Power System
Power System
com)
Contact : 01715 591 542
Power
System
IRh- P1- volume 1
1
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Index
2
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
3
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝐿𝑜𝑎𝑑
Load Factor =
𝑀𝑎𝑥 𝐷𝑒𝑚𝑎𝑛𝑑
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝐿𝑜𝑎𝑑
Plant capacity Factor =
𝑃𝑙𝑎𝑛𝑡 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦
𝑀𝑎𝑥 𝐷𝑒𝑚𝑎𝑛𝑑
Demand Factor =
𝐶𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑 𝐿𝑜𝑎𝑑
𝑠𝑢𝑚 𝑜𝑓 𝑖𝑛𝑑𝑖𝑣𝑖𝑑𝑢𝑎𝑙 𝑀𝑎𝑥 𝑑𝑒𝑚𝑎𝑛𝑑
Diversity Factor =
𝑀𝑎𝑥 𝑑𝑒𝑚𝑎𝑛𝑑 𝑜𝑛 𝑡ℎ𝑒 𝑠𝑦𝑠𝑡𝑒𝑚
𝑀𝑎𝑥 𝐷𝑒𝑚𝑎𝑛𝑑
Utilization Factor =
𝑃𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦
4
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
1.
2.
3.
Ans: 20.8%
4.
5.
6.
Ans: 3750 KW
5
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
7.
8.
9.
10.
6
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
11.
12.
13.
7
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
14. (EGCB-2017)
The daily base load in a system is 3500 MW. The load changes to 4000 MW at 6
PM only and persists till 11 PM. Find the load Factor?
Ans : 90.104%
15. (PGCB-2018)
Determine the load Factor and peak demand of a power station in which the annual
load duration curve varies linearly between 12 GW to 4 GW. If the total transmission
loss is 3% and for frequently regulation reserve margin of 20% is to be mentioned, then
what should be the total generation capacity of the system?
Ans: 66.667%, 12; 15.46 GW
16. (NWPGCL-2018)
A Power Station has 3 MW reserve capacity, 60% load factor and 50% plant capacity
Factor. Find Maximum demand of the station.
Ans: 15 MW
17.
( a) (EGCB-2012)
A commercial group has 12 consumer each with a connected load of 12 KW and
demand Factor of 80%. The group has a group diversity factor of 1.2 and peak diversity
factor of 1.1.
Find the demand of consumer group at the time of system peak.
Ans: 87.2727 kW
(b)
A new load is to be added in a power station. There are two loads each of 5-MW and 10-
MW. The demand factors are 50% & 70% respectively. The group diversity factors are
1.1 & 1.4 respectively. The peak diversity factors are 0.45 & 0.30 respectively. Consider
4% transmission loss. Find the transformer rating for supply the load.
Ans: 22.625 MW
Hints: P = Max Demand + 0.04P
8
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(b) (DESCO)-2019)
A residential complex with 400 apartments, each of 10 KW load is built. The complex
also has a common amenities of 40 KW load.
The demand factor, group diversity factor and peak diversity factor of the apartment
load are 0.4, 4, & 1.2 respectively.
The demand factor, group diversity factor and peak diversity factor of the common
amenities load are 0.8, 1.3 & 1.1 respectively.
The transformer is cooled through Oil Forced Air Natural (OFAN) cooling and allow
150% emergency loading.
Ans: 666.958 KVA
(c)
Find the annual load factor if the average daily load factor is 0.825.
the ratio of average daily peak load to monthly peak load is 0.87 and
The ratio of average monthly peak load to annual peak load is 0.78
Ans: 0.559845
9
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(d)
A feeder supplies 3 distribution transformers which feed the following loads:
The diversity factor of the loads on the three transformers may be taken as 2.3, 2.5, 2.0.
The diversity factor between transformers is 1.4.
Find
( i) peak load on each transformer
(ii) peak load on feeder
Ans: 100, 80, 100; 200
10
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
19.
Ans: 81.620 KW
11
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
12
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
1
P= Vm Im CosΦ = Vrms Irms CosΦ
2
Qc = P ( tanΦ1 - tanΦ2 )
𝑄𝐶
C=
ω 𝑉2
C/phase = Qc / ω VP2
13
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
25.
Ans: 91 uF
26. (i)
(ii)
Ans: 310 uF
27. (i)
Ans: 46.42 uF
14
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(ii) (Important)
(iii)
Ans: 47 uF
15
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(iv) (important)
28.
Ans:
16
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
17
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Industrial Bill
= Unit consumed (kWh) * tk + Max kVA demand * tk
(constant)
Saving
= Bill before power factor improvement
– Bill after power factor improvement
18
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
29.
Ans: 9,836 tk
30.
Ans: 4,530 tk
31. (i)
(ii)
Ans: 834 tk
32. (i)
Calculate the annual bill of a consumer whose maximum demand is 100 KW, power
factor=0.8 and Load Fatcor = 60%. The tariff is 75 BDT per kVA of maximum demand
plus 0.15 BDT per kWh consumed.
Ans: 88,215 tk
(ii)
Calculate the annual bill of a consumer whose maximum demand is 200 kW at 40% load
Factor. If the tariff is 100 BDT per kW of maximum demand plus 0.10 BDT per kWh.
Ans: 90,080 tk
19
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
20
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
21
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
22
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
23
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
24
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
25
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
26
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
27
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Ans: 75%
(b)
34.
Ans: 100%
35. (Important)
36.
(Important)
Ans: 50%
Hints:
28
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
37.
Ans: 400 kW
Hints:
38.
29
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
39. (Important)
Ans: 4400 v
Hints:
30
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
31
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Stevenson, P-208
𝑉1 𝑉2
P= 𝑍
𝑆𝑖𝑛δ
𝑉2
Q= 𝑍
(𝑉1 𝐶𝑜𝑠δ − 𝑉2 )
Ferranti Effect:
The effect for which Voltage at the receiving end of a transmission line is more than the
sending end voltage, is known as Ferranti Effect.
32
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
40. (GTCL-2018)
41.
(a) (PGCB-2019)
A transmission line has 4 ohm inductive reactance. To improve the real power
flow by 10%; how much & what type reactance should be added in series?
Ans: -j0.3636 ohm
(b) (PGCB-2021)
A transmission line has phase difference 15 degree. If the real power flow is
increased by 10%, what will be the phase angle?
Ans: 16.54 degree
33
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
34
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
35
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
42.
Ans :
43. (a)
Ans :
36
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(b) (CPGCL-2018)
A 200-MVA, 345Y / 20.5 (Del) kV rated transformer, which is connected at the receiving
end of a transmission line, feeds an induction motor rated at 180 MVA, 0.8 pf lagging,
22.5 kV. If the base in the transmission line is 100 MVA, 345 kV, determine the per–
unit impedance of the Load?
Ans: 0.5354+0.4015i
2 2
Hints: ZL= Vp /SP*; Zpu= ZL (100/20.5 )
44.
Ans:
37
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
45.
38
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Ans:
46.
Ans:
39
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
40
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
41
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(a)
(b)
P-317
(c)
P-300
42
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
43
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(phase value)
(phase value)
R = R1+R2+R0
Y = Y1+Y2+Y0
B = B1+B2+B0
44
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
45
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
48.
Ans: 4 A
49.
50. (a)
(b)
51. (a)
46
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(b)
Ans:
, , ;
(c) **
53.
47
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
54. (a)
Ans: 5.78∠ -30, 5.78 ∠30, 0; 5.78 ∠-150, 5.78∠150, 0; 5.78 ∠ 90, 5.78∠-90, 0;
(b)
Ans: 11.54∠ -30, 11.54∠30, 0; 11.54 ∠-150, 11.54∠150, 0; 11.54∠ 90, 11.54 ∠-90, 0;
55. (a)
Three resolution of a set of three-phase unbalanced voltage into symmetrical
components gave the following results:
(b)
The positive and negative components of “a” phase voltage of a Y-connected resistive
load are
0.9867∠43.6 p.u. and 0.2346∠250.3 p.u. respectively.
The neutral of the load is not connected to the ground. Calculate the power consumed
by the load if the system base is 100-MVA.
Ans: 308.58 MW
48
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(c)
For a three-phase system, the voltage of phase to neutral had the following sequence
components during phase to phase fault condition.
56. ***
Solve:
Ans: 60 ∠-90,
40∠ 90,
20∠ 90
49
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
57. ***
Ans:
58.
Ans:
50
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
51
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
𝐼𝑟𝑎𝑡𝑒𝑑 𝑉𝑟𝑎𝑡𝑒𝑑
Ipu = Vpu =
𝐼𝑏𝑎𝑠𝑒 𝑉𝑏𝑎𝑠𝑒
P-305 (Gupta)
√3
𝐸/𝐿𝑖𝑛𝑒
ILG = 𝑍1 + 𝑍2 + 𝑍0 + 3(𝑍𝑛 + 𝑍𝐹 )
𝐸/𝐿𝑖𝑛𝑒
ILL =
𝑍1 + 𝑍2 + 𝑍𝐹
√3 (𝐸/𝐿𝑖𝑛𝑒) 𝑍2
ILLG = 𝑍1 𝑍2 + 𝑍2 𝑍0 + 𝑍0 𝑍1
𝐸/𝑝ℎ𝑎𝑠𝑒
ILLL =
𝑍1 + 𝑍𝐹
52
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
53
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
59.
Ans: 6188∠-90 A
54
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
62. (PDB-2018)
A 20 MVA, 6.6 KV solidly grounded Y connected generator has a
If a single phase to ground fault occurs on phase ‘a’ through impedance of j2 ohm, what
will be the fault current?
Hints: It doesn’t matter on which ‘phase’ fault has occur, (Hadi Saddat, P-431) ; but it matters on which ‘BUS’ fault has occur
Ans: 1270.17∠-90 v
Both synchronous machines are rated 1250-KVA, 4160-V with reactance X1=X2=10%.
Each transformer is rated 1250-KVA, 600/4160 V with leakage reactance 5%.
Reactance of transmission line X1=X2=15%, X0=50% on base value of 1250-KVA, 4.16-
KV
Determine fault current when fault occur at point “P” for Single line to ground fault
Ans: 14678.4 A
64.
A 3-phase 37.5-MVA, 33-KV alternator having X1=0.18 p.u., X2=0.12 p.u., X0= 0.10 p.u.
based on its rating is connected to a 33-KV overhead transmission line having the
following reactance: X1=6.6 ohm, X2=6.3 ohm, X0=12.6 ohm per conductor. A single line
to ground fault occur at the remote end of the transmission line. The alternator star
point is solidly earthed. Calculate the fault current
Ans: 1540 A
55
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Summary:
An alternator (star point is solidly earthed) is connected to a transmission line.
Calculate the fault current when a single line to ground fault occur at the remote end of
the transmission line.
65.
Ans: 9447.5 A
66.
A solidly earthed Y-connected generator is connected to a delta connected motor.
Generator & motor having reactance X1= 0.2 p.u., X2= 0.2 p.u., X0= 0.1 p.u.
Ans: - j6998.2 A
56
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
69.
Three alternators operating in parallel have identical constants:
X1=21%, X2=12%, X0=10%
Neutral of only 1 is grounded solidly; others have un-grounded neutral. Calculate
Three 3-phase alternators rated 10-MVA, 6.6-kV are connected to a common bus-bar.
Each alternator has positive sequence reactance 0f 0.15 pu. The negative & zero
sequence reactance are 75% & 30% of positive sequence network.
A single line to ground fault occurs on the bus-bar. Find fault current when
(a) One alternator neutral is solidly grounded & neutral of other two are isolated
(b) One alternator neutral is grounded through 0.3 ohm resistance & neutral of other
two are isolated
Ans: 19806.2 A, 10691.968∠-32.67 A
71.
72.
Ans: 1.284
57
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
73. **
A generator is connected to a transmission line through a transformer.
G: 75-MVA, 11.8-KV
X1= 17.5%, X2= 13.5%
A fault occur at the secondary side of transformer. Determine the fault current when
Transformer: X = 0.05 pu
Find fault current & voltage at fault point when fault at mid-point of line when
58
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(c) Line to line fault, find fault current (Exc-10.20) Ans: 2.8867
(d) Double line to ground fault , find fault current (Exc-10.24) Ans: j0.4
75. *
Find short-circuit current in a single-phase system shown below. The reactance between
the transformer and the fault point F is 2 ohm. The voltage at F is 6.6 KV
G: 2 MVA, 10%
T: 1.2 MVA, 7%
Ans: 982.289 A
76. *
A 3-phase, 6000-KVA, 11-KV alternator has 10% direct axis sub-transient reactance. It is
connected to a 6000-KVA, 11/66-KV transformer having 9% leakage reactance. A
sym-metrical delta connected fault of impedance 12+j3 ohm occurs between the lines
near the H.V. terminals of the transformer when the system is on no-load. Calculate the
current supplied by alternator.
59
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
77.
Two generators rated 11 KV, 3000 KVA, having 20% reactance are inter-connected by a
100 km long transmission line. The reactance of line is 0.10 ohm per km. the
transformers near the generators are rated 6000 KVA, 11/66 KV and have 5% reactance.
A 3-phase fault occurs at a distance of 20 km from one end of the line when the system
is on no-load but at rated voltage. Calculate
The other end of line is connected to a transformer T2 having x1 =x2 =x0 =0.1 pu.
Another generator B feeds T2. The sequence reactances of generator B are 0.25, 0.15 &
0.03 pu. The transformer T2 is connected star-star with both neutral earthed.
A line to line fault occurs on secondary side of T1. Find fault current
Ans: 4.224 (4.2655) pu
79.
Ans: 1012 A
60
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
80.
Two generators are connected to their unit transformer in the given figure
81.
A generator have the following sequence reactance:
X1= 60%, X2=25%, X0=15%
Calculate the value of resistance to be connected to neutral such that the current for
single line to ground fault does not exceed the rated current
Ans: 0.9428 p.u.
To be connected in neutral circuit so that fault current for a single line to ground fault
(of zero fault impedance) does not exceed rated line current
61
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
83.
when
(i)
(ii)
84.
62
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Assume that generator neutral is solidly grounded and the generator is operating at no
load and rated voltage at the occurrence of Line to ground fault.
Calculate
(a) Fault current Ans: 10496.3 A;
(b) Line to neutral voltage at fault point (Post fault)
Ans: 0, 0.882∠-100.89 (5.6k) , 0.882∠100.89 (5.6k)
Assume that generator neutral is solidly grounded and the generator is operating at no
load and rated voltage at the occurrence of Line to Line fault.
Calculate
(a) Fault current Ans: 6818.18 A
(b) Line currents Ans: 0, -6818 A, 6818 A
(c) Line to neutral voltage at fault point (Post fault)
Ans: 1(6.35k), -0.5(-3.1754k), -0.5(-3.1754k)
63
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Assume that generator neutral is solidly grounded and the generator is operating at no
load and rated voltage at the occurrence of Double Line to Ground fault.
Calculate
(a) Fault current Ans: j15745.91643 A
64
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Find
(a) Fault current
(b) Voltage of healthy phases at fault point
Ans: 0.7376∠-28.33; -0.68479 - j0.8236, -0.6660468 + j0.8983
65
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Two 11-kV, 20-MVA, Y-connected generators operate in parallel. The positive, negative
and zero sequence reactance of each being 0.18, 0.15 , 0.10 pu. The star point of one
generator is isolated and that of other is solidly earthed.
Find
(a) Fault current
(b) voltage of healthy phase
Ans: 1428.40∠-55.236 A, 371.39∠-21.8 v
Two 11-kV, 20-MVA, Y-connected generators operate in parallel . The positive , negative
and zero sequence reactance of each being 0.18, 0.15 , 0.10 pu. The star point of one
generator is isolated and that of other is solidly earthed.
66
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
67
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
93.
Ans: 4330 A
94.
Ans:
68
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
95.
96.
Ans: 875 A
A generating station has four identical three-phase alternators A,B,C,D each having
20,000 KVA, 11 KV and 20% reactance. They are connected to a bus-bar which has a bus-
bar reactor of 25% reactance on basis of 20,000 KVA base, inserted between B & C.
A 66 KV feeder is taken off from the bus-bar through a 10,000 KVA transformer having
5% reactance. A short-circuit occur across all phases at the high voltage terminal of the
transformer.
Calculate the fault current
Ans: 984.2 A
69
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
A 20-MVA, 11-kV generator having 15% reactance and a 10-MVA generator having 10%
reactance connected to a common bus-bar.
The bus-bar feeds a 30-MVA, 11/33-kV transformer with 5% reactance. A 33-kV feeder
takes off from transformer and has an impedance of (3 + j15) Ω.
If a 3-phase fault occur at the far end of feeder, calculate fault MVA & fault current?
99. (a)
(b)
70
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
100. (a)
A 33-KV bus-bar of a station are in two sections “A” & “B” separated by a reactor.
“A” is fed from four 10-MVA generators each having 0.20 per unit reactance
and “B” is fed from the grid through a 50-MVA transformer of 0.10 per unit reactance.
Find the reactance of the reactor to prevent the circuit breaker being overloaded when
a symmetrical short-circuit occur on an outgoing feeder connected to it.
Ans: 1.452 ohm
(b)
(c)
71
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(d) *
A generating station has two alternators “A” & ”B” of 3-MVA and 4.5-MVA and per unit
reactance 0.07 & 0.08.
It is intended to extend the system by a supply from the grid through a transformer of
7.5-MVA with 0.075 per unit reactance.
Find the reactance of the reactor to protect the switchgear if a short-circuit occur on an
outgoing feeder connected to the alternator bus-bar.
Ans: 0.105 ohm
(e) *
Two three-phase generators are connected to a bus-bar. A three-phase short-circuit
occurs on the bus-bar.
Find the reactance of a reactor to be connected in series with generator 1 to limit the
short-circuit KVA of bus-bar to 10000.
101.
Ans: 87.02
72
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Hints:
Bus bars A & B are connected through a 5% reactor on 10-MVA base. Bus bars B & C are
connected through a 4% reactor on 8-MVA base.
Find Fault MVA & fault current for a 3-phase fault at bus A
73
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
74
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
104.
(a)
(b)
A large generating station has its bus bars divided into 4 sections.
Find fault MVA when a fault occurs on the bus bars of one section.
Ans: 250 MVA
75
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
105. *
Ans: 40
Hints:
76
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
𝐼𝑠𝑐 100
=
𝐼 %𝑍
𝑀𝑉𝐴𝑠𝑐 100
=
𝑀𝑉𝐴𝐵 %𝑍
77
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(ii) Calculate fault level on L.T. side of the transformer if a 1-MVA capacitor bank was
installed on L.V. side
Ans: 18.37 ; 17.37
108.
(i) **** (Gupta Ex 10.28)
2 1
The negative and zero sequence source reactance are & 3 of positive sequence
3
reactance. The zero sequence source resistance is 60 Ω.
Find fault current & fault MVA when fault at high side of transformer
78
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(ii) BIFPCL-2019)
109.
Two buses having fault level of 50-MVA & 100-MVA respectively are inter-connected by
a line of negligible impedance. Calculate fault level at any point on the line
Ans: 150
110.
111.
(a)
(b)
79
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(b)
80
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
113. *
Two alternators “A & B” are connected in parallel.
The system is on no-load before fault with voltage on HT side equal to 66-KV.
Two alternators are connected in parallel to the low-voltage side of a three-phase Delta-
Wye transformer.
Before the fault occur, the voltage on HT side of transformer is 66-KV. The transformer
is un-loaded and there is no circulating current between the generators..
81
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Ans: 2727.95∠-88.646 A
82
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
A 3-phase fault occurs at the motor terminals when the motor is taking an input of 15-
MW at unity power factor. The line voltage across motor terminals at the time of fault is
10.45-kV.
Find the total current supplied by generator & motor to the fault.
A synchronous generator and synchronous motor each rated 25-MVA, 11-kV having
15% sub-transient reactance are connected through transformers. Transformers are
rated at 25-MVA, 66-kV.
The motor is drawing 15-MW at 0.8 power factor leading and at a terminal voltage of
10.6-kV when a symmetrical fault occur at motor terminals.
Calculate
(a) Total Fault current Ans: -j11533.364 A
83
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
A synchronous generator and motor are rated 30-MVA, 13.2-kV and both have sub-
transient reactance of 20%. The line connecting them has a reactance of 10% on the
base of machine rating.
The motor is drawing 20-MW at 0.8 pf leading and a terminal voltage of 12.8-kV when a
symmetrical three-phase fault occurs at the motor terminals.
84
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
The motor is drawing 40-MW at 0.8 pf leading with a terminal voltage of 10.95-kV when
a single line to ground fault occurs at the generator terminals of phase “a”.
Calculate the total current in the phase “a” of generator & motor under fault condition.
85
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
86
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
87
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(a)
Ans:
(b)
Ans:
88
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(c) * (P -380)
Ans:
122. **
Consider a 3-bus system. The series impedance and shunt admittance of each line are
0.026 + j0.11 pu and j0.04 respectively. Find YBUS=?
89
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
YBUS =?
Ans:
0.882 − 𝑗3.499 − 0.294 + 𝑗1.176 − 0.588 + 2.352 0
−0.294 + j1.176 0.862 – j3.026 −0.333 + j1 −0.235 + j0.94
−0.588 + j2.352 −0.333 + j1 1.215 – j4.468 −0.294 + j1.176
0 −0.235 + j0.94 −0.294 + j1.176 0.529 − j2.056
125.
PDB-2018
90
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Ans:
91
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
126.
Ans:
92
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
93
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
127.
Determine Ybus=?
Ans:
128. (NWPGCL-2018)
Consider a two bus power system where these buses are connected through two
parallel transmission lines. The per unit impedance of each line is j0.2.
Determine YBUS
Ans: -10 10
10 -10
129.
94
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Solve :
Ans:
95
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
96
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
130. **
97
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
131.
98
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Determine
(a) Impedance to the fault point Ans:
99
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Ans:
(a) -2i
0.76, 0.68, 0.32
-1.1i, -0.9i, -0.1i
(b)
-2.5i
0.8, 0.4, 0.6
-0.5i, -0.5i, -0.5i
(c) -3.125i
0.5, 0.75, 0.625
-0.3125i, -0.3125i, -0.3125i
(Hints: before converting to admittance diagram, series connections in impedance form must
be added)
100
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
101
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
1
Time, t = = π √𝐿𝐶
2𝑓𝑛
𝐿
Chopping voltage, e = I √𝐶
102
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
135.
136.
137.
138.
Ans: 866 KV
103
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
139.
140. (BIFPCL-2019)
A 13.8 kV alternator has a ground relay pick-up current of 1A, a neutral resistance of 30
ohm and a neutral CT rated 200/5. Determine the percent of alternator unprotected
winding.
Ans: 15.06%
141.
Ans: 19.69%
142.
143.
104
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
144.
(a)
Ans: 12 :5√3
(b)
Ans: 10.5 : 5
(c)
Ans: 60 : 5/√3
(d)
105
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
146. **
A three phase delta-wye connected 30-MVA, 33/11-kV transformer is protected by a
differential relay. The CT current ratio on primary side is 500:5 and that on secondary
side is 2000:5.
Calculate the relay current setting for fault drawing up to 200% of rated current?
106
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
Hints: Relation exists between line current of main supply (transformer) & phase current of CT.
Here first find line currents of Transformer, then phase currents of CT’s and then Line
currents of CT’s
Reversely first find phase currents of CT’s, then line currents of Transformer
107
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
108
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
109
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
110
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
111
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
148.
149.
Ans: 13.6 km
150.
151.
152.
153.
112
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
154.
Ans: 37.18 km
155.
113
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
114
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
(Page-256)
115
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
157.
158.
Ans: 0.992 angle 0.18, 55.5 angle 69, 0.000315 angle 90, 0.992 angle 0.18;
143 kv, 9.25%
159.
160.
Find
(a) Sending end power
(b) Efficiency
(c) regulation
Ans: 48.6 MW, 82.3% , 40.5%
116
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
A 3-phase load of 1-MW at a power factor of 0.8 lagging is supplied by a 30-kV line
of resistance 25 ohm and inductive reactance 12 ohm per phase. The voltage across the
load is 10 kV. A 30/10 kV transformer step downs the voltage at the receiving end. The
equivalent resistance and reactance of the transformer as referred to 10-kV side are 0.8
ohm and 2.5 ohm respectively. Find sending end voltage and regulation.
Ans: 31.94 kV, 6.45%
162. **
A 15-km long 3-phase overhead line delivers 5-MW at 11-kV at a power factor of
0.8 lagging. Line loss is 12% of the power delivered. Line inductance is 1.1 mH/km/phase.
Calculate
(a) Sending end voltage and regulation
Ans:
(b) Power factor of Load to make regulation zero
Ans:
117
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
2.
3.
118
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
4. (Important)
119
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
120
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
121
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
165.
Ans: 13.7 m
166.
167.
Ans: 9.5 m
168.
Ans: 3
122
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
169.
170.
171.
Ans: 55 m
123
Facebook page : EEE Career Academy | Facebook
Iftikhar Reza ([email protected])
Contact : 01715 591 542
124
Facebook page : EEE Career Academy | Facebook