BMS Point Schedule

This document provides a list of point types and descriptions for a building management system to monitor and control the mechanical and plumbing equipment at a textile and garment industrial park in Hung Yen Province, Vietnam. It includes 9 categories of equipment with over 70 monitoring points for items like chillers, pumps, air handling units, temperatures, pressures, and valve/damper positions. The points will integrate with the BMS via protocols like BACnet MS/TP, BACnet IP, temperature sensors, and dry contacts.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views

BMS Point Schedule

This document provides a list of point types and descriptions for a building management system to monitor and control the mechanical and plumbing equipment at a textile and garment industrial park in Hung Yen Province, Vietnam. It includes 9 categories of equipment with over 70 monitoring points for items like chillers, pumps, air handling units, temperatures, pressures, and valve/damper positions. The points will integrate with the BMS via protocols like BACnet MS/TP, BACnet IP, temperature sensors, and dry contacts.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

Linea Aqua Vietnam Company Limited,

Plot No.L1, Pho Noi B Textile & Garment Industrial Park, Lieu Xa ward (Di Su ward), Yen My district (My Hao district), Hung Yen Province, Vietnam

Building Management System - Mechanical and Plumbing point list

POINT TYPE Software


Provision provided in
ITEM
NO EQUIPMENT TYPE / POINT DESCRIPTION POINT LOCATION INTERFACE TYPE AND/OR DEVICE AC contract- filled by
QTY
the bidder
DI DO AI AO Interface

1 Chillers 2
Auto/Manual Status 2 PLANT ROOM DRY CONTACT
Chiller Enable 2 PLANT ROOM DRY CONTACT
On / Off Status 2 PLANT ROOM DRY CONTACT
Trip Alarm 2 PLANT ROOM DRY CONTACT
2-Way Motorised Butterfly Valve Control 4 PLANT ROOM BF VALVE ACTUATOR
2-Way Motorised Butterfly Valve Open/Close Status 4 PLANT ROOM BF VALVE ACTUATOR
Chilled Water Return Temperature 2 PLANT ROOM TEMPERATURE SENSOR
Chilled Water Supply Temperature 2 PLANT ROOM TEMPERATURE SENSOR
Condenser water supply temperature 2 PLANT ROOM TEMPERATURE SENSOR
Condenser water return temperature 2 PLANT ROOM TEMPERATURE SENSOR
Flow Status - Chilled Water and Condenser Water 4 PLANT ROOM FLOW SWITCH
Chiller Microprocessor Interface for Internal Data 3 1 PLANT ROOM RS485 - BACnet over MS/TP or BACNet IP.

2 Main By Pass valves 1


Differential Pressure 1 PLANT ROOM DIFF. PRESSURE TRANSM.
Modulating Valve Control 1 PLANT ROOM MOTORIZED VALVE
Valve Position 1 PLANT ROOM POTENTIOMETER

3 Pressurised Expansion Tank Water Level 1


High Level 1 PLANT ROOM DRY CONTACT
Low Level 1 PLANT ROOM DRY CONTACT

4 Outdoor Conditions 1
Outdoor Temperature 1 PLANT ROOM TEMPERATURE SENSOR
Outdoor Humidity 1 PLANT ROOM HUMIDITY SENSOR

5 Chilled Water Pumps - CHWP 3


Auto/Manual Status 3 PLANT ROOM DRY CONTACT
On / Off Control 3 PLANT ROOM DRY CONTACT
On / Off Status 3 PLANT ROOM FLOW SWITCH

Page 59
Building Management System - Mechanical and Plumbing point list

POINT TYPE Software


Provision provided in
ITEM
NO EQUIPMENT TYPE / POINT DESCRIPTION POINT LOCATION INTERFACE TYPE AND/OR DEVICE AC contract- filled by
QTY
the bidder
DI DO AI AO Interface

Trip Alarm 3 PLANT ROOM DRY CONTACT

Page 60
Building Management System - Mechanical and Plumbing point list

POINT TYPE Software


Provision provided in
ITEM
NO EQUIPMENT TYPE / POINT DESCRIPTION POINT LOCATION INTERFACE TYPE AND/OR DEVICE AC contract- filled by
QTY
the bidder
DI DO AI AO Interface

6 Condenser Water Pumps - CWP 3


Auto/Manual Status 3 PLANT ROOM DRY CONTACT
On / Off Control 3 PLANT ROOM DRY CONTACT
On / Off Status 3 PLANT ROOM FLOW SWITCH
Trip Alarm 3 PLANT ROOM DRY CONTACT

7 Building Load Measurements 1


Chilled Water Return Flow Rates 1 PLANT ROOM FLOW METER
Chilled Water Supply Temp 1 PLANT ROOM TEMPERATURE SENSOR
Chilled Water Return Temps 1 PLANT ROOM TEMPERATURE SENSOR

8 Chemical Dosing System for Condenser & Chilled Water 1


Condenser Water Dosing System Common Fault 1 PLANT ROOM DRY CONTACT
Chilled Water Dosing System Common Fault 1 PLANT ROOM DRY CONTACT
Trip Alarm 1 PLANT ROOM DRY CONTACT

9 Air Handling Units - VSD type 7


AHU Auto / Manual 7 AHU PANEL DRY CONTACT
AHU Start/Stop Command 7 AHU PANEL RELAY CONTACT
AHU Run Status 7 AHU PANEL DRY CONTACT
AHU Fan Trip Status 7 AHU PANEL DRY CONTACT
Supply Air Temp. 7 SUPPLY DUCT TEMPERATURE SENSOR
Supply Air Static Pressure 7 SUPPLY DUCT STATIC PRESSURE SENSOR
Speed Control of AHU Fan Motor 7 AHU PANEL VSD
Speed Feedback of AHU Fan Motor 7 AHU PANEL VSD
Return/Space Temperature 7 SPACE / RETURN DUCT TEMPERATURE SENSOR
Return CO2 Level 7 SPACE / RETURN DUCT CO2 SENSOR
2 - Way Valve Control 7 AHU PIPING VALVE ACTUATOR
Valve Status 7 AHU PIPING VALVE ACTUATOR
Chilled Water In / Out Temperatures 14 AHU PIPING TEMPERATURE SENSOR
Pre-Filter and Bag-Filter Alarms 7 AHU DIFF. PRESSURE SWITCHES
Fan Belt Break Alarm 7 AHU DIFF. PRESSURE SWITCHES
Fire Alarm Input 7 AHU PANEL DRY CONTACT

Page 61
Building Management System - Mechanical and Plumbing point list

POINT TYPE Software


Provision provided in
ITEM
NO EQUIPMENT TYPE / POINT DESCRIPTION POINT LOCATION INTERFACE TYPE AND/OR DEVICE AC contract- filled by
QTY
the bidder
DI DO AI AO Interface

10 COOLING TOWERS 2
Auto/Manual Status 2 CT PANEL DRY CONTACT
CT Fan Enable 2 CT PANEL RELAY CONTACT
Fan On / Off Status 2 CT PANEL VSD
Fan Speed Control 2 CT PANEL VSD
Fan Speed Feed Back 2 CT PANEL VSD
Trip Alarm 2 CT PANEL DRY CONTACT
Motorised Butterfly Valve Control 2 CT PANEL BF VALVE ACTUATOR
Motorised Butterfly Valve Status 2 CT PANEL BF VALVE ACTUATOR
Condenser water entering temperature 2 CT PANEL TEMPERATURE SENSOR
Condenser water leaving temperature 2 CT PANEL TEMPERATURE SENSOR
Flow Status - Condenser Water 4 CT PANEL FLOW SWITCH

11 Supply Air Fan - SAF 7


SAF Fan Auto / Manual 7 SAF PANEL DRY CONTACT
SAF Fan Start/Stop Command 7 SAF PANEL RELAY CONTACT
SAF Fan Status 7 DIFFERENTIAL PRESSURE SWICTH

12 Water Booster Pump Sets 1


Supply Line Pressure 1 BOOSTER PUMP HEADER PRESSURE SENSOR By plumbing contractor
Pump Run Status 3 BOOSTER PUMP PANEL DRY CONTACT
Trip Alarm 3 BOOSTER PUMP PANEL DRY CONTACT
Power Failure Alarm to booster panels 1 BOOSTER PUMP PANEL DRY CONTACT

13 Water Tank Levels - 200kL By plumbing contractor


Tank Level 1 ALL TANKS LEVEL SENSOR
Over Flow Alarm 1 ALL TANKS LEVEL SWITCH

14 Water Meter - All Meters 2


Volumetric Flow ALL METER PULSE GENERATOR - 1 Pulse / xx Liters By plumbing contractor

Page 62
Building Management System - Mechanical and Plumbing point list

POINT TYPE Software


Provision provided in
ITEM
NO EQUIPMENT TYPE / POINT DESCRIPTION POINT LOCATION INTERFACE TYPE AND/OR DEVICE AC contract- filled by
QTY
the bidder
DI DO AI AO Interface

15 Sewerage Pumps and Sump By plumbing contractor


Auto/Manual Status 1 SEWERAGE PUMP CONTROL PANEL DRY CONTACT
On / Off Control 2 SEWERAGE PUMP CONTROL PANEL DRY CONTACT
On / Off Status 2 SEWERAGE PUMP CONTROL PANEL DRY CONTACT
Trip Alarm 2 SEWERAGE PUMP CONTROL PANEL DRY CONTACT
Sewerage Sump High Level Alarm 1 SEWERAGE PIT DRY CONTACT
Power Failure Alarm 1 SEWERAGE PUMP CONTROL PANEL DRY CONTACT

16 HIGH LEVEL INTERFACE

Followig Systems should provide communication inteface at respective mocroprocessor control devices for interfacing with the BMS.

16.1 HVAC - Chillers 2 2 Chiller Micro-Processors BACnet MS/TP or BACnet IP

16.2 VRV AC system 2 2 VRV Micro procssor BACnet MS/TP or BACnet IP - Modbus RTU

16.3 Fire Alarm System - FACP 1 1 Fire Alarm Control Panel BACnet MS/TP or BACnet IP - Modbus RTU By Fire contractor