General Notes On Modeling Using SAP - ECG - v1
General Notes On Modeling Using SAP - ECG - v1
Prepared by
Version (1.0)
10-5-2009
1. Before modeling
1.1. Column and shear walls locations and distribution
In choosing suitable locations for lateral force resisting structural system, the
following aspects should be considered:
2. For the best torsional resistance, as many of the walls as possible should be
located at the periphery of the building. Such an example is shown in the
following figure. The walls on each side may be individual cantilevers or they
may be coupled to each other.
3. The more gravity load can be routed to the foundation via a structural wall,
the less will be the demand for flexural reinforcement in that wall and the
more readily can foundations be provided to absorb the overturning moments
generated in the wall.
2. Load path
Load should be transferred from slab to foundation. Circular path as shown in the
following figures is not allowed.
B
Slab T = 200 mm
Beam Width, B = 300 mm
5.0 m
Beam Depth, D
a) 300 mm
b) 500 mm
c) 1000 mm
4. Analysis methods
Linear-Elastic Linear-Inelastic
Action
Action
Deformation Deformation
Action
Action
Nonlinear-Elastic Nonlinear-Inelastic
Deformation Deformation
5. Materials
a. Young's Modulus (Ec ): for concrete elements should be calculated from
the following equations:
6. Frame elements
a) Sections:
Note: for L-sec and T-sec the section can be defined as R-sec and multiply the inertia
around the main axis (3) ; I3-3- by the ratio:
b) Local axes
The local axis 3 should be parallel to the width (b) in all cases as shown in the
above figure.
Table (1): (Recommended values for design and to consider effect of cracking in
deflection calculation) for GRAVITY and WIND loads
member ECP ACI-318 (2008) UBC (1997)
Columns Ig
Shear walls Ig
Prestressed slab Ig
* For T-sec use 2x Ig, For L-sec use 1.5 x Ig (as discussed before)
--------------------------------
d) Torsion rigidity
In this case redistribution of torsion is NOT allowed and the member should
be designed based on the acting torsion.
In this case redistribution of torsion is allowed and the torsion rigidity of the
member can be considered equal to zero in analysis but additional rft, enough
to resist torsion equals to cracking torsion moment, should be added (for small
value of torsion moment stirrups used to resist shear could be enough)
7. Shell elements
a) Shell element shape
b) Type
c) Meshing
The term ‘mesh’ is used to describe the sub-division of surface members into elements
(see Figure 4), with a finer mesh giving more accurate results. The engineer has to assess
how fine the mesh should be; a coarse mesh may not give an accurate representation of
the forces, especially in locations where the stresses change quickly in a short space e.g.
at supports, near openings or under point loads. This is because there are insufficient
nodes and the results are based on interpolations between the nodes. However, a very fine
mesh will take an excessive time to compute, and is subject to the law of diminishing
returns
d) Shells numbers:
For lateral load analysis (to design columns, walls and check drift) use a coarse mesh, for
example, ( 2 x 2 units)
For design of slabs and beams, use moderate mesh; the least of:
• Minimum number (4x 4 units).
• Maximum width (1x1 m.)
e) Local axes
Local axes of shell elements in the same plan should be in the same direction
8. Structureal Modeling
a) Under vertical load:
b) Each floor can be represent as 2-d model (in plan) but columns should be
modeled above (if any) and bottom the floor.
In this case column (or shear wall) is modeled using frame element at its center line
(point) and the points on its edges are constrained to the center point as follows
Alternatively, a stiff beam with small area section can be used as below:
c) Moment release
Moments at the ends of beams can be neglected (released) but additional top
reinforcement at the edge connections enough to resist moment equals to (wL2/24) should
be added. (if beam length is less than 8 m). if beam is longer than 8 m, connecting
moment will be higher and may result in considerable cracking.
7. earthquake (E)
8. wind (W)
UBC-1997 COMBINATION
NOTE: generally mxy can be assumed = 0.2 maximum span moment in each direction
(according to the limit of total moment).hence
M (+ve) design:= 1.2 Mult.
13. Deflection
If the above values are not satisfied deflection should be calculated as follows
In sap model deflection can be calculated from the results then total long term
deflection can be calculated from the following relation
The above equation is based on stiffness modifier factors given in table (1). If the
stiffness of slabs is taken as the gross value, ∆total sould be increased to take effect of
cracking.
--------------------
15. Springs under footing or raft
To represent the contact between soil and footing, joint sprting or area spring can be
used. Stiffness of spring can be calculated as follows:
K= (100-120) * qall
Where qall = allowable soil bearing stress under the footing (ton/m2)
__
where
b33 = axial pile stiffness
C33 = constant which accounts for the interaction between the soil and the pile
A = cross-sectional area of the pile
E = modulus of elasticity of the pile
L = length of the pile
The term AE/L is the elastic stiffness of the pile acting as a short column with no soil
present. The coefficient (C33) accounts for the stiffness of the soil-pile system.
For design purposes, C33 for a compression pile ranges between 1.0 and 2.0 although
values as low as 0.1 and as high as 3.0 have been noted in the literature.
There appears to be a relationship between C33 and pile length. Longer piles tend to have
higher values of C33 than shorter piles.
C33 for tension piles in sand can be taken as one half of the value used for compression
piles. For tension piles in clay use 75 to 80 percent of the value of C33 for compression
piles.
(2) Long-term loading, cyclic loading, pile group effects, and pile batter can affect C33 .
In sand, long-term loading has little effect on the value of C33 ; however consolidation in
clay due to long-term loading can reduce C33 . At present, the effect of cyclic loading on
C33 is neglected.
For design purposes, if piles are driven to refusal in sand or to a hard layer, there is no
change in the value of C33 for pile groups; however, C33 may be reduced for groups of
friction piles.
18. REFERENC
O Brooker " How to design reinforced concrete slab using Finite element analysis" The Concrete Centre,
May 2006
Appendices
Appendix A
Typical damping ratio