BMS Point Schedule
BMS Point Schedule
Plot No.L1, Pho Noi B Textile & Garment Industrial Park, Lieu Xa ward (Di Su ward), Yen My district (My Hao district), Hung Yen Province, Vietnam
1 Chillers 2
Auto/Manual Status 2 PLANT ROOM DRY CONTACT
Chiller Enable 2 PLANT ROOM DRY CONTACT
On / Off Status 2 PLANT ROOM DRY CONTACT
Trip Alarm 2 PLANT ROOM DRY CONTACT
2-Way Motorised Butterfly Valve Control 4 PLANT ROOM BF VALVE ACTUATOR
2-Way Motorised Butterfly Valve Open/Close Status 4 PLANT ROOM BF VALVE ACTUATOR
Chilled Water Return Temperature 2 PLANT ROOM TEMPERATURE SENSOR
Chilled Water Supply Temperature 2 PLANT ROOM TEMPERATURE SENSOR
Condenser water supply temperature 2 PLANT ROOM TEMPERATURE SENSOR
Condenser water return temperature 2 PLANT ROOM TEMPERATURE SENSOR
Flow Status - Chilled Water and Condenser Water 4 PLANT ROOM FLOW SWITCH
Chiller Microprocessor Interface for Internal Data 3 1 PLANT ROOM RS485 - BACnet over MS/TP or BACNet IP.
4 Outdoor Conditions 1
Outdoor Temperature 1 PLANT ROOM TEMPERATURE SENSOR
Outdoor Humidity 1 PLANT ROOM HUMIDITY SENSOR
Page 59
Building Management System - Mechanical and Plumbing point list
Page 60
Building Management System - Mechanical and Plumbing point list
Page 61
Building Management System - Mechanical and Plumbing point list
10 COOLING TOWERS 2
Auto/Manual Status 2 CT PANEL DRY CONTACT
CT Fan Enable 2 CT PANEL RELAY CONTACT
Fan On / Off Status 2 CT PANEL VSD
Fan Speed Control 2 CT PANEL VSD
Fan Speed Feed Back 2 CT PANEL VSD
Trip Alarm 2 CT PANEL DRY CONTACT
Motorised Butterfly Valve Control 2 CT PANEL BF VALVE ACTUATOR
Motorised Butterfly Valve Status 2 CT PANEL BF VALVE ACTUATOR
Condenser water entering temperature 2 CT PANEL TEMPERATURE SENSOR
Condenser water leaving temperature 2 CT PANEL TEMPERATURE SENSOR
Flow Status - Condenser Water 4 CT PANEL FLOW SWITCH
Page 62
Building Management System - Mechanical and Plumbing point list
Followig Systems should provide communication inteface at respective mocroprocessor control devices for interfacing with the BMS.
16.2 VRV AC system 2 2 VRV Micro procssor BACnet MS/TP or BACnet IP - Modbus RTU
16.3 Fire Alarm System - FACP 1 1 Fire Alarm Control Panel BACnet MS/TP or BACnet IP - Modbus RTU By Fire contractor
Page 63