Testing Hager AFDD: Arc Fault Detection
Testing Hager AFDD: Arc Fault Detection
Arc Fault
Hager AFDD Hager Ltd.
Hortonwood 50 Detection
Telford
01 Insulation resistance test in accordance with BS Shropshire
7671 TF1 7FT
Internal components contain sensitive electronics
which are connected to load side of device. Device Customer Contact Centre: 01952 675612
outgoing terminals should NOT be subject to 500V Technical Helpline: 01952 675689
test. A test at 250Vdc will not harm the components
but will produce a false reading. The procedure for hager.com/uk
carrying out the insulation resistance test is:- [email protected]
[email protected]
Test 1 – Between Live conductors
@Hager_uk
Test 2 – Between Live conductors & Earth
- Can be tested from busbar with AFDD’s ON
- Testing all circuits together is possible
- Perform test at 500Vdc
- Test between L-E & N-E OR L/N joined together
-E
microprocessors to identify characteristic current arc faults. Unlike circuit breakers or RCDs, an
flow and voltage curves that indicate an arc fault and AFDD does not have an electromechanical trigger,
automatically trip the affected circuit. but utilises electronic technology to analyse
the signature (waveform) of an arc. It reliably
Ring Final Circuits
This significantly reduces the risk of fire due to differentiates between an arc fault and the signature
faulty conductors and connections. The protective Contrary to common belief, AFDD’s do offer
(waveform) in normal switching and control events,
function of the AFDD has already proven its worth protection against arc faults in ring final circuits and
preventing false tripping.
internationally, and has been used in Germany since to the equipment being fed from this circuit. A series
February 2016. arc fault in one leg however, is unlikely to be at a
dangerous level so will not be detected. This is due
The 18th edition of BS 7671, when published in July, to current in this instance flowing around the other
recommends the use of these to provide additional leg of the ring. A series arc fault will be detected in
protection against fire. equipment and in flexible cables connected to the
ring final circuit. Parallel arc faults are detected and
disconnected in all parts of the ring circuit and on all
Kink/break in the Cable wear due Line damage resulting Incorrect
cable to frequent use from drilling or wire stripping connected equipment.
construction work