these nine (independent) equations, it is possible to determine
the nine unknown charges. The rigorous solution though possible is too
involved.
With the usual spacing of conductors, sufficient accuracy is obtained
by assuming:
values of VAB designated as VAB1, VAB2, and VAB3, in the three sections. The
solution can be considerably simplified by taking VAB as the average of
these three voltage, that is,
1
VAB (avg ) = (V + VAB2 + VAB3 )
3 AB1
1 dd d r3 d d d
VAB = QA log e 1 23 3 + QB log e + QC log e 1 2 3
3 × 2πε 0 r d d d
1 2 3 d1d2d3
1 Deq r
VAB = QA log e + QB log e (8.45)
2πε 0 r Deq
1 Deq r
VAC = QA log e r + QC log e D (8.46)
2πε 0 eq
1 Deq r
VAB + VAC = 2QA log e r + (QB + QC )log e D (8.47)
2πε 0 eq
and
QB + QC = −QA
3QA Deq
3VAN = log e
2πε 0 r
Transmission Line Parameters ◾ 145
QA Deq
VAN = log e (8.48)
2πµ 0 r
QA 2πε 0
CN = = F/m to neutral (8.49)
VAN log e (Deq /r )
+Q –Q
r
A B
d
Earth
A′ B′
–Q +Q
1 d r 4h 2 + d 2
VAB = Q log e + QB log e + QA ′ log e
2πε 0 A r d 2h
2h
+ QB ′ log e (8.50)
4h 2 + d 2
1 d r 4h 2 + d 2
VAB = QA log e − QB log e − QA ′ log e
2πε 0 r d 2h
2h
+ QB ′ log e
4h2 + d 2
Transmission Line Parameters ◾ 147
or
Q 2hd
VAB = log e (8.51)
πε 0 r 4h 2 + d 2
Q Q
CAB = =
VAB
(( ))
(Q / πε 0 ) log e d / r 1 + (d 2 / 4h2 )
πε 0 (8.52)
= F/m line to line
e ((
log d / r 1 + (d 2 / 4h2 )
))
and
2πε 0
CN = F/m to neutral (8.53)
log e (d /r 1 + (d 2 / 4h2 ) )
It is observed from the above equation that the presence of earth modi-
fies the radius r to r(1 + (d2/4h2))1/2. When h is large compared to d (this is
the case normally), the effect of earth on line capacitance is of negligible
order.
B A C
(a) 2 (b) 2 (c) 2
D23 D23 D23
D12 C D12 B D12 A
1 1 1
D31 3 D31 3 D31 3
A C B
H13 H2 H13 H2 H13 H2
H31 H31 H31
H3 H3 H3
H1 H23 H1 H23 H1 H23
A′ C′ B′
3′ 3′ 3′
D31 D31 D31
1′ C′ 1′ 1′
D12 D12 B′ D12 A′
D23 D23 D23
2′ 2′ 2′
B′ A′ C′
1 d h r h
VAB1 = Q log 12 − log e 12 + QB log e − log e 2
2πε 0 A e r h1 d12 h12
d h
+ QC log e 23 − log e 23 (8.54)
d31 h31
For the second portion of the transposition with conductor C in posi-
tion 1, A in position 2, and B in position 3 (see Figure 8.23b):
1 d23 h23 r h3
VAB2 = QA log e r − log e h + QB log e d − log e h
2πε 0
2 23 23
d h
+ QC log e 31 − log e 31 (8.55)
d12 h12
1 d h r h
VAB3 = Q log 31 − log e 31 + QB log e − log e 1
2πε 0 A e r h3 d 31 h 31
d h
+ QC log e 12 − log e 12 (8.56)
d23 h23
Transmission Line Parameters ◾ 149
1
VAB (avg ) = (VAB1 + VAB2 + VAB3 )
3
1 Deq (h12h23h31 )1/3
VAB = Q log − log
6πε 0 A e r e
(h1h2h3 )1/3 (8.57)
r (h h h )1/3
+ QB log e − log e 1 2 3 1/3
Deq (h12h23h31 )
2πε 0
Cn = F/m to neutral (8.59)
( )
log e (Deq /r ) − log e ((h12h23h31 )1/3 )/(h1h2h3 )1/3
Equation 8.59 shows that the effect of ground gives a higher value for
the capacitance than that the obtained by neglecting the ground effect.
1. The BD lines transmit bulk power with reduced losses thereby giving
increased transmission efficiency.
2. It has a higher capacitance to neutral in comparison with single con-
ductor lines, therefore, they have higher charging current, which
helps improving the power factor.
3. By bundling GMR is increased, the inductance per phase, in com-
parison with single conductor lines, is reduced. As a result reactance
per phase is reduced.
s
d d
DS = r ′ s
DS = 3 r ′ s 2
DS = 4 r ′ s 3
+ + ++
+
++ +
++ +
+
+
+
+ + ++
Current No current
flows over flow
the surface
1. Nature of material
2. Diameter of wire—increase with the diameter of wire
3. Frequency—increases with increase in frequency
4. Shape of wire—less for stranded conductor than the solid conductor
It may be noted that the skin effect is negligible when the supply fre-
quency is low (< 50 Hz), and the conductor diameter is small (< 1 cm).
c b a a′ b′ c′
sections). Pairs aa′, bb′, and cc′ can form three loops in parallel. The flux
linking loop aa′ (and therefore its inductance) is the least and it increases
somewhat for loops bb′ and cc′. Thus the density of AC flowing through
the conductors is highest at the inner edges (aa′) of the conductors and
is the least at the outer edges (cc′). This type of nonuniform AC current
distribution becomes more pronounced, as the distance between con-
ductors is reduced. Like skin effect, the nonuniformity of current distri-
bution caused by proximity effect also increases the effective conductor
resistance. For normal spacing of overhead lines, this effect is always of a
negligible order. However, for underground cables where conductors are
located close to each other, proximity effect causes an appreciable increase
in effective conductor resistance.
WORKED EXAMPLES
EXAMPLE 8.1
Calculate the GMR of 6/3 mm AC, 1/3 mm steel ACSR conductor
(Figure 8.27).
D12
D13 1
3
D14 D16
4 6
Solution
An ACSR conductor with six outer conductors of aluminum each
of radius r = 3 mm and one central conductor of steel also of radius
r = 3 mm.
= (4r )2 − (2r )2 = 2 3r
DS1 = DS2 = DS3 = DS4 = DS5 = DS6
= 7 0.7788r × 2r × 2 3r × 4r × 2 3r × 2r × 2r
= 7 299r
DS7 = 7 2r × 0.7788r × 2r × 2r × 2r × 2r × 2r
= 7 49.8432r
Geometric mean radius is
EXAMPLE 8.2
A single-phase double circuit transmission line is shown in the
Figure 8.28. Conductors 1 and 2 in parallel from one path where
1 1′
1.0 m 2.0 m
2′
Solution
Radius of each conductor = 3/2 = 1.5 cm
GMR, r′ = 0.7788, r = 1.168 cm
′ = d12′ = 223.60 cm
d21
′ = 200 cm
d22
Dm 211.47
Loop inductance = 0.4 log e = 0.4 log e = 1.189 mH/km
Ds 10.8
EXAMPLE 8.3
A three-phase overhead line is designed with an equilateral spacing
of 3.5 m with a conductor diameter of 1.2 cm. If the line is con-
structed with horizontal spacing with suitably transposed conduc-
tors, find spacing between adjacent conductors which would give
the same value of inductance as in the equilateral arrangement
(Figure 8.29).
156 ◾ Elements of Power Systems
A
(a) (b)
A B C
3.5 m 3.5 m
d d
3.5 m
B C
Solution
Conductor radius, r = 1.2/2 = 0.6 cm or 6 mm
Geometric mean radius, r′ = 0.7786 × 6 = 4.6728 mm
In equilateral arrangement of line conductors spacing of
conductors = 3.5 m = 3500 mm
d
Inductance per phase, L = 2 × 10−7 log 5 , H/m
r
3500
= 2 × 10−7 log e = 1.324 × 10−6 H/m
4.6728
(L / A) + (L / B) + (L /C )
Lav =
3
1 d 1
Lav = × 2 × 10−7 log e + log e 2 − j 0.866 log e 2
3 r ′ 2
d d 1
+ log e + log e + log e 2 + j 0.866 log e 2 H/m
r′ r′ 2
d 1
= 2 × 10−7 log e + log e 2
r ′ 3
Transmission Line Parameters ◾ 157
d 1
1.324 × 10−6 = 2 × 10−7 log e + log e 2
4 . 6728 3
or d = 4.67286.389 = 2781.5 mm or 2.781 m.
EXAMPLE 8.4
A three-phase, 50-Hz, 132-kV overhead line conductors are placed
in a horizontal plane as shown in Figure 8.30. The conductor diam-
eter is 2 cm. If the line length is 150 km, calculate (1) capacitance per
phase, (2) charging current per phase, assuming complete transposi-
tion of the line.
Solution
Figure shows the arrangement of conductors of the three-phase line.
The equivalent equilateral spacing is
d = 3 d1d2d3 = 3 1 × 2 × 3 = 1.81 m
2
Conductor radius, r = = 1 cm
2
1m 2m
3m
Vph 132,000
IC = = × 2πfC
XC 3
132,000
= × 2π × 50 × 1.605 × 10−6 = 38.427 A
3
EXAMPLE 8.5
Find out the capacitance of a two-wire, one-phase line running at a
height of h meters above the earth. Calculate the capacitance to neu-
tral in the case of single-phase line, whose conductors with radius
of 0.25 cm are separated by 1.5 m and which are lying 7 m above
ground. Line length is 50 km.
Solution
Radius of each conductor, r = 0.25 cm
Spacing between conductors, d = 1.5 m = 150 cm
Height of the conductors above earth, h = 7 m = 700 cm
Capacitance between conductor,
πε 0
C= F/m
log
( )
e d r 1+ ( d 2 / 4 h2 )
π × 8.854 × 10−12
C=
log
(
0.25
e 120 21+ (150 /1400 ) )
= 4.5 × 10 −12
F/m
EXERCISES
Performance of
Transmission Lines
9.1 INTRODUCTION
A transmission line comprises of resistance R, inductance L, capacitance
C, and shunt or leakage conductance G. All the parameters are distributed
uniformly on the whole distance of the cable. These parameters along with
load current and power factor determine the electrical performance of the
line. The term performance includes the calculation of sending-end volt-
age, sending-end current and sending-end power factor, power loss in the
line, efficiency of transmission, regulation, and limits of power flow dur-
ing steady-state and transient conditions. The values of voltage, current,
and power factor at the receiving end are usually known. Calculation of
prior performance is helpful in system planning. The purpose of deriving
the formulae to study the performance of a line is to know the effect of the
line parameters on various loads.
161
162 ◾ Elements of Power Systems
(a) (b)
XL C
I R
Vs
IXL
A IR
B
Load
Vs Vr
Vr
φr
φS
O
E D I
FIGURE 9.1 (a) Equivalent circuit of a single-phase short line. (b) Phasor dia-
gram for a short line (lagging power factor).
Performance of Transmission Lines ◾ 163
OD Vr cos φR + IR
cos φs = =
OC Vs
Vr = Vr ∠0° = Vr + j0
Z = R + jX L
164 ◾ Elements of Power Systems
Vs = Vr + ZI
Also in Figure 9.1a and b, I is the phase current, R is the line resistance
per phase, XL is the line reactance per phase, Z is the line impedance per
phase, Vs is the sending-end-phase voltage, and Vr is the receiving-end-
phase voltage.
For balance three-phase star-connected line,
1
Phase voltage = × Line voltage
3
Performance of Transmission Lines ◾ 165
Vs A B Vr
I = C D I
s r
The validity of Equations 9.1 and 9.2 is based on the fact that a trans-
mission line can be represented by a linear, passive, and bilateral network.
By virtue of reciprocity, the generalized constants are related to each other
by the following equation.
AD − BC = 1 (9.3)
Vs = Vr + ZIr (9.4)
Is Ir
A B
Vs Vr
C D
Is = Ir (9.5)
Comparing the coefficient of Equations 9.4 and 9.5 with the general
Equations 9.1 and 9.2, ABCD constants for short line are
A = 1 = D, B = Z, C = 0
|Vrnl | − |Vrfl |
Per-unit regulation
|Vrfl |
|Vrnl | − |Vrfl |
Percent regulation × 100
|Vrfl |
Vs = AVr + BIr
Ir = 0, Vr = Vr 0
|Vrfl | = |Vr |
1. Nominal T model
2. Nominal π model
It should be noted that nominal T and π models are not equivalent rep-
resentations. They are different representations for actual lines.
168 ◾ Elements of Power Systems
Z
V1 = Vr + I
2 r
V1
Current in the capacitor , IC = = YV1
Z1
Sending-end current,
Z
Is = Ir + IC = Ir + YV1 = Ir + Y Vr + Ir
2
IC
Load
Vs V1 C Vr
Neutral
ZY
Is = YVr + 1 + I (9.6)
2 r
By KVL,
Z Z Z ZY
Vs = V1 + Is = Vr + Ir + YVr + 1 + I
2 2 2 2 r
ZY ZY
Vs = 1 + V + Z 1 + I (9.7)
2 r 4 r
Equations 9.6 and 9.7 give the sending-end current and sending-end
voltage, respectively. These equations can be written in the matrix form as
ZY ZY
Vs 1 + 2 Z 1 +
4 Vr
I = (9.8)
s Y ZY Ir
1+
2
Also,
Vs A B Vr
I C D I
s r
Hence, ABCD constants for nominal T-circuit model of medium line are
ZY ZY
A = D = 1+ , B = Z 1 + , C=Y
2 4
VS
C IS Z XL
2 IS
V1 2
IS R D
2
A Ir Z
O φs 2 XL
Vr Ir
φr 2
Ir 2
Is
R
Ir
IC B
current IC leads V1 by 90° as shown. The phasor sum of Ir and IC gives Is.
Now CD = IsR/2 is in phase with Is, while DE = Is XL/2 leads Is by 90°. Then,
OE represents the sending-end voltage Vs.
9.8.2 Nominal π Model
In this method, capacitance of each conductor (i.e., line-to-neutral) is
divided into two halves; one half being lumped at the sending end and the
other half at the receiving end as shown in Figure 9.5. It is obvious that
capacitance at the sending end has no effect on the line drop. However, its
charging current must be added to line current in order to obtain the total
sending-end current.
V1 = Vr
1
Z1 =
Y1
IS R I XL Ir
IC2 IC1
Load
Vs C/2 C/2 Vr
Neutral
V1 Y
IC1 = = Vr
Z1 2
Line current:
Y
IIR + IC1 = Ir + V
2 r
Y
Vs = V2 = V1 + ZI = Vr + Z Ir + Vr
2
or
ZY
Vs = 1 + V + ZIr (9.9)
2 r
By Ohm’s law:
V2 Y Y ZY
IC 2 = = Vs = 1 + Vr + ZIr
Z2 2 2 2
Sending-end current,
Y Y ZY
Is = I + IC 2 = Ir + Vr + 1 + Vr + ZIr
2 2 2
ZY ZY
Is = Y 1 + V + 1+ I (9.10)
4 r 2 r
ZY
1+ Z
Vs 2 V
I = r
s Y 1 + ZY ZY Ir
4 1 + 2
172 ◾ Elements of Power Systems
C
Vs
φs A
O
Is Vr IXL
φr
IR
IC2
B
IL
Ir IC1
Also,
Vs A B Vr
I C D I (9.11)
s r
Hence, ABCD constants for nominal π-circuit model of medium line are
ZY ZY
A = D = 1+ , B = Z, C = Y 1 + (9.12)
2 4
Ss = 3 VSP ISP
*
= Ps + jQs
Performance of Transmission Lines ◾ 173
where Ps is the active power in watts at the sending end, and Qs is the reac-
tive volt-ampere at the sending end.
The transmission efficiency can be calculated as follows:
PR
ηT =
Ps
Vs = AVr + BIr
Ir = 0, Vr = Vrnl
Vs = AVrnl
Vs
Vrnl =
A
Vs
| Vrnl | =
A
ZY
A = 1+
2
174 ◾ Elements of Power Systems
R XL R XL
n n n n
Vs B G B G Vr
n n n n
Neutral
I + dI z dx I
Load
Vs V + dV y dx V Vr
dx x
the voltage at distance (x + dx) from the receiving end, I + dI, the current
at distance (x + dx) from the receiving end, and I is at a distance x from
the receiving end.
Then for the small element dx,
z dx = Series impedance
y dx = Shunt admittance
The rise in voltage over the element length in the direction of increasing x.
Obviously, dV = I z dx:
dV
= Iz (9.13)
dx
The difference dI of the current between the two ends of the section
due to leakage current through the shunt admittance y dx of the section
is given by;
dI = V y dx
dI
= yV (9.14)
dx
d2V dI
=z
dx 2 dx
176 ◾ Elements of Power Systems
d2V (9.15)
= zyV
dx 2
V = A1e yz x
+ A2e − yz x (9.16)
dV
= yz A1e yz x
− A2e − yz x (9.17)
dx
dV
= Iz
dx
1
I= yz A1e yz x − A 2e − yz x
z
(9.18)
y
= A e yz x − A 2e − yz x
z 1
Equations 9.16 and 9.17 thus give the expressions for V and I in the form
of unknown constants A1 and A2. The values of A1 and A2 can be deter-
mined by receiving-end condition as under
Vr = A1 + A 2 (9.19)
and
Y (9.20)
Ir = [A − A 2 ]
Z 1
Performance of Transmission Lines ◾ 177
1 z 1
A1 = Vr + Ir = [V + Z cIr ]
2 y 2 r
1 z 1
A2 = Vr − Ir = [V − Z cIr ]
2 y 2 r
1 1 (9.21)
V = [Vr + Z cIr ]eδx + [Vr − Z cIr ]e − δx
2 2
e δx + e − δx eδx − e − δx
V = Vr + Z cIr
2 2
or
1 Vr 1V
I= + Ir eδx − r − Ir e − δx (9.23)
2 Zc 2 Z
c
eδx + e − δx Vr eδx − e − δx
I = Ir + Z
2 c 2
or
Vr
I = Ir cosh δx + sinh δx (9.24)
Zc
178 ◾ Elements of Power Systems
Vr
Is = Ir cosh δl + sinh δl (9.26)
Zc
Vr
Is = Ir cosh YZ + sinh YZ (9.28)
Zc
Comparing above equations with the general voltage and current equa-
tions of the line, we define the ABCD parameters:
A = D = cosh YZ
B = Z c sinh YZ
1
C= sinh YZ
Zc
Equations 9.25 and 9.26 can be written in matrix form as
cosh δl Z c sinh δl
Vs Vr
=
I 1
s Z sinh δl cosh δl Ir
c
Performance of Transmission Lines ◾ 179
and
δ 2l 2 δ 4 l 4
cosh δl = 1 + + + (9.33)
2! 4!
δ 3l 3 δ 5 l 5 (9.34)
sinh δl = δl + + +
3! 5!
180 ◾ Elements of Power Systems
The above series converge rapidly for the values of δl usually found
for power lines. Sufficient accuracy can be obtained by taking only
the first two terms. Thus,
δ 2l 2 YZ (9.35)
cosh δl = 1 + = 1+
2! 2
δ 3l 3 1
sinh δl = δl + = YZ 1 + YZ (9.36)
3! 2
YZ (9.37)
A = D = coshδl = 1 +
2
Z 1 1
B = Z c sinhδl = × YZ 1 + YZ = Z 1 + YZ (9.38)
Y 2 2
1 Y 1 1
C= sinhδl = × YZ 1 + YZ = Y 1 + YZ (9.39)
Zc Z 2 2
(a) (b)
Is R XL Ir
IC XL
IC
Vs
Vs C Vr IC IC R
Neutral
Vr
FIGURE 9.9 (a) Line representation (lumped) under no-load condition. (b) Its
phasor diagram.
(Figure 9.9b) is given below for this operating condition. The charging
current produces drop in the reactance of the line which is in phase oppo-
sition to the receiving-end voltage and hence the sending-end voltage
becomes smaller than the receiving-end voltage.
Vs = AVr + BI r (9.40)
I s = CVr + DI r (9.41)
I r = −CVs + DI s (9.44)
182 ◾ Elements of Power Systems
Again,
Vs = E = 0 + BI 2
E (9.48)
I2 =
B
Now we short circuit the sending end and connect the generator at the
receiving end as shown in Figure 9.10b. The positive directions of flow of
current are shown in the figures.
(a) (b)
IS Ir IS Ir
+ A, B, C, D A, B, C, D +
VS E
FIGURE 9.10 (a) Two terminal pair network. (b) Source at the receiving end.
Performance of Transmission Lines ◾ 183
∴ 0 = AE + BI r (9.49)
I s = − I 2 = CE + DI r (9.50)
− AE (9.51)
− I r = CE − D
B
E − AE
− = CE + D
B B
or
1 A
− =C−D
B B
or
−1 = BC − AD
or
AD − BC = 1 (9.52)
IS Ir Ir
A1 B1 A2 B2
VS V Vr
C1 D1 C2 D2
The net constants of the system relating the terminal conditions can be
found as follows:
V = A 2 ⋅ Vr + B2 I r (9.55)
I = C 2Vr + D2 I r (9.56)
From Equations 9.53 and 9.55 and Equations 9.54 and 9.56, respectively,
Since A1D1 − B1C1 = 1, the constants for the two networks in tandem are
A = A1A 2 + B1C 2
Performance of Transmission Lines ◾ 185
B = A1B2 + B1D2
D = B2C1 + D1D2
Vs = A 2Vr + B2 I r2 (9.63)
Is1 A1 B1
C1 D1
Is Ir
Vs Vr
Is2 A2 B2
C2 D2
Vs = AVr + BI r (9.64)
where I r = I r1 + I r2 .
Therefore, multiplying Equations 9.62 and 9.63 by B2 and B1, respec-
tively, and adding, we get
or
A1B2 + A 2B1 BB
Vs = Vr + 1 2 I r (9.65)
B1 + B2 B1 + B2
A1B2 + A 2B1
A=
B1 + B2
and
B1B2
B= (9.66)
B1 + B2
AD − BC = 1 (9.68)
(A1 − A2 )(D2 − D1 )
C = C1 + C 2 + (9.69)
B1 + B2
Performance of Transmission Lines ◾ 187
Using equations
Vs = AVr + BI r (9.70)
I s = CVr + DI r (9.71)
Vs A
Zso = = for I r = 0 (open-circuit test) (9.72)
Is C
(a)
Is
A
A B
Vs V V′r, I
C D
(b)
Is
A
A B
Vs V Vr = 0
C D
Vs B
Zss = = for Vr = 0 (short-circuit test) (9.73)
Is D
Vr = DVs − BI s (9.74)
I r = −CVs + AI s (9.75)
Vr = DVs + BI s (9.76)
− I r = − CVs − AI s
or
I r = CVs + AI s (9.77)
Vr D
Z ro = = (9.78)
Ir C
Vr B
Z rs = = (9.79)
Ir A
Performance of Transmission Lines ◾ 189
D B AD − BC 1
Z ro − Z rs = − = =
C A AC AC
Z ro − Z rs 1 C 1
= = 2
Z so AC A A
Z so
A= (9.80)
Z ro − Z rs
B
Z rs =
A
Z so
B = AZ rs = Z rs (9.81)
Z ro − Z rs
A
Z so =
C
A 1 Z so
C= = (9.82)
Z so Z so Z ro − Z rs
D
Z ro =
C
Z ro Z so
D = CZ ro =
Z so Z ro − Z rs
1
= Z ro
Z so (Z ro − Z rs )
Z so
D=A= (9.83)
Z ro − Z rs
190 ◾ Elements of Power Systems
WORKED EXAMPLES
EXAMPLE 9.1
ABCD constants of a 220-kV line are A = D = 0.94∠1°, B = 130∠73°,
and C = 0.001∠90°. If the sending-end voltage of a line for a given
load delivered at nominal voltage is 240 kV, determine the voltage
regulation of the line.
Solution
|VR 0 | − |VR |
Voltage regulation = × 100%
|VR |
VS = AVR + BIR
IR = 0, VR = VR 0
EXAMPLE 9.2
A 220-kV transmission line represented as T model. Parameters are
A = D = 0.8∠1°, B = 170∠85°, and C = 0.2 × 10−3∠90.4°. Sending-end
voltage = 400 kV. Determine:
Solution
Receiving-end voltage under no-load condition is
Vs
VR 0 = (∴ IR = 0)
A
220
=
0. 9
= 244.4 kV
EXAMPLE 9.3
Generalized circuit constants of a three-phase, 220-kV rated voltage
medium length are A = D = 0.936 ∠98°, B = 142 ∠76.4°. If the load at
receiving end is 50 MW at 220 kV with a pf 0.9 (lagging), determine
the magnitude of line to line sending-end voltage.
Solution
PR = 3 × VR × I R × cos φ
220 × 103
Sending-end line-to-neutral = (0.936∠98°)
3
+ 142∠776.4° × 145.8∠ − 25.8°
= 133∠7.77° V
EXAMPLE 9.4
Three-phase, 50 Hz transmission line of length 100 km has a capac-
itance (0.03/π)μF/km. It is represented as π model. Determine the
shunt admittance at each end of transmission line.
Solution
Capacitance of each end of a π model = C/2
Y 1 1
∴ Admittance = = j
2 2 XC
1 1
= j
2 XC
1 1
= jωC = j2πfC
2 2
1 0.03
= j(2π × 50) × 100
2 π
= j150 × 10−6 Siemens
= 150 × 10−6 ∠90° Siemen
ns
EXAMPLE 9.5
Estimate the distance over which a load of 10,000 kW at a pf 0.8
lagging can be delivered by a three-phase transmission line having
Performance of Transmission Lines ◾ 193
Solution
Power delivered
Line current, I =
3 × Line voltage × Power factor
1000 × 103
= = 109.346 A
3 × 66 × 103 × 0.8
500 × 103
R= = 13.94 Ω
3 × (109.346)2
13.94
∴ Length of line = km = 9.2928 km
1. 5
EXERCISES
Underground Cables
10.1 INTRODUCTION
Cables are used for transmission and distribution of electrical energy in
highly populated areas of towns and cities. Cables form the artery sys-
tem for the transmission and distribution of electrical energy. A cable is
basically an insulated conductor. External protection against mechanical
injury, moisture entry, and chemical reaction is provided on the cable. The
conductor is usually aluminum or annealed copper, while the insulation is
mostly polyvinyl chloride (PVC) or other chemical compounds.
Transmission line is more expensive than overhead lines, especially at
high potentials. Besides increase in temperature is high in cables. However,
there is limitation of raising the operating voltage. In low and medium
voltage distribution in urban areas, cables are more widespread.
An underground cable essentially consists of one or more conductors
covered with suitable insulation and surrounded by a protecting cover.
In general, a cable must fulfill the following necessary requirements:
195
196 ◾ Elements of Power Systems
Conductor
Paper
insulation
Lead sheath
Bedding
Armoring
Serving
Cores or conductor: A cable may have one or more than one core (con-
1.
ductor) depending upon the type of service for which it is intended.
For instance, the three-conductor cable shown in Figure 10.1 is used
for three-phase service. The conductors are made of tinned copper or
aluminum and are usually stranded in order to provide flexibility to
the cable.
A cable may have one or more than one core depending upon the type
of service for which it is intended. It may be (a) single core, (b) two cores,
(c) three cores, and (d) four cores.
For a three-phase service, either three single core cables or three cores
can be used depending upon the operating voltage and load demand. For
three-phase, four-wire system, four-core cables may be used.
The constructional details of a single-core, low-tension cable is shown
in Figure 10.2. The cable has ordinary construction because the stress
developed in the cable for low voltage (up to 6600 V) is generally small.
It consists of one circular core of tinned stranded copper (or aluminum)
insulated by layers of impregnated paper. The insulation is surrounded by
a lead sheath that prevents the entry of moisture into the inner parts. In
order to project the lead sheath from corrosion, an overall serving of com-
pounded fibrous material (jute, etc.) is provided. Single core cables are not
usually armored in order to avoid excessive sheath losses. The principal
advantages of single core cables are simple construction and availability
of larger copper section.
Serving
Lead
sheath
Stranded Impregnated
copper paper
conductor
Lead sheath
Thickness of
insulation
between
conductor and
sheath
Paper belt
Thickness of insulation
between conductors
is covered with one or more layers of armoring with an outer serving (not
shown in the figure).
The belted type construction is suitable only for low and medium volt-
age, as the electrostatic stresses developed in the cables for these voltages
are more or less radial, that is, across the insulation. However, for high
voltages (beyond 22 kV), the tangential stresses also become important.
These stresses act along the layers of paper insulation. As the insulation
resistance of paper is quite small along the layers, therefore, tangential
stresses setup leakage current along the layers of paper insulation. The
leakage current causes local heating, resulting in the risk of breakdown of
insulation at any moment. In order to overcome this difficulty, screened
cables are used where leakage currents are conducted to earth through
metallic screens.
Lead sheath
Bedding
Conducting
Armoring belt
Paper
insulation
Metallic
screen
Serving
Lead covering
Conductor
Cotton tape
Armoring
Serving
sheath. The voltage limit for solid type cables is 66 kV due to the following
reasons:
elimination of voids, oil-filled cables can be used for higher voltages, the
range being from 66 kV to 230 kV. Oil-filled cables are of three types viz.,
single-core conductor channel, single-core sheath channel, and three-core
filler-space channels.
Figure 10.6 shows the constructional details of a single-core conduc-
tor channel, oil-filled cable. The oil channel is formed at the center by
stranding the conductor wire around a hollow cylindrical steel spiral
tape. The oil under pressure is supplied to the channel by means of exter-
nal reservoir. As the channel is made of spiral steel tape, it allows the
oil to percolate between copper strands to the wrapped insulation. The
oil pressure compresses the layers of paper insulation and prevents the
possibility of void formation. The system is so designed that when the oil
gets expanded due to increase in cable temperature, the extra oil collects
in the reservoir. However, when the cable temperature falls during light
load conditions, the oil from the reservoir flows to the channel. The dis-
advantage of this type of cable is that the channel is at the middle of the
cable and is at full voltage wrt earth, so that a very complicated system of
joints is necessary.
Figure 10.7 shows the constructional details of a single-core sheath
channel oil-filled cable. In this type of cable, the conductor is solid similar
to that of solid cable and is paper insulated. However, oil ducts are provided
in the metallic sheath as shown. In the three-core, oil-filled cable shown in
Figure 10.8, the oil ducts are located in the filler spaces. These channels are
composed of perforated metal-ribbon tubing and are at earth potential.
The oil-filled cables have three principal advantages. Firstly, formation of
voids and ionization are avoided. Secondly, allowable temperature range
and dielectric strength are increased. Thirdly, if there is leakage, the defect
Conductors
Serving
Oil duct
Bedding
Lead
sheath
Paper
insulation
Oil channels
Paper
insulation
Conductor
Grooved
sheath
in the lead sheath is at once indicated and the possibility of earth faults
is decreased. However, their major disadvantages are the high initial cost
and complicated system of laying.
Oil ducts
Lead sheath
Conductor
Paper
insulation
for triangular shape is that the lead sheath acts as a pressure membrane.
The sheath is protected by a thin metal tape. The cable is laid in a gas-tight
steel pipe. The pipe is filled with dry nitrogen gas at 12–15 atmospheres.
The gas pressure produces radial compression and closes the voids that
may have formed between the layers of paper insulation. Such cables can
carry more load current and operate at higher voltages than a normal
cable. Moreover, maintenance cost is small and the nitrogen gas helps in
quenching any flame. However, it has the disadvantage that the overall
cost is very high.
Trench
Concrete
cover
Cable
Sand bed
The trench is then covered with bricks and other materials in order to
protect the cable from mechanical injury. When more than one cable is to be
laid in the same trench, a horizontal or vertical inter-axial spacing of at least
30 cm is provided in order to reduce the effect of mutual heating and also to
ensure that a fault occurring on one cable does not damage the adjacent cable.
Cables to be laid in this way must have serving of bituminized paper and hes-
sian tape so as to provide protection against corrosion and electrolysis.
Advantages:
Disadvantages:
This method of laying cables is used in open areas where excavation can
be done conveniently and at low cost.
Disadvantages:
Ducts
Concrete
covering
This method of cable laying is suitable for congested areas where exca-
vation is expensive and inconvenient, for once the conduits have been
laid, repairs or alterations can be made without open undergrounding the
ground. This method is generally used for short length cable routes such as in
workshops, road crossings where frequent digging is costlier or impossible.
dx
r1
x
r2
dx
ρ
2πxl
ρ r
R= log e 2
2πl r1
between core and lead sheath. Obviously ε = ε0 εr, where εr is the relative
permittivity of the insulation.
Consider a cylinder of radius x meters and axial length l meter. The
surface area of this cylinder is = 2πx × 1 = 2πx m2.
Therefore, electric flux density at point P on the considered cylinder is
Dx = (Q/2πx)c/m2.
Electric intensity at point P, Ex = (Dx/ε) = Q/(2πxε0εr) V/m.
Potential difference between the capacitor plates (between core and
sheath):
D /2 D /2
Q Q D
∫
V = E x dx =
∫ 2πxε ε dx = 2πε ε log
0 r 0 r
e
d
d /2 d /2
Q Q
C= = F/m
V (Q /2πε 0 ε r )log e (D /d )
or
2πε 0 ε r 2πε r × 8.854 × 10−12
c= F/m = F/m
log e (D /d ) 2.303 log10 (D /d )
εr
= × 10−9 F/m
41.4 log10 (D /d )
If the cable has a length of l meters, then capacitance of the cable is
εr l
= × 10−9 F/m
41.4 log10 (D /d )
Sheath
d/2 dx
D x
2
P
Q
Ex = V/m
2πε 0 ε r x
g = Ex
or
Q
g = V/m (10.1)
2πε 0 ε r x
Q D
V = log e V
2πε 0 ε r d
or
2πε 0 ε rV
Q= (10.2)
log e (D /d )
(2πε 0 ε rV /log e (D /d )) V
g = = V/m (10.3)
2πε 0 ε r x x log e (D /d )
2V
g max = V/m
d log e (D /d )
2V
g min = V/m
D log e (D /d )
g 2V /(d log e (D /d )) D
∴ g max = =
min 2V /(D log e (D /d )) d
2V
g max = V/m
d log e (D /d )
(10.4)
εr
d
D 2
2
gmax
gmin
d D
d log e = 0
dd d
or
D d −D
log e +d⋅ ⋅ 2 = 0
d D d
or
D
log e −1 = 0
d
or
D D
log e =1 = e = 2.718
d d
216 ◾ Elements of Power Systems
2V
g max = V/m
d
in such a way that its value is increased in the outer layers of dielectric.
This is known as grading of cables. The following are the two main meth-
ods of grading of cables:
1. Capacitance grading
2. Intersheath grading
ε3 ε2 ε1
d
2
d1
2 d2
D 2
gmax 2
There are three dielectrics of outer diameter d1, d2, and D and rela-
tive permittivity ε1, ε2, and ε3, respectively. If the permitivities such that
ε1 > ε2 > ε3 and three dielectric are worked at the same maximum stress,
then
1 k
εr ∝ , ∴ εr ∝
x x
where k is a constant.
Q Q Q
= = = constant
2πε 0 ε r x 2πε 0 (k / x )x 2πε 0 k
Q Q Q
g 1max = , g 2 max = , g 3max =
2πε 0 ε1d πε 0 ε 2d1 πε 0 ε 3d2
1 1 1
= =
ε1d ε 2d1 ε 3d2
d1 /2 d1 /2
Q Q d g d
V1 =
∫ g dx =
∫ 2πε 0 ε1x
dx =
2πε 0 ε1
log e 1 = max d log e 1
d 2 d
d /2 d /2
Similarly, potential across second layer (V2) and third layer (V3) is
given by
g max d g D
V2 = d1 log e 2 , V3 = max d2 log e
2 d1 2 d2
Underground Cables ◾ 219
g max d1 d2 D
V = V1 + V2 + V3 = d log e d + d1 log e d + d2 log e d
2 2
1
If the cable had homogeneous dielectric, then for the same values of
d, D, and gmax, the permissible potential difference between core earthed
sheath would have been
g max D
V′ = d log e
2 d
1. As the permissible values of gmax are peak values, therefore all the
voltages in above expressions should be taken as peak values and not
the rms values.
2. If the maximum stress in the three dielectrics is not the same, then,
g 1max d g d g D
V = d log e 1 + 2 max d1 log e 2 + max d2 log e
2 d 2 d1 2 d2
The principal disadvantage of this method is that there are a few high-
grade dielectrics of reasonable cost whose permitivities vary over the
required range.
V1
g 1max =
(d /2)log e (d1 /d )
Similarly,
V2
g 2 max =
(d1 /2)log e (d2 /d1 )
V3
g 3 max =
(d2 /2)log e (D /d2 )
Lead
sheath
Inter-
sheath 1
Inter-
sheath 2
d
2
d1
2 d2
2
D
2
gmax
V1 V2 V3
∴ = =
(d /2)log e (d1 /d ) (d1 /2)log e (d2 /d1 ) (d2 /2)log e (D /d2 )
As the cable behaves like three capacitors in series, all the potential are
in phase, that is, voltage between conductor and earthed lead sheath is
V = V1 + V2 + V3
Disadvantages
A
Ce
A
Cc Cc Cs
Cc Cc
S
B C
Cc Ce Cs Cs
Ce
B C
Cc
1.5Cc = 0.5C1
or
C1 = 3Cc
C0 = C1 + Cs = 3Cc + Cs
A
A
CC CC C1
C1
C1
B C
CC B C
CS
C1
N
C1 C1
B C
CS CS
S S
VL
I c = Vp ωC0 = ω(3Cc + Cs )A
3
C1 CS
N
C1 C1
CS CS
B C
C0
N
C0
C0
B C
FIGURE 10.21 Final equivalent circuit with three capacitances in star connection.
C c + Cs 1 1
CL = Cc + = (3Cc + Cs ) = C0
2 2 2
(a) A (b)
A
CC CS
CC
CC CS
S
CS CS CC
C
B C
CC
CC CS
FIGURE 10.22 (a) Conductor C is connected to the sheath. (b) Equivalent circuit
of (a).
CS Sheath
CS
A
CS
A, B, C S
CS
B CS
C
CS
CC
A
CC
B C
CS CS
CS
The safe working temperature is 65°C for armored cables and 50°C for
lead-sheathed cables laid in ducts. The maximum steady temperature con-
ditions prevail when the heat generated in the cable is equal to the heat
dissipated. The heat dissipation of the conductor losses is by conduction
through the insulation to the sheath from which the total loss (including
CC CC
CS
B C
Temperature rise (t )
S=
Watts dissipated (P )
or
t
S=
P
L
∴S ∝
a
or
L
S=k
a
dx
dS = k ×
2πx
r1
dx
S= k×
∫
r
2πx
r1
k dx
=
2π x ∫
r
r r1
X
dx
These simple tests can be used to locate the earth fault or short-circuit fault
in underground cables provided that a sound cable runs along the faulty cable.
Both these tests employ the principle of Wheatstone bridge for fault location.
P R
=
Q X
G
Low
K2 resistance
Q C Faulty cable D connection
K1 X F
+
B
– Earth fault
E
Earth path
FIGURE 10.27 Circuit diagram for locating the earth fault by Murray loop test.
Underground Cables ◾ 231
or
P R
+1 = +1
Q X
or
P +Q R+ X
=
Q X
P + Q 2r
∴ =
Q X
or
Q
X= × 2r
P +Q
If l is the length of each cable in meters, then resistance per meter length
of cable = r/1.
Therefore, distance of fault point from test end is
X Q 1 Q
d= = × 2r × = × 2l
(r /l ) P + Q r P +Q
or
Q
d= × (Loop length) meters
P +Q
Thus the position of the fault is located. Note that resistance of the
fault is in the battery circuit and not in the bridge circuit. Therefore, fault
resistance does not affect the balancing of the bridge. However, if the fault
resistance is high, the sensitivity of the bridge is reduced.
232 ◾ Elements of Power Systems
P R
=
Q X
or
P + Q R + X 2r
= =
Q X X
Q
∴X = × 2r
P +Q
or
K1
FIGURE 10.28 Circuit diagram for locating the short-circuit fault by Murray
loop test.
Underground Cables ◾ 233
Q
d= × (Loop length) meters
P +Q
or
P + Q R + X + S1
=
Q X + S1
K2 2
FIGURE 10.29 Circuit diagram for locating the earth fault by Varley loop test.
234 ◾ Elements of Power Systems
Far end
Test end R
P Sound cable
G
Low
K1 resistance
Q S connection
+
B X
–
Short circuit
2
fault
K2
1
Faulty cables
FIGURE 10.30 Circuit diagram for locating the short-circuit fault by Varley loop
test.
or
Q(R + X ) − PS1
X= (10.5)
P +Q
P R+X
=
Q S2
or
(R + X )Q = PS2 (10.6)
P (S2 − S1 )
X=
P +Q
Underground Cables ◾ 235
Since the values of P, Q, S1, and S2 are known, the value of X can be
determined.
P
Loop resistance = R + X = S
Q 2
If r is the resistance of the cable per meter length, then distance of fault
from the test end is
X
d= m
r
WORKED EXAMPLES
EXAMPLE 10.1
The insulation resistance of a single-core cable is 500 MΩ/km. If the
core diameter is 3 cm and resistivity of insulation is 3.5 × 1014 Ω cm,
find the insulation thickness.
Solution
Length of cable, l = 1 km = 1000 m
Cable insulation resistance, R = 500 MΩ = 500 × 106 Ω
Conductor radius, r1 = (3/2) = 1.5 cm
Resistivity of insulation, ρ = 3.5 × 1014 Ω cm = 3.5 × 1012 Ω m
Let r2 centimeter be the internal sheath radius.
ρ r
Now, R = log e 2
2πl r1
or
r2
2.3 log10 = 0.897
r1
or
r2 0.897
= Antilog = 2.45
r1 2. 3
236 ◾ Elements of Power Systems
or
EXAMPLE 10.2
A single core cable for use on 11 kV, 50 Hz system has conductor area
of 0.5 cm2 and internal diameter of sheath is 3 cm. The p ermittivity
of the dielectric used in the cable is 3. Find (1) the maximum
electrostatic stress in the cable, (2) minimum electrostatic stress in
the cable, (3) capacitance of the cable per kilometer length, and (4)
charging current.
Solution
Area of cross-section of conductor, a = 0.5 cm2
Diameter of the conductor,
4a 4 × 0. 5
d= = = 0.798 cm
π π
2V 2 × 11
g max = = = 20.82 kV/cmrms
d log e (D /d ) 0.798 log e (3/0.798)
2V 2 × 11
g min = = = 5.53 kV/cmrms
D log e (D /d ) 3 log e (3/0.798)
εr l
3. Capacitance of cable, C = 41.4 log (D /d ) × 10 F
−9
10
Here εr = 3, l = 1 km = 1000 m
3 × 1000
C= × 10−9 = 0.125 × 10−6 F = 0.125 µF
41.4 log10 (3/0.798)
Underground Cables ◾ 237
EXAMPLE 10.3
Find the most economical size of a single-core cable working on a
66 kV, three-phase system, if a dielectric stress of 40 kV/cm can be
allowed.
Solution
Phase voltage of cable = (66/ 3 ) = 38.10 kV
Peak value of phase voltage, V = 38.10 × 2 = 53.88 kV
Maximum permissible stress, gmax = 40 kV/cm
Therefore, most economical conductor diameter is
2V 2 × 53.88
d= = = 2.64 cm
g max 40
EXAMPLE 10.4
A single core cable employing three layers of insulation with dielec-
tric constant Er1 = 8, Er2 = 6, and Er3 = 4, respectively, has conductor
of radius 3 cm. Assuming that all the three insulating materials are
worked at a same maximum potential gradient, work out the potential
difference in kV between core and earthed sheath. The inner radius of
the sheath is 3 cm and the maximum potential gradient is 50 kV/cm.
Solution
Diameter of conductor = 2 × 1.5 = 3 cm
The diameter over the insulation, D = 2 × 3.0 = 6 cm
Maximum potential gradient, gmax = 50 kV/cm
Let the diameters over the insulation of relative permittivities 8
and 6 be d1 and d2, respectively.
As the maximum stress in three dielectric is same
or
Er1 8
d1 = d = × 3 = 4 cm
Er2 6
and
Er1 8
d2 = d = × 3 = 6 cm
Er3 4
g max
d log (ed1 / d ) + d1 log e 2 1 + d2 log e 2
(d /d ) ( D /d )
2
50
3 log (e4 /3) + 4 log (e6/ 4 ) + 6 log (e6/6) = 62.12 kV
2
EXAMPLE 10.5
A 33 kV, single core metal sheathed cable is to be guarded by means
of a metallic inter sheath. Calculate the diameter of inter sheath
and the voltage at which it must be maintained in order to obtain
minimum overall cable diameter. The maximum voltage gradient at
which the insulating material can be worked is 40 kV/cm.
Solution
RMS value of cable voltage, Vmax = 33 kV
Peak value of cable voltage = 33 × 2 = 46.67 kV
Maximum permissible potential gradient of dielectric,
gmax = 40 kV/cm
Let d be the conductor diameter, d1, the outer diameter of the
insulating layer, and D, the outer diameter of outer insulating layer.
If V1 = potential difference between core and sheath and
V2 = potential difference between inter sheath and the outer sheath,
then
Underground Cables ◾ 239
V1 V2
g max = =
(d /2)log 5 (d1 /d ) (d1 /2)log 5 (D /d1 )
2Vmax 2 × 46.67
d= = = 0.858 cm
e × g max 2.71828 × 40
V 46.67
V1 = = = 17.17 kV
e 2.71828
EXERCISES
b. H-type cable
c. SL-type cable
7. What are the limitations of solid-type cables? How are these over-
come in pressure cables?
8. Write a brief note on oil-filled cables.
9. Describe the various methods of laying underground cables. What
are the relative advantages and disadvantages of each method?
10. Derive an expression for the insulation resistance of a single-core
cable.
11. Deduce an expression for the capacitance of a single-core cable.
12. Show that maximum stress in a single-core cable is
2V
d log e (D /d )
where V is the operating voltage, and d and D are the conductor and
sheath diameter.
13. Prove that gmax/gmin in a single-core cable is equal to D/d.
14. Find an expression for the most economical conductor size of a
single core cable.
15. Explain the following methods of cable grading:
a. Capacitance grading
b. Intersheath grading
16. Write short notes on the following:
a. Laying of 11 kV underground power cable
b. Capacitance grading in cables
c. Capacitance of three-core belted cables
17. Derive an expression for the thermal resistance of dielectric of a
single-core cable.
Underground Cables ◾ 241
Distribution Systems
11.1 INTRODUCTION
The electrical energy produced at the generating station is conveyed to
the consumers through a network of transmission and distribution sys-
tems. It is often difficult to draw a line between the transmission and
distribution systems of a large power system. The transmission and dis-
tribution systems are similar to a human circulatory system. The trans-
mitting system may be compared to arteries in the human body and
distribution system with capillaries. They serve the same purpose of
supplying the ultimate consumer in the city with the life giving blood of
civilization—electricity.
That part of power system which distributes electric power for local use
is known as distribution system.
In the general distribution system is the electric system between the
substation fed by the transmitting system and the consumers’ meters. It
mostly consists of feeders, distributors, and the service main. Figure 11.1
shows the single-line diagram of a typical low-tension distribution sys-
tem. Good voltage regulation of a distribution network is probably the
most significant factor responsible for delivering expert service to the
consumers. For this purpose, design of feeders and distributors requires
careful consideration.
243
244 ◾ Elements of Power Systems
s
ain B
m
ice
rv
Se
Feeder Feeder
C S A
Feeder
Se
rv
ic
em
ai
ns D
11.3 DC DISTRIBUTION
It is a common knowledge that electric power is almost exclusively generated,
transmitted, and distributed as AC. However, for certain applications, DC
supply is absolutely necessary. For instance, DC supply is required for the
operation of variable speed machinery (i.e., DC motors), for electrochemical
work and for congested areas where storage battery reserves are necessary.
For this purpose, AC power is converted into DC power at the substation by
using converting machinery, for example, mercury arc rectifiers, rotary con-
verters, and motor-generator sets. The DC supply from the substation may
be obtained in the form of (a) two wires or (b) three wires for distribution.
246 ◾ Elements of Power Systems
V L L M
+
V L
Neutral 2V
M
wire
V
–
11 kV/400 V, 230 V
Sub- Sub-
station O A C station O A C
Feeder Feeder
Feeder Feeder
FIGURE 11.4 (a) Radial DC distribution system. (b) Radial AC distribution system.
1. The end of the distributor nearest to the feeding point will be heavily
loaded.
2. The consumers are dependent on a single feeder and single distrib-
utor. Therefore, any fault on the feeder or distributor cuts off sup-
ply to the consumers who are on the side of the fault away from the
substation.
3. The consumers at the distant end of the distributor would be sub-
jected to serious voltage fluctuations when the load on the distribu-
tor changes.
Distributor Loads
L F N
M
Distributor
Sub- S Primary
O
station ring
Loads
Q
R P
Distribution
Transformer
Distributor Loads
Advantages:
Distributor
Loads
S1 S2
D C
P
Distributor Q Distributor
O
Loads Loads
R
A B
Distribution
Transformer
Distributor Loads
I1 I2 I3
1. The current in the various sections of the distributor away from feed-
ing point goes on decreasing. Thus current in section AC is more
than the current in section CD and current in section CD is more
than the current in section DE.
2. The voltage across the loads away from the feeding point goes on
decreasing. Thus in Figure 11.7, the minimum voltage occurs at the
load point E.
3. In case a fault occurs on any section of the distributor, the whole
distributor will have to be disconnected from the supply mains.
I1 I2 I3
A I1 I1 +I2 C I3 +I4 I4 B
I1 I2 I3 I4
I1
Distributor ring
B
Feeder
A C I2
D
I3
1. Concentrated loading
2. Uniform loading
3. Both concentrated and uniform loadings
252 ◾ Elements of Power Systems
A C D E F B
r1 r2 r3 r4
I1 I2 I3 I4
It is easy to see that the minimum potential will occur at point F, which
is farthest from the feeding point A.
Now, consider a section of very small length dx near point C. Its resis-
tance is r dx and the voltage drop over length dx is,
dv = i(l − x )r dx = ir (l − x ) dx
A B
i i i i
l
C
A B
x dx
FIGURE 11.13 Point C on the distributor at a distance x meters from the feeding
point A.
254 ◾ Elements of Power Systems
The voltage drop up to point B (i.e., over the whole distributor) can be
obtained by putting x = l in the above expression.
where il = I, the total current entering at point A, and rl = R, the total resis-
tance of the distributor.
Thus, in a uniformly loaded distributor fed at one end, the total volt-
age drop is equal to that produced by the whole of the load assumed to be
concentrated at the middle point.
x y
V V
I1 I2 I3 I4 I5
FIGURE 11.14 Distributor fed at both ends at equal voltage with concentrated
loading.
Distribution Systems ◾ 255
volts as we reach the other feeding point B. All the current tapped off between
points A and E (minimum pd point) will be supplied from the feeding point
A, while those tapped off between B and E will be supplied from the feeding
point B. The current tapped off at point E itself will be partly supplied from A
and partly from B. If these current are x and y, respectively, then
I3 = x + y
I AC = I A , I CD = I A − I1
I DE = I A − I1 − I 2 , I EB = I A − I1 − I 2 − I 3
Voltage drop between A and B = Voltage drop over AB
or
V − V = I A RAC + (I A − I1 )RCD + (I A − I1 − I 2 )RDE
+(I A − I1 − I 2 − I 3 )REB
From this equation, the unknown IA calculated as the values of other
quantities are generally given. Suppose actual directions of current in the
various sections of the distributor are indicated in Figure 11.15b. The load
point where the current are coming from both sides of the distributor is the
point of minimum potential, that is, point E in this case.
(a) A C D E B (b) A C D E B
IA
V V V V
I1 I2 I3 I1 I2 I3
FIGURE 11.15 (a) Current distribution in the various sections of the distributor.
(b) Actual directions of current in the various sections of the distributor.
256 ◾ Elements of Power Systems
A C D E F B
V1 V2
I1 I2 I3 I4
FIGURE 11.16 Distributor fed at both ends at unequal voltage with concentrated
loading.
l
xx dx
A B
C
V V
i i i i i
FIGURE 11.17 Distributor fed at both ends at equal voltage with uniform dis-
tributed loading.
Distribution Systems ◾ 257
l l
dv = i − x rdx = ir − x
2 2
x
l lx x 2 ir
∫ ir − x dx = ir − = (lx − x 2 )
2 2 2 2
0
ir
Max. voltage drop = (lx − x 2 )
2
ir l l2
= l × − [Putting x = l/2]
2 2 4
1 1 1
= irl 2 = (il )(rl ) = IR
8 8 8
where il = I, the total current fed to the distributor from both ends, and
rl = R, the total resistance of the distributor.
IR
Minimum voltage = V − volts
8
x l–x
C B
A
VA VB
i i i i i
FIGURE 11.18 Distributor fed at both ends at unequal voltage with uniform dis-
tributed loading.
irx 2
Voltage drop in section AC = volts
2
ir (l − x )2
Voltage drop in section BC = volts
2
VC = VB − Drop over BC
ir (l − x )2 (11.2)
= VB −
2
irx 2 ir (l − x )2
VA − = VB −
2 2
VA − VB l
x= +
irl 2
Distribution Systems ◾ 259
As all the quantities on the right hand side of the equation are known,
the point on the distributor where minimum potential occurs can be
calculated.
I1
A B
I2
E C
I4
D
I3
(a) I1 (b)
B R0
A
+
E E0 RBD
C I2 –
I4
D
I3
E0
Current in interconnector BD =
R0 + RBD
11.13 AC DISTRIBUTION
One important reason for the widespread use of alternating current in
preference to direct current is the fact that alternating voltage can be con-
veniently changed in magnitude by means of a transformer.
It can be classified as follows.
Primary distribution
Substation
3-Phase
3-Wire 11 kV
33 kV
Substation
33/11 kV
11 kV Phase R
Three-phase Phase Y 400V
400V
Three-wire Phase B 400V 230V
230V
Neutral 230V
Three-phase delta/star
distribution transformer
11/0.4 kV
Factory three-phase
load
A R1 + j X1 C R2 + j X2 B
VA
X1
VC I AC
φS
I AC
θ
R1
I2 X 2
φ2 VB I2
φ1 R
I2 2
I1
IAC
FIGURE 11.24 Phasor diagram of Figure 11.23 for pf with respect to receiving end.
Distribution Systems ◾ 265
VA
VC X1
I AC
I AC
α
R1
φ2 VB I2 X2
I2
φ1 R
I2 2
I1
IAC
FIGURE 11.25 Phasor diagram of Figure 11.23 but with pf with respect to load
points.
Now , IAC = I1 + I2
= I1[cos(φ1 − ∝) − j sin (φ1 − ∝)] + I 2 (cos φ2 − j sin φ2 )
WORKED EXAMPLES
EXAMPLE 11.1
The load distribution on a two-wire DC distributor is shown in Figure
11.26. The cross-sectional area of each conductor is 0.36 cm2. The end A
is supplied at 230 V. Resistivity of the wire is ρ = 1.97 μΩ cm. Calculate
(1) the current in each section of the conductor, (2) the two-core resis-
tance of each section, and (3) the voltage at each tapping point.
266 ◾ Elements of Power Systems
A 100 m B 125 m C 75 m D
230 V
10 A 12 A 15 A
Solution
1. Current in the various sections are
l 100 × 100
ρ = 1.97 × 10−6 × = 0.054 Ω
a 0.36
EXAMPLE 11.2
Calculate the voltage at a distance of 250 m of a 350 m long distribu-
tor uniformly loaded at the rate of 1 A/m. The distributor is fed at
Distribution Systems ◾ 267
one end at 230 V. The resistance of the distributor (go and return)
per meter is 0.00018 Ω. Also find the power loss in the distributor.
Solution
Voltage drop at a distance x from supply end is
x2
ir lx −
2
2502
Voltage drop = 1 × 0.00018 × 350 × 250 − = 10.125 V
2
EXAMPLE 11.3
A ring distributor is supplied through a feeder AB and is loaded as
shown below: calculate the cross-section volume of copper. Assume
that the maximum voltage drop from A to the point of minimum
potential is 15 V. Take ρ = 1.73 µΩ/cm3 (Figure 11.27).
20 A
60 A
100 m
C D
100 m
A 500 m 150 m
B
180 A
250 m E
100 A
Solution
Let the resistance per 100 m of ring distributor length (both conduc-
tors) be r ohms.
Resistance of both conductors of various section is determined as
below:
r
RBC = × 100 = r Ω
100
Similarly,
r
RCD = × 100 = r Ω
100
r
RDE = × 150 = 1.5r Ω
100
and
r
REB = × 250 = 2.5r Ω
100
or
or
6 I x r = 590 or I x = 98.333 A
Distribution Systems ◾ 269
and
180 × 0.173
vF = (11.3)
αF
and
81.667 × 0.0865
vD = (11.4)
αD
3,114,000 847,700
vOC = +
15 − v D vD
3,114,000 847,700
− =0
(15 − v D )2 v D2
or
or
and
EXAMPLE 11.4
A two-wire DC street mains AB, 600 m long is fed from both ends
at 230 V. Loads of 20, 40, 50, and 30 A are tapped at distances of
100, 250, 400, and 500 m from the end A, respectively. If the area of
cross-section of distributor conductor is 1 cm2, find the minimum
consumer voltage. Take ρ = 1.7 × 10−6 Ω cm.
Solution
Figure 11.28 shows the distributor with its tapped current. Let IA
amperes be the current supplied from the feeding end A. Then
current in the various sections of the distributor are as shown in
Figure 11.28.
Resistance of 1 m length of distributor,
230 V 230 V
20 A 40 A 50 A 30 A
or
0.204 I A = 12.58
or
12.58
IA = = 61.7 A
0.204
EXAMPLE 11.5
A two-wire DC distributor AB is fed from both ends. At feeding
point A, the voltage is maintained as at 220 V and at B 225 V. The
total length of the distributor is 200 m and loads are tapped off as
Distribution Systems ◾ 273
Solution:
Figure 11.29 shows the distributor with its tapped current. Let IA amperes
be the current supplied from the feeding point A. Then current in the
various sections of the distributor are as shown in Figure 11.29.
Resistance of 1000 m length of distributor (both wires):
2 × 0.3 = 0.6 Ω
50
Resistance of section AC, RAC = 0.6 × = 0.03 Ω
1000
5
Resistance of section CD, RCD = 0.6 × = 0.015 Ω
1000
5
Resistance of section DE, RDE = 0.6 × = 0.015 Ω
1000
50
Resistance of section EF, REF = 0.6 × = 0.03 Ω
1000
50
Resistance of section FB, RFB = 0.6 × = 0.03 Ω
1000
A IA C IA – 25 D IA – 75 E IA – 105 F IA – 145 B
50 m 25 m 25 m 50 m 50 m
230 V 225 V
25 A 50 A 30 A 40 A
or
or
or
or
229 − 225
IA = = 33.34 Ω
0.012
I AC = I A = 33.34 A
EXAMPLE 11.6
A two-wire DC distributor cable 900 m long is loaded with
0.6 A/m. Resistance of each conductor is 0.08 Ω/km. Calculate the
maximum voltage drop if the distributor is fed from both ends with
equal voltage of 230 V. What is the minimum voltage and where it
occurs?
Solution
Current loading, i = 0.6 A/m
Resistance of distributor/m, r = 2 × 0.08/1000 = 0.16 × 10−3 Ω
Length of distributor, l = 900 m
Total current supplied by distributor, I = il = 0.6 × 900 = 540 A
Total resistance of the distributor, R = rl = 0.16 × 10−3 × 900 = 0.1
442 Ω
IR 540 × 0.1442
∴ Maximum voltage drop = = = 9.72 V
8 8
EXAMPLE 11.7
A 800-m, two-wire DC distributor AB fed from both ends is uni-
formly loaded at the rate of 1.25 A/m run. Calculate the voltage at
the feeding points A and B if the minimum potential of 220 V occurs
276 ◾ Elements of Power Systems
Solution
Figure 11.30 shows the single-line diagram of the distributor.
0.05
Resistance of distributor/m, r = 2 × = 0.0001 Ω
1000
Voltage at C, VC = 220 V
450 m 350 m
A B
C
EXAMPLE 11.8
A single-phase distributor 1 km long has resistance and reactance
per conductor of 0.2 and 0.3 Ω, respectively. At the far end, the volt-
age VB = 220 V and the current is 150 A at a pf of 0.8 lagging. At
the midpoint M of the distributor, a current of 150 A is tapped at a
pf of 0.6 lagging with reference to the voltage VM at the midpoint.
Calculate:
1. Voltage at midpoint
2. Sending end voltage
3. Phase angle between VA and VB
Solution
Figure 11.31 shows the single-line diagram of the distributor AB
with M as the midpoint.
Total impedance of distributor = 2(0.2 + j0.3) = (0.4 + j0.6)Ω
Impedance of section AM, Z AM = (0.2 + j0.3)Ω
A 500 m M 500 m B
I1 = 100 A I2 = 100 A
cos φ1 = 0.6 lag cos φ2 = 0.8 lag
18
Phase angle between VM and VB , α = tan −1 = tan −1 0.0276 = 3.8°.
217
2. The load current I1 has a lagging pf of 0.6 wrt VM. It lags behind
VM by an angle ϕ1 = cos−1 0.6 = 53.13°.
42.571
tan θ =
375.681
Distribution Systems ◾ 279
or
θ = 6.46°
EXERCISES
Fault Analysis
12.1 INTRODUCTION
Most faults on the power system occur when two or more conductors that
normally operate with a potential difference come in contact with each
other. These faults may be caused by sudden failure of a piece of equip-
ment, accidental damage, short circuit to overhead lines, or by insulation
failure resulting from lightning surges. When such a condition occurs, a
large current (called short-circuit current) flows through the equipment,
doing reasonable damage to the equipment and interruption of service to
the consumer. The choice of apparatus and the design and arrangement
of practically every equipment in the power system depends upon short-
circuit current considerations.
Unsymmetrical faults. The faults on the power system which give rise
1.
to unsymmetrical fault current (i.e., unequal fault current in the lines
with unequal phase displacement) are known as unsymmetrical faults.
If an unsymmetrical fault occurs, the current in the three lines
become unequal and so is the phase displacement among them. It
may be noted that the term “unsymmetry” applies only to the fault
itself and the resulting line current. However, the system impedances
and the source voltage are always symmetrical through its main ele-
ments, namely generators, transmission lines, synchronous reactors,
etc. There are three ways in which unsymmetrical faults may occur
in a power system.
281
282 ◾ Elements of Power Systems
Symmetrical faults. The fault on the power system which gives rise
2.
to symmetrical fault current (i.e., equal fault current in the line with
120° displacements) is called a symmetrical fault.
The symmetrical fault occurs when all the three conductors of a
three-phase line are brought together simultaneously into a short-
circuit condition. This type of fault gives rise to symmetrical current,
that is, equal fault current with 120° displacement. Because of bal-
anced nature of fault, only one phase need to be considered in calcu-
lations since condition in the other two phases will also be similar.
The following points may be particularly noted:
a. The symmetrical fault rarely occurs in practice as majority of the
faults are of unsymmetrical nature. However, symmetrical fault
calculations are being discussed in this chapter to enable the
reader to understand the problems that short-circuit conditions
present to the power system.
b. The symmetrical fault is the most severe and imposes more heavy
duty on the circuit breaker.
Va2 Va0
Va1 Vb0
Vc0
Vc2
Vb1
1. Positive-sequence components
2. Negative-sequence components
3. Zero-sequence components
α = 1∠120°
α2 = α ⋅ α
= 1∠120° ⋅ 1∠120°
= 1∠240°
= cos 240° + j sin 240°
= −0.5 − j0.866
α3 = α ⋅ α ⋅ α
= 1∠120° ⋅ 1∠120° ⋅ 1∠120°
= 1∠360°
= cos 360° + j sin 360°
Therefore,
α3 = 1
or
(α 3 − 1) = 0
or
(α − 1)(α 2 + α + 1) = 0
α2 + α + 1 = 0
Vb1 = α 2Va1
This means in order to express Vb1 in terms of Va1, Va1 should be rotated
anticlockwise through 240°.
286 ◾ Elements of Power Systems
Similarly,
Vc1 = –Va1
Va 0 = Vb0 = Vc0
and
Va 1 1 1 Va1
Vb = 1 α α Va2 (12.10)
2
Vc 1 α α 2 Va0
Fault Analysis ◾ 287
and
−1
Va1 1 1 1 Va
Va 2 = 1 α α Vb
2
Va 0 1 α α 2 Vc
Va1 1 α α 2 Va
1
∴ Va2 = 1 α 2 α Vb (12.11)
3
Va0 1 1 1 Vc
1 (12.12)
Va1 = (V + αVb + α 2Vc )
3 a
1 (12.13)
Va2 = (V + α 2Vb + αVc )
3 a
1 (12.14)
Va0 = (V + Vb + Vc )
3 a
1 (12.15)
I a1 = (I + αI b + α 2 I c )
3 a
1
Ia 2 = (I + α 2 I b + αI c ) (12.16)
3 a
1 (12.17)
Ia 0 = (I + I b + I c )
3 a
voltage revolving at the same rate which may exist in the three-phase sys-
tem. Similarly three current could be phase current, line current, and the
current following into a fault from the line conductors.
In = Ia + I b + I c
= (I a1 + I a2 + I a 0 ) + (α 2 I a1 + αI a2 + I a 0 ) + (αI a1 + α 2 I a2 + I a0 )
= I a1 (1 + α + α 2 ) + I a2 (1 + α + α 2 ) + 3I a0
= 3I a0 ∵ (α 2 + α + 1) = 0
∴ Vn = −3I a 0 Z n (12.18)
Ia
Ea
Zn
N
Eb
Ec
Ib
Ic
Ia1
Z1
Ea Ia1
Z1
N Va1
Eb
Ec Ea
Z1 Z1
Ib1
ZBP
Ic1
Va 2 = Ea 2 − I a 2 Z 2
Va2 = − I a2 Z 2 (12.20)
Ea0 = 0
Va0 = Vn − I a0 Z g 0 = −3I a0 Z n − I a0 Z g 0 = − I a 0 (Z g 0 + 3Z n )
Z 0 = Z g 0 + 3Z n
Va 0 = − I a 0 Z 0 (12.21)
Ia2
Z2
Ia2
N Va2
Z2 Z2
Z2
Ib2
ZBP
Ic2
Ia1
Z0
Ia0
N Va0
Z0 Z0
Z0
Ib0
ZBP
Ic0
1. Synchronous generators
2. Transformers
3. Transmission lines
Ib = 0 (12.22)
a
Ia
Ea
N
Eb
Ec
b Ib
c
Ic
Ic = 0 (12.23)
Va = 0 (12.24)
Va 2 = − I a 2 Z 2 (12.26)
Va 0 = − I a 0 Z 0 (12.27)
The solution of these six equations will give six unknowns Va1, Va2, Va0,
and Ia1, Ia2, Ia0.
Also we know
1
I a1 = (I + αI b + α 2 I c ) (12.28)
3 a
1
Ia 2 = (I + α 2 I b + αI c ) (12.29)
3 a
1 (12.30)
Ia 0 = (I + I b + I c )
3 a
1
I a1 = I
3 a
1
Ia 2 = I
3 a
1
Ia 0 = I
3 a
Therefore, Ia1 = Ia2 = Ia0 = (1/3)Ia.
Fault Analysis ◾ 295
Also we know
Va = Va1 + Va 2 + Va 0
Now substituting the values of Va1, Va2, Va0 from the sequence network
equation,
0 = Ea − I a1Z1 − I a 2 Z 2 − I a 0 Z 0 (12.31)
∵ I a1 = I a 2 = I a 0
Ea − I a1 (Z1 + Z 2 + Z 0 ) = 0
Ea
I a1 = (12.32)
(Z1 + Z 2 + Z 0 )
Ia1
+ + +
Z1 Z2 Z0
Ea – – –
Ea
I a1 = (12.33)
(Z1 + Z 2 + Z 0 + 3Z f )
It may be added here that if the neutral is not grounded, then zero-
sequence impedance will be infinite and the fault current is zero. This is
expected because now no path exists for the flow of fault current.
Ib + Ic = 0 (12.34)
a
Ia
Ea
N
Eb
Ec
b Ib
c
Ic
Ia = 0 (12.35)
Vb = Vc (12.36)
Va 2 = − I a 2 Z 2 (12.38)
Va0 = − I a0 Z 0 (12.39)
1
I a1 = (I + αI b + α 2 I c )
3 a
1
Ia 2 = (I + α 2 I b + αI c )
3 a
1
Ia 0 = (I + I b + I c )
3 a
1 1 1
I a1 = (I + αI b + α 2 I c ) = (αI b − α 2 I b ) = I b (α − α 2 )
3 a 3 3
1 1
Ia 2 = (0 + α 2 I b + αI c ) = (α 2 I b − αI b ) = I b (α 2 − α)
3 3
1
Ia0 = (0 + 0 + 0) = 0
3
298 ◾ Elements of Power Systems
I a1 = − I a 2 (12.40)
And we know
Vb = (α 2Va1 + αVa 2 + Va 0 )
Vc = αVa1 + α 2Va 2 + Va 0
Va1 (α 2 − α) = Va 2 (α 2 − α)
Va1 = Va 2 (12.41)
Ea − I a1Z1 = − I a 2 Z 2
or
Ea − I a1Z1 = I a1Z 2
Ea
I a1 = (12.42)
Z1 + Z 2
Ia1 Ia2
+ +
Z1 Z2
Va1 Va2
– –
Ea
Ea
I a1 = (12.43)
Z1 + Z 2 + Z f
a
Ia
Ea
N
Eb
Ec
b Ib
c
Ic
Ib + Ic
Ia = 0 (12.44)
Vb = 0 (12.45)
Vc = 0 (12.46)
Va 2 = − I a 2 Z 2 (12.48)
Va 0 = − I a 0 Z 0 (12.49)
1
Va1 = (V + αVb + α 2Vc )
3 a
1
Va 2 = (V + α 2Vb + αVc )
3 a
1
Va 0 = (V + Vb + Vc )
3 a
Substituting for Va, Vb, and Vc from Equations 12.45 and 12.46,
1
Va1 = Va
3
1
Va 2 = Va
3
1
Va 0 = Va
3
Fault Analysis ◾ 301
that is,
Va1 = Va 2 = Va 0 (12.50)
Va1 = Va 2
Ea − I a1Z1 = − I a 2 Z 2
I a1Z1 − Ea
Ia 2 = (12.51)
Z2
Similarly,
Va 2 = Va 0
− Ia 2 Z2 = − Ia 0 Z0
Z2
Ia 0 = Ia 2 (12.52)
Z0
I a = (I a1 + I a2 + I a0 ) = 0
Substituting the values of Ia2 and Ia0 from Equations 12.51 and 12.52,
I a1Z1 − Ea I a1Z1 − Ea Z 2
I a1 + + ⋅ Z = 0
Z2 Z2 0
I a1Z1 Ea I a1Z1 Ea
I a1 + − + − =0
Z2 Z2 Z0 Z0
302 ◾ Elements of Power Systems
+ + +
Z1 Z2 Z0
Va2 Va0
Va1 – – –
Ea
Z Z 1 1
I a 1 1 + 1 + 1 = Ea +
Z2 Z0 Z 2 Z 0
Ea ((Z 0 + Z 2 )/Z 2 Z 0 )
I a1 =
(1 + (Z1/Z 2 ) + (Z1/Z 0 ))
Ea ( Z 0 + Z 2 )
I a1 =
Z 2 Z 0 + Z1Z 0 + Z1Z 2
Ea ( Z 0 + Z 2 )
I a1 =
Z 2 Z 0 + Z1 (Z 2 + Z 0 )
Ea
I a1 = (12.53)
Z1 + (Z 2 Z 0 /(Z 0 + Z 2 ))
From Equation 12.53, it is clear that all the three sequence networks
are required to simulate L–L–G fault and also that the negative and zero-
sequence networks are connected in parallel. Interconnection of sequence
network for (L–L–G) as shown in Figure 12.11.
a
Ia
Ea
N
Eb
Ec
b Ib
c
Ic
Va = Vb = Vc (12.54)
(Ia + I b + I c ) = 0 (12.55)
I c = αI a and I b = α 2 I a
Using the relation,
1
I a1 = (I + αI b + α 2 I c )
3 a
1
Ia 2 = (I + α 2 I b + αI c )
3 a
1
Ia 0 = (I + I b + I c )
3 a
1
I a1 = (I + – 3 Ia + – 3 Ia )
3 a
304 ◾ Elements of Power Systems
I a1 = I a (12.56)
1
Ia 2 = (I + α 4 Ia + α 2 Ia )
3 a
1 1
Ia 2 = I (1 + α 4 + α 2 ) = I a (1 + α 3 ⋅ α + α 2 )
3 a 3
1
Ia 2 = I (1 + α + α 2 )
3 a
I a2 = 0 (12.57)
1
Ia 0 = (I + I b + I c )
3 a
I a0 = 0 (12.58)
1
Va1 = (V + αVb + α 2Vc )
3 a
1
Va1 = Va (1 + α + α 2 ) = 0 (12.59)
3
Since
Va1 = 0 = Ea − I a1Z1
Ea
I a1 = (12.60)
Z1
Ia1
+
Z1
–
Ea
WORKED EXAMPLES
EXAMPLE 12.1
100 MVA, 20 kV generator has subtransient reactance which is the
same as the positive- and negative-sequence reactance, and it is 20%.
Its neutral is grounded through a reactance 0.32 Ω and the zero-
sequence reactance of the generator Xg0 is 5%. The generator is oper-
ating at rated voltage at no load and disconnected from system when
a line-to-ground fault occurs, find the subtransient current in fault
phase. Neglect reactance.
Solution
Let the line-to-neutral voltage at the fault point before the fault be 1 pu:
3 Ea
Fault current I f ( pu ) =
x1( pu ) + x2( pu ) + x o( pu )
(MVA)base 0.32 × 100
Reactance of the neutral X n( pu ) = X n.ohm =
(kV)2 base 202
= 0.08 pu
X o( pu ) = X g 0( pu ) + 3 X n( pu )
= 0.05 + 0.24
= 0.29 pu
3 × 1. 0
I f ( pu ) = = 4.34 pu
0.2 + 0.2 + 0.29
306 ◾ Elements of Power Systems
EXAMPLE 12.2
With reference to Example 12.1, determine the subtransient current
in fault phase when a line-to-line fault occurs. Neglect resistance.
Solution
Let the line-to-neutral voltage at the fault point before the fault be
1 pu:
3 Ea 3 ×1
Fault current I f ( pu ) = = = 4.33 pu
x1( pu ) + x2( pu ) 0.2 + 0.2
EXAMPLE 12.3
Positive-sequence current for a line-to-line fault of a 2-kV sys-
tem is 1400 A, current for double line-to-ground fault is 2220 A.
Determine the zero-sequence impedance of the system. Neglect
resistance.
Solution
Ea
Fault current for L – L fault , I f (amp) =
X1 + X2
= 1400
Here the line voltage is 2 kV. But we consider the phase voltage as
a reference voltage,
2000
∴ Ea = V
3
Fault Analysis ◾ 307
2000
∴ = 1400 A
3 ( X1 + X2 )
X1 + X2 = 0.82 Ω
or
0.82
X1 + X2 = = 0.41
2
Ea
I f (L − L −G) = = 2220 A
X1 + ( X2 X0 )
2000
∴ = 2220
3[0.41 + (0.41 X0 )]
∴ X0 = 0.15 Ω
EXAMPLE 12.4
Zero-sequence current of a line-to-ground fault is (j2.4) pu.
Determine the current through neutral during fault and neutral
potential if neutral reactance is 5%.
Solution
Current through the neutral is
I n = 3I a0 = 3 × j2.4 = j7.2 pu
EXAMPLE 12.5
At a 220-kV substation of a power system, it is given that 3-ϕ fault
level is 4000 MVA and line-to-ground fault level is 5000 MVA.
308 ◾ Elements of Power Systems
Solution
1. Fault current for L–L–L fault is
Ea
If =
X1
Ea
∴ 3 Ea × = 4000 × 106
X1
( )
2
3 (220 × 103 )/ 3
= 4000 × 106
X1
3 Ea
If =
X1 + X2 + X0
Let X1 = X2
( )
2
9 × (220 × 103 )/ 3
∴ = 5000 × 106
2 X1 + X0
3 Ea
∴ 3 Ea = 5000 × 106
2 X1 + X0
Fault Analysis ◾ 309
( )
2
9 × (220 × 103 )/ 3
∴ = 5000 × 106
2 X1 + X0
EXERCISES
Circuit Breakers
13.1 INTRODUCTION
A circuit breaker (CB) is a device that can operate under normal or abnor-
mal conditions to make or break the circuit by manually, automatically,
or remote control. It can act in different voltage levels from low to high
and some big CBs have the auto reclosing facility by which they can
close their constants automatically when the fault subsides from the
system.
The CB cannot operate individually without the help of relay, CT and
PT, and other some auxiliary equipments. The function of a relay is to
sense the fault in a system and to give a signal to the CB and the CB opens
the circuit by tripping automatically. The necessary power of tripping is
supplied from a DC source. The time from the occurrence of the fault to
the total clearing of the fault is known as fault-clearing time and it is in the
order of fraction of a second (two to three cycles).
311
312 ◾ Elements of Power Systems
13.3 OPERATING PRINCIPLE OF CB
The function of a CB is to isolate the faulty part of the power system in case
of abnormal condition such as faults. A protective relay detects abnormal
conditions and sends a tripping signal to CB. After receiving the trip signal
from the relay the CB isolates faulty part of the power system. The simpli-
fied diagram of the CB control for opening operation is shown in Figure
13.1. When a fault occurs in the protected circuit the relay connected to the
CT and VT detects the fault, actuates, and closes its contacts to complete
the trip circuit. Current flows from the battery in the trip circuit. As the
trip coil of the CB energized, the CB operating mechanism is actuated and
it operates for the opening operation to disconnect the faulty element. A
CB has two contacts—a fixed and a moving. These are placed in a closed
Bus bar
VT
Relay
CT
Line
FIGURE 13.1 Simplified diagram of circuit breaker control for opening operation.
Circuit Breakers ◾ 313
13.4 ARC PHENOMENON
After the occurrence of the fault, when the contacts of the CB begins to
separate an arc is established in the contact gap. The physics behind this
arc can be categorically described in two steps:
1. Initiation of arc
2. Maintenance of arc
1. Initiation of arc: The contact gap after separation gets ionized due to
following two reasons:
Thermionic emission. At the time of separation the contact area
a.
sharply decreases and the current density becomes very high. It
is worthwhile to remember that the fault current is much higher
than the normal. This increased density of current causes the
generation of high heat which ultimately leads to thermionic
emission at the contact gap.
Field emission. During separation of contacts as contact area
b.
decreases resistance increases. The high fault current flowing
314 ◾ Elements of Power Systems
Current i
Restriking
voltage
2Em
Recovery
Em voltage
Time
L CB
(a) (b)
CB
V C
FIGURE 13.3 (a) Fault on a feeder near circuit breaker. (b) Equivalent electrical
circuit for analysis of restriking voltage.
318 ◾ Elements of Power Systems
C are the inductance and capacitance per phase of the system up to the
point of CB location, respectively. The resistance of the circuit has been
neglected. During the time of fault, a heavy fault current flows in the cir-
cuit. When the CB is closed, the fault current flows through L and the
contacts of the CB, the capacitance C being short circuited by the fault.
Hence, the circuit of Figure 13.3b becomes completely reactive and the
fault current is limited entirely by inductance of the system.
The fault is cleared by opening of the CB contacts. The parting of
the CB contacts does not in itself interrupt the current because an arc
is established in between the parting contacts and the current continues
to flow through the arc. Successful interaction depends upon controlling
and finally extinguishing the arc. Extinction of the arc takes place at the
instant when current passes through zero.
Since the circuit of Figure 13.3b is completely reactive, the voltage at
the instant of current zero will be at its peak. The voltage across the CB
contacts, and therefore across the capacitor C, is the arc voltage. In high-
voltage circuits, it is usually only a small percentage of the system voltage.
Hence, the arc voltage may be assumed to be negligible.
For the analysis of this circuit, the time is measured from the instant of
interruption, when the fault current comes to zero. Since the voltage is a
sinusoidally varying quantity and is at its peak at the moment of current
zero, it is expressed as “Vmcos ωt.”
When the CB contacts are opened and the arc is extinguished, the current
i is diverted through the capacitance C, resulting in a transient condition.
The inductance and the capacitance from a series oscillatory circuit. The volt-
age across the capacitance which is restriking voltage rises and oscillates.
Vm cos ωt
Vm cos ωt = Vm
1
fn = (13.1)
2π LC
1
ωn = (13.2)
LC
Circuit Breakers ◾ 319
The voltage across the capacitance which is the voltage across the con-
tacts of the CB can be calculated in terms of L, C, fn, and system voltage.
The mathematical expression for the transient condition is as follows:
di 1
L +
dt C ∫
i dt = Vm cosωt
(13.3)
di 1
L +
dt C ∫
i dt = Vm
(13.4)
dq d(cv c )
i= = (13.5)
dt dt
di d 2 (cv c ) d 2v c
= = c (13.6)
dt dt 2 dt 2
1 q
C∫i dt = = v c
c
(13.7)
d 2v c
LC + v c = Vm (13.8)
dt 2
320 ◾ Elements of Power Systems
Vm
LCS 2v c (s) + v c (s) =
s
Vm
v c (s)[LCS 2 + 1] =
s
Vm Vm
or v c (s) = =
s(LCS 2 + 1) LCS[s 2 + (1/LC )]
1 1
ωn = , ∴ ω 2n =
LC LC
1 1
ωn = , ∴ ω 2n = (13.9)
LC LC
∫
vc (t ) = ω nVm sin ω nt
0
t
− cos ω nt
= ω nVm
ω n 0
v c (t ) = Vm (1 − cos ω nt ) (13.10)
π
t= = π LC
ωn
Circuit Breakers ◾ 321
d
RRRV = [V (1 − cos ω nt )]
dt m
13.9 CURRENT CHOPPING
It is the phenomenon of current interruption before the natural current
zero is reached. Current chopping mainly occurs in air-blast CBs because
they retain the same extinguishing power irrespective of the magnitude
of the current to be interrupted. When breaking low current (e.g., trans-
former magnetizing current) with such breakers, the powerful deionizing
effect of air blast causes the current to fall abruptly to zero well before the
natural current zero is reached. This phenomenon is known as current
chopping and results in the production of high-voltage transient across
the contacts of the CB as discussed below.
Suppose the arc current is i when it is chopped down to zero value as
shown by point a in Figure 13.4. As the chop occurs at current i, the energy
stored in inductance is L i2/2. This energy will be transferred to the capac-
itance C, charging the latter to a prospective voltage e given by
1 2 Ce 2
Li =
2 2 (13.11)
i L
e= V
C
in action, chop occurs again but the arc current this time is smaller than the
previous case. This induces a lower prospective voltage to reignite the arc.
In fact, several chops may occur until a low enough current is interrupted
which produces insufficient induced voltage to restrike across the breaker
gap. Consequently, the final interruption of current takes place.
13.10 RESISTANCE SWITCHING
It has been discussed above that current chopping, capacitive current
breaking, etc., give rise to severe voltage oscillations. These excessive volt-
age surges during circuit interruption can be prevented by the use of shunt
resistance R connected across the CB contacts as shown in the equivalent
circuit in Figure 13.5. This is known as resistance switching.
R
(a) (b)
Oscillatory
L CB restriking voltage
Voltage
Recovery
voltage
e C
Damped
restriking voltage
Time
FIGURE 13.5 (a) Equivalent circuit for analysis of resistance switching. (b)
Restriking voltage oscillation.
Circuit Breakers ◾ 323
When a fault occurs, the contacts of the CB are opened and an arc is
struck between the contacts. Since the contacts are shunted by resistance
R, a part of arc current flows through this resistance. This results in the
decrease of arc current and an increase in the rate of deionization of the
arc path. Consequently, the arc resistance is increased. The increased arc
resistance leads to a further increase in current through shunt resistance.
This process continues until the arc current becomes so small that it fails
to maintain the arc. Now, the arc is extinguished and circuit current is
interrupted.
The shunt resistor also helps in limiting the oscillatory growth of
restriking voltage. It can be proved mathematically that natural frequency
of oscillations of the circuit shown in Figure 13.5a is given by
1 1 1
fn = −
2π LC 4 R2C 2
In order to keep RRRV within the rating of CB, the critical value of
resistance R can be determined by making fn, that is,
1 1 1
fn = − =0
2π LC 4 R2C 2
1 1 1 1
− = 0 or =
LC 4 R C2 2 LC 4 R2C 2
∴ R = 0.5 L /C
13.11 CB RATINGS
A CB may be called upon to operate under all conditions. However, major
duties are imposed on the CB, when there is a fault on the system in which
it is connected. Under fault conditions, a CB is required to perform the
following three duties:
1. It must be capable of opening the faulty circuit and breaking the fault
current.
2. It must be capable of being closed on to a fault.
3. It must be capable of carrying fault current for a short time, while
another CB (in series) is clearing the fault.
D
D-D′, instant of constant
separation
B
A x
y
o
Normal
C zero
D′
13.12 AUTORECLOSING
The fault which exist on the system. Depending upon the time are classi-
fied as follows:
1. Transient fault
2. Semi-permanent fault
3. Permanent fault
It has been found that above 80% fault are transient fault, and 12% are
semi-permanent faults.
Transient faults are exist only for a short time. It can be removed faster
still if the line is disconnected from the system momentarily so that the
arcs blows out. After the arc is deionized, the line can be reclosed to
restore normal service. Semi-permanent fault may occur due to twig fall-
ing on the power conductor or the bird spanning the power conductor.
The reclosing could be restored with some delay so that the cause of the
fault could be dispensed with during a time delay trip and the line could
be reclosed to restore normal service. In case of permanent fault, reclosing
does not help as it is to be attended or removed, and the line is to be taken
out till the fault is cleared. Therefore, if the fault is not cleared after first
Circuit Breakers ◾ 327
13.13 CLASSIFICATION OF CBs
There are several ways of classifying the CBs. However, the most general
way of classification is on the basis of medium used for arc extinction.
The medium used for arc extinction is usually oil, air, SF6, or vacuum.
Accordingly CBs may be classified into the following:
1. Oil CBs
2. Air-blast CBs
3. SF6 CBs
4. Vacuum CBs
13.14 OIL CBs
In such CBs, some insulating oil (e.g., transformer oil) is used as an arc
quenching medium. The contacts are opened under oil and an arc is struck
between them.
The heat of the arc evaporates the surrounding oil and dissociates it into
a substantial volume of gaseous hydrogen at high pressure. The hydrogen
gas occupies a volume about one thousand times that of the oil decom-
posed. The oil is, therefore, pushed away from the arc and an expanding
hydrogen gas bubble surrounds the arc region and adjacent portions of the
contacts (Figure 13.7).
The arc extinction is facilitated mainly by two processes:
1. The hydrogen gas has high heat conductivity and cools the arc, thus
aiding the deionization of the medium between the contacts.
2. The gas sets up turbulence in the oil and forces it into the space between
contacts, thus eliminating the arcing products from the arc path. The
result is that arc is extinguished and circuit current interrupted.
328 ◾ Elements of Power Systems
Parting
contacts
Arc Bubble of
oil vapor
Oil
FIGURE 13.7 Gas bubble surrounds the arc region and adjacent portions of the
contacts of an oil CB.
1. It absorbs the arc energy to decompose the oil into gases which have
excellent cooling properties.
2. It acts as an insulator and permits smaller clearance between live
conductors and earthed components.
3. The surrounding oil presents cooling surface in close proximity to
the arc.
13.15.1 Bulk-Oil CBs
Bulk-oil CBs use a large quantity of oil. The oil has to serve two purposes.
Circuit Breakers ◾ 329
13.15.2 Low-Oil CBs
Low-oil CBs use minimum amount of oil. In such CBs, oil is used only
for arc extinction; the current conducting parts are insulated by air or
porcelain or organic insulating materials.
1. The hydrogen gas bubble generated around the arc cools the arc
column and aids the deionization of the medium between the
contacts.
2. The gas sets up turbulence in the oil and helps in eliminating the arc-
ing products from the arc path.
3. As the arc lengthens due to the separating contacts, the dielectric
strength of the medium is increased.
330 ◾ Elements of Power Systems
Air cushion
Oil level
Fixed
contacts
Moving
contacts
Transformer oil
Disadvantages:
1. There is no special control over the arc other than the increase in
length by separating the moving contacts. Therefore, for successful
interruption, long arc length is necessary.
2. These breakers have long and inconsistent arcing times.
3. These breakers do not permit high-speed interruption.
Due to these disadvantages, plain-break oil CBs are used only for low-
voltage applications where high breaking capacities are not important. It
is a usual practice to use such breakers for low-capacity installations for
voltage not exceeding 11 kV.
Fixed contact
Pot
Throat
Moving
contact
extinguish it. If the final arc extinction does not take place while the mov-
ing contact is still within the pot, it occurs immediately after the mov-
ing contact leaves the pot. It is because emergence of the moving contact
from the pot is followed by a violent rush of gas and oil through the throat
producing rapid extinction. The principal limitation of this type of pot is
that it cannot be used for very low or for very high fault current. With low
fault current, the pressure developed is small, thereby increasing the arc-
ing time. On the other hand, with high fault current, the gas is produced
so rapidly that explosion pot is liable to burst due to high pressure. For
this reason, plain explosion pot operates well on moderate short-circuit
current only where the rate of gas evolution is moderate.
Gas bubble
Fixed
Back contact
passage
Arc
Path of
cool oil Oil forced
out
Arc splitters
Moving contact
low fault current, the gas pressure is small and consequently the pot does
not give a satisfactory operation.
13.17.2 Forced-Blast Oil CB
The major limitation of such breakers is that arcing times tend to be long
and inconsistent when operating against current considerably less than
the rated current. It is because the gas generated is much reduced at low
Fixed contact
Cross-jet explosion pot
P
Arc splitters
Moving contact
Throat
values of fault current. This difficulty is overcome in forced blast oil CBs in
which the necessary pressure is generated by external mechanical means
independent of the fault current to be broken.
In this breaker, oil pressure is created by the piston-cylinder arrange-
ment. The movement of the piston is mechanically coupled to the moving
contact. When a fault occurs, the contacts get separated by the protective
system and an arc is struck between the contacts. The piston forces a jet of
oil toward the contact gap to extinguish the arc.
Advantages:
13.18 LOW-OIL CBs
The oil in the bulk oil CB serves two purposes.
Firstly, it acts as an arc quenching medium and secondly, it insulates
the live parts from earth. It has been found that only a small percentage
of oil is actually used for arc extinction while the major part is utilized for
insulation purposes. For this reason, the quantity of oil in bulk oil CBs
reaches a very high figure as the system voltage increases. Consequently
besides increase in the expenses, tank size and weight of the breaker the
fire risk and maintenance problems are also increase. This factors led to
the development of a low-oil CB. A low-oil CB employs solid materials for
insulation purposes and uses a small quantity of oil which is just sufficient
for arc extinction.
13.18.1 Construction
Figure 13.12 shows the cross-section of a single phase low-oil CB. There are
two compartments separated from each other but both filled with oil. The
upper chamber is the circuit-breaking chamber while the lower one is the
supporting chamber. The two chambers are separated by a partition and
oil from one chamber is prevented from mixing with the other chamber.
Top chamber
(a) (b)
Gas vent Oil level Breather
Supporting
chamber
Operating rod
Drain valve
FIGURE 13.12 (a) Low oil circuit breaker and (b) cross-section of a single phase.
chamber and the annular space formed between the porcelain insu-
lation and bakelized paper is employed for insulation purposes only.
Circuit-breaking chamber. It is a porcelain enclosure mounted on the
2.
top of the supporting compartment. It is filled with oil and has the
following parts:
a. Upper and lower fixed contacts
b. Moving contact
c. Turbulator
The moving contact is hollow and includes a cylinder which moves
down over a fixed piston. The turbulator is an arc control device and
has both axial and radial vents. The axial venting ensures the inter-
ruption of low current, whereas radial venting helps in the interrup-
tion of heavy current.
Top chamber. It is a metal chamber and is mounted on the circuit-
3.
breaking chamber. It provides expansion space for the oil in the cir-
cuit-breaking compartment.
13.18.2 Operation
Under normal operating conditions, the moving contact remains engaged
with the upper fixed contact. When a fault occurs, the moving contact is
336 ◾ Elements of Power Systems
pulled down by the tripping springs and an arc is struck. The arc energy
vaporizes the oil and produces gases under high pressure. This action con-
strains the oil to pass through a central hole in the moving contact and
results in forcing series of oil through the respective passages of the tur-
bulator. The process of turbulation is orderly one, in which the sections of
the arc are successively quenched by the effect of separate streams of oil
moving across each section in turn and bearing away its gases.
Advantages: A low-oil CB has the following advantages over a bulk oil CB:
1. Check the current carrying parts and arcing contacts. If the burning
is severe, the contacts should be replaced.
Circuit Breakers ◾ 337
2. Check the dielectric strength of the oil. If the oil is badly discolored,
it should be changed or reconditioned.
3. Check the insulation for possible damage. Clean the surface and
remove carbon deposits with a strong and dry fabric.
4. Check the oil level.
5. Check closing and tripping mechanism.
13.20 AIR-BLAST CBs
These breakers employ a high pressure air blast as an arc quenching
medium. The contacts are opened in a flow of air blast established by the
opening of blast valve. The air blast cools the arc and sweeps away the
arcing products to the atmosphere. This rapidly increases the dielectric
strength of the medium between contacts and prevents from re-establish-
ing the arc. Consequently, the arc is extinguished and flow of current is
interrupted.
Advantages: An air-blast CB has the following advantages over a low-
oil CB:
Disadvantages:
Blast Blast
Fixed Moving
Moving Moving contact contact
contact contact
FIGURE 13.13 (a) Axial-blast type. (b) Cross-blast type. (c) Radial-blast type.
13.21 TYPES OF AIR-BLAST CB
Depending upon the direction of air blast in relation to the arc, air-blast
CB may be classified into the following types:
13.22 VACUUM CBs
In such breakers, vacuum (VCB, degree of vacuum being in the range
from 10−7 to 10−5 torr) is used as the arc quenching medium. Since, vacuum
offers the highest insulating strength, it has far superior arc quenching
properties than any other medium.
13.22.1 Construction
Figure 13.14 shows the parts of a typical vacuum CB. It consists of fixed
contact, moving contact, and arc shield mounted inside a vacuum cham-
ber. The movable member is connected to the control mechanism by
stainless steel bellows. This enables the permanent sealing of the vacuum
chamber so as to eliminate the possibility of leak. A glass vessel or ceramic
vessel is used as the outer insulating body. The arc shield prevents the dete-
rioration of the internal dielectric strength by preventing metallic vapors
Circuit Breakers ◾ 339
Insulating vessel
Fixed
member
Contacts
Insulating vessel
falling on the inside surface of the outer insulating cover. The vapor con-
densing shield is made of synthetic resin.
13.22.2 Working Principle
When the breaker operates, the moving contact separates from the fixed con-
tact and an arc is struck between the contacts by the ionization of metal vapors
of contacts. However, the arc is quickly extinguished because the metallic
vapors, electrons, and ions produced during arc rapidly condense on the sur-
faces of the CB contacts, resulting in quick recovery of dielectric strength.
Advantages:
13.22.3 Application
In India, where distances are quite large and accessibility to remote
areas is difficult, the installation of such outdoor, maintenance free CBs
should proof a definite advantage. Vacuum CBs are being employed for
outdoor applications ranging from 22 to 66 kV. Even with limited rating
of say 66–100 MVA, they are suitable for a majority of applications in
rural areas.
13.23 SF6 CBs
SF6 is an electro-negative gas and has a strong tendency to absorb free
electrons. The contacts of the breaker are opened in a high pressure flow of
SF6 gas and an arc is struck between them. The conducting free electrons
in the arc are rapidly captured by the gas to form relatively immobile nega-
tive ions. This loss of conducting electrons in the arc quickly builds up
enough insulation strength to blow out the arc.
Owing to the following properties, SF6 proves superior to other medium
such as oil or air for use in CB:
SF6 breakers can withstand severe RRRV and this are most suitable for
short line faults without switching resistors and can interrupt capacitive
current without restriking.
Circuit Breakers ◾ 341
Moving
member Contacts Arcing
horn
Fixed
Arc chamber
Gas chamber
outlet
13.23.1 Construction
It consists of an interruption chamber which houses fixed and moving con-
tacts and is connected to SF6 gas reservoir (Figure 13.15). When the break-
ers contacts open, the valve mechanism permits a high pressure SF6 gas
from the reservoir to flow toward the interruption chamber.
The fixed contact is a hollow cylindrical current carrying contact fitted
with an arc horn.
The moving contact is also a hollow cylinder with rectangular holes in
the sides to permit the SF6 gas to let out through these holes after flowing
along and across the arc. The tips of fixed contact, moving contact and arc-
ing horn are coated with copper–tungsten arc-resistant material. SF6 gas
being costly, it is reconditioned and reclaimed by suitable auxiliary system
after each operation of the breaker.
13.23.2 Working
When the breaker in closed position of the breaker, the contacts remain
surrounded by SF6 gas at a pressure of about 2.8 bar. As the breaker oper-
ates, the moving contact is pulled apart and an arc is struck between the
contacts. The movement of the moving contact is synchronized with
the opening of a valve which permits SF6 gas at 14 kg/cm2 pressure from
the reservoir to the arc interruption chamber. The high pressure flow of
SF6 rapidly absorbs the free electrons in the arc path to form immobile
negative ions which are ineffective as charge carriers. The result is that the
342 ◾ Elements of Power Systems
Disadvantages:
13.24 HIGH-VOLTAGE DC CB
In AC circuit, current passes through natural current zeros, and hence it
is possible to design AC CB to interrupt large current. This feature is not
available in DC. If a high current is suppressed abruptly in DC, a very
high-transient voltage appears across the contacts of the CBs. Therefore,
in DC CB, some external circuit have to be provided to bring down the
current from full valve to zero, smoothing without suppressing it abruptly.
The additional circuit creates artificial current zeros which are utilized for
arc interruption as shown in Figure 13.16.
A schematic diagram of high-voltage DC (HVDC) CB is shown in Figure
13.17. HVDC CB consists of a main CB (MCB) and a circuit to produce
artificial current zero and to suppress transient voltage. MCB may either be
an SF6 or vacuum CB. R and C are connected in parallel with the MCB to
reduce dv/dt after the final current zero. L is a saturable reactor in series with
the MCB. It is used to reduce di/dt before current zero. CpLp are connected
Circuit Breakers ◾ 343
Current
Idc
Time
L MCB
Cp Lp S
in parallel to produce artificial current zero after the separator of the con-
tacts in the MCB. A nonlinear resistor is used to suppress the transient over-
voltage which may be produce across the contacts of the MCB.
Switch S, which is a triggered vacuum gap, is switched immediately after
the opening of the contacts of the main CB. The capacitor Cp is precharged
in the direction as shown in figure when S is closed, the precharged capac-
itor Cp is discharges through the main CB and sends a current in opposi-
tion to the MCB. This will force the main circuit current to become zero
with a few oscillations. The arc is interrupted at a current zero.
WORKED EXAMPLES
EXAMPLE 13.1
A CB interrupts the magnetizing current of a 50-MVA t ransformer
at 110 kV. The magnetizing current of the transformer is 6% of the
full load current. Determine the maximum voltage which may
appear across the gap of the breaker when the magnetizing current
is interrupted at 50% of its peak value. The stray capacitance is 2000
μF. The inductance is 25 H.
344 ◾ Elements of Power Systems
Solution
50 × 106
The full load current of the transformer = = 262.43A
3 × 110 × 103
6
Magnetizing current = × 262.43 = 15.75 A
100
1 2 1
Li = CV 2
2 2
1 1
× 25 × (11.13)2 = × 2000 × 10−6 V 2
2 2
V = 1.244 kV
EXAMPLE 13.2
For a 110 kV system, the reactance and capacitance up to the location
of the CB is 2 Ω and 0.012 μF, respectively. Calculate the following:
Solution
2
L=
1. = 6.36 mH = 0.00636H
2π × 50
1 1
fn = = = 18.218 kHz
2π LC 2π 0.00636 × 0.012 × 10−6
3.
The maximum value of RRRV = wnVm
110
= 2πf n × × 2 × 1000
3
132
= 2π × 18.218 × 1000 ×
3
× 2 × 1000 V/s
= 20.56 kV/µs
EXAMPLE 13.3
In a short-circuit test on a CB, the following readings were obtained
on single frequency transient:
1. Time to reach the peak restriking voltage, 60 μs.
2. The peak restriking voltage, 110 kV
Determine the average RRRV and frequency of oscillation.
Solution
Peak restriking voltage
Average RRRV =
Time to reach peak value
110 kV
= = 1.83 kV/µs = 1.83 × 106 kV/s
60 µs
1
fn =
2 × Time to reach peak value
1
= = 8.33 kHz
2 × 60 × 10−6
EXAMPLE 13.4
In a 132 kV system, the reactance and capacitance up to the location
of CB is 6 Ω and 0.020 µF, respectively. A resistance of 500 Ω is con-
nected across the contacts of the CB determine the following:
Solution
XL 6
L= = = 0.019 H
2πf 2π50
1 1
Natural frequency of oscillation =
1.
2π LC
1
=
2π 0.019 × 0.020 × 10−6
= 8.143 kHz
2. Frequency of damped oscillation,
1 1 1
f = −
2π LC 4c 2 R2
= 1.825 kHz
1 L
R= = 487.34 Ω
2 C
1
× 8.14 kHz = 2035 Hz
4
1 1 1
2035 = −
2π LC 4c 2 R2
R = 503.22 Ω
EXERCISES
14.1 INTRODUCTION
Relay is a device which is used to sense fault. It sends information to the cir-
cuit breaker (CB), which interrupts the faulty circuit as early as possible (gen-
erally within two or three cycles). If the fault exists for a long time, it results in
Speed. The faulty part of the system should be isolated within a mini-
1.
mum possible time after the occurrence of a fault. If a particular type
of fault is allowed to exist in the system for a abnormally long time,
it may result more faults in addition to the existing one. So the speed
of the protective system should be reasonably high. The operating
349
350 ◾ Elements of Power Systems
1. Electromechanical
2. Static relay
3. Numerical relay
1. Electromagnetic relays
2. Thermal relays
According to the speed of operation relay also can be classified into four
categories:
1. Instantaneous relay
1. Under voltage
2. Overcurrent
5. Differential relay
6. Distant relay
352 ◾ Elements of Power Systems
relay may be instantaneous or may have a time lag and may operate
within large limits of the actuating quantity.
14. Seal-in-relay. This is a kind of an auxiliary relay. It is energized by the
contacts of the main relay. Its contacts are placed in parallel with that
of the main relay and designed to relieve the contacts of the main
relay from their current carrying duty. The seal-in contacts are usu-
ally heavier in comparison with the main relay.
15. Backup relay. A backup relay operates after a slight delay, if the main
relay fails to operate.
16. Flag or target. Flag is a device that gives visual indication whether a
relay has operated or not.
Ires = IA + IB + IC
1 3 5 8 10 12
2 4 6 9 11 13
Generator
Low-voltage Power High-voltage Transmission High-voltage
protection transformer switchgear line protection switchgear
switchgear
protection protection protection protection
Zone B
Zone A
X
C
ϕs To actuating
Disk ϕu
Shading quantity source
ring
Upper magnet
I1 Primary
Secondary
I2 ϕ1
To trip
circuit
ϕ2
Lower magnet
The fluxes induce current iϕ1 and current iϕ2 in the aluminum disk. The
direction of this current will be according to left hand rule.
Now assuming the self-inductance of the disk being negligible, the disk
current will be in phase with their voltage:
Different Types of Relays ◾ 359
dφ1
iφ1 ∝
dt
iφ1 ∝
(
d |φ1| sin ωt )
dt
The fluxes interacting with current produce forces with direction indi-
cated in Figure 14.5 above.
The net force,
F = |F2 − F1| ∝ (|φ2 | sin (ωt + θ) ⋅ |φ1| cos ωt − |φ1| sin ωt ⋅ |φ2 | cos(ωt + θ)
∝ |φ1||φ2 |[sin (ωt + θ) cos ωt − sin ωt cos(ωt + θ)]
∝ |φ1||φ2 | sin θ
The greater the phase angle θ between the fluxes, the greater is the net
force applied to the disk. Obviously, the maximum force will be produced,
when the two fluxes are 90° out of phase.
ϕ2 ϕ1
ϕ2 ϕ1
i2
i1
i2 i1 i2
F2 F1
i1
14.8.1.1.2 Induction Cup Relay The induction cup relay (Figure 14.6) may
have two, four, or more number of poles. These poles are energized by the
current from CT. There is a stationary iron core and the center over which
a hollow metallic cup (rotor conductor) is placed. This cup is free to rotate.
It just resembles an induction motor. By the method of induction eddy
current are produced in metallic cup. These current interact with the flux
produced to avoid continuous rotation. A control spring is attached to the
spindle of rotating cup. The rotating cup carries an arm that closes the
contact of trip circuit.
The basic theory is same for the disk relay and cup relay. In both cases,
the net torque varies as ϕ1 ϕ2 sin θ. But the cup relays are more efficient
torque producer and hence they are faster. A modern induction cup relay
may have an operating time in the order of 0.01 s.
14.8.1.2.1 Attracted Armature Type These are simplest type of relays shown
in Figure 14.7. These relays have a coil or an electromagnet energized by
coil. The coil is energized by operating quantity which may be propor-
tional to circuit current or voltage. A plunger or armature is subjected
to the action of magnetic field produced by operating quantity. It is basi-
cally a single actuating quantity relay. Attracted armature relay responds
to both AC and DC because torque is proportional to I2. These relays are
fast relays. They have fast operation and fast reset because of small length
Rotor
To trip circuit
S1
Stationary core
S2
To trip
C circuit
of travel and light moving parts. They are described as instantaneous but
their operating time does vary with current. Slow operating and reset-
ting time can be obtained by decaying of flux in the magnetic circuit by
fitting a Cu ring around the magnet. The eddy current produced in the
ring opposes the very cause as per Lenz’s law so effective flux is reduced.
Operating time may be as slow as 0.1 s and resetting time may be as slow
as 0.5 s. On the other hand, very high operating speed is possible. A mod-
ern relay has an operating time of 0.5 ms. As fault current increases oper-
ating time decreases, so they have the inverse relationship which leads to a
hyperbolic curve (Figure 14.8).
The only disadvantage of this type of relays is that they are so fast that
they can operate even in transient state. VA burden depends upon their
construction. For a typical relay, it is in order of 0.2–0.6 VA. These relay
are compact, robust, and reliable.
Operating Principle: The electromagnetic force exerted on the moving
elements is proportional to the square of the operating current.
Operating time
Pickup
value
O A Current
To trip
circuit
Electromagnet Armature
F = K1 I 2 − K 2
To trip
circuit
Iron
plunger
To trip
circuit
N S Spring
14.8.1.2.2 Balanced Beam Relay Figure 14.12 shows a balance beam relay.
This type of balance beam relay consists of a horizontal beam pivoted cen-
trally with one electromagnet attached to either side. The beam remains in
horizontal position till the operating force become more than restraining
force. The beam is just given a slight mechanical bias by means of spring
such that in normal condition the contacts are open. When operating,
torque increases the beam tilts and the contacts closes.
Operating Principle: Neglecting spring effect, the net torque
T = K1 I 2 − K 2 I 22
Iron
armature
To
trip Spring
circuit
Fixed
coil
I1 K2
= = Constant
I2 K1
These relays are fast and instantaneous. It has the time in the order of
one cycle. Its VA burden varies from 0.2 to 0.6 VA.
Bimetallic
strip
Heater coil
(c)
To trip
circuit
Heating Unimetallic
element strip
FIGURE 14.13 (a) Bimetallic thermal relay. (b) Bimetallic spiral type thermal
relay. (c) Unimetallic thermal relay.
0.14
t=
(I − 1)
0.02
b
Operating time
Inverse-time characteristic
a Definite-time characteristic
Pickup value
Actuating quantity
k
t=
(I n − 1)
13.5
t=
(I − 1)
80
t=
(I − 1)
2
These types of relays are very suitable for the protection of machines
against overheating, protection of alternators, power transformers, earth-
ing transformers, expensive cables, and railway trolley wires. They have
highest selectivity.
To relay
operating
coil
associated and represented the value above which the disk commences to
rotate and finally closes the trip circuit.
For example, let current setting is at 125%. If the relay fed from the CT
of ratio 200/5, then pickup current will be 1.25 × 5 = 6.25 A.
Secondary current of CT
PSM =
Relay current setting
Actual fault current of CT primary
=
Relay current setting × CT ratio
Figure 14.16 shows the curve between time of operation and PSM of a
typical relay.
12
10
8
Operating time (s)
0 2 4 6 8 10 12 14 16 18 20
PSM
0.4
0.6
Time
0.2 multiplier
0.8
0 1.0
A B C
Time 1.5 s 1s
0.5 s
Time characteristic
A B C
80%
relay at A should trip for fault A and B. The relay at C should trip for
fault beyond C.
The ideal operation is not achieved due to the following reasons:
a. The relay at A is not able to differentiate between faults very close
to B which may be on either side of B. If a fault in the section BC
is very close to the section B, the relay at A understands that it
is in section AB. This happens due to the fact that there is very
little difference in fault current if a fault occurs at the end of the
section AB or in the beginning of the section BC.
b. The magnitude of the current cannot be accurately determined,
as all the circuit parameters may not be known.
Consequently to obtain proper discrimination, relays are set to
protect only a part of the feeder; usually about 80%. Since this scheme
cannot protect the entire feeder, this system is not used along. It may
be used in conjunction with IDMT (Figure 14.20).
The advantage of this system as compared to the time graded
scheme is that the operating time is less near the power source.
Time
A B C
T = φ1φ2 sinθ
To trip
circuit (b)
From PT
V
ϕ2
ϕ
θ
I (or I1)
I2
Current
ϕ1 coil
From CT
On the other hand, I1 is the load current coming from CT secondary lags
V by an angle ϕ (Figure 14.21b). Therefore,
θ = (90° − φ)
T = I1I 2 sin (90° − φ) ∝ I1I 2 cos φ ∝ VI cos φ
(a) (b)
–I Current coil
For normal power flow
–ve torque
V
ϕ
For reverse V Voltage Loads
power flow coil
I +ve torque
FIGURE 14.22 (a) Phasor diagram for directional relay. (b) Connection of cur-
rent coil for reverse power relay.
374 ◾ Elements of Power Systems
Potential coil
From PT
Directional
1 element
2
Current
coil
From CT
Overcurrent element
(nondirectional
To trip
element)
circuit
A C
Load
B D
relay. At other end of the feeders (at C and D), directional overcurrent
relays are required. The arrow marks for the directional relay placed at C
and D indicate that the relay will operate if the current flows in the direc-
tion shown by the arrow. If a fault current occurs at F, the directional relay
at D trip, as the direction of the current is reversed. The relay at C, does
not trip, as current flows in the normal direction. The relay at B trips for
a fault at F. Thus the faulty feeder is isolated and the supply of the healthy
feeder is maintained. For faults at feeders, the direction of current at A
and B does not change and hence relays used at A and B are nondirec-
tional and also current graded. In other arrangement, if nondirectional
relays are used at C and D, then healthy feeder will also be tripped which
is highly undesirable.
B B′
0.1 1.1
Cu
1.6 lt rre 0.6
u nt
Fa
A C
Infeed
A′ C′
Fa t F1
ul n
1.6 t rre 0.6
F
2
Cu
0.1 1.1
D D′
Relays used in earth fault protection are known as earth fault relays. The
PSM of earth fault relays varies from 20% to 80% of the CT. These relays
are highly sensitive. Figure 14.26a shows current in the secondary of CTs
of different phases. Earth fault relays are mainly energized by the residual
current in a three-phase system, that is, (IA + IB + IC), which is zero under
balanced condition. But in earth fault condition, this current will have a
value. If this value is higher than the pickup value of the relay then it oper-
ates. Theoretically its current setting may be at any value above zero. But in
practical cases, it is normally 20%–30% PSM. The manufacturer provides
a range of plug settings for earth fault relay from 20% to 80% of the CT
secondary rating in steps of 10%.
The magnitude of the earth fault current depends on the fault imped-
ance. In case of earth fault, the fault impedance depends on the system
parameter and on the type of the neutral earthing. The neutral may be
solidly grounded or grounded through resistance and reactance. The
fault impedance for earth faults is much higher than that for phase faults.
Hence, the earth fault current is low compared to phase fault current. An
earth fault relay is independent of load current. Its setting is below normal
load current.
Figure 14.26b and c show an earth fault relay used for the transformer
and alternator, respectively. When an earth fault occurs, zero sequence
current flows through the neutral. This current is actually responsible for
actuating the relay. Figure 14.26d shows the connection of an earth fault
relay using a special type of CT, known as core balance CT or ring CT,
which encircles the three-phase conductor.
Different Types of Relays ◾ 377
(a) (b) A
CTs
A
ia
B
ib
C
ic B
R C
CT R
(c)
Ring CT
A
B
C
1. Impedance relays
2. Reactance relays
3. Mho relays
4. Angle impedance relays
5. Quadrilateral relays
T = K1I 2 − K 2V 2 − K 3
where K1, K2, and K3 are constants, K3 being the torque due to the control
spring effect. Neglecting the spring effect, we have
T = K1I 2 − K 2V 2
For the operation of the relay, the following operation should be satisfied.
K1 I 2 > K 2V 2
V2 K
or < 1
I2 K2
V where K is a constant
or < K
I
or Z < K
Different Types of Relays ◾ 379
14.21.2 Characteristic
The characteristic of impedance relay can be shown in Figure 14.27a, in
terms of voltage and current at the relay location. The curve is slightly
bent due to the control spring effect. The R-X diagram (Figure 14.27b) of
the impedance relay is also shown below. Here Z = K represents a circle
and Z < K indicates the area within the circle. It is the operating zone of
the relay. The radius of the circle is setting of the relay. Here ϕ is the phase
angle between V and I. The operating time is constant, irrespective of the
fault location within the protected section.
(a) (b)
x
+ve torque Operating
region characteristic z
Block
I –ve torque region
ϕ
Trip R
Z3
+ve torque
III zone Z2
t3
II zone Z1 t
t1 2
I zone α
–ve torque
Directional
relay
T = K1 I 2 − K 2VI cos(θ − α) − K 3
where T is the torque, V is the voltage, I is the current, K1, K2 are the con-
stants, and K3 is the spring constant.
K1I2 represents the characteristic of overcurrent relay, and K2VI sin θ
represents the characteristic of directional element.
At balance point
K1 I 2 = K 2VI sin θ + K 3
Different Types of Relays ◾ 381
V K
K1 = K 2 sinθ + 23
I I
or
V K K
sin θ = Z sin θ = 1 − 3 2
I K2 K2I
K1
X= = Constant
K2
+ve torque +X
Operating
characteristic
–ve torque
–R +R
–X
due to the fact that it has more stable swings than reactance or impedance
relay.
This relay has a voltage restraining element that opposes the directional
element. The operation of this relay is same as that of impedance type
distance relay but with a difference that no separate directional unit is
required because mho units are inherently directional.
The torque equation is given as
T = K1VI cos(θ − α) − K 2V 2 − K 3
At balance point:
K 2V 2 = K1VI cos(θ − α) − K 3
V K K3
= Z = 1 cos(θ − α) −
I K2 K 2VI
K1
Z= cos(θ − α)
K2
+X
+ve torque
area
–ve torque
area
α
90º
+R
–R
–X
If both the current and voltage winding are employed, torque devel-
oped by the interaction between fluxes is
= K 3VI cos(θ − α)
where θ is the angle between V and I, and α is the value of torque angle
(known as relay maximum torque angle). It is the design control of the relay.
Where all elements are present, the torque will be produce by all the
three cases, so that the total torque produce in general case is
T = K1 I 2 + K 2V 2 + K 3VI cos(θ − α) + K 4
where K1, K2, K3 are the tap settings or constants of I and V, and K4 is the
mechanical constraint due to a spring or gravity.
By assigning plus or minus sign to some of the terms and letting others
be zero and sometime adding some terms having a combination of volt-
age and current, the operating characteristics of all types of relays can be
obtained.
For example, for overcurrent relay K2 = 0, K3 = 0 and the spring torque
will be K4. Similarly for directional relay K1 = 0, K2 = 0.
element exceeds a pre determined value. Most of the differential relays are
of current differential types.
The following are the various type of differential relays:
CT CT
I1 I2
To load
i1 i2
Operating coil of
overcurrent relay
i1
i2
I1 CT CT I2
i1 i2
O = Operating coil
R = Restraining coil
O i1 – i2
i1 i2
in the form of its fractional relation to the current following through the
protected section. It is essentially an overcurrent balanced beam type relay
with an additional restraining coil. The restraining coil produce a bias
force in the opposite direction to the operating force.
Under normal and through conditions, the bias force due to restrain-
ing coil is greater than the operating force therefore the relay remains
inoperative.
When an internal fault occurs, the operating force exceeds the bias
force and consequently the trip contacts are closed to open the CB.
The differential current in the operating coil O is (i1 − i2), while the cur-
rent in the restraining coil R is ((i1 + i2)/2), since the operating coil is con-
nected to the midpoint of the restraining coil. The number of turns in the
restraining coil is Nr, so the total ampere turns are ((i1Nr/2) + (i2Nr/2)).
Now the ampere turns of the operating coil, (AT)o = No(i1 − i2).
Neglecting spring restraint, the relay will operate when
( AT )o > ( AT )r
i + i
N o (i1 − i2 ) > N r 1 2
2
or
N r i1 + i2
(i1 − i2 ) >
N o 2
∴ io > Kir
Thus, at the threshold of operation of the relay, the ratio of the dif-
ferential operating current (io) to the restraining current (ir) is a fixed
386 ◾ Elements of Power Systems
Alternator
I1 winding I2
To load
e1 e2
Relay operating
coil
CT Feeder CT
Pilot wires
WORKED EXAMPLES
EXAMPLE 14.1
The current setting of an IDMT relay is 5 A. The relay has a plug set-
ting of 125% and the TMS of 0.6. The CT ratio is 400/5. Determine
the operating time of the relay for a fault current 4000 A. At TMS = 1,
operating time at various PSH are given in Table 14.1.
Solution
Secondary current
CT ratio =
Relay current setting
primary current)) / CT ratio
(Fault current(p
=
Relay current settings
4000/80
= =8
6.25
The operating time from the given table at PSM 8 is 3 s with
TMS = 1.
Therefore, with PSM = 8, TMS = 0.6, operating time top = 0.6 ×
3 = 1.8 s.
EXAMPLE 14.2
A 20-MVA transformer, which may be called upon to operate at 25%
overload, feeds 11-kV bus bars through a CB; other CB supply outgo-
ing feeders. The transformer CB is equipped with 1000/5 A CTs and
the feeder CBs with 500/5 A CTs and all sets of CTs feed induction-
type overcurrent relays. The relays on the feeder CBs have a 125%
plug seeting and a 0.4 time setting. If a three-phase fault current of
7500 A flows from the transformer to one of the feeders, find the
operating time of the feeder relay, the minimum plug setting of the
transformer relay, and its time setting assuming a discriminative
time margin of 0.5 s. The time–current characteristic of the relays is
same as shown in Figure 14.16.
Solution
1. Feeder:
5
Secondary current = 7500 × = 75 A
500
Secondary current 75
PSM = = = 12
Relay current setting 6.25
5
Secondary current = 1312 × = 6.56 A
1000
6.56
PSM =
PS × 5
5
Secondary fault current = 7500 × = 37.5 A
1000
The operating time from the curve in figure at PSM of 5 and TMS
of 1 = 4.7 s. But,
EXERCISES
Protection of Alternators
and Transformers
15.1 INTRODUCTION
The modern power system comprises of several elements that include
alternators, transformers, induction motors, bus bar, transmission lines,
and other equipment. It is suitable and necessary to protect each element
from a mixture of fault conditions. The protective relays can be produc-
tively applied to detect the unlawful conduct of any circuit element and
initiate disciplinary measures. As a matter of convenience, this chapter
deals with the protection of alternator and transformers only.
15.2 PROTECTION OF ALTERNATORS
The generator or alternator is the most important and costly equipment
of the power system. It is subjected to most number of faults and the
nature of the faults is most severe. So the protection of alternator is com-
plex and elaborate. A modern generator is provided with the following
protections:
1. Stator protection:
a. Percentage differential protection
b. Protection against stator inter-turn faults
c. Stator overheating protection
393
394 ◾ Elements of Power Systems
2. Rotor protection:
a. Field ground fault protection
b. Loss of excitation protection
c. Protection against rotor overheating because of unbalanced 3ϕ
stator current
3. Miscellaneous:
a. Overvoltage protection
b. Overspeed protection
c. Protection against motoring
d. Protection against vibration
e. Bearing overheating protection
f. Protection against auxiliary failure
g. Protection against voltage regulator failure
15.3 STATOR PROTECTION
15.3.1 Percentage Differential Protection
This protection is used for the generators above 1 MW. It protects genera-
tors against internal winding faults, that is, phase-to-phase and phase-to-
ground faults. This is also called bias differential protection. The polarities
of the secondary voltages of current transformers (CTs) at a particular
moment for an external fault are shown in Figure 15.1a. This polarity is
also true for normal direction of current flow in healthy condition.
In the operating coil, the current sent by the upper CT is cancelled by
the current sent by the lower CT and the relay does not operate. For an
internal fault, the polarity of the secondary voltage of the upper CT is
reversed, as shown in Figure 15.1b, in that particular phase affected by the
fault. Now, the operating coil carries the sum of the current sent by the
upper CT and the lower CT, it operates and trips the circuit breaker (CB).
This protection does not respond to external faults and overloads.
This protection is also known as circulating current protection or
Merz–Price protection.
Protection of Alternators and Transformers ◾ 395
(a)
ic
+ +
CTs + ia Ib
– – –
ia
CB ia′
Ic Ib Bias coil
Ia
+ + + Operating
CTs – ia′ coil
ib′ ic′
–
–
(b)
IC IB IA ic
+ +
CTs – ib
– – + ia
ia
CB ia′
Restraining
IC IB coil
IA2
+ + + ia′ Operating
CTs – ib′ coil
– ic′
–
FIGURE 15.1 (a) Percentage of differential protection for external fault condi-
tion (instantaneous current directions shown for external fault condition). (b)
Percentage of differential protection for generator (instantaneous current direc-
tions shown for internal fault condition).
396 ◾ Elements of Power Systems
A B C
R
R
R
CTs
CTs O O O
Generator
windings
AC supply
Polarizing coil
of the relay
Series
resistor
Operating coil
of the relay
In one method, the inlet and outlet temperature of the cooling medium
which may be hydrogen/water are compared for detecting overheating.
In the other method, the temperature sensing elements are embedded in
the stator slots to sense the temperature. Figure 15.3 shows a stator over-
heating relaying scheme. When the temperature exceeds a certain pres-
ent maximum temperature limit, the relay sounds an alarm. The scheme
employs a temperature detector limit, relay, and Wheatstone bridge for
the purpose. The temperature sensing elements may either be thermistors,
thermocouples, or resistance temperature indicators. They are embedded
in the stator slots at different locations. These elements are connected to a
multiway selector switch which checks each one in turn for a period long
enough to operate an alarm relay.
For small generators, a bimetallic strip heated by the secondary current
of the CT is placed in the stator circuit. This relay will not operate for the
failure of cooling system.
15.4 ROTOR PROTECTION
15.4.1 Field Ground-Fault Protection
As the field circuit is operated undergrounded, a single ground fault does
not affect the operation of the generator or cause any damage. However,
a single rotor fault to earth increases the stress to the ground in the field
when stator transient induces an extra voltage in the field winding. Thus,
398 ◾ Elements of Power Systems
Field
Gen
Auxiliary
AC supply
Sensitive relay
Trip
iron. The rotors of salient pole generators are not overheated because they
have damper windings which carry induced current. The stators of both
salient and non-salient pole generators are overheated due to wattles cur-
rent drawn by the machines as magnetizing current from the system. The
stator overheating does not occur as quickly as rotor overheating. A large
machine may upset the system stability because it draws reactive power
from the system when it runs as an induction generator, whereas it supplies
reactive power when it runs as a generator. A machine provided with a
quick-acting automatic voltage regulator and connected to a very large sys-
tem may run for several minutes as an induction generator without harm.
Field failure may be caused by the failure of excitation. A protective
scheme employing offset mho or directional impedance relay.
I 22t = K
Generator
windings CTs
A
CB
B
Negative
sequence filter
Overcurrent
relay
15.5 MISCELLANEOUS
15.5.1 Overvoltage Protection
Overvoltage protection may be caused by a defective voltage regulator or it
may occur due to sudden loss of electrical load on generator. When a load
is lost, there is an increase in speed and hence the voltage also increases.
Overvoltage relays are provided.
15.5.2 Overspeed
A turbo generator is provided with a mechanical overspeed device. The
speed governor normally controls its speed. It is designed to prevent
any speed rise even with 100% load rejection. An emergency centrifu-
gal overspeed device is also incorporated to trip emergency steam valves
when the speed exceeds 110%.
Protection of Alternators and Transformers ◾ 401
15.5.4 Field Suppression
When a fault occurs in the generator winding the CB trips and the gen-
erators is isolated from the system. However, the generator still continues
to feed the fault as long as the excitation is maintained, and the damage
increases.
Therefore, it is desirable to suppress the field as quickly as possible. The
field cannot be destroyed immediately. The energy associated with the flux
must be dissipated into an external device. To achieve this, the field wind-
ing is connected to a discharging resistor to absorb the stored energy. The
discharged resistor is connected in parallel with the field winding before
opening the field CB.
15.6 TRANSFORMER PROTECTION
Transformer faults may be classified as follows:
1. External faults
2. Internal faults
15.6.1 External Faults
In case of external faults, the transformer must be disconnected if other
protective devices meant to operate for such faults, fails to operate within
a predetermined time. For external faults, time-graded overcurrent relays
are employed as backup protection. Also in case of sustained overload
conditions, the transformer should not be allowed to operate for long
duration. Thermal relays are used to detect overload condition and give
an alarm.
15.6.2 Internal Faults
Internal faults are classified into two groups.
402 ◾ Elements of Power Systems
O O O
R
R R
the current in the operating coil from CTs of both sides is in the same
direction and causes the operation of the relay. In the star side of the trans-
former, CTs are connected in delta or vice versa.
15.8 OVERHEATING PROTECTION
Overheating of transformer is usually caused by sustained overloads or
short circuits and very occasionally by the failure of the cooling system.
The relay protection is also not provided against this contingency, and
thermal accessories are generally used to sound an alarm.
15.10 OVERCURRENT PROTECTION
Overcurrent relays are used for the protection of transformers of rating
100 kVA and below 5 MVA. An earth fault tripping element is also pro-
vided with overcurrent protection. For small transformers, OC relays are
used for both overload and fault protection. An extremely inverse relay
is desirable for overload for light faults, with instantaneous OC relay for
heavy faults.
15.11 OVERFLUXING PROTECTION
The magnetic flux increases when voltage increases. This results in
increased iron loss and magnetizing current. The core and core bolts
get heated and the lamination insulation is affected. Protection against
overfluxing is required where overfluxing due to sustained overvoltage
can occur. The reduction in frequency also increases the flux density and
consequently, it has similar effects as those due to overvoltage.
The expression of flux in a transformer is given by
E
φ=K
f
404 ◾ Elements of Power Systems
Power transformer
Supply
Load
Residual
overcurrent
relay Restricted earth
fault relay
where ϕ is the flux, f is the frequency, E is the applied voltage, and K is the
constant. Therefore, to control the flux, the ratio E/f is controlled.
Electronic circuits with suitable relays are available to measure E/f ratio.
Usually 10% overfluxing can be allowed without damage. If E/f exceeds
1:1, overfluxing protection operates. Overfluxing does not require high-
speed tripping and hence instantaneous operation is undesirable when
momentary disturbances occur.
15.13 BUCHHOLZ RELAY
Buchholz relay is a gas-actuated relay installed in oil-immersed trans-
formers for protection against all kinds of faults. Named after its inventor,
Protection of Alternators and Transformers ◾ 405
Conservator
Buchholz
relay
9.5°
Transformer
main tank
Release
To cock
alarm circuit Float
Mercury
switch
Hinged To
point trip circuit
Mercury
switch
From To
transformer conservator
main tank
the Buchholz relay and in doing so tilts the flap to close the contacts of
mercury switch. This completes the trip circuit to open the CB controlling
the transformer.
Advantages:
Disadvantages:
G
CB
T
O
WORKED EXAMPLES
EXAMPLE 15.1
The neutral point of a three-phase, 20-MVA, 11-kV alternator is earthed
through a resistance of 5 Ω. The relay is set to operate when there is an
out of balance current of 1.5 A. The CTs have a ratio of 1000/5. Deter
mine (1) the percentage of protected winding, and (2) value of earthing
resistance required to protect 90% of the winding (Figure 15.11).
R
X%
B Y
Solution
11
EMF induced = x % × kV
3
x 11 × 103
= ×
100 3
110 x
=
3
110 x / 3
Fault current through it =
R
110 x / 3 22 x
= = A
5 3
22 x
= 300
3
x = 23.6%
11,000 1
∴ EMF induced in 10% winding = ×
3 10
1100
= V
3
Protection of Alternators and Transformers ◾ 409
When the fault current becomes 300 A, the relay will trip.
1100/ 3
∴ = 300
R
R = 2.12 Ω
EXAMPLE 15.2
A 3-ϕ transformer of 33,000/6600 line volts is connected in star/
delta. The protective transformers on LV side have ratio 300/5. What
should be the CT ratio on HV side?
Solution
VL
Vph =
3
33,000
= V
3
= 19,052 V
Vph = VL = 6600 V
n1 V1 19,052
= = = 2.887
n2 V2 6600
I1 I1 I n
= = 1 = 2
I 2 300/5 60 n1
60
I1 = = 20.8 A
2.887
EXERCISES
Traveling Wave
16.1 INTRODUCTION
A transmission line is a distributed parameter circuit with the unique
ability to support traveling waves of voltage and current. Finite velocity
of electromagnetic field propagation is present in a circuit which have dis-
tributed parameters. In such a circuit, the changes in voltage and current
do not occur simultaneously in all parts of the circuit but spread out in
the form of traveling waves and surges. When a transmission line is sud-
denly connected to a voltage source by closing a switch, the whole of the
line is not energized all at once. This is due to the presence of distributed
constants (inductance and capacitance in a loss free line). When a switch
S is closed, the inductance L1 acts as an open circuit and capacitance C1
as short circuit instantaneously. The same instant next section cannot
be charged because the voltage across capacitor C1 is zero. So unless the
capacitor C1 is charged to the some value whatsoever, charging of the
capacitor C2 through L2 is not possible which, of course, will take some
finite time. The same line of reasoning applies to the third section, fault
section, and hence along. Thus, it has been ascertained that the potential
at the successive section builds up step by step. This gradual buildup of
potential over the transmission line conductor can be regarded, as though
a voltage wave is traveling from one terminal to another final stage, and
the gradual loading of the capacitances is due to associated current wave.
The current wave, which is accompanied by a voltage wave, sets up a mag-
netic field in the surrounding space. At junction and terminations, these
surges undergo reflections and refractions. In an extensive network with
many lines and junctions, the number of traveling waves initiated by a
411
412 ◾ Elements of Power Systems
single incident wave will mushroom at a considerable rate as the wave split
and multiple reflections occur. It is rightful that the entire energy of the
resulting waves cannot exceed the energy of the incident wave. However,
it is possible for the voltage buildup at certain junctions due to reinforc-
ing action of several waves. For a perfect study of the phenomenon, the
use of Bewely lattice diagram or digital data processor is necessary. The
study of traveling wave, therefore, plays an important role in knowing the
voltage and current at all points in a power system. It assists in the design
of insulators, protective equipment, the insularity of the terminal equip-
ment, and overall insulation coordination.
S L1 L2 L3
Load
V C1 C2 C3
Neutral
Suppose that the wave after time t has travelled through a distance x.
Since, we have assumed lossless lines, whatever is the value of voltage and
current waves at the kickoff, they remain same throughout the change of
location. Take a distance dx which is moved by the waves in time dt. The
electrostatic flux is related with the voltage wave and the electromagnetic
flux with the current wave. The electrostatic flux which is equal to the
charge between the conductors of the line up to a distance x given by
q = CVx (16.1)
dq dx
I = = CV (16.2)
dt dt
Here, dx/dt is the velocity of the traveling wave over the line conductor
and is represented by v, then
I = VCv (16.3)
ψ = ILx (16.4)
The voltage is the rate at which the flux linkages link with the
conductor:
dψ dx
V = = IL = ILv (16.5)
dt dt
V LIv LI
= =
I VCv VC
414 ◾ Elements of Power Systems
or
V2 L
=
I 2 C
or
V L
=
I C
L
Zn = (16.6)
C
The expression is the ratio of voltage and current which has the dimen-
sions of impedance and is therefore here designated as surge impedance
of the line. It is also called the natural impedance because this impedance
has nothing to do with the load impedance, but depends only on the line
constant. The value of this impedance is 400–600 Ω for an overhead line
and 40–60 Ω for a cable.
Multiplying Equations 16.3 and 16.5:
VI = CVv × LIv
I = LCv 2
1
v=
LC
d
L = 2 × 10−7 ln H/m
r
2πε
C= F/m
ln(d /r )
Traveling Wave ◾ 415
1
v=
2 × 10 ln(d /r ) ⋅ [(2π × 8.854 × 10−12 )/ ln(d /r )]
−7
= 3 × 10−8 m/s
V = IZ C (16.7)
E
Zc
VT = I T Z (16.8)
VR = − I R Z C (16.9)
The negative sign Equation 16.9 is because of the fact that VR and IR are
traveling in the negative direction of x or backwards on the same line. The
transmitted voltage and a current will be, respectively, the algebraic sum
of incident and reflected voltage and current waves.
VT = V + VR (16.10)
IT = I + IR (16.11)
Substituting the values of I, IR, and IT from Equations 16.7 through 16.9
in Equation 16.11, we have
VT V VR
= − (16.12)
Z ZC ZC
VT V VT − V
= −
Z ZC ZC
or
ZC
VT × + VT = 2V
Z
or
Z
VT 1 + C = 2V
Z
or
2Z
VT = V ⋅ (16.13)
Z + ZC
Traveling Wave ◾ 417
VT = β ⋅ V
Now,
VT 2V 2 IZ C
IT = = = (16.14)
Z Z + ZC Z + ZC
2ZV Z − ZC
VR = VT − V = −V =V ⋅ (16.15)
Z + ZC Z + ZC
Z − ZC
VR = V ⋅ (16.16)
Z + ZC
VR = α ⋅ V
Now,
Z − ZC Z + ZC + Z − ZC 2Z
1+ α = 1+ = = = β (16.17)
Z + ZC Z + ZC Z + ZC
+
V
–
1 2 1 2
LI = Ce
2 2
or
LI 2 = Ce 2
L
e=I = IZ C = V
C
V + V = 2V
As soon as the incident current wave I reaches the open end, the cur-
rent at the open end is zero. That means a current wave of I magnitude
travels back over the transmission line. This means for an open-end line,
a current wave is reflected with negative sign and coefficient of reflection
unity. The variation of current and voltage waves over the line is explained
in Figure 16.4.
After the voltage and current waves are reflected back from the open
end, they reach the source end, the voltage over the line becomes 2V and
the current is zero. The voltage at source end cannot be more than the
source voltage V; therefore, a voltage wave −V and current wave of −I are
Traveling Wave ◾ 419
Voltage Current
T = 0+ V I
T=1 V I
2V
T = 1+ V I
–I
T = 2l 2V
I=0
–V
T = 2l+ V 2V
–I
T = 3l V
–I
T= 3l+ V
I
–V –I
V=0 I=0
T = 4l
reflected back into the line. It can be seen that after the waves have travelled
through a distance of 4l, where l is the length of the line, they would have
wiped out both the current and voltage wave, leaving the line momentarily
in its original state. The above cycle repeats itself.
+
V
–
Energy can never be destroyed but only can be converted from one
to another, that is, electrostatic energy is converted to electromagnetic
energy. So electromagnetic energy increases.
Let i be the increase in current,
1 1
CV 2 = Li 2
2 2
CV 2 = Li 2
V V
i= = =I
L /C ZC
that is, current at short circuit receiving end increases by incident cur-
rent I. As a result the total current at the shorted end, when the current
waves reaches the end is I + I = 2I A.
Therefore, for a short-circuit end, a current wave is reflected back with
positive sign and coefficient of reflection as unity. Since the voltage at
the shorted end is zero, a voltage wave of −V could be considered to have
been reflected back into the line with coefficient of reflection as unity.
The variation of voltage and current waves over the line is explained in
Figure 16.6.
It is seen from above that the voltage wave periodically reduces to
zero after it has travelled through a distance of twice the length of the
line, whereas after each reflection at either end, the current is built
up by an amount V/Z n = I. Theoretically, the reflection will be infi-
nite and t herefore the current will reach infinite value. But practically
in an actual system, the current will be limited by the resistance of the
line.
Voltage Current
T = 0+ V I
T=I V I
I
T = I+ V I 2I
–V
2I
T = 2I V=0
I
T = 2I+ V 3I 2I
3I
T = 3I V
3I 4I
T = 3I+ V
–V
4I
T = 4I V=0
Z2
Z1
Z3
VT = V + VR
V + VR = VT
V V
I = , IR = − R
Z1 Z1
VT V
I T2 = , I T3 = T
Z2 Z3
422 ◾ Elements of Power Systems
I + I R = I T2 + I T3
V VR VT VT
− = +
Z1 Z1 Z2 Z3
V VT − V VT VT
− = +
Z1 Z1 Z2 Z3
2V 1 1 1
= VT + +
Z1 Z
1 Z Z 3
2
2V /Z1
VT =
(1/Z1 ) + (1/Z 2 ) + (1/Z 3 )
WORKED EXAMPLES
EXAMPLE 16.1
An overhead line with surge impedance of 400 Ω is connected in
series with an underground cable having a surge impedance of
100 Ω. If a surge of 50 kV travels from line toward cable, determine
the transmitted voltage wave at junction.
Solution
2Z
Transmitting coefficient, β =
Z + ZC
2Z 2 × 100
Transmitted voltage, VT = V = 50 × = 20 kV
Z + ZC 100 + 400
EXAMPLE 16.2
A surge of 100 kV is traveling in a line of impedance 600 Ω arrives at
a junction with two lines of impedance 800 and 200 Ω. Determine
the transmitted voltage and currents.
Traveling Wave ◾ 423
Solution
In the problem, Z1 = 600 Ω, Z2 = 800 Ω, Z3 = 200 Ω, and V = 100 kV.
2V /Z1
Transmitted voltage, VT =
(1/Z1 ) + (1/Z2 ) + (1/Z3 )
(2 × 100)/600
= = 42.04 kV
(1/600) + (1/800) + (1/200)
VT 42.04 × 1000
I T2 = = = 52.55 A
Z2 800
VT 42.04 × 1000
I T3 = = = 210.2 A
Z3 200
EXAMPLE 16.3
A surge of 20 kV magnitude travels along a lossless cable toward its
junction with two identical lossless overhead transmission lines. The
inductance and capacitance of the cable are 0.4 mH and 0.5 μF/km,
and the same of the overhead transmission lines are 1.5 mH and
0.015 μF/km. Find out the magnitude of voltage at the junction due
to surge.
Solution
2/Z Cable
Transmitted voltage, VT = V
(1/Z L1 ) + (1/Z L 2 ) + (1/Z Cable )
Now,
L 0.4 × 10−3
Z Cable = = = 28.28 Ω
c 0.5 × 10−6
L 1.5 × 10−3
Z L1 = Z L 2 = = = 316.22 Ω
c 0.015 × 10−6
424 ◾ Elements of Power Systems
2/28.28
∴ VT = 20 = 33.93 kV
(2/316.22) + (1/28.28)
EXERCISES
Earthing
17.1 INTRODUCTION
The term “earthing” or “grounding” means connecting the noncurrent-
carrying parts of the electrical equipment or the neutral point of the sup-
ply system to the general mass of earth in such a manner that all times an
immediate discharge of electrical energy takes place without danger. The
neutral grounding is an important aspect of power system design because
the performance of the system in terms of short circuits, stability, protec-
tion, etc., is greatly affected by the condition of the neutral.
1. Equipment grounding
2. System grounding
425
426 ◾ Elements of Power Systems
S Line IL
Re
Metal
230 V enclosure M IL
Neutral Rb
IL
FIGURE 17.1 A person having a body resistance Rb would complete the current path.
Earthing ◾ 427
S Line IL
Re
230 V M
IL Rb
IL Neutral
the switch is inadvertently in series with the neutral rather than the
live wire shown in Figure 17.3, the motor can still be turned on and
off. However, if someone touched the enclosure when the motor is off,
he would receive a severe electric shock. It is because when the motor
is off, the potential of the enclosure rises to that of the live conductor.
Ground wire connected to enclosure. To get rid of this problem, we
3.
install a third wire, called ground wire, between the enclosure and
the system ground as shown in Figure 17.4. The ground wire may be
bare or insulated. If it is insulated, it is colored green.
230 V M IL
S Rb
Neutral
IL
Line IL
Re
230 V M
S IL Rb
Neutral
Ground IL
conductor
FIGURE 17.4 Ground wire, between the enclosure and the system ground.
428 ◾ Elements of Power Systems
Vph
I CR = I CY = I CB =
XC
where Vph is the phase voltage and XC is the reactance due to the capaci-
tance of the line to ground.
R
Y
N
CR CB
CY
(a) (b)
R VYN
ICR
N Y
ICY
ICB
B
ICB ICY
CR CB
CY
VRN ICR VBN
FIGURE 17.6 (a) Three phase system with isolated neutral. (b) Phasor diagram
for isolated neutral system.
Earthing ◾ 429
The capacitive currents ICR, ICY, and ICB are balanced and their resultant
is zero and no current flows to the earth and the potential of neutral is the
same as the ground potential. Phasor diagram as shown in Figure 17.6b.
VRY 3Vph
I CR = =
XCR XC
Similarly,
VBY 3Vph
I CB = =
XCB XC
Now IF is equal to phasor sum of ICR and ICB. Magnitude of ICR and ICB
are equal to angle between them 60°.
FIGURE 17.7 (a) Isolated neutral system with fault on one phase. (b) Phasor
diagram for fault on phase Y.
430 ◾ Elements of Power Systems
60°
I F = 2 I R cos
2
= 2 I R cos 30°
3
= 2I R = 3I R
2
Therefore,
3Vph 3Vph
I F = 3 I CR = 3 × =
XC XC
= 3 × Per-phase capacitive current under normal condition
healthy conductors may rise to five to six times its normal value. The
over voltages in healthy conductors may damage the insulation in
the line.
N Y
When there is a ground fault over any phase, the phase to earth volt-
age of a grounded phase will become zero, but the voltage to earth of the
remaining two healthy phases will be the normal phase voltage as in this
case neutral point will not shift. Under a line-to-ground fault on phase
B, as shown in Figure 17.9a, the neutral and the terminal B are at earth
potential. The phasor diagram for such a condition is shown in Figure
17.9b. The reversed phasor is shown at VB. Capacitive current ICR leads VNR
by 90° and ICY leads VNY by 90°. The resultant capacitive current IC will be
phasor sum of ICR and ICY. It should be noted that in this system, in addition
to capacitive current, the supply source also supplies the fault current IF.
This current will go to the fault point F through the faulty phase and then
return back to supply source through the earth and neutral connection.
The fault current IF lags behind the faulty phase voltage by approximately
90° since the circuit is predominately inductive (due to transformers,
machines, and line inductance). The fault current IF will be in phase oppo-
sition to capacitive current IC. Due to this effect the capacitive current IC
will be faulty neutralized by the large fault current. Therefore, no arcing
ground phenomenon or over voltage condition can occur.
(a) ICR (b) R
R
ICY
N Y
IC
IF
B ICY
ICR ICY 90°
IF IC CR CY ICR
90°
IF
IF B Y
IF
IC IC
FIGURE 17.9 (a) Solidly grounded system with ground fault on one phase. (b)
Phasor diagram for fault on phase B.
Earthing ◾ 433
1. The solid grounding results in heavy earth fault currents. Since the
fault has to be cleared by the circuit breaker, the heavy earth fault
currents may cause the burning of circuit breaker contacts.
2. The increased earth fault current results in greater interference in
neighboring communication line.
FIGURE 17.10 (a) Resistance grounded system with ground fault on one phase.
(b) Phasor diagram for fault on phase B.
N
Y
Reactance B
current. By changing the earthing resistance, the earth fault current can
be changed to obtain the condition similar to that of solid grounding.
This method is not used these days because of the following disadvan-
tages:
FIGURE 17.12 (a) Resonant grounded system with ground fault on one phase. (b)
Phasor diagram for fault on phase B.
436 ◾ Elements of Power Systems
ICR = I CY = 3Vph ωC
Capacitive current
I C = I CR + I CY = 3 × 3Vph ωC = 3Vph ωC
For balance condition,
IL = IC
VP 1
= 3Vph ωC or L =
WL 3ω 2C
WORKED EXAMPLES
EXAMPLE 17.1
Calculate the reactance of arc suppression coil suitable for a 33-kV,
three-phase transmission line having a capacitance to earth of each
conductor as 4.5 μF. Assume supply frequency to be 50 Hz.
Solution
Supply frequency, f = 50 Hz.
Line to earth capacitance, C = 4.5 μF = 4.5 × 10−6 F.
For Peterson coil grounding, reactance XL of the arc suppression
coil should be equal to XC/3, where XC is line to earth capacitive reac-
tance. Therefore, reactance of arc suppression coil is
XC 1 1
XL = = =
3 3ωC 3 × 2πf × C
1
= = 235.8 Ω
3 × 2π × 50 × 4.5 × 10−6
EXAMPLE 17.2
A 66-kV, three-phase, 50-Hz, 100-km transmission line has a
capacitance to earth of 0.03 μF/km per phase. Calculate the induc-
tance and kVA rating of the Peterson coil used for earthing the
above system.
Solution
Supply frequency, f = 50 Hz.
Capacitance of each line to earth, C = 100 × 0.03 = 3 × 10−6 F.
Required inductance of Peterson coil is
1
L=
3ω 2C
1
= = 1.12 H
3 × (2π × 50)2 × 3 × 10−6
Vph 66 × 103 / 3
IF = = = 108.296 A
XL 2π × 50 × 1.12
438 ◾ Elements of Power Systems
VL 66 × 103
Vph = = V
3 3
66 × 103 1
Vph × I F = × 108.296 × = 4126.63 kVA
3 1000
EXAMPLE 17.3
A 33-kV, three-phase, 50-Hz transmission line of 100 km long con-
sists of three conductors of effective diameter 30 mm arranged in a
vertical plane with 3 m spacing and regularly transposed. Find the
inductance and kVA rating of the arc suppression coil in the system.
Solution
Radius of conductor, r = 30/2 = 15 mm = 0.015 m
Conductor spacing, d = 3 m
1 1
L= = = 3.207 H
3ω 2C 3 × (2π × 50)2 × 10.53 × 10−7
Earthing ◾ 439
Vph 33 × 103⁄ 3
IF = = = 18.91 A
X L 2π × 50 × 3.207
33
∴ Rating of the coil = Vph × I F = × 18.91 = 360.29 kVA
3
EXERCISES
Substation
18.1 INTRODUCTION
The modern electrical power system is generated, transmitted, and dis-
tributed in the form of alternating current. The electric power is produced
at the power stations which are located in suitable places, generally quite
away from the consumers. It is delivered to the consumers through a large
network of transmission and distribution. At many places in the line of
the power system, it may be desirable and necessary to change some char-
acteristic (e.g., voltage, AC to DC, frequency, power factor [pf], etc.) of
electric supply. For that, in between the power station and ultimate con-
sumer, a number of transformations and switching stations have to be cre-
ated. These are generally known as substation.
18.2 SUBSTATION
The assembly of apparatus used to change some characteristic (e.g., volt-
age, AC to DC, frequency, pf, etc.) of electric supply is called a substation.
Substations are important part of power system. The continuity of sup-
ply depends to a considerable extent upon the successful operation of sub-
stations. It is, therefore, essential to exercise utmost care while designing
and building a substation. The following are the important points which
must be kept in view while laying out a substation:
Entrance
Ground level
Switchgear
Transformer
11 kV O.H. line
Fuse
Fuse Lightning
Isolator arrester Isolating
400 switch
V
400 V
R R
Y Y Transformer
B B
N N
Transformer OCB
11 kV/400 V LT
OCB
from the consumers in the event of any fault. The pole-mounted substa-
tions are generally used for transformer capacity up to 200 kVA. The fol-
lowing points may be noted about pole-mounted substations:
1. Step-up substation
2. Primary grid substation
3. Secondary substation
4. Distribution substation
Figure 18.3 shows the block diagram of a typical electric supply system,
indicating the position of above types of substations. It may be noted that
it is not necessary that all electric supply schemes include all the stages
shown in the figure. For example, in a certain supply scheme there may
not be secondary substations and in another case, the scheme may be so
small that there are only distribution substations.
Generating
station
(11 kV)
Step up 11/220 kV
substation
Primary grid
substation
220/66 kV
Inter
66/11 kV Secondary connection Secondary 66/11 kV
substation substation
3′ 4′
1 2 3 4
LA
open the circuit breaker in this section and then open the isolators 1
and 2. This procedure will disconnect section II for repairs. After the
repairs has been done, close the isolators 1 and 2 first and then the
circuit breaker.
Circuit breaker. A circuit breaker is equipment which can open
4.
or close a circuit under normal as well as fault conditions. It is so
designed that it can be operated manually (or by remote control)
under normal conditions and automatically under fault conditions.
11 kV Bus bar
Isolator LA
Bus bar
Trip coil
11 kV OCB
CB
CT
CT
F Relay coil
Transformer Transformer
11 kV/400 V 11 kV/400 V
PT PT
Incoming
line
11 kV Outgoing Outgoing Incoming
line line line
400 V 400 V 11 kV
33 kV Bus-section I Bus-section II 33 kV
Isolator
Bus bar
Trip coil
33 kV 33 kV
OCB OCB CB
CT
CT
F Relay coil
33 kV 33 kV
OCB OCB
CT
Trans- Trans-
former LA former
33/11 kV 33/11 kV
PT PT
Incoming
line
33 kV Outgoing Outgoing Incoming
line 11 kV line 11 kV line
33 kV
LA
CT
LA
Bus-coupler
CB
CT
F Relay coil
Transformer
66/11 kV
11 kV line
GO switch
Cable box
Underground
cable
11 kV OCB
50 : 5 CT
To To Bus bar
1 MVA 11 kV/400V
consumers consumers Trip coil
CB
400 V Main 400 V
OCB OCB OCB CT
CT
1200/5
200 : 5 F Relay coil
EXERCISES
1. What is a substation? Name the factors that should be taken care of
while designing and erecting a substation.
2. Discuss the different ways of classifying the substations.
3. Give the comparison of outdoor and indoor substations.
4. What is a transformer substation? What are the different types of
transformer substations? Illustrate your answer with a suitable block
diagram.
5. Draw the layout and schematic connection of a pole-mounted
substation.
6. Draw the layout of a typical underground substation.
7. Write a short note on the substation equipment.
8. What are the different types of bus-bar arrangements used in substa-
tions? Illustrate your answer with suitable diagrams.
9. What are terminal and through substations? What is their purpose
in the power system?
10. Draw the key diagram of a typical 11 kV/400 V indoor substation.
This page intentionally left blank
Chapter 19
19.1 INTRODUCTION
The stability of an interconnected power system is its ability to return
to normal or stable operation after having been subjected to some form
of disturbance. Conversely, instability means a condition denoting loss
of synchronism or falling out of step. Stability considerations have been
recognized as an essential part of power system planning for a long time.
With interconnected systems continually growing in size and extending
over vast geographical regions, it is becoming increasingly more difficult to
maintain synchronism between various parts of a power system. The stabil-
ity problem is concerned with the behavior of synchronous machines after
a disturbance. Under stable conditions the system stays in synchronism.
Synchronous stability may be divided into two main categories depend-
ing upon the magnitude of disturbance.
19.4 SYNCHRONOUS GENERATOR
CONNECTED TO AN INFINITE BUS
Consider a simple system consisting of a synchronous generator connected
to an infinite bus through a network presented by the ABCD parameters
as shown in Figure 19.1.
460 ◾ Elements of Power Systems
Is Ir
Infinite bus
A B
Vs Vr
C D
VS = VS ∠δ, Vr = Vr ∠0°
We have
Vs = AVr + BIr
Vs A V ∠δ A∠α V AVr
Ir = − V = S − V ∠0° = S ∠(δ − β) − ∠(α − β)
B B r B∠β B∠β r B B
Sr = Vr Ir* = Pr + jQr
Vs AVr
I*r = ∠(β − δ) − ∠(β − α)
B B
VsVr AVr2
Pr + jQr = Vr I*r = ∠(β − δ) − ∠(β − α)
B B
VV AVr2
= s r [cos(β − δ) + j sin(β − δ)]− [cos(β − α) + js(β − α)]
B B
VsVr AVr2
Pr = cos(β − δ) − cos(β − α)
B B
VsVr AVr2
Qr = sin(β − δ) − sin(β − α)
B B
Power System Stability ◾ 461
VsVr AVr2
Pr max = − cos(β − α)
B B
*
E∠δ − V ∠0°
S = VI = V
*
j( X d + X l ) (19.1)
Let
Xd + Xl = X
(19.2)
E∠δ V
S =V +j
X ∠90° X
EV V2 EV EV V2
∠(90° − δ) − j = sin δ + j cos δ − j
X X X X X
Xd XI I
Xd XI Infinite
E δ V 0° bus
V 0°
Infinite E δ
bus
EV EV V2
Pe + jQe = sin δ + j cos δ − (19.3)
X X X
EV (19.4)
Pe = sinδ
X
EV V2
Qe = cosδ − (19.5)
X X
EV EV (19.6)
Pe max = sin90° =
X X
Prmax
Generator
action
180° 360°
0 δ
90°
Motor
action
VV
i j
Pij = sinδ ij (19.8)
Xij
where Pij is the active power flow from bus i to bus j, Vi is the voltage at bus
i, Vj is the voltage at bus j, δij is the angle between bus i and bus j with bus
i taken as reference, and Xij is the equivalent transfer reactance between
buses i and j.
The reactive power flow is given by
VV
i j Vij2
Qij = cosδ ij = (19.9)
Xij Xij
XS
(a) XG XS (b) XG
I
Xf
E δ Xf
V 0° E δ V
Xf XS +Xf
E(( X f )/( Xs + X f )V ) EV
Pe = sin δ =
XG + (( Xs X f )/( Xs + X f )) XG (( Xs + X f )/X f ) + Xs
(19.10)
EV
sin δ = sin δ
XG + Xs + (( XG Xs )/X f )
Equation 19.10 gives the power–angle relation for the network configu-
ration, as shown in Figure 19.4a.
Based upon the sign conventions adopted for synchronous generators, the
value of the shaft torque and electromagnetic torque are taken as negative
for motor action.
Let Te be the electromagnetic torque and Ts, the shaft torque. If the
losses are neglected, the difference between the shaft torque and the elec-
tromagnetic torque is equal to the accelerating or deceleration torque. For
a generator, when Ts > Te, then Ta is positive and the rotor accelerates. In
case of synchronous motor Ta is positive only when Te > Ts, since Ts and Te
are both negative.
dθ dδ
= ωs + (19.12)
dt dt
d 2θ d 2δ (19.13)
= 2
dt 2 dt
d 2θ d 2δ (19.14)
α= = 2 elec. rad/s2
dt 2 dt
Power System Stability ◾ 467
Ta = Ts − Te (19.15)
M = Jω (19.16)
Pa = Ps − Pe
But
d2θ d2δ
J = Ta , J = Ta
dt 2 dt 2
d2δ
ωJ = ωTa
dt 2
d2δ
M = Pa = Ps − Pe (19.17)
dt 2
Equation 19.17 gives the relation between the accelerating power and
angular acceleration. It is called the swing equation. It is a nonlinear dif-
ferential equation of the second order. With this differential equation, we
can discuss stability in a quantitative way, because it describes swings in
the power angle δ during transient.
468 ◾ Elements of Power Systems
δ
Unstable
Stable
0 t
Hz, T, the torque in N m, P, the power in watts, and α, the angular accel-
eration of the rotor.
19.11.1 M Constant
Now, j = mr2
1 2
W = Jω
2
2W
M = Jω =
ω
T = Jα
P = ωT = ωJα = Mα
P
M=
α
It is expressed in MJ/MVA.
If W is the stored energy in megajoles. MJ and S is the rating of the
machine in MVA.
470 ◾ Elements of Power Systems
Then
W ωM 2πfM πfM
H = = = = (19.18)
S 2S 2S S
HS
M= MJs/elec.radian (19.19)
πf
HS
M= MJs/elec. degree (19.20)
180 f
HS d 2δ
= Ps − Pe (19.21)
180 f dt 2
HS d 2δ
= Ps pu − Pe pu = Pa pu (19.22)
180 f dt 2
Smach
H syst = H mach
Ssyst
W = W1 + W2 + + Wn (19.23)
Se H e = S1H1 + S2 H 2 + + Sn H n (19.24)
Se = S1 + S2 + + Sn (19.25)
If the base MVA is equal to the combined MVA rating of the individual
machine, that is, Sb = Sr, Equation 19.24 becomes
S S S
H e = H1 1 + H 2 2 + + H n n
Sb Sb Sb
Thus the equivalent inertia constant is the sum of the individual con-
stant, when this is referred to the total rating of the machine.
If the machine is identical,
S1 = S2 = = Sn = S (say )
H1 = H 2 = = H n = H (say )
472 ◾ Elements of Power Systems
Sb = Se = nS
nHS
He = =H
nS
d 2δ (19.26)
M = Ps − Pe
dt 2
d 2 δ1 (19.27)
M1 = Ps1 − Pe1
dt 2
d 2δ 2 (19.28)
M2 = Ps 2 − Pe2
dt 2
Let δ be the relative angle between the rotors of the two machine,
δ = δ1 − δ 2 (19.29)
d 2 δ d 2 δ1 d 2 δ 2 1 1
= − = (Ps1 − Pe1 ) − (P − Pe2 )
dt 2
dt 2
dt 2 M1 M2 s2
M1M2 d 2δ M2 M1
⋅ 2 = (Ps1 − Pe1 ) − (P − P )
M1 + M2 dt M1 + M2 M1 + M2 s 2 e2
(19.30)
M2 Ps1 − M1Ps 2 M2 Pe1 − M1Pe2
= −
M1 + M2 M1 + M2
Power System Stability ◾ 473
d 2δ (19.31)
M′ = Ps′ − Pe′
dt 2
M1M2
M′ = (19.32)
M1 + M2
M2 Ps1 − M1Ps 2
Ps′ = (19.33)
M1 + M2
M2 Pe1 − M1Pe2
Pe′ = (19.34)
M1 + M2
d 2δ
M = Ps − Pe
dt 2
d 2 δ1
M1 = Ps1 − Pe1
dt 2
d 2δ 2
M2 = Ps 2 − Pe2
dt 2
d 2δ n
Mn = Psn − Pen
dt 2
474 ◾ Elements of Power Systems
Ps0 a
0 δ0 δ1 π δ2 π δ
2
d 2δ Pa (19.36)
=
dt 2 M
dδ d 2 δ P dδ
2 =2 a ⋅
dt dt 2 M dt
2
d dδ P dδ (19.37)
=2 a ⋅
dt d t M dt
The time rate of change of load angle dδ/dt is the speed of the machine
with respect to the synchronously revolving reference frame. For the sta-
bility, this speed must become zero at sometime after disturbance. That is,
dδ/dt = 0.
Since the condition (dδ/dt) = 0 implies synchronous running, Equation
19.37 is integrated between the limits of swinging of δ, that is, from
476 ◾ Elements of Power Systems
2 δ2
dδ 2
dt = M Pa dδ ∫
δ0
For stability,
dδ
=0
dt
δ2
∴
∫P a =0 (19.38)
δ0
δ2 δ2
∫ P dδ + ∫ P dδ = 0
a a
δ0 δ1
δ2 δ2
∫ P dδ = − ∫ P dδ
a a (19.39)
δ0 δ1
A1 = − A2 (19.40)
where
δ1
A1 =
∫ P dδ = Positive or accelerating area
δ0
a
δ2
A2 =
∫ P dδ = Negative or decelerating area.
δ1
a
δ 2 = δ max = 180° − δ1
478 ◾ Elements of Power Systems
Pe
Pmax m
A2
b c Mechanical power
Ps1
Input line
A1
Ps0
a
f e d h
0 δ0 δ1 π δ π δ
2
2
FIGURE 19.7 Limiting case of transient stability with mechanical input sud-
denly increased.
Any further increase in Ps1 means that the area available for A2 is less
than the area A1, so that excess kinetic energy causes δ to increase beyond
point c and the retarding power changes over to accelerating power with
the system consequently become unstable.
It may also be noted from Figure 19.7 that the system will remain stable
even though the rotor may oscillate beyond δ = 90° so long as equal area
criterion is met. The condition δ = 90° is meant for use in steady-state sta-
bility only, and does not apply to the transient stability.
Applying the equal-area criterion to Figure 19.7, we have
Area A1 = Area A2
∫
=Ps1 (δ1 − δ 0 ) − Pm sin δ dδ
δ0
∫
= Pm sin δ dδ − Ps1 (δ 2 − δ1 )
δ1
Area A1 = Area A2
Ps1 (δ1 − δ 0 ) + Pm (cos δ1 − cos δ 0 ) = Pm (cos δ1 − cos δ 2 ) − Ps1 (δ 2 − δ1 )
or
Also,
δ 2 = δ max
and
The above nonlinear algebraic equation can be solved by trial and error
method for δmax. Once δmax is obtained, the maximum permissible power
or the transient stability limit is found from
Ps1 = Pm sinδ1
480 ◾ Elements of Power Systems
where
δ1 = π − δ max
EV
Pe1 = sinδ
XA
where XA is the transfer reactance when both the lines are operating in
parallel.
X1 X2
X A = X d′ + X1||X2 = X d′ +
X1 + X2
EV
Pe1 = sin δ
X d′ + ( X1 X2 /( X1 + X2 ))
CB1 X1 CB2
Line 1
E δ Xd′ Infinite
bus
Generator V 0°
X2
Line 2
CB3 CB4
or
where
EV
Pmax 1 =
X d′ + ( X1 X2 /( X1 + X2 ))
EV
Pe2 = sinδ
XB
X B = X d′ + X2
Pe
Pmax1 A
Pe1 (Both the lines in operation)
Pmax2 B
d Pe2 (Line 1 switched off )
a c A2 Mechanical
Ps
A1 Input line
b
P1
0 δ0 δ1 δ2 π δm π δ
2
FIGURE 19.9 Power–angle curves. Curve A for two lines in parallel and curve
B for line 2.
482 ◾ Elements of Power Systems
EV
Pe2 = sin δ
X d′ + X2
where
EV
Pmax 2 =
X d′ + X2
δ 2 = δ m = (π − δ1 ) elec.radians
Power System Stability ◾ 483
Pmax1
Pmax2
A2
Ps A1
0 δ0 δ1 π δm π δ
2
FIGURE 19.10 Transient stability limit for the system in Figure 19.8.
CB1 CB2
Line 1
E δ Infinite
bus
Generator V 0°
Line 2
CB3 CB4
EV
Pe1 = sinδ = Pmax 1 sin δ
XA
EV
Pe2 = sinδ = Pmax 2 sin δ
XB
EV
Pe3 = sinδ = Pmax 3 sin δ
XC
Pe
Pre-fault curve A
Pmax1
0 δ0 δ1 π δ2 π δ
2
one healthy line remains in the circuit. The transfer reactance changes
to a new value due to the opening of the CBs. The operating point moves
to point e on the post-fault curve C. The load angle δ goes on increasing
due to the inertia of the rotor. Now, the output power is greater than the
input power, and the rotor starts retarding till the point f is reached. At
the point f, the angle δ is δ2 and the speed of the rotor with respect to
the synchronous speed becomes zero. The extent of overshoot, that is, the
value of δ2 can be determined by equating the area s defg and abcd. If
the area included between the curve C and the line Pe = Ps, bounded by
δ = δ1 is less than area abcd, the machine will lose synchronism after the
operation of the CBs. The system will be stable if the retardation area A2
(area defg) is equal to the acceleration area A1 (area abcd). It is to be noted
that the acceleration area A1 depends upon the clearing angle δ1. When δ1
increases, area A1 also allowable value of δ for stability. Such a condition
is shown in Figure 19.13a, where δ1 = δc. The angle δc is called the critical
clearing angle. For the system to be stable, the clearing angle should be less
than the critical angle. If the actual clearing angle is greater than the criti-
cal clearing angle, the system becomes unstable. Thus, more rapidly the
fault is cleared, the smaller will the accelerating area be, and the greater
the chance of stable operation being restored.
For simplicity, let us take Pmax1 = Pm1, Pmax2 = Pm2, and Pmax3 = Pm3.
486 ◾ Elements of Power Systems
Pe Pe
(a) (b)
b b
g n k m
0 δ0 δq δ1 = δc δ2 = δm π δ 0 δ0 δc δr δ2 δm π δ
FIGURE 19.13 (a) Determination of critical clearing angle. (b) Equal area crite-
rion for system fault, circuit isolation, and reclosing.
∫
= Ps (δ c − δ 0 ) − Pm2 sin δ dδ
δ0
=
∫P
δC
m3 sin δ dδ − Ps (δ m − δ C )
P
δ m = π − δ q = π − sin −1 s radians
Pm 3
Power System Stability ◾ 487
PS (δ m − δ 0 ) − Pm 2 cos δ 0 + Pm 3 cos δ m
cos δ c = (19.44)
Pm 3 − Pm 2
EV
Pmax =
X
It can be seen from this expression that Pmax can be increased by increas-
ing either V or E, or both and reducing the transfer reactance. The follow-
ing methods are available for reducing the transfer reactance:
WORKED EXAMPLES
EXAMPLE 19.1
A round rotor generator with internal voltage E1 = 2 pu, X = 1.1 pu is
connected to a round rotor synchronous motor with internal voltage
E1 = 1.3 pu, X = 1.2 pu. The reactance of the line connecting generator
to the motor is 0.5 pu when the generator supplies 0.5 pu power (Figure
19.14), what will be the rotor angle difference between the machines?
Solution
Let δ1 and δ2 be the load angle of the generator and motor, respectively.
Power System Stability ◾ 489
XL = 0.5 pu
FIGURE 19.14 A round rotor generator connected with a round rotor synchro-
nous motor.
EV EE
Active power transferred, Pe = sin δ = 1 2 sin(δ1 − δ 2 )
X X
or
2 × 1. 3
0.5 = sin(δ1 − δ 2 )
(1.1 + 0.5 + 1.2)
or
(δ1 − δ 2 ) = 32.58°
EXAMPLE 19.2
A generator with constant 1 pu terminal voltage supplies power
through a step up transformer of 0.12 pu reactance and a double cir-
cuit line to an infinite bus bar as shown in Figure 19.15. Neglecting
resistance and susceptances of system, SSSPL (steady state stability
power limit) of the system is 6.25 pu. If one of the double circuit is
tripped then what will be the resulting SSSPL in pu?
Solution
Reactance of the transformer (X1) = 0.12pu
2 3
X
1
∴ X2 = X3 = X ′
or
1
6.25 =
0.12 + ( X ′ /2)
or
X′ = 0.08pu
If one of the double circuit is tripped,
EV 1×1 1
∴ Pe = = = = 5pu
X 0.12 + X ′ 0.12 + 0.08
EXAMPLE 19.3
The power angle characteristics of a machine-infinite bus system are
Pe=2 sin δpu. It is operating at δ=30°. Determine the synchronizing
power coefficient at the operating point.
Solution
Synchronizing power coefficient,
dPe d
= (2 sin δ)
dδ dδ
= 2 cos δ
= 2 cos 30°
= 3 pu
Power System Stability ◾ 491
EXAMPLE 19.4
A synchronous generator is connected to an 11-kV infinite bus
through a transmission line. The reactances of generator and trans-
mission line are 1.2 and 0.8 Ω, respectively. The terminal voltage of
synchronous generator is 15 kV. If the generator delivers 70 MW
power to infinite bus, then what will be the load angle?
Solution
Active electrical power transmitted
EV
Pe = sinδ
X
or
11 × 15
70 = sin δ
2
or
140
sinδ =
165
or
δ = 58.04°
EXAMPLE 19.5
A 500-MW, 21-kV, three-phase, two-pole synchronous generator
having a rated power factor=0.9 has moment of inertia 27.5 × 103
Nm. Determine inertia constant H.
Solution:
2πN
Angular velocity , ω =
60
2π × ((120 × 50)/2)
=
60
= 314.15 rad/s
492 ◾ Elements of Power Systems
1 1
∴ Kinetic energy = Iω 2 = × (27.5 × 103 ) × (314.15)2 = 1357 MJ
2 2
Kinetic energy
∴ Inertia constant, H =
S
1357
=
(P / cos φ)
1357
=
(500/0.9)
= 2.44 MJ/MVA
EXAMPLE 19.6
A 50-Hz, four-pole, turbo alternator 20 MVA, 13.2 kV has an inertia
constant of H as 9 kW s/kVA. If the shaft input less the rotational
losses is 26,800 HP of metric and electrical power developed 16,000
kW. Then determine kinetic energy stored by rotor and accelerating
torque.
Solution
Inertia constant, H = 9 kW s/kVA = 9 MJ/MVA
Kinetic energy stored by rotor = S × H = 20 × 9 = 180 MJ
Accelerating torque, Ta
or
2π × ((120 × 50)/ 4)
3698 = × Ta
60
Ta = 23.541 Nm
EXAMPLE 19.7
Inertia constant of a 100-MVA, 50-Hz, four-pole generator is 10 MJ/
MVA. If mechanical input is suddenly raised to 75 MW from 50
MW, then determine rotor acceleration.
Solution
d 2δ Pa 25 MW 25
Rotor acceleration, α = = = =
dt 2 M SH / nf (100 × 10)/(180 × 50)
= 225 elec. degree/s2
EXAMPLE 19.8
A synchronous motor of negligible resistance is receiving 25% of
power that is capable of receiving from infinite bus. If the motor load
is suddenly doubled, determine angle at which the system is stable,
after making an oscillation between the two possible swings.
Solution
Initially,
or
Ps1 = Pe1
Ps 2 = 2, Ps1 = Pe2
or
2Ps1 = Pe2
or
2 × (0.25Pm ) = Pm sin δ 2
or
δ 2 = 30°
EXAMPLE 19.9
A synchronous generator having inertia constant 6 MJ/MVA is
delivering power of 1pu to an infinite bus through a purely reactive
network. Suddenly a fault occurs and reduces the output power to 0.
The maximum power that could be delivered is 2.5pu. Determine
Solution
Let Ps = Pe1 = 1pu.
Now,
P
δ 0 = sin −1 s = 23.57° = 0.411 rad
Pm1
and
P
δ max = 180° − sin −1 s = 156.43° = 2.73 rad
Pm 3
1/2
2 M (δ c − δ 0 )
Critical clearing time, t c =
PS
Now,
GH 1 × 6
M= = = 0.0382
πf π × 50
1/2
2 × 0.0382(1.56 − 0.411)
∴ tc =
1
= 0.296 s
EXERCISES
Load Flows
20.1 INTRODUCTION
The flow of active and reactive power is called power flow or load flow.
Load flow (or power flow) analysis of the determination of current, volt-
age, active power, and reactive volt-amperes at various points in a power
system operating under normal steady-state or static conditions. Load
flow studies are made to plan the best operation and control of the exist-
ing system as well as to plan the future expansion to keep space with the
load growth. Such studies help in ascertaining the effects of new loads,
new generating stations, new lines, and new interconnections before they
are installed. The prior information serves to minimize the system loses
and to provide a check on the system stability.
The mathematical formulation of load flow problem results in a set of
algebraic nonlinear equations. A lot of calculation work is involved in the
solution of this equation. Hand computations are very tedious and time
consuming. Earlier load flow studies were made by AC network analyz-
ers (analog computers). Digital computers, because of greater flexibility,
economy accuracy, and quicker operation, have practically replaced net-
work analyzers for the solution of load flow problems.
20.2 BUS CLASSIFICATION
Load flow studies are performed to calculate the magnitude and phase
angles of voltages and buses, and also the active power and reactive volt-
amperes flow for the given terminal or bus condition.
The following variables associated with each bus or node are
Load bus or P-Q bus. A load bus is a bus where active power Pi and
1.
reactive power Qi are specified. Magnitude and phase angle of the
bus voltages are to be found.
Generator bus or voltage-controlled bus or PV bus. A generator bus is
2.
a bus where the magnitude of bus voltage |Vi| and the corresponding
generated power Pi are known. Reactive power Qi and power angle δ
are to be obtained.
Stack bus or swing bus or reference bus. A stack bus is a generator bus
3.
where the magnitude and phase angle of bus voltage are specified.
Real (Pi) and reactive (Qi) power are to be obtained. This bus is first
to respond to a changing load condition.
I2 V2 Z12 V1 I1
2 1
Transmission
lines
Z23 Z31
V3 3
I3
Y30
− I 3 = y31 (V3 − V1 ) + y23 (V3 − V2 ) + y30V3 = − y31V1 − y23V2 + ( y31 + y23 + y30 )V
V3
Y11 = y12 + y31 , Y22 = y12 + y23 , Y33 = y31 + y23 + y30
Y12 = Y21 = − y12 , Y23 = Y32 = − y23 , Y13 = Y31 = − y31
where [Ybus] is called bus admittance matrix, [V] and [I] are N element
voltage matrix and current matrix, respectively, where
IK = ∑Y V
Kn n (20.5)
n =1
Advantages:
For a large power system, more than 90% of its off-diagonal ele-
ments are zero. This is due to the fact that in power system net-
works, each node (bus) is connected to not more than three nodes
in general and an element Ypq exists only if a transmission line links
nodes p and q.
*
n
Si = Pi + jQi = V I = Vi YikVk
*
i i
k =1
∑ (20.6)
where
Si* = Vi* Ii
Pi − jQi = Vi *
∑Y V
k =1
ik k
Pi = ∑|Y V V |cos|φ
ik i k ik + δ k − δi |
k =1
or
Qi = ∑|Y V V |sin|φ
ik i k ik + δ k − δi |
k =1
or
Equations 20.7 and 20.8 are called static load flow equations (SLFE).
Equation 20.7 gives n real power flow equations. Similarly, Equation 20.8
gives n reactive power flow equation. Thus, Equations 20.7 and 20.8 repre-
sent 2n power flow equations. At each bus, we have four variables Pi, Qi, Vi,
and δi resulting in total of 4n variables. In order to find a solution, it is nec-
essary to specify two variables at each bus. Thus, the number of unknown
variables is reduced to 2n. The solution of these remaining 2n variables is
done by numerical methods because Equations 20.7 and 20.8 are nonlinear.
No exact analytical solution of nonlinear equation is possible. These
equations may be solved by iterative techniques that employ successive
approximations eventually converging upon a solution. Before the advent
of digital computers, these trial and error techniques were tedious and
time consuming. However, today these methods find widespread appli-
cations for solving load flow problems. The iteration procedure involves
an initial assumed value for each of the unknown independent variable.
These numerical values are substituted in the original equation to obtain a
new set of corrected values of these independent variables. The second set
Load Flows ◾ 503
is used to find the third corrected set. The process is repeated. Each calcu-
lation of a new set of variables is called iteration. The iteration is continued
until the unknown values converge within required limits.
1. It is very simple.
2. Computing costs are less.
3. Sometimes it is used to find the initial solution for the other iterative
procedures.
f ( x ) = x 2 − 3x + 2 = 0
x 2 − 3x + 2 = 0
1 2 2
∴x = x +
3 3
x ( 0 ) = 1. 5
1 2
∴ x (1) = × (1.5)2 + = 1.4167
3 3
1 12 2
x (r + 1) = (x ) +
3 3
504 ◾ Elements of Power Systems
Here,
x (r +1) = 1.3356
Step 3.
1 r +1 2 2 1 2
x (r +1)+1 = (x ) + = (1.3356)2 + = 1.261
3 3 3 3
Sk = Pk + jQk = Vk I k* (20.10)
1
Ik = (P − jQk ) (20.12)
Vk* k
1
Yk1V1 + Yk 2V2 + + YkkVk + + YknVn = (P − jQk ) (20.13)
Vk* k
Load Flows ◾ 505
1 Pk − jQk
n
Vk =
Ykk Vk*
− ∑i =1
YkiVi
(20.14)
i ≠k
1 P2 − jQ2
V2 = − Y21V1 − Y23V3 − − Y2nVn (20.15)
Y22 V2*
At bus 3,
1 P3 − jQ3
V3 = − Y31V1 − Y32V2 − Y34V4 − Y3nVn (20.16)
Y33 V3*
k −1 n
1 Pk − jQk
V k
(r +1)
=
( )
Ykk V (r ) *
− ∑ YkiVi (r +1)
− ∑ YkiVi(r )
(20.17)
k i =1 i = k +1
In the above equation, the quantities Pk, Qk, Ykk, and Yki are known and
do not vary during the iteration cycle.
f1 (x1 , x2 ) = c1 (20.18)
f 2 (x1 , x2 ) = c2 (20.19)
Let x1(0) and x2(0) be the initial estimates for solutions of Equations 20.18
and 20.19. Let ∆x1(0) and ∆x2(0) be the values by which the initial estimates
differ the exact solution. Thus,
( )(
f1 x1(0) + ∆x1(0) , x2(0) + ∆x2(0) = c1
) (20.20)
( )(
f 2 x1(0) + ∆x1(0) , x2(0) + ∆x2(0) = c2
) (20.21)
δf1 δf1
( )
f1 x1(0) , x2(0) + ∆x1( )
0
δx1
+ ∆x2(0)
δx 2
= c1 (20.22)
x1( 0 ) x2( 0 )
δf 2 δf 2
( )
f 2 x1(0) , x2(0) + ∆x1(0)
δx1 (0)
+ ∆x2(0)
δx 2 (0)
= c2 (20.23)
x1 x2
or
δf1 δf1
c1 − f1 ( x1(0) , x2(0) ) δx1 δx 2 ∆x1(0)
= (0) (20.24)
c2 − f 2 ( x1 , x2 ) δff 2 δf 2 ∆x2
(0) (0)
δx1 δx2 x( 0 ), x( 0 )
1 2
or
∆c1(0) ∆x1(0)
(0) = j(0) (0) (20.25)
∆c2 ∆x2
where
δf1 δf1
δx δx 2
j(0) = 1
δf 2 δf 2
δx1 δx2
Matrix j(0) is called “Jacobian” and ∆c1(0) and ∆c2(0) are the differences.
Solution of Equation 20.25 gives ∆x1(0) and ∆x2(0) .
In the next step, a better estimate of the solution is made when
The whole process is then repeated, and the iterations continued until
Δx1 and Δx2 become very much smaller than predetermined value.
In the two-bus power system model,
EV (20.26)
P = f1 (δ,V ) = sin δ
X
EV V2 (20.27)
Q = f 2 (δ,V ) = cos δ −
X X
δf1 δf1
∆P (0) δδ δV ∆δ
(0)
(0) = (20.28)
∆Q δf 2 δf 2 ∆V (0)
δδ δV
−1
δf1 δf1
∆δ ∆P δδ
(0) (0)
δV
(0) = (0) (20.29)
∆V ∆Q δf 2 δf 2
δδ δV
The values determined for Δδ(0) and ΔV(0) are then added to the previous
estimates of V and δ to obtain new estimate of V and δ to start next itera-
tion. That is,
Vk = |Vk |∠δ k
Vn = |Vn |∠δ n
where
and
If P and Q are specified for every bus except the swing bus, it
c orresponds to specifying C1 and C2. Let us first estimate V and δ for
each bus except the slack or swing bus, for which they are known. Then
Load Flows ◾ 509
where the subscripts s and c are the specified and calculated val-
ues, respectively. These correspond to the values of ∆c1(0) and ∆c2(0) in
Equation 20.25.
Thus, NR method in a three-bus power system model gives, similar to
Equations 20.25 and 20.29.
δP2 δP2 δP2 δP2
(0) δδ 2 δδ 3 δV2 δV3 (0)
∆P2 ∆δ 2
∆P3(0) = δP3 δP3 δP3 δP3 (0)
∆δ 3
(0) δδ 2 δδ 3 δV2 δV3
∆Q2 δQ δQ2 δQ2 δQ2 ∆V2
(0 )
∆Q (0) 2 (0 )
3 δδ 2 δδ 3 δV2 δV3 ∆V3
δQ3 δQ3 δQ3 δQ3
δδ δδ 3 δV2 δV3
2
20.8.1 Advantages of GS Method
1. It can be easily programmed.
2. The solution technique is simple.
3. Computer memory requirements are smaller.
4. It takes less computational time per iteration.
20.8.2 Limitations of GS Method
1. The rate of convergence is slow and therefore, larger numbers of itera-
tions are required. The GS method would take hundreds of iterations to
converge, if a system with several hundred buses were to be analyzed.
2. The number of iterations increases directly with the number of buses
in the system.
3. This method is sensitive to the choice of reference bus.
The GS method is used only for the system having small number of
buses.
20.8.3 Advantages of NR Method
1. NR method possesses quadratic convergence characteristics. Therefore,
the convergence is very fast.
2. The number of iterations are independent of the size of the system.
Solution to a high accuracy is obtained nearly always in two to three
iterations for both small and large systems.
3. The NR method convergence is not sensitive to the choice of the slack
bus.
4. Overall there is a saving in computation time, since fewer numbers
of iterations are required for convergence.
20.8.4 Limitations of NR Method
1. The solution technique is difficult.
2. It takes longer time as the elements of the Jacobian are to be com-
puted for each iteration.
3. The computer memory requirement is large.
Load Flows ◾ 511
WORKED EXAMPLES
EXAMPLE 20.1
Network shown in Figure 20.2 has impedances in per unit (pu) as
indicated. Determine the diagonal element Y22 of the Ybus matrix
of the network.
Solution
From the Figure 20.2, we get admittances connected to bus 2 is
1 1 1
Y22 = + +
j0.1 j0.1 − j20
= − j10 − j10 + j0.05
= − j19.95pu
EXAMPLE 20.2
A three-bus network is shown in Figure 20.3, indicating pu imped-
ances of each element. Find Ybus matrix of the network.
1 2 3
j0.1 j0.1
1 2 3
j0.2 j0.08
j0.1 j0.1
Solution
1 1
Y11 = Admittance connected to the bus 1 = +
j 0. 1 j 0. 2
1 1
Y22 = Admittance connected to the bus 2 = +
j0.2 − j0.08
1 1
Y33 = Admittance connected to the bus 3 = +
− j0.08 j0.1
1 1
j0.1 + j0.2 j5 0
1 1
Ybus = j5 j0.2 + − j0.08 − j12.5
1 1
0 − j12.55 − j0.08 + j0.1
− j15 j5 0
= j5 j 7. 5 − j12.55
0 − j12.5 j2.5
Load Flows ◾ 513
Example 20.3
Find the values of and for the following equations by NR method up
to second iteration x12 − x2 − 4 = 0, 2 x1 − x2 − 2 = 0.
Solution
Let the initial guess be such that
Then
f1 (x1(0) , x2(0) ) = 1 + 4 − 1 = 1
f 2 (x1(0) , x2(0) ) = 2 + 1 − 2 = 1
Also
δf1 δf 2
= 2 x1 = 2, =2
δx1 δx1
δf1 δf 2
= −4, = −1
δx 2 δx 2
However,
δf1 δf
f1 (x1(0) , x2(0) ) + ∆x1(0) + ∆x2(0) 1 = 0
δx1 δx 2
δf 2 δf
f 2 (x1(0) , x2(0) ) + ∆x1(0) + ∆x2(0) 2 = 0
δx1 δx 2
Substitution yields,
1 + 2∆x1 − 4 ∆x2 = 0
1 + 2∆x1 − ∆x2 = 0
EXERCISES
1. Develop the equations for real and reactive bus powers. Show that a
diagonal element of a Ybus is equal to the sum of admittances directly
connected to that bus and an off-diagonal element is equal to the
negative of the sum of admittances directly connected between the
buses.
2. What are the advantages of Ybus over Zbus?
3. Compare the performance of Gauss–Siedel and Newton–Raphson
methods for load flow solution. Explain the method of formation of
Ybus.
4. What is the significance of load flow analysis in a power system? Give
the classification of various types of buses in a power system for load
flow studies. Justify the classification.
Bibliography
515
516 ◾ Bibliography
20. R.T. Lythall, The J. & P. Switchgear Book, Johnson & Phillips, London, 1969.
21. H. Trendam, Circuit Breaking, Butterworth, London, 1953.
22. E.W. Kimbark, Power System Stability, Vol. I, John Wiley & Sons, New York,
1974.
23. S.B. Crary, Power System Stability, Vol. I, John Wiley & Sons, New York,
1947.
24. I.J. Nagrath and D.P. Kothari, Modern Power System Analysis, Tata McGraw-
Hill, New Delhi, 2008.
25. C.L. Wadhwa, Electrical Power Systems, New Age International Publishers,
India, 2010.
26. A. Husain, Electrical Power System, CBS Publishers and Distributors Pvt.
Ltd., India, 2012
27. B. Ram and D.N. Vishwakarma, Power System Protection and Switchgear,
Tata McGraw-Hill, New Delhi, 2011.
28. A. Chakrabarti, M.L. Sony, P.V. Gupta, and U.S. Bhatnagar, A Textbook on
Power System Engineering, Dhanpat Rai & Co., India, 2012.
29. J.B. Gupta, A Course in Electrical Power, S.K. Kataria & Sons, India, 2010.
30. D. Das, Electrical Power System, New Age International (P) Limited
Publishers, India, 2006.
31. V.K. Mehta and R. Metha, Principles of Power System, S. Chand & Company
Ltd., India, 2005.
This page intentionally left blank
Elements of
ELECTRICAL ENGINEERING
K26369
ISBN: 978-1-4987-3446-2
90000
Pradip Kumar Sadhu • Soumya Das
9 781498 734462