K-060 General Installation

This manual provides instructions for installing and maintaining air valves. It describes receiving, handling, and storing air valves properly. The installation section outlines best practices for installing air valves and connecting them to pipelines and vent pipes. Periodic maintenance involves shutting an isolation valve, disassembling the air valve parts, cleaning them, reassembling correctly, and reopening the isolation valve.

Uploaded by

SannyBombeoJomoc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views

K-060 General Installation

This manual provides instructions for installing and maintaining air valves. It describes receiving, handling, and storing air valves properly. The installation section outlines best practices for installing air valves and connecting them to pipelines and vent pipes. Periodic maintenance involves shutting an isolation valve, disassembling the air valve parts, cleaning them, reassembling correctly, and reopening the isolation valve.

Uploaded by

SannyBombeoJomoc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

General Installation and Operating

Manual for Air Valves.

Table of Contents:
1. Introduction 2
2. Receiving, Handling & Storage 2
3. Air Valve Installation 3-10
4. Maintenance Manual 11
1 Introduction
This manual will provide you with the information to properly install and maintain the air valve and
ensure a long service life. The Air Valves have rugged construction to provide many years of trouble-free
operation.
Combination Air Valves intake air to protect the pipeline from the destructive effects caused by cavitation
and vacuum (negative pressure), discharge air during pipe fill to increase fill efficiency and release air
continuously in a pressurized pipeline to lower head losses and improve flow.
The material type is indicated clearly on the casting inscription of the valve body. The air valve size and
pressure class are clearly indicated on the ID tag attached to the air valve body.

2 Receiving, Handling & Storage


Inspect air valves upon receipt for damage in shipment. Carefully remove the air valve from the shipping
package. Unload all air valves carefully to a sturdy level surface taking care not to drop them. Air valves
should be lifted by using the eye bolts only and not by any other means (Fig.1). For small- sized air valves,
they should be lifted by means of belts which are to be placed around the flange necks (Fig. 2).
When the valves are to be stored for some time before being fitted, storage should be in the original
delivery crates or cases. Storage should be off the ground in a clean, dry indoor area.

2
Illustration No.1: Lifting Options
Fig.1 - Lifting Option for Air Valves 6” and larger

Fig.2 - Lifting Option for Air Valves up to 4”

Fig. 1

Fig. 2

3
3 Air Valve Installation

1. Recommendation for Riser Dimensions

d=D for D ≤ 300 mm


d=0.6 D for 300 mm < D ≤ 1500 mm
d ≥ 0.35 D for D > 1500 mm

h ≥ D or h=D/2 and h ≥ 150 mm


h=ØD or D/2

Ød

ØD

4
2. The air valve should be installed in a vertical position.

Not Correct Correct

3. The standpipe should be attached to the crown of the pipe and not from the side of the pipe.

Not Correct Correct

5
4. The standpipe should connect directly to the air valve and must be of an equal or greater diameter
than the air valve.

Not Correct Correct

6
5. An isolation valve must be installed to allow for proper maintenance and should be positioned close
to the main pipe.

Not Correct

Correct

7
6. In case of installation in an underground chamber, a vent pipe must be installed with a diameter
equal to or greater than the air valve. The vent outlet must have a mesh screen to prevent entry of
animals or objects.

Not Correct Correct

8
7. In installations, such as under a road, where the air valve must be displaced to the side, the
connecting pipe after the isolation valve must be on a slight incline. The standpipe at this point can be
connected vertically to the air valve.

9
8. If the event that a drain pipe needs to be attached to the air valve outlet, this pipe must be rigid and
will have a diameter equal or greater than the outlet diameter of the air valve. AVOID USING COLLAPSIBLE
FLEXIBLE HOSE.

Not Correct Correct

10
K-060 2”
Periodic Maintenance
1. Shut the isolating valve below the air valve.
2. 2.Unscrew the bolts (8) that connect the valve cover (2) to the body (1).
3. Wash the body (2) and the cover (1).and in clean water in order to
remove coarse grime or accumulated scale. Check if the seal (4) , the
seat (3) , or the float (5) are dirty, and clean them.
4. Reinstall in reverse order and fasten and tighten all bolts. Make sure to
re-assemble the components correctly.
5. Open the isolating valve beneath the air valve.

PARTS LIST AND SPECIFICATION

No. Part Material Coating / Colour Coating procedure


1. Elbow Stainless Steel SAE 316 Epoxy Coated RAL 9003 DIN 30677 Part 2
2. Plug Nylon BLACK
3. Nipple ASTM A744 CF8M Epoxy Coated RAL 9003 DIN 30677 Part 2
4. Bolt, Nut & Washer Stainless Steel SAE 316 CATAPHORETIC Cathodic Electro Deposition (CDP) Black 8-15 µm
Acc. MIL-DTL-0053084B
5. Cover Cast Duplex ASTM A890 GR. 5A Epoxy Coated RAL 9003 DIN 30677 Part 2
6. Orifice Seat Cast Duplex ASTM A890 GR. 5A
7. Orifice Seal E.P.D.M.
8. O-Ring E.P.D.M.
9. Float POLYCARBONATE
10. Body Cast Duplex ASTM A890 GR. 5A Epoxy Coated RAL 9003 DIN 30677 Part 2