0% found this document useful (0 votes)
162 views2 pages

MBCI01

This document summarizes test results for a pilot wire differential relay. It includes general information about the relay and circuit under test. It then details the results of mechanical checks, electrical tests including pickup values and timing, and a functional test of output contacts and LEDs. The tests confirm the relay is functioning as expected within specified parameters.

Uploaded by

THILAKKUMAR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
162 views2 pages

MBCI01

This document summarizes test results for a pilot wire differential relay. It includes general information about the relay and circuit under test. It then details the results of mechanical checks, electrical tests including pickup values and timing, and a functional test of output contacts and LEDs. The tests confirm the relay is functioning as expected within specified parameters.

Uploaded by

THILAKKUMAR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

Customer Contract

Location #
Project
Contractor
AREVA T&D Site test record RELAY TEST Doc. Ref.

MBCI01- PILOT WIRE DIFF. RELAY


1. GENERAL DATA AND INFORMATION:
Circuit Ref. Designation
Panel No. Serial No.
Make Model No.
Dwg & Sh No. Aux. Voltage
Flag Type No. of Contacts
Stabilizing resistor

2. MECHANICAL CHECKS AND VISUAL INSPECTION:


ITEM DESCRIPTION CHECKED
1 Inspect for any physical damage or defects.
2 Verify connections as per approved drawings.
3 Check that serial no. of relay matching with serial no. of case.
4 Relay CT shorting function checked.
5 Test switch checked for correct function.
6 Final set value of stabilizing resistor is set.

3. ELECTRICAL TESTS:
3.1 RELAY BURDEN:
Nominal DC
Condition Relay DC voltage Relay DC current Remarks
current
No operation 15mA
175mA for 48/54V
Operation
90mA for 110/125V

3.2 PICK UP TEST:


(Operation Values Without Pilots) ---Setting: Rpp = 5x100, Ks = 1, Kt = 20, N = 3.
Operating Calculated Actual Operating Value (A) Time at 5 x Pickup in mS
Phase
Value Value (A) Pick-up (A) Reset (A) Pick-up (mS) Reset (mS)

R–N 0.5 x 19% In

Y–N 0.5 x 25% In

B–N 0.5 x 33% In

R–Y 0.5 x 80% In

Y–B 0.5 x 100% In

B-R 0.5 x 44% In


Note: pickup current should be +/- 10% of calculated value.

Test performed by Test witnessed by Date of test


AREVA T&D
Name MUSTAFA HAJI

Signature
Customer Contract
Location #
Project
Contractor
AREVA T&D Site test record RELAY TEST Doc. Ref.

MBCI01 – PILOT WIRE DIFF. RELAY


3.2 PICKUP TEST (CONN..):
(Operation Values Without Pilots) ---Setting: Rpp = 5x100, Ks = 1, Kt = 20, N = 6.
Operating Calculated Actual Operating Value (A)
Phase
Value Value (A) Pick-up (A) Reset (A)
R–N 0.5 x 12% In

Y–N 0.5 x 14% In

B–N 0.5 x 17% In


Note: pickup current should be +/- 10% of calculated value.
3.3 TIMIG TEST:
Current Actual Operating Time at Multiples of KT in milliseconds
Phas
=5x
e 3 6 14 20 40
Pick-up
R– Typical 300 90 65 50 30
N Actual

4. FUNCTIONAL TEST:

Item Description Checked

1 All output contacts resistance measured.


2 LED operation checked.

Test performed by Test witnessed by Date of test


AREVA T&D
Name MUSTAFA HAJI