Submittal Asd872a
Submittal Asd872a
precision air conditioning unit for telecommunication, IT, computer and EDP installations.
close control operation .
dehumidification function
incorporated controller for autarc operation of the A/C unit
entire maintenance accessibility from the front
the A/C unit meets the current technical regulations and standards, the European guidelines for machines
and the German safety regulations
CE certification
manufacturing in a company certified according to DIN ISO 9001/ EN 29001
protection of all ESD sensible elements by manufacturing according to DIN EN 61340-5-1 (Protection of
electronic devices from electrostatic phenomena)
functional test before delivery for unit versions A and ACW
runnning test for unit versions AS and ASCW
A - type:
cold production in the unit
two separate open refrigerant circuits
one split evaporator
condensation by external air-cooled condensers
dehumidification by reducing the refrigerant mass flow and the fan speed
hot gas and liquid lines end pointing downwards in the unit
connection to piping on site by soldered connections
connections can be individually shut off
Suction direction:
Air suction from top
Discharge direction:
Airflow through the unit to the bottom
Fan blowing out of the unit
Discharge to the bottom
Frame, housing:
self-supporting construction
frame parts are made of galvanized steel or high-quality powder coating
harmonized colour allocation
interior sheet metals for highest stability and air conduction
Panelwork:
the unit is delivered with all sides closed
panels and doors can be removed on all sides.
back- and side panels are firmly screwed
all parts of sheet steel are provided with a high-grade plastic powder coating for a persistent corrosion
protection
the panelwork is executed with doors at the unit front
the doors are assembled to the unit frame with lockable security fasteners which prevent from unauthorized
access to the units
panelwork and door insulation with appropriate B1-insulation material
fire classification of the insulation is B1 according to DIN 4102, hardly inflammable, self-extinguishing
chemical-free
no mould fungus according to DIN IEC 68
resistent against house dust mites and vermins
non-provoking allergies
decay-proof
sound absorbent features > 5 kN/m4 according DIN52213
toxicologically recognized as safe according Öko-Tex Standard 100
detergent-proof
thermal isolation characteristics until WLG 0,040 (040) DIN 52612
UV-proof
Unit colour:
Panelwork and sheet steel parts in STULZ anthracite grey
Fronttop-C7000 in Stulz telegrey 4 (RAL 7047)
Filter:
located on suction side
large filter surface
small pressure loss
long service life
fixed fold distance
fully combustible, metal-free
self-extinguishing according to DIN 53438 (fire class F1)
filter exchange from the front
filter monitor installed in the unit
Filter Control Management for constant airflow
Filter quality:
DIN EN 779 G4
Refrigerant:
Standard: R407C
ternary blend: 23% R32, 25% R125, 52% R134a
ODP: 0
GWP: 1770
with the optional application of an alternative refrigerant (R134a, R410A) the standard R407C refrigerant
charge is omitted.
Scroll-Compressor:
smooth and even compression
little vibrations at operation
low noise level
hermetic design
suction gas cooling
internal oil management
internal motor protection incl. evaluation unit
electrical type of protection according to VDE is IP 21
non-return valve at connection piece, pressure side
maintenance-free
high efficiency
indifferent to malfunctions
Electric cabinet:
design of the cabinet according to VDE and DIN standards
filter monitor
accommodation of high voltage and control components
accessible from the front
installed main switch operable and lockable from the outside
clear and space saving structure of high voltage and control components
completed wiring of motor circuit breakers, contactors and control components in wiring ducts
top hat rail or busbar system for high voltage components
main power supply provided by customer
protection class: IP20
Feeding direction:
Power supply and piping connection from bottom
Voltage:
380 V - 415 V, 3ph, 60 Hz with N and PE protective conductor
C7000-IO-Controller:
supply voltage: 24 V (+15%/-15%) VAC
I/O-board interface: EIA485 (RS485)
service, download- and printer interface: EIA232 (RS232)
4 sensor inputs: signal current 0-20 mA or 4-20 mA or signal voltage 0-10 V
11 alarm inputs: 24 VAC/DC (+ 24V = no alarm) status display via LED's
4 analog outputs: 0-10 VDC; max. load 20 mA
7 digital outputs (relais with two way contact), 24 VAC, max. 6 A, status display via LED's
C7000-IO-Controller
automatic or manual start after power loss, unit start time delay also selectable for individual
components.
energy-saving fan speed control depending on temperature
free allocation of all digital/analoge inputs and outputs at respective terminals.
runtime equalization and sequencing of 2 compressors in a unit with 2 refrigerant circuits
service warning according to pre-set time intervals.
manual operation of individual components.
day and night operation
recording of up to 200 alarms with time and date
temperature- and humidity recording up to 1440 data points, freely scalable within 1 to 60000
minutes
variable alarm delay, selectable alarm priority, text input for auxiliary alarms.
1*common alarm
winter start operation
RS232 port on microprocessor board for servicing and software upload. Print out of alarm
protocols, temperature/humidity values, diagnostics and parameter setting
serial RS485 interface available for connection to user interface C7000AdvancedTerminal
(C7000AT)
sequencing of all connected C7000-IO-Controller
sequencing can be divided in up to 20 zones
turn over conditions: unit failure and selectable temperature for Std-By unit activation
selectable sequencing time
alarm priority configuration
Modbus protocol preinstalled
If the unit is equipped with respective options, the following functions can be controlled and supervised:
Documents:
The A/C units are dispatched with the following documents:
operation instructions manual
maintenance instructions manual
wiring diagrams
refrigeration diagram
replacement parts list
CE - declaration of conformity
test certificate of final function and safety test
The commissioning, the final function check and the instruction of the operator are
not part of the delivery volume.
Electrical heating
to ensure a constant room temperature, e.g. during dehumidifying operation
single-stage electrical heating, capacity 1x 9kW (on/off control, controlled by the A/C unit's controller)
each heating stage protected against overload and short circuit through circuit breakers in the electric
cabinet of the unit
easy access for maintenance purposes
position downstream the heat exchanger related to the airflow
each stage consisting of 3 finned heating bars (material: heating bars 1.4306, fins 1.4306), designed for low
casing temperatures and stable, long-life operation the same as optimum heat transmission to the air
one overheat protection for each stage (trigger temperature: 60°C to interrupt the control circuit) with
integrated, automatic restart
A Schrader valve is located in the hotgas line for connecting a pressure gauge to adjust the speed controller by
maintenance personnel.
Technical data:
voltage supply: 230/1/50-60 V/Ph/Hz
number of fans: 3
max. operating pressure: 28 bar
Speed controller
adjustment of the pressure for maximum speed
switch for behaviour below the proportional range (cut off/minimum speed)
adjustment range: 8 to 28 bar
proportional range: 4 bar (fix)
minimum speed: 45% (50Hz) / 35% (60Hz)
ambient temperature: -45 to +55°C
protection: IP 54
A free digital input on the C7000 is required for the detection of one of the above phase errors.
This option is necessary for each power supply.
Features:
Large backlit LCD display
LCD display located at a height of 1.55m
Control input via 5 keys
Operation of up to 19 C7000 IO-Controllers via Windows technology
Redundant user-interface by usage of up to 19 C7000AT
Menu in 12 languages
Visual and acustic signals of events
Alarm transfer via SMS and E-mail (additional options required)
Interfaces:
RS232 - Service Port (Sub-D 9) for configuration
RS485 - for internal Stulz I/O-Bus
RS232 or RS485 for connection to BMS
Protocol:
Modbus RTU
only 50 data points can be requested
Floor stand:
Floor stand for A/C unit, adjustable height 495-545 mm.
The floor stand serves for a vibration-decoupled positioning of the A/C unit, the same as for adjusting the
A/C unit position to the existing raised floor height.
The floor stand consists of the following components, which must be assembled on site:
o a sufficient number of galvanized profile steel frames (70x40 mm), which is adapted to the unit
construction
o threaded supports with adjustable height incl. base plate (circular) and a head plate (serrated disc)
o vibration reducing Mafund support strips (25 mm thickness)
o the associated fixing material, e.g. hammer head screws
The number of threaded supports is adapted to the unit dimensions and weight.
Seaworthy case packing
Polyethylene air cushion film
Polyethylene stretch film
Box base with rubber strips
Lid and walls made of plywood with 9 mm thickness
WinPlan
Unit
Unit type: ASD 872 A
Cooling capacity (total): 95,5 kW
Cooling capacity (sensible): 82,7 kW
Net total cooling capacity: 91,7 kW
Net sensible cooling capacity: 78,9 kW
Condensing temperature: 47 °C
EER: 3,82 kW/kW
AER: 0,17 W/(m³/h)
Sound power level: 81,3 dB(A)
LpA (2m freefield): 60,4 dB(A)
Airflow: 23.000 m³/h
Air velocity: 2,9 m/s
Return air temperature: 24 °C
Return air humidity: 50 rel.%
Supply air temperature: 13 °C
Altitude above sea level: 0 m
Height: 1.980 mm
Width: 2.550 mm
Depth: 890 mm
Weight: 828 kg
Refrigerant: R407C
Power supply: 380V/60Hz/3Ph/N/PE
Total power consumption: 25,0 kW
Condenser
Unit type: KSV057A31p
Ambient temperature: 35 °C
Sound pressure group: Standard
Required condenser capacity: 58,2 kW
Available condenser capacity: 61,3 kW
Difference: 5,3 %
Weight: 161 kg
Current consumption (per fan): 4,05 A
Power consumption (per fan): 0,93 kW
Height: 947 mm
Width: 2.360 mm
Depth: 770 mm
Airflow: 18.480 m³/h
LpA (5m freefield): 59,5 dB(A)
Number of fans: 3
Number of condensers: 2
The above mentioned data are subject to the measuring tolerances of Eurovent. Unless otherwise stated, all
data refer to a product in basic version.